McQuay MCW200D, MCW800D, MCW900D, MCW400D, MCW1000D Technical Manual

...
CEILING CONCEALED Chilled Water Fan Coil Unit
Models: MCW200D MCW800D MCW300D MCW900D MCW400D MCW1000D MCW500D MCW1200D MCW600D MCW1400D
Technical Manual
Engineered for flexibility and performance.
TM
1
Nomenclature.............................................................................................................................. 2
Main Features .............................................................................................................................3
Specications ............................................................................................................................. 4
Sound Pressure Level ................................................................................................................ 6
Performance Data ....................................................................................................................... 7
Air Flow vs ESP Table ................................................................................................................ 8
Operating Limits ......................................................................................................................... 9
Water Flow vs Pressure Drop Chart ....................................................................................... 10
Outlines and Dimensions ........................................................................................................ 11
Wiring Diagrams ....................................................................................................................... 12
Installation .................................................................................................................................13
Exploded-view & Part List .......................................................................................................15
Guide Specications ................................................................................................................ 17
Contents
“McQuay” is a registered trademark of McQuay International. All rights reserved throughout the world.
© 2007 McQuay International.
Bulletin illustrations cover the general appearance of McQuay International products at the time of publication. We reserve the right to change
design and construction specications at any time without notice.
Note: Installation and maintenance are to be performed only by qualied personnel who are familiar with
local codes and regulations, and experienced with this type of equipment.
Caution: Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.
Warning: Moving machinery and electrical power hazard may cause severe personal injury or death.
Disconnect and lock off power before servicing equipment.
2
Nomenclature
MCW 200 D- 8 R X F-A A F1 - E
Export
1-100mm Extended Drain Pan 2-200mm Extended Drain Pan Omitted for Standard Drain Pan
Description of Products: A-Standard Drain Pan F-Extended Drain Pan G-Extended Drain pan+2Way Valve H-Extended Drain Pan+3Way Valve I-Standard Drain Pan+2Way Valve J-Standard Drain Pan+3Way Valve K-Standard Drain Pan+Controller L-Extended Drain Pan+Controller M-Extended Drain Pan+2 Way Valve+Controller N-Extended Drain Pan+3 Way Valve+Controller O-Standard Drain Pan+2 Way Valve+Controller P-Standard Drain Pan+3 Way Valve+Controller
Material of Drain Pan A-Standard Material S-Stainless Steel
Power Supply: A-220V/1PH/50Hz
With Filter
Back Rerurn Air Plenum With Bottom Removal Filter
Pipe Connection: R-Right Hand
L-Left Hand(Facing Air Flow)
75Pa External Static Pressure
Design Series: D-4 Rows and 2 Pipes
Nominal Air Flow(CFM)
McQuay Horizontal Ceiling concealed Fan Coil Unit
3
Main Features
General
The new MCW-D FCUs are specically designed to satisfy high cooling capacity application requirement. They
represent one of the most cost effective solutions to provide a comfortable environment for both commercial and residential applications. Their quiet operation, compact dimensions and particularly low height, make units ideal for ceiling concealed installation even in buildings with narrow ceiling spaces. Units are standard supplied with
soundproofed suction plenum and air lter. Centrifugal fans, with forward-curved blades, are statically and dynamically
balanced and driven by single-phase motors with three speeds.They feature elegant design, advanced structure,
high efciency, low noise, convenient installation and low maintenance. They are widely used in houses, shopping malls, hospitals and ofce etc.
Higher Cooling Capacity in High Delta T Application
These units are particularly suitable for high External Static Pressure and high Delta T(chilled water temperature difference) applications. They can delivery more cooling capacity in high Delta T conditions with the specially designed fans & motors, coils and excellent combination of them.
Low Chilled Water Pressure Drop
In order to meet even the most demanding customer requirements, the new FCUs adopt the most reasonable and optimization water circuit design and utilize the national level thermal test room to guarantee both the perfect performance and a low chilled water pressure drop.
Extra High Air Flow Volume at High ESP
These units can supply more air ow at high ESP. 10 models of MCW-D cover an air ow range from 340 to 2380CMH
at medium speed with ESP of 75Pa in wet coil condition.
Air Filter
All units can provide up to one-inch thick washable lters. Filters are held by a removable metal strip and can be
easily pulled out from the bottom for cleaning or replacement.
High Efciency Heat Exchanger
A boundary layer lm of air adhering to the n surface will insulate the n surface and severely reduces the heat exchange efciency. McQuay slit n design eliminates this boundary layer of air and creates continuous turbulence for best heat exchange efciency.
Flexibility
Units are available with left or right hand water connections, which can be easily switched in the eld by changing the positions of the fan-motor assembly and the supply air ange assembly if required.
Compact Design
The low height design makes this fan coil unit series ideally suited for the tight ceiling concealed installation
Low Noise Design
Enlarged fan wheels design allows lower fan RPM selection for the same external static pressure and airow requirement. Thereby noise level is signicantly reduced.
