McQuay MHC018 User Manual

Catalog 1104-2
®
Ennity™ Console Water Source Heat Pumps 1/2 to 1½ Ton
R-410A Models MHC Standard Range & MHW Geothermal Range
Size 007–018
Contents
Model Nomenclature . . . . . . . . . . . . . . . . . . . . . . . 3
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Features and Options . . . . . . . . . . . . . . . . . . . . .5-6
Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-10
Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Features-MicroTech III Unit Controller. . . . . . . . 8
Features-MicroTech III with I/O Expansion
Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Features-MicroTech III with Communication
Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-15
Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-12
Considerations. . . . . . . . . . . . . . . . . . . . . . . . . 13
Typical Heating & Cooling Refrigeration
Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Unit Selection. . . . . . . . . . . . . . . . . . . . . . . . . . 15
Capacity Data . . . . . . . . . . . . . . . . . . . . . . . . . .16-35
Cooling Capacity - Size 007 . . . . . . . . . . . .16-17
Heating Capacity - Size 007 . . . . . . . . . . . .18-19
Cooling Capacity - Size 009 . . . . . . . . . . . .20-21
Heating Capacity - Size 009 . . . . . . . . . . . .22-23
Cooling Capacity - Size 012 . . . . . . . . . . . .24-25
Heating Capacity - Size 012 . . . . . . . . . . . .26-27
Cooling Capacity - Size 015 . . . . . . . . . . . .28-29
Heating Capacity - Size 015 . . . . . . . . . . . .30-31
Cooling Capacity - Size 018 . . . . . . . . . . . .32-33
Heating Capacity - Size 018 . . . . . . . . . . . .34-35
Performance Data. . . . . . . . . . . . . . . . . . . . . . .36-39
Water Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Ground Loop . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Ground Source. . . . . . . . . . . . . . . . . . . . . . . . . 36
Electrical - Standard Static Motor . . . . . . . . . . 37
Electrical - Standard Static Motor and
Optional Electric Heater . . . . . . . . . . . . . . . . . . 37
Electric Heater Current & Power . . . . . . . . . . . 37
Fan Performance . . . . . . . . . . . . . . . . . . . . . . . 38
Operating Limits. . . . . . . . . . . . . . . . . . . . . . . . 38
Additional Information for Start-Up . . . . . . . . . 38
Standard Range Units. . . . . . . . . . . . . . . . 38
Geothermal Range Units. . . . . . . . . . . . . . 38
Airflow Correction Factors . . . . . . . . . . . . . . . . 39
Antifreeze Correction Factors . . . . . . . . . . . . . 39
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . .40-43
Size
Right Hand Piping . . . . . . . . . . . . . . . . . . . . . . 40
Size 007-012 Flat Top-High Sill,
Left Hand Piping . . . . . . . . . . . . . . . . . . . . . . . 40
Size 007-012 Slope Top, Low Sill,
Right Hand Piping . . . . . . . . . . . . . . . . . . . . . . 41
Size 007-012 Flat Top, Low Sill,
Left Hand Piping . . . . . . . . . . . . . . . . . . . . . . . 41
Size 015-018 Slope Top, High Sill,
Right Hand Piping . . . . . . . . . . . . . . . . . . . . . . 42
Size 015-018 Flat Top, High Sill,
Left Hand Piping . . . . . . . . . . . . . . . . . . . . . . . 42
Size 015-018 Slope Top, Low Sill,
Right Hand Piping . . . . . . . . . . . . . . . . . . . . . . 43
Size 015-018 Flat Top, Low Sill,
Left Hand Piping . . . . . . . . . . . . . . . . . . . . . . . 43
Accessories (General) . . . . . . . . . . . . . . . . . . .44-49
Thermostats and Sensors . . . . . . . . . . . . . .44-47
Supply and Return Hoses . . . . . . . . . . . . . . . . 48
Combination Balancing and Shutoff Valves. . . 48
2-Way Motorized Valve . . . . . . . . . . . . . . . . . . 48
Piping Packages . . . . . . . . . . . . . . . . . . . . . . . 48
Outdoor Air Dampers . . . . . . . . . . . . . . . . . . . . 49
Extended End Pocket (Option) . . . . . . . . . . . . 49
Multiple Unit Control Panel (MUCP) . . . . . . . . 49
Typical Wiring Diagrams . . . . . . . . . . . . . . . . .50-52
Unit-Mounted - MicroTech III
Unit Controller for Sizes 007-015
208/230/60Hz/1-Phase . . . . . . . . . . . . . . . . . . 50
Unit-Mounted - MicroTech III Unit
Controller With Electric Heat for Size 018
208/230/60Hz/1-Phase . . . . . . . . . . . . . . . . . . 51
Unit-Mounted - MicroTech III Unit
Controller With BACnet Module for
All Units without Electric Heat
265/277/60Hz/1-Phase . . . . . . . . . . . . . . . . . . 52
Engineering Guide Specifications . . . . . . . . .53-55
007-012 Slope Top-High Sill,
Model Nomenclature
NOTE: For illustration purposes only. Not all options available with all models.
Please consult your McQuay Sales Representative for specic availability.
W MHC 1 009 B E H B T 01 F2
Product Category
W = WSHP
Product Identier
MHC = Standard Range Console WSHP MHW = Geothermal Range Console WSHP
Design Series
1 = A Design 2 = B Design 3 = C Design 4 = D Design
Nominal Capacity
007 = 7,000 BTU/h 009 = 9,000 BTU/h 012 = 12,000 BTU/h 015 = 15,000 BTU/h 018 = 18,000 BTU/h
Controls
B = MicroTech® III Unit Controller C = MicroTech III Unit Controller w/LonWorks® Communication Module
D = MicroTech III Unit Controller w/BACnet® Communication Module
Voltage
A = 115/60/1 E = 208-230/60/1 J = 265/60/1
Cabinet Type
F = Flat Top S = Slope Top
Discharge Grille
2 = Standard Stamped
Louver
3 = Multi-Directional Grille
Blower Motor
01 = Standard
Discharge Air
T = Top
Return Air
B = Bottom Return (High Sill) F = Front Return (Low Sill)
Cabinet Height
H = High Sill L = Low Sill
Console Water Source Heat Pumps – Sizes 007-018 (1/2 to 1½ Tons)
Model MHC (Standard Range: 55°F to 110°F) Model MHW (Geothermal Range: 30°F to 110°F)
“McQuay” is a registered trademark of McQuay International.
©McQuay International 2009. All rights reserved throughout the world.
The information in this manual supersedes and replaces previous catalogues with regards to McQuay Water Source Heat Pump products. Illustrations cover the general appearance of McQuay International products at the time of publication and McQuay International reserves the right to make changes in design and construction at anytime without notice.
®
The following are trademarks or registered trademarks of their respective companies: LonTalk from Echelon Corporation, BACnet from ASHRAE, Open
Choices, and MicroTech III from McQuay International.
Catalog 1104-2 McQuay Ennity Console Water Source Heat Pumps 3
Introduction
Ennity™ Water Source Heat Pumps
More than 30 years ago, McQuay designed the rst
complete line of water source heat pumps for high efcien-
cy, individually-zoned comfort control in ofces, schools,
assisted living facilities, manufacturing facilities and other commercial buildings. Our reputation for outstanding reli-
ability and quiet operation has been reinforced in thousands
of successful installations.
Ennity water source heat pumps incorporate the best of
our past and the best of what’s new. Using feedback from building owners, consulting engineers, contractors and ser-
vice engineers, we designed Ennity products to give you maximum exibility to design, install, operate and maintain
the ideal water source heat pump system for your building project. And we incorporated non-ozone depleting R-410A
refrigerant, which–along with high Energy Efciency Ra-
tios (EER’s)–helps preserve our environment and precious
energy resources.
Factory-installed, unit-mounted thermostats save time
and money versus installing wall-mounted thermostats.
Wide range of factory-installed options, including elec-
tric heat, motorized valves and thermostat options help
you meet more specic application requirements with
minimum design or installation time and expense.
Easy, Low-Cost Maintenance
Easy access to the unit compressor (end panel), fan
section and coil (front panel) and unit controls (left or right end panel).
A easily removable blower motor allows the tangen-
tial fan wheel to remain in the housing during motor replacement.
A hinged control box allows easy access to the piping
compartment.
With Ennity Water Source Heat Pumps, you benet from:
High efciency that minimizes environmental impact and lowers operating costs
Units exceed ASHRAE Standard 90.1 minimum
requirements
Standard range or geothermal application exibility
Engineered For Flexibility and Performance
Two cabinet sizes, each with McQuay’s subtle
aesthetic and small footprint design, make it easy to
meet the space requirements of your new construction
or replacement application.
MicroTech® unit controller with Open Choices™ fea-
ture allows easy, low cost integration with the Building Automation System (BAS) of your choice.
Improved Efciency
35% greater efciency than the
minimum required by ASHRAE
90.1, for units less than 17,000 Btuh
per ISO Standard 13256-1 for Boiler/Tower applications.
Quiet Operation
New Gentleo™ fan wheel allows the fan motor to
operate at lower speed for quieter operation.
High efciency rotary compressor mounted on a mass
plate system reduces noise due to vibration.
Superior Indoor Air Quality (IAQ)
Removable, non-corrosive and double-sloped polymer
drain pan promotes positive condensate drainage.
Optional closed-cell insulation prevents insulation
bers from entering the air stream.
R-410A Refrigerant With Zero Ozone Depletion Potential or Phase-Out Date
R-410A is classied as A1/A1 – lower toxicity, no
ame propagation – per ASHRAE Standard 31.
Console Unit Features & Options
1. Cabinets – Selectable at top or slope top cabinet
congurations with multiple grille options, including user congurable, multi-directional grilles. Individual panels-
top,
front and end panels are designed for easy removal and provides easy access to unit components for service and maintenance. Optional extended cabinet end pocket for high sill units, providing 11" of additional area inside the left or
right end pocket for piping or a eld-installed pump.
2
. Compressor - High efciency rotary type, using R-410A re-
f
rigerant with zero ozone depletion potential or phase-out date.
3. Gentleo™ Fan – User
selectable, multi-speed tangential fan
system provides high efciency and very quiet operation
suitable
for noise sensitive applications.
4. LED Annunciator – LED
status lights display fault conditions to provide easy troubleshooting and diagnosis. Accessed by removing the left or right end panel to the control enclosure.
5. Filter
– Units come standard with a 1/2" (12.7mm) thick
disposable lter that is easy to access and replace without
removing
panels.
6. Hinged Control Box– Provides added accessibility to plumbing
end compartment for easier access for service.
7. 2-Way Motorized Valve Packages (Option) – Factory installed or eld-installed for variable pumping applications. Other valve options available upon request.
8. MicroTech® III Unit Controller – Designed for exibility, the
main control board is used in standalone applications. An optional I/O expansion module can be used to control electric
heat and multiple fan speeds. A separate optional-
L
onWorks® or BACnet® communication module can be
easily snapped onto the board to accommodate the building automation system of your choice.
9. Double-Sloped Drain Pan
polymer
, promotes positive condensate drainage for superior
– Made of durable, non-corrosive
Indoor Air Quality (IAQ). Drain Pan is easy to remove for
cleaning.
Air Dampers (Field-installed Accessory) – Motorized or manually
operated
outside air dampers provide ventilation air.
Expanded Paint Colors – Color selections that compliment any
decor.
Cupola White Off White Antique Ivory
Putty Beige
Soft Gray Oxford Brown
MicroTech III Controller
I/O Expansion Module
L
onWorks
Module
BACnet Module
(Discharge Grille
& Subbase)
Multi-Directional Grilles
Extended
(High Sill Units Only)
Provides 11" of additional area inside the left or right end pocket.
Cabinet End Pocket
Catalog 1104-2 McQuay Ennity Console Water Source Heat Pumps 5
Console Design Features
Conguration
Console water source heat pumps are available in ve cooling capacity sizes, from 1⁄2 through 1½ tons, (1757 to 5274 watts). Each is available in four different congurations.
Flat top units meet the traditional requirements for a rugged
unit. Slope top units offer a more modern look. The high
silhouette unit is 25" (635mm) high and the low silhouette unit is only 22½" (572mm) high. The overall unit dimensions are very compact; unit sizes 007 through 012 are 46" (1168mm) long and sizes 015 through 018 are 54" (1372mm) long. All units are a constant 10¾" (273mm) deep for minimum oor
space and a consistent “look” for all unit sizes.
All units incorporate a slide-out chassis concept which
allows it to be installed easily or removed and replaced quickly when service is required to minimize downtime for the space
the unit serves. The cabinet is made up of individual panels, each of which can be easily removed to expose the chassis for
eld hook-up of water and electrical connections. The chassis
easily slides off the subbase for service or changeout.