4
Specications
General Data
MODEL 200D 300D 400D 500D 600D 800D 900D 1000D 1200D 1400D
AIR FLOW
HIGH
m3/h 332 606 757 894 1154 1446 1622 2115 2455 2748
CFM 195 356 445 526 679 851 954 1244 1444 1616
MEDIUM
m3/h 311 527 709 859 1120 1408 1538 1980 2217 2576
CFM 183 310 417 505 659 828 905 1165 1304 1515
LOW
m3/h 237 331 501 616 770 1096 1201 1465 1569 1870
CFM 139 195 295 362 453 645 706 862 923 1100
TOTAL COOLING CAPACITY
W 2044 3350 4402 5003 6300 8087 9022 10808 11939 13523
BTU/h 6974 11430 15020 17070 21496 27593 30783 36877 40736 46140
SENSIBLE COOLING CAPACITY
W 1224 2150 2897 3450 4502 5468 6428 7710 8898 10084
BTU/h 4176 7336 9885 11771 15361 18657 21932 26307 30360 34407
WATER FLOW RATE
m3/h 0.223 0.341 0.439 0.499 0.632 0.803 0.889 1.067 1.223 1.368
USGPM 0.981 1.500 1.932 2.196 2.781 3.533 3.912 4.695 5.381 6.019
WATER PRESSURE DROP (COOLING)
KPa 5.7 12.0 24.6 11.1 18.2 15.8 19.9 29.0 22.2 30.3
PSI 0.827 1.740 3.567 1.610 2.639 2.291 2.886 4.205 3.219 4.394
EXTERNAL STATIC PRESSURE
Pa 75 75 75 75 75 75 75 75 75 75
in.wg 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3
RATED POWER INPUT W 74 98 107 123 167 268 275 304 501 555
SOUND PRESSURE LEVEL DB(A) 42.9 43.1 45.9 46.2 47.9 50.0 48.8 49.1 53.3 53.0
CONDENSATE DRAIN PIPE R3/4
DIMENSION
LENGTH mm 714 934 1014 1114 1214 1464 1564 1664 1464 1664
WIDTH mm 534 534 534 534 534 534 534 534 599 599
HEIGHT mm 251 251 251 251 251 251 251 251 295 295
PACKING DIMENSION
LENGTH mm 737 957 1037 1137 1237 1487 1587 1687 1487 1687
WIDTH mm 553 553 553 553 553 553 553 553 618 618
HEIGHT mm 276 276 276 276 276 276 276 276 321 321
NET WEIGHT
kg 21 25 29 31 33 44 46 49 53 57
lb 46.2 55 63.8 68.2 72.6 96.8 101.2 107.8 116.6 125.4
GROSS WEIGHT
kg 23 28 32 34 37 48 51 54 58 63
lb 50.6 61.6 70.4 74.8 81.4 105.6 112.2 118.8 127.6 138.6
OPERATING WEIGHT kg 22 26 31 33 35 46 49 52 56 61
Notes:
1. ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2. ALL THE UNITS ARE BEING TESTED UNDER FOLLOWING CONDITION: a) COOLING: 27°C DB/19.5°C WB INDOOR AND WATER INLET 7°C OUTLET 12°C b) HEATING: 21°C DB INDOOR AND WATER 60°C INLET.WATER FLOW:SAME WITH COOLING CONDITION.
3. THE NOMINAL AIR FLOW, POWER INPUT AND CAPACITY TEST IS UNDER THE POWER SUPPLY OF 220V/1PH/50HZ.
5
COMPONENTS DATA
MODEL
200D 300D 400D 500D 600D 800D 900D 1000D 1200D 1400D
FAN
TYPE CENTRIFUGAL (BLADE: FORWARD-CURVED)
QUANTITY 1 2 3 4 3
MATERIAL GALVANIZED STEEL
DRIVE DIRECT DRIVE
DIAMETER
mm 160 200
in 6.299 7.875
LENGTH
mm 200 160 200 160 190
in 7.874 6.299 7.874 6.299 7.480
MOTOR
TYPE Split-capacitoR motoR with ball beaRing
NUMBER OF MOTORS 1 2
POWER SUPPLY 220-240V/1/50
IP/INSULATION CLASS IP20/Class B
COIL
TYPE Seamless copper tube mechanically bonded to congurated aluminum n
TESTING PRESSURE Pressure test:3.3MPa for 1 minute; Leakage test:1.6MPa for 5 minutes
TUBE
MATERIAL COPPER
DIAMETER
mm 9.52
in 3/8
THICKNESS
mm 0.3
in 0.012
FIN
MATERIAL ALUMINIUM
THICKNESS
mm 0.11
in 0.0043
FACE AREA
m20.1 0.14 0.16 0.18 0.20 0.25 0.27 0.29 0.25 0.29
ft21.06 1.54 1.71 1.93 2.15 2.70 2.91 3.13 2.70 3.13
ROW 4
FIN PER INCH 11
AIR FILTER (OPTIONAL)
SIZE
LENGTH
mm 502 722 802 902 1002 1252 1352 1452 1252 1452
in 19.76 28.43 31.57 35.51 39.45 49.29 53.23 57.17 49.29 57.17
WIDTH
mm 244 244 244 244 244 244 244 244 244 244
in 9.61 9.61 9.61 9.61 9.61 9.61 9.61 9.61 11.34 11.34
THICKNESS
mm 25 25 25 25 25 25 25 25 25 25
in 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98
Loading...
+ 13 hidden pages