Cabinet
All cabinets are painted with optional Antique Ivory or Cupola White baked enamel nish for an aesthetically
pleasing appearance that matches room decor. The discharge grilles and subbase can be Oxford Brown or match the
cabinetry on at top or slope top units.
The shallow 22° slope top cabinet is constructed of 18-
gauge steel. The top and side corners and grille are constructed of tough, impact-resistant ABS polycarbonate. The grille extends to the front and sides for a smooth look as well as providing a curtain stop in back. The discharge grilles can be rotated to direct the air in an 11° angle from the vertical and can be reversed for a 33° discharge angle. The control door has
a nger slot and simply lifts up for access to the thermostat. Overall, the slope top unit allows minimal airow interference
from curtains and objects resting on the cabinet, while at the same time providing a rugged, aesthetically pleasing look.
The flat top cabinet is constructed of 18-gauge steel with grille options that meet basic needs with its rugged construction and its 11° discharge angle.
Chassis
The chassis houses the fan section, refrigerant circuit and controls. The air enters through the bottom of the chassis, through the subbase or through the front panel in low sill units.
The refrigeration system includes a rotary compressor, reversing valve, coaxial heat exchanger, capillary tubes, air coil, high and low side access valves, and safety controls.
Access to the compressor is through a removable end panel. The compressor is isolated from the unit with external vibration
mounts, mass plate/viscoelastic dampening material and the compartment is totally insulated to make the quietest console
unit on the market. Safety controls include low temperature (freezestat) and refrigerant high pressure switches. The control box is hinged for easy access to all of the controls.
The MicroTech III unit controller offers both standalone or
communicating (LonWorks or BACnet) control options.
Each uses a printed circuit board for clean wiring and a low voltage control circuit with a 50 VA transformer. See “Controls” section for more detailed information. Main power
is made to a chassis-mounted 2" x 4" (51mm x 102mm)
junction box.
The fan section employs McQuay's Gentleo tangential system fan and efcient, two-speed PSC motor for selectable airow and/or noise level. Access to the fan wheel is made
through the top panel. The motor is secured to the chassis with three screws for easy service.
Water piping connections are 1⁄2" FPT ttings which
terminate in the outward position in the piping compartment
for easy access. Unique left- and right-hand piping (includes condensate and electrical) locations are available. The 3⁄4" (19mm) I.D. exible clear vinyl condensate drain tube is
internally trapped and extends 14" (356mm) into the piping
compartment for easy connection. Piping (electrical and
condensate also) can enter through the back wall or through
the oor within the subbase. The chassis allows for a piping
compartment between the chassis and the cabinet.
Optional Factory Installed Features
Boilerless system electric heat eliminates the need for a boiler in the heat pump water loop. An electric heater is added
to the discharge side of the fan scroll. If the entering water
temperature falls to 58°F (15°C) the thermostat locks out compressor operation. On a call for heat, the electric heater is energized. When the entering water temperature raises, the unit will resume compressor operation on a call for heat. An emergency electric heat override plug allows for electric heat, if the compressor (mechanical) heat should fail. Each unit has various heater sizes to select from. Not available on 115 volt units. Not CSA listed.
Optional Extended End Pockets (High Sill Units)
Optional extended cabinet end pocket for high sill units, provides 11" of additional area inside the left or right end
pocket for piping or a eld-installed pump.
Optional Multi-Directional Grilles
Selectable plastic Multi-Directional Grilles can rotate
90, 180 or 270 degrees for added control of discharge air
direction.
Control Options – Control Choices And Added Functionality
The control box is accessible through the left or right end
corner panel. It houses the major operating electrical controls including the MicroTech® III unit controller, transformer,
compressor relay and fan relay. Each component is easily accessed for service or replacement.
Four unique control choices are offered with the Micro-
Tech III unit controller:
■ Standalone operation using a MicroTech III unit controller
■ MicroTech III unit controller with I/O Expansion module
■ MicroTech III unit controller with a Lonworks® commu-
nication module
■ MicroTech III unit controller with a BACnet® communica-
tion module
Each option features direct quick-connect wiring to all
unit-controlled components for “clean” wiring inside the control box. Each control circuit board receives power from a 50 VA transformer.
Control Description Application Protocol
MicroTech III
(Standalone)
Unit Controller
The MicroTech III unit controller is
a standalone microprocessor-based control board conveniently located in the unit control box for accessibil
. The board is designed to provide
ity standalone control of a Water Source
Heat Pump using a wall thermostat
r a wall mounted temperature sen-
o s
or. Each unit controller is factory
programmed, wired, and tested. For
added functionality an optional I/O
expansion
MicroTech III controller for complete
control water source heat pump.
module interconnects to the
and operation of your McQuay
Each unit controller is factory programmed, wired, and tested for complete control of single zone, stand­alone
operation of your McQuay Water Source Heat
Pump.
-
Unit- mounted or wall-mounted thermostat
I/O Expansion
Module
LonWorks
Communication
Module
BACnet
Communication
Module
The I/O Expansion Module is an exten­sion of the Microtech III unit controller
and
provides additional functionality.
It is required on all units with an LED
annunciator the boilerless electric heat feature.
The MicroTech III unit controller can
a
ccept a plug-in LonWorks commu­nication module to provide network communications and added functional
to easily integrate with an existing
ity BAS. The communication module can be factory- or field-installed and is
tested with all logic required to monitor
and control the unit.
The MicroTech III unit controller
can nication module to provide network communications and added functional ity to easily integrate with an existing BAS. The communication module can be factory- or field-installed and is
tested with all logic required to monitor
and
and provides operation of
accept a plug-in BACnet commu-
control the unit.
Allows
for:
• Monitoring of entering water temperature for boilerless electric heat control.
• Outputs for optional electric heat .
Designed to be linked with a centralized building automation system (BAS) through a L munications network for centralized scheduling and management of multiple heat pumps.
-
Designed to be linked with a centralized building automation system (BAS) through a BACnet com munications
-
management of multiple heat pumps.
network for centralized scheduling and
onWorks com-
U
nit-m ounted or wall-mounted thermostat
onMark 3.4
L
BaCnet
-
Control Features – MicroTech® III Unit Controller
The MicroTech III Unit Controller is a microprocessor-
based control board conveniently located in the unit control box for easy access through a removable access panel. The standalone unit controller is a hard wired interface and pro-
vides all the necessary eld connections. The board can be wired for 24-volt AC output to the wall thermostat by using
terminals R & C. An LED annunciator is located on the front
corner of the unit chassis to quickly check the operating status
of the unit.
MicroTech III Operating Features
Assumes cycle fan operation-not continuous fan operation:
Start-up – The unit will not operate until all the inputs
and safety controls are checked for normal conditions.
Cooling mode – On a call for cooling, the compressor
and fan will start 0 to 30 seconds later. When the load is
satised, the compressor and fan shut off.
Heating Mode – On a call for heating, the reversing valve
is energized after 60 seconds and the compressor and fan
start. When the load is satised, the compressor and fan
shut off. The reversing valve is de-energized 60 seconds later.
Short Cycle Protection & Random Start – Each time
the compressor stops, a new random compressor start-
delay time between 180 and 240 seconds is generated.
This prevents compressor short cycling and prevents units from starting simultaneously after coming back from an unoccupied cycle.
Unoccupied Mode – A simple “grounded” signal between
terminals U and C (no power source required), puts the
unit into the unoccupied mode for night setback operation.
Override Mode – A switch on the deluxe automatic
changeover thermostat can be activated during the unoc­cupied mode to put the unit back into the occupied mode for two hours for after-hours heating or cooling.
Motorized Valve/Pump Restart – The IV/PR (H8) ter-
minals on the The MicroTech III unit controller are used
to energize (open) a motorized valve or start a water pump to get water circulating prior to starting the compressor
on call for heating or cooling. The IV/PR (H8) terminal may be “daisy chained” between 200 units.
Brownout Protection – The MicroTech III unit controller
measures the input voltage and will suspend compressor and fan operation if the voltage falls below 80% of the unit nameplate rated value. A unique LED status is gen­erated and an output is available to a “fault” LED at the thermostat.
Unit Shutdown – A simple grounded signal puts the unit
into the shutdown mode. Compressor and fan operations
are suspended. A unique LED status is generated and an
output signal is made available for connection to a “fault” LED at the thermostat.
Condensate Overow Protection – The MicroTech III unit controller incorporates a liquid sensor at the top of the drain pan. Upon sensing water ow, cooling operation is suspended. A unique LED status is generated and output
is available to a “fault” LED at the thermostat. Heating operation is not suspended.
Remote Reset of Automatic Lockouts – The Remote Re-
set feature provides the means to remotely reset automatic
lockouts generated by high-pressure and/or low-tempera-
ture faults. When the MicroTech III unit controller is in
automatic lockout due to one of these faults, and the cause of the fault condition has been alleviated, energizing the O-terminal for 10 seconds or more will force the control board to clear the lockout. A unit power cycle can also be used to clear an automatic lockout if the conditions causing the fault have been alleviated.
Intelligent Reset – The Fault Retry feature helps to
minimize nuisance trips of automatic lockouts caused by
high-pressure and/or low-temperature faults. This feature clears faults the rst two times they occur within a 24-hour
period and triggers an automatic lockout on the 3rd fault.
The retry count is reset to zero every 24 hours.
Equipment Protection Control – The MicroTech III
unit controller receives separate input signals from the refrigerant high-pressure switch and the low suction line
temperature sensor. In a high-pressure situation, compres-
sor operation is suspended. In a low temperature situation,
the unit goes into a defrost cycle where the unit is put into cooling operation for 60 seconds until the coaxial heat exchanger is free of ice. Each switch generates its own
unique LED status and output is available to a “fault”
LED at the thermostat if either situation exists.
Note: Most unit fault conditions are the result of operating
the equipment outside the unit specications.
MicroTech III unit controller LED & fault outputs
Mode / Fault
Occupied, Bypass, Standby Override Unoccupied On On Off Energized Condensate Overow On Off Off De-energized High Pressure 1 Fault
Low Pressure 1 Fault Off Off On De-energized Low Temperature 1 Fault Flash Off Off De-energized
Brownout
Emergency Shutdown
Room/Return
Temp Sensor 1 Failure
Service Test Mode
Enabled
Serial EEPROM Corrupted
Network “Ofine” Received
1
Compressor relay/compressor terminal is labeled COMP, switched line of
the same electric input as any of the L1 terminals.
Status LED’
, or Tenant Off On Off Energized
Air or Low
1
ellow Green Red Output-Terminal “A”
Y
Off Off Flash De-energized
Off Flash Off De-energized
Off Flash Off De-energized
Flash Flash On De-energized
On On Off De-energized
On On On De-energized
Off Off Off De-energized
s
Thermostat Alarm Light
Control Features – MicroTech III with I/O Expansion Module
I/O Expansion Module
The I/O Expansion Module is a factory installed option. It is an extension of the MicroTech III unit controller and
provides extra functionality.
The I/O Expansion Module has 2 main purposes:
• The I/O Expansion Module has outputs to control electric heat on a standard Water Source Heat Pump.
• The I/O Expansion Module has an independent LED
annunciator to identify operational fault conditions for the electric heater.
I/O Expansion Module LED & Fault Outputs
Invalid Conguration Jumper Setting
Base Board Communication Fail
High Pressure #2 Fault Off Off Flash De-energized
Low Pressure #2 Fault Off Off On De-energized
Unoccupied Mode On On Off Energized
Occupied, Bypass, Standby, or Tenant Override Modes
Note: Mode / Faults are listed in order of priority.
1
Boilerless electric heat only
2
Alarm/fault LED indications take precedence over service test mode LED
Mode / Fault
Low Suction Temp #2 Fault Flash Off Off De-energized
Sensor Failures Low Suction
Low Suction
1
EWT (w/ Boilerless EH only)
2
Service Test Mode Enabled Flash Flash Flash De-energized
Normal Operation
indication. The controller shall use service test mode if the service test mode jumper is installed, even if the LED’s indicate an alarm/fault.
= Not used with Console Water Source Heat Pump unit.
Y
Temp #2, Flash Flash On De-energized
Off On Off De-energized
Status LED's
ellow Green Red
Flash Flash Off De-energized
Off Flash Flash N/A
Off On Off Energized
Terminal “A”
Thermostat Alarm
Light Output
I/O Expansion Module Conguration Jumper Settings
Jumper Description Options
JP1 Number of
JP2
Water Reheat Shorted to enable reheat
Compressors Shorted for dual compressor
Hot Gas/
Open for single compressor
Open to disable reheat
JP3 and JP4 open for no supplemental heat JP3 Supplemental JP3 open, JP4 shorted for
& JP4 Heat Type boilerless electric heat
JP3 and JP4 shorted is an invalid setting JP5 and JP6 open for single-speed fan
Fan Speed three-speed fan
JP5
JP5 open, JP6 shorted for
& JP6 Selection JP5 shorted and JP6 open for two-speed fan JP 5 and JP6 shorted is an invalid setting
JP7
Speed Type Shorted for two-speed compressor
Compressor Open for single-speed compressor
JP8 Future Spare
= Not used with Console Water Source Heat Pump unit.
I/O Expansion Module Conguration Jumper Terminals
Jumper Terminals
Adding an I/O Expansion Module (with an interconnect
cable) to the unit controller allows the operation of boilerless electric heat with the Console Water Source Heat
Pump.
Features
Standard Heat Pumps / Single Circuit Units
• Monitors entering water temperature for boilerless electric heat control
Catalog 1104-2 McQuay Ennity Console Water Source Heat Pumps 9
Control Features – MicroTech III with Communication Module
MicroTech
orks or BACnet Communication Module
W
Each McQuay Console Water Source Heat Pump can
be equipped with a LonWorks or BACnet communication
module. The LonWorks module is LonMark 3.4 certied and designed to communicate over a LonWorks communi­cations network to a Building Automation System (BAS). The BACnet module is designed to communicate over a
BACnet MS/TP communications network to a building
automation system. Both controllers are microprocessor-
based and can be factory or eld-installed.
The control modules are programmed and tested with all the logic required to monitor and control the unit. Op­tional wall sensors may be used with the communication modules to provide limited local control of the Console
Water Source Heat Pump. The MicroTech III unit controller
monitors water and air temperatures and passes information to the communication module. The module communicates with the BAS, to provide network control of the Water
Source Heat Pump.
MicroTech III L
The LonWorks communication module is designed for units that are integrated into a LonWorks communication network for centralized scheduling and management of multiple heat pumps.
®
III Unit Controller with Lon-
onWorks Communication Module
MicroTech III Unit Controller with Communication Modules Features
The MicroTech III Unit Controller with LonWorks or BACnet Communication Module orchestrates the following unit operations:
Enable heating and cooling to maintain space temperature setpoint based on a room sensor setting
Enable fan and compressor operation
Monitors all equipment protection controls Monitors room and discharge air temperatures Monitors leaving water temperature Relays status of all vital unit functions
An amber, on-board status LED indicates the status of the MicroTech III LonWorks or BACnet module.
The MicroTech III unit controller includes:
A unit-mounted return air sensor A unit-mounted discharge air sensor A leaving water temperature sensor
The communication modules provide network access to setpoints for operational control
Available wall sensors include:
Room sensor Room sensor with LED status and tenant override
button Room temperature sensor with LED status, timed-
MicroTech III BACnet Communication Module
Designed to be linked with a centralized building auto­mation system (BAS) through a BACnet communications network for centralized scheduling and management of multiple heat pumps.
override button, and ±3°F setpoint adjustment
Room temperature sensor with LED status, timed-
override button, 55° to 90°F setpoint adjustment
Applications – Systems
Water source heat pump systems are one of the most ef-
cient, environmentally friendly systems available for heating and cooling buildings. High-efciency, self contained units (sizes 7,000 btuh to 420,000 btuh) can be placed in virtually
any location within a building. Each unit responds only to the heating or cooling load of the individual zone it serves. This permits an excellent comfort level for occupants, better control of energy use for building owners and lower seasonal
operating costs. The Air-Conditioning Refrigeration Institute (ARI) and the International Standards Organization (ISO)
publish standards so that water source heat pumps are rated
for specic applications. The ARI/ISO loop options shown in
this catalog are typical water source heat pump loop choices
available in today’s market. These systems offer benets rang-
ing from low cost installation to the highest energy efciency
available in the market today.
Boiler / Tower Applications: ARI 320 / ISO 13256-1
A “Boiler/Tower” application uses a simple two-pipe
water circulating system that adds heat, removes heat or transfers rejected heat to other units throughout the build­ing. The water temperature for heating is generally main-
tained between 65ºF – 70ºF and is usually provided by a
natural gas or electric boiler located in a mechanical room. The condensing water temperature, during cooling months,
is maintained between 85ºF and 95ºF and requires the use
of a cooling tower to dissipate waste heat. Cooling tow­ers can be located on the roof, or inside or adjacent to the building. This application can be the lowest cost of the loop options available.
Note: ASHRAE 90.1 standards require that circulating pumps over 10 HP will require use of “variable frequency drive” equipment and pipe insulation to be used whenever
water temperatures are below 60 degrees and above 105 degrees. See ASHRAE 90.1 Standards for details.
Open Loop Well Water Applications: ARI 325 / ISO 13256-1
“Open Loop” well water systems use ground water
to remove or add heat to the interior water loop. The
key benet of an open loop system is the constant water temperature, usually 50ºF to 60ºF, which provides efcient operation at a low rst cost. Most commercial designers
incorporate a heat exchanger to isolate the building loop from the well water. Using heat exchangers can reduce maintenance issues while still allowing the transfer of heat from unit to unit as with the “Boiler/Tower System”. A suc­cessful design provides an ample amount of groundwater
(approximately 2 GPM per ton) and adequate provisions for discharging water back to the aquifer or surface. Open
Loop applications are commonly used in coastal areas where soil characteristics allow reinjection wells to return
the water back to the aquifer. Note that some states have re-
quirements on the depths of return water reinjection wells,
and such wells must be approved by the United States En-
vironmental Protection Agency. Also, bad water quality can
increase problems with heat exchanger scaling. Suspended solids can erode the heat exchanger. Strainers can be used to contain suspended solids.
Open Loop Well Application
Boiler/Tower Application
Catalog 1104-2 McQuay Ennity Console Water Source Heat Pumps 11
Applications – Systems
Closed Loop Geothermal Applications ARI 330/ISO 13256-1
“Vertical Closed Loop” applications are installed by drilling vertical bore holes into the earth and inserting
a plastic polyethylene supply/return pipe into the holes.
The vertical wells are connected in parallel reverse return fashion to allow the water from the building to circulate evenly throughout the boreeld. The circulating uid dis­sipates heat to the ground in a similar manner as a “tower”
and adds heat back to the loop like a boiler. If properly designed, the loop eld can maintain the loop temperatures
necessary to condition the building without the use of a boiler or a tower. Loop temperatures usually range from
37ºF to 95ºF in Northern climates. Southern applications
can see temperatures ranging from 40ºF to 100ºF. The number of bore holes and their depth should be determined
by using commercial software that is specically designed
for vertical geothermal applications. Typical bore depths of a vertical loop range from 150 to 400 feet and generally
require about 250 feet of surface area per ton of cooling.
Vertical Loop Application
Horizontal Loop Application
A “Surface Water” or “Lake” closed loop system is a
geothermal loop that is directly installed in a lake or body
of water that is near the building. In many cases, the body
of water is constructed on the building site to meet drain-
age or aesthetic requirements. Surface loops use bundled
polyethylene coils that are connected in the same manner as a vertical or horizontal loop using a parallel reverse return design. The size and the depth of the lake is critical. Commercial design services should be used to certify that a
given body of water is sufcient to withstand the building
loads. Loop temperatures usually range from 35ºF to 90ºF and prove to be the best cooling performer and lowest cost loop option of the three geothermal loops. Some applica­tions may not be good candidates due to public access or
debris problems from ooding.
Surface Water Loop Application
A closed loop “Horizontal” geothermal application is similar to a vertical loop application with the exception that the loops are installed in trenches approximately 5 feet below the ground surface. The piping may be installed
using a “four-pipe” or “six-pipe” design and could require 1,500 to 2,000 square feet of surface area per ton of
cooling. Loop temperatures for a commercial application can range from 35ºF to 95ºF in Northern climates. Southern climates can see temperatures ranging from 40ºF to 100ºF. Horizontal loops are generally not applied in urban areas because land use and costs can be prohibitive. New advances in installation procedures have improved the
assembly time of horizontal loops while keeping the rst
cost lower than a vertical loop.
Applications Considerations
Typical Console Installation
Unit Location
The Console Water Source Heat Pump is typically
installed on an exterior wall.
Locate a Console unit to allow for easy removal of
the lter and access panels. Allow a minimum of 18" (46
cm) clearance on each side of the unit for service and maintenance access.
To reduce noise emissions, install a eld-provided 1/4
inch thick, rubber isolator pad below the entire base of the
unit. The pad should be equal to the overall foot-print size
of the unit to provide sound dampening of the unit while
in operation. The unit must sit at on the oor to prevent
unwanted noise and vibration.
Condensate Drain
The factory provided condensate drain trap on the console unit is located inside the end cabinet. Condensate removal piping must be pitched away from the unit not
less than 1/4" per foot. A vent is required after the trap so
that the condensate will drain away from the unit. The vent can also act as a clean out if the trap becomes clogged. To avoid having waste gases entering the building, the
condensate drain should not be directly piped to a drain/ waste/vent stack. See local codes for the correct application
of condensate piping to drains.
McQuay has available optional re-rated exible hoses
to better facilitate supply and return piping connections.
These exible hoses reduce vibration between the unit and
the rigid piping system.
Fire Rated Supply or Return Hoses
Piping
The console water source heat pump unit is typically
connected to the supply / return piping using a “reverse return” piping system which includes a ow control device so that ow requirements are met for each zone. A short, high pressure “exible hose” is used to connect
the unit to the building’s hard piping and acts as a sound attenuator for both the unit operating noise and hydronic
pumping noise. One end of the hose has a swivel tting to
facilitate removal of the unit for replacement or service.
Include supply and return shutoff valves in the design to
allow removal of a unit without the need to shut down the entire heat pump system. The return valve may be used for balancing and will typically have a “memory stop” so
that it can be reopened to the proper position for the ow required. Fixed ow devices are commercially available
and can be installed to eliminate the need for memory stop
shut off valves. Include Pressure / Temperature ports to allow the service technician to measure water ow and unit
operation.
Catalog 1104-2 McQuay Ennity Console Water Source Heat Pumps 13
@ 70° to 90° Radius
24" 400 psig 1200 psig 2½"
Hose Type
1/2" MPT
12"
Supply
& Return
Fixed End, MPT
Nominal
9"
18"
Max. Recommended
Length
Working Pressure
400 psig 1200 psig 2½"
400 psig 1200 psig 2½"
400 psig 1200 psig 2½"
Assembled Length
Minimum Minimum
Burst Pressure Bend
Female Swivel
Adapter
Applications – Systems
Typical Cooling and Heating Refrigeration Cycles
Note: For standard heat pump operation only
Cooling Refrigeration Cycle
When the wall thermostat calls
for COOLING, the reversing valve directs the ow of the refrigerant, a
hot gas, from the compressor to the water-to-refrigerant heat exchanger. There, the heat is removed by the water, and the hot gas condenses
to become a liquid. The liquid then ows through a thermal expansion
valve to the air-to-refrigerant heat
exchanger coil. The liquid then
evaporates and becomes a gas, at the same time absorbing heat and cooling the air passing over the surfaces of
the coil. The refrigerant then ows as
a low pressure gas through the revers­ing valve and back to the suction side of the compressor to complete the cycle.
Heating Refrigeration Cycle
When the wall thermostat calls
for HEATING, the reversing valve directs the ow of the refrigerant, a
hot gas, from the compressor to the air-to-refrigerant heat exchanger coil. There, the heat is removed by the air passing over the surfaces of the coil and the hot gas condenses and
becomes a liquid. The liquid then ows through a thermal expansion
valve
to the water-to-refrigerant heat
exchanger. The liquid then evaporates
and becomes a gas, at the same time absorbing heat and cooling the water.
The refrigerant then ows as a low
pressure gas through the reversing valve and back to the suction side of the compressor to complete the cycle.
Air to
Refrigerant
Heat
Exchanger
Coil
Blower
Air to
Refrigerant
Heat
Exchanger
Coil
Blower
Return Air
Conditioned Air
(Cooling)
Return Air
Conditioned Air
(Heating)
Thermal
Expansion Valve
Reversing Valve
Thermal
Expansion Valve
Reversing Valve
Water to Refrigerant
Heat Exchanger
Water In
Water Out
Sensing Bulb and Capillary Tube
Compressor
Water to Refrigerant
Heat Exchanger
Water In
Water Out
Sensing Bulb and
Capillary
Tube
Compressor
Applications – Unit Selection
Achieving optimal performance with water source heat
pump systems requires both accurate system design and proper equipment selection. Use a building load program to
determine the heating and cooling loads of each zone prior
to making equipment selections. With this information, the McQuay SelectTools™ software selection program for
Water Source Heat Pumps can be used to provide fast, ac-
curate and complete selections of all McQuay water source heat pump products. SelectTools software is available by contacting your local McQuay Representative.
While we recommend that you use McQuay SelectTools software for all unit selections, manual selections can be accomplished using the same zone load information and the capacity tables available in this catalog.
Boiler / Tower Application Manual Selections:
The following example illustrates a typical selection for
a zone in a boiler/tower system for a commercial building.
A building load program determines that this zone needs 10,430 BTUH of total cooling, 6,950 BTUH of sensible cooling and 9,150 BTUH of total heating. The water tem-
peratures for the boiler/tower system are 90ºF for cooling and 70ºF for heating. The return air temperature is 80ºF dry bulb with 67ºF wet bulb for cooling and 70ºF for heating.
Zone Requirements:
Total Cooling Load = 10,430 BTUH Sensible Cooling Load = 6,950 BTUH Total Heating Load = 9,150 BTUH
Air Flow Required = 275 CFM Return Air Cooling = 80ºFDB/ 67ºFWB Return Air - Heating = 70ºFDB
Since a McQuay Model MHC 009 produces approxi-
mately 10,000 BTUH of cooling, it is not sufcient for this zone and a model MHC 012 should be considered. Model MHC is chosen because it is specically designed for a boiler/tower application. Typical water ow rates for boiler/tower applications are 2.0 to 2.5 GPM per ton and in
this example no antifreeze is used.
Selection:
Model .............................MHC 012 (Boiler / Tower model)
Total Cooling Capacity @ 90 EWT = 11,511 BTUH
Sensible cooling capacity @ 90 EWT = 7,660 BTUH Total Heating Capacity @ 70 EWT = 14,160 BTUH CFM = 275 Water Flow required to meet capacity = 8 GPM Water Pressure drop = 2.5 (FT. H2O)
Final Selection ....................................................MHC 012
Geothermal Applications:
The following example illustrates the same zone in a
geothermal application.
The load requirements for the zone are the same as the
above example – 10,430 BTUH of total cooling and 6,950
BTUH of sensible cooling and 9,150 BTUH of heating. Geothermal loop software programs are available to help
determine the size of the loop eld based on:
Desired entering water temperatures for the system.
Specic acreage available for the loop which produces
specic min./max loop temps for the unit selection.
Entering water temperatures for geothermal systems can
be as high as 90º to 100ºF and as low as 30ºF based on the
geographical location of the building. Water ow rates are typically 2.5 to 3 GPM per ton and the use of antifreeze is required in most northern applications.
Zone Requirements:
Total Cooling Load = 10,430 BTUH Sensible Cooling Load = 6,950 BTUH Total Heating Load = 9,150 BTUH
Air Flow Required = 275 CFM Return Air Cooling = 80 DB / 67 WB Return Air - Heating = 70 DB
A McQuay Model MHW is chosen for this geothermal application. Model MHW offers insulated water piping for condensation considerations and a different freezestat set­ting to allow entering water temperatures lower than 40ºF (with antifreeze). Output capacities should be recalculated using the antifreeze reduction tables that are shown on page
34. The Model MHW 012 is rst considered but may not
meet the heating load because of the reduced entering water temperatures (35ºF) and an antifreeze solution of 21 % propylene (see page 39).
Selection:
Model ..................................MHC 012 (Geothermal model)
Total cooling capacity @ 100 EWT = 10,555 BTUH x .980 = 10,344
Sensible cooling capacity @ 100 EWT = 7,257 BTUH x .980 = 7,112 Total heating capacity @ 35 EWT = 9,430 BTUH x .975 = 9,240 Btuh CFM = 284 Water Flow required to meet capacity = 2.4 GPM Water Pressure drop = 2.5 x 1.5 = 3.75 (FT. H2O)
Final Selection ....................................................MHC 012
Note:
In applications where the zone may be a corner ofce or have excessive glass area, the heating load could be greater than the heating output capacity of the MHC 012 model (say 7,800 BTUH). The choices are to upsize the unit to the next model available (015).
Cooling Capacity Data – Console Unit Size 007
EWT
30
40
50
60
70
80
85
90
GPM
1.0
1.
2.0
1.0
1.5
2.0
1.0
1.5
2.0
1.0
1.5
2.0
1.0
1.5
2.0
1.0
1.5
2.0
1.0
1.5
2.0
1.0
1.5
2.0
WPD
0.6
5
1.
3
2.2
0.6
1.3
2.2
0.6
1.3
2.2
0.6
1.3
2.2
0.6
1.3
2.2
0.6
1.3
2.2
0.6
1.3
2.2
0.6
1.3
2.2
EA LWT TOT SEN kW EER TOT kW EER THR
75 80 85 75 80 85 75 80 85 75 80 85 75 80 85 75 80 85 75 80 85 75 80 85 75 80 85 75 80 85 75 80 85 75 80 85 75 80 85 75 80 85 75 80 85 75 80 85 75 80 85 75 80 85 75 80 85 75 80 85 75 80 85 75 80 85 75 80 85 75 80
85
63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71
50
52.1
53.5
43.9
44.8
45.8
40.5
41.2
41.9
60.3
61.7
63.2
53.7
54.7
55.7
50.3
51.1
51.8
69.9
71.3
72.8
63.5
64.4
65.4
60.2
60.9
61.6
79.4
80.8
82.3
73.2
74.1
75.1
69.9
70.7
71.4
88.9
90.2
91.6
82.8
83.7
84.7
79.7
80.4
81.1
98.3
99.6
101.0
92.4
93.3
94.3
89.4
90.1
90.8
103.1
104.3
105.7
97.2
98.1
99.0
94.2
94.9
95.6
107.7
109.0
110.3
102.0
102.9
103.8
99.1
99.7
100.4
System ISO
9791
.7
10556 11371 10000 10792 11642 10085 10892 11759
9368 10106 10891
9583 10352
11173
9673 10456 11291
8931
9639 10393
9149
9889 10679
9240
9995 10802
8487
9163
9882
8702
9412 10169
8793
9518 10292
8041
8680
9365
8251
8925
9648
8340
9030
9769
7596
8199
8842
7800
8434
9117
7885
8534
9237
7369
7958
8582
7573
8191
8852
7657
8289
8968
7139
7713
8319
7342
7946
8587
7426
8043
8702
7001 7188 7356 7099 7291 7464 7139 7334 7510 6806 6998 7169 6905 7101 7278 6946 7145 7324 6609 6804 6980 6707 6907 7089 6748 6951 7135 6409 6607 6789 6506 6710 6897 6547 6754 6942 6209 6409 6595 6303 6510 6700 6342 6553 6746 6013 6215 6403 6103 6310 6503 6140 6350 6547 5915 6119 6308 6003 6212 6406 6040 6251 6448 5815 6022 6213 5903 6114 6310 5939 6152 6351
.186
0
0.163
0.136
0.143
0.112
0.076
0.129
0.095
0.055
0.268
0.254
0.237
0.233
0.212
0.187
0.221
0.197
0.169
0.338
0.333
0.324
0.309
0.296
0.280
0.299
0.284
0.266
0.398
0.399
0.398
0.373
0.369
0.362
0.365
0.359
0.349
0.452
0.456
0.461
0.429
0.431
0.431
0.422
0.422
0.420
0.507
0.514
0.520
0.484
0.488
0.492
0.477
0.480
0.483
0.533
0.542
0.551
0.512
0.518
0.522
0.505
0.510
0.513
0.557
0.569
0.580
0.538
0.547
0.553
0.532
0.539
0.544
52.6
64.9
83.4
69.8
96.3
153.0
78.0
114.6
214.6
35.0
39.7
45.9
41.1
48.9
59.9
43.7
53.0
66.9
26.4
29.0
32.1
29.6
33.4
38.1
30.9
35.2
40.7
21.4
23.0
24.8
23.3
25.5
28.1
24.1
26.5
29.5
17.8
19.0
20.3
19.2
20.7
22.4
19.8
21.4
23.3
15.0
16.0
17.0
16.1
17.3
18.5
16.5
17.8
19.1
13.8
14.7
15.6
14.8
15.8
16.9
15.2
16.3
17.5
12.8
13.6
14.3
13.6
14.5
15.5
14.0
14.9
16.0
9517 10282 11098
9727 10519 11369
9812 10619 11486
9094
9833 10618
9310 10079 10900
9400 10183 11017
8658
9366 10120
8876
9616 10406
8967
9722 10528
8214
8890
9609
8429
9139
9896
8520
9244 10019
7768
8407
9092
7978
8652
9375
8066
8757
9496
7323
7926
8569
7527
8161
8844
7611 8260 8964 7096 7685 8309 7300 7918 8579 7384 8016 8695 6866 7440 8046 7069 7673 8314 7153 7770 8429
.187
0
0.163
0.137
0.146
0.115
0.079
0.136
0.101
0.061
0.269
0.255
0.238
0.236
0.215
0.189
0.227
0.204
0.175
0.339
0.334
0.324
0.312
0.299
0.283
0.305
0.290
0.272
0.398
0.399
0.399
0.376
0.372
0.365
0.371
0.365
0.356
0.453
0.457
0.462
0.432
0.434
0.434
0.428
0.429
0.426
0.508
0.515
0.521
0.487
0.491
0.495
0.484
0.487
0.489
0.534
0.543
0.551
0.515
0.521
0.525
0.512
0.516
0.520
0.558
0.570
0.581
0.541
0.549
0.556
0.538
0.546
0.550
50.9
62.9
80.9
66.6
91.5
144.0
72.3
104.7
187.8
33.8
38.5
44.6
39.5
47.0
57.6
41.3
50.0
62.9
25.5
28.1
31.2
28.5
32.1
36.7
29.4
33.5
38.7
20.6
22.3
24.1
22.4
24.6
27.1
23.0
25.3
28.2
17.2
18.4
19.7
18.5
20.0
21.6
18.8
20.4
22.3
14.4
15.4
16.4
15.5
16.6
17.9
15.7
17.0
18.3
13.3
14.1
15.1
14.2
15.2
16.3
14.4
15.5
16.7
12.3
13.1
13.8
13.1
14.0
15.0
13.3
14.2
15.3
10232 10922 11651 10318 11012 11747 10364 11063 11802 10046 10739 11468 10162 10862 11602 10217 10924 11669
9815 10503 11224
9946 10647 11384 10009 10716 11464
9542 10219 10935
9687 10384
11117
9756 10460 11201
9248
9901 10598
9395 10074 10796
9465 10155 10887
8956
9581 10244
9099
9745 10438
9165
9823 10533
8801
9419 10069
8948
9584 10260
9014
9661 10350
8637
9248
9889
8790
9419 10081
8857
9496 10171
16 McQuay Ennity Console Water Source Heat Pumps Catalog 1104-2
Cooling Capacity Data – Console Unit Size 007
EWT
GPM
1.0
1.
100
5
2.0
1.0
110
1.5
2.0
Capacity Tables Notes: EWT = Entering Water Temperature (°F) WPD = Water Pressure Drop (Ft. Hd) EA = Entering Air Temperature (°F) LWT = Leaving Water Temperature (°F) TOT = Total Heat (Btu) SEN = Sensible Heat (Btu) kW = Kilowatts COP = Coefcient of Performance THA = Total Heat of Absorption (Btu) THR = Total Heat of Rejection (Btu) GPM = Gallons Per Minute
Performance data based on 208/1ph power supply.
WPD
0.6
1.
2.2
0.6
1.3
2.2
3
EA LWT TOT SEN kW EER TOT kW EER THR
75 80 85 75 80 85 75 80 85 75 80 85 75 80 85 75 80 85
63 67 71 63 67 71 63 67 71 63 67 71 63 67 71 63 67 71
17.1
1
118.3
119.6
111.6
112.4
113.3
108.8
109.4
110.1
126.3
127.5
128.7
121.1
121.9
122.8
118.4
119.0
119.7
System ISO
6669 7212 7784 6870 7443 8050 6953 7539 8162 6185 6694 7231 6382 6923 7495 6463 7018 7606
5615 5826 6023 5700 5916 6117 5735 5953 6157 5410 5626 5830 5493 5715 5921 5527 5751 5960
.602
0
0.619
0.634
0.585
0.599
0.611
0.580
0.593
0.604
0.641
0.663
0.684
0.628
0.647
0.663
0.624
0.641
0.656
11.1
11.7
12.3
11.7
12.4
13.2
12.0
12.7
13.5
9.7
10.1
10.6
10.2
10.7
11.3
10.4
10.9
11.6
6396 6939 7511 6597 7170 7777 6680 7266 7888 5912 6421 6958 6109 6650 7222 6190 6745 7332
.603
0
0.619
0.635
0.588
0.602
0.614
0.587
0.599
0.610
0.642
0.664
0.685
0.631
0.649
0.666
0.630
0.647
0.663
10.6
11.2
11.8
11.2
11.9
12.7
11.4
12.1
12.9
9.2
9.7
10.2
9.7
10.2
10.8
9.8
10.4
11.1
8286 8881 9503 8444 9060 9706 8513 9139 9797 7902 8481 9083 8066 8667 9293 8138 8749 9385
17 McQuay Ennity Console Water Source Heat Pumps Catalog 1104-2
Loading...
+ 39 hidden pages