McQuay MCM, MWMV, M5CM, M5CMY, MCK Service Manual

...
SERVICE GUIDE BOOK
MCQUAY Service Guide Book Table of Contents
1
1.0 MODEL NAME
1.1 Product Name Description ............................... 2
2.0 CONVERSION TABLE
2.1 Conversion Table ............................... 3
3.0 PRODUCT MAINBOARD VS HANDSET MATRIX
3.1 Product Mainboard vs. Handset Matrix ............................... 4
4.0 HANDSET OPERATING GUIDE
4.1 G6 ............................... 6
4.2 G7 ............................... 7
4.3 G11 ............................... 8
4.4 G17 ............................... 9
4.5 GS01 ............................... 10
4.6 APJ1 ............................... 12
4.7 SLM3 ............................... 14
4.8 SLM8 ............................... 15
4.9 Sequential LCD ............................... 17
4.10 Netware 3/3C ............................... 18
4.11 Rooftop Panel ............................... 19
4.12 Chiller Panel ............................... 20
4.13 MC301 ............................... 21
4.14 MC303 ............................... 24
5.0 CONTROLLER SETTING
5.1 Auto Random Restart ............................... 26
5.2 Hot Keep Selection ............................... 26
5.3 Sequential Board (SQ2.0) ............................... 28
5.4 Chilled Water Fan Coil Unit – W1V3 ............................... 30
5.5 Chilled Water Fan Coil Unit – W2.0
5.6 Hardware Setting – SLM8
...............................
...............................
31 32
6.0 CONVERSION CONFIGURATION
6.1 Auxiliary Heater Conversion 33
6.2 Multi Split Conversion ............................... 36
6.3 U1.5 Æ L208A Conversion ............................... 37
6.4 WMF U1.4 to L2EF Conversion ............................... 38
6.5 SQ Board for Wiring up to 1000m Conversion ............................... 39
6.6 Room Sensor On Netware 3 ............................... 41
7.0 SERVICE DIAGNOSIS
7.1 LED Lights Diagnosis Table ............................... 42
7.2 Error Codes Diagnosis By Handset ............................... 62
7.3 MDS Diagnosis ............................... 72
7.4 General Check ............................... 75
7.5 General Troubleshooting Guide ............................... 76
APPENDIX
A. Resistance – Temperature Characteristic ............................... 77
B. MDS Compatibility ............................... 80
C. MDS Outdoor Capacity Dip Switch Setting ............................... 81
D. Cable Length Of Wired Handset ............................... 82
“Mcquay” is a registered trademark of Mcquay International. All rights reserved.
© 2012 Mcquay International. All rights reserved throughout the world.
Bulletin illustrations cover the general appearance of Mcquay International products at the time of publication.
We reserve the right to change design and construction specification at any time without notice
MCQUAY Service Guide Book Model Name
2
1.0 MODEL NAME
1.1 Product Name Description
No. Description Generic Model Name MCQUAY Brand
1 Wall Mounted Fan Coil Unit WM / 5WM MWM / M5WM
2 Wall Mounted AC Inverter Fan Coil Unit WMV MWMV
3 Wall Mounted DC Inverter Fan Coil Unit 5WMX M5WMX
4 Wall Mounted DC Inverter-Y Fan Coil Unit 5WMY M5WMY
5 Ceiling Exposed Fan Coil Unit CE / 5CE MCM / M5CM
6 Ceiling Exposed Inverter-Y Fan Coil Unit 5CEY M5CMY
7 Ceiling Cassette Fan Coil Unit CK / 5CK MCK / M5CK
8 Ceiling Cassette Inverter-Y Fan Coil Unit 5CKY M5CKY
9 Ceiling Concealed Fan Coil Unit CC / 5CC MCC / M5CC
10 Ceiling Concealed Inverter-Y Fan Coil Unit 5CCY M5CCY
11 Ducted Split Blower Unit SB MDB
12 Chilled Water Fan Coil Unit CW MCW
13 Water Source Heatpump Split Unit WSS / 5WSS MWSS / M5WSS
14 Horizontal Water Source Heatpump Unit WH MWH
15 Air Cooled Mini Chiller AC / 4AC / 5AC MAC / M4MAC /
M5MAC
16 Single Split Condensing Unit SL / 4SL / 5SL MLC / M4LC / M5LC
17 Single Split AC Inverter Condensing Unit SLV MLCV
18 Single Split DC Inverter Condensing Unit 5SLX M5LCX
19 Single Split DC Inverter Condensing Unit 5SLY M5LCY
20 Modular Split Condensing Unit MSS / 4MSS MMC / M4MC
21 Multi Split Series MSD / 4MSD MMSD / M4MSD
MST / 4MST MMST / M4MST
MSH MMSH
22 Multi Split AC Inverter Condensing Unit MSV MMSV
23 Multi Split DC Inverter Condensing Unit 5MSX M5MSX
24 Multi Split DC Inverter Condensing Unit 5MSY M5MSY
25 Multi Digital Scroll Units MDS/ 5MDS MDS/ 5MDS
26 Horizontal Condensing Unit HDC / 5HDC AHDC / A5HDC
27 Vertical Condensing Unit VCU MVCU
28 Air Cooled Roof Top Packaged Air
Conditioner
RT / 4RT / 5RT MRT / M4RT / M5RT
29 Air Cooled Inverter Mini Chiller 5ACV M5ACV
MCQUAY Service Guide Book Conversion Table
3
2.0 CONVERSION TABLE
2.1 Conversion Table
Capacity
Btu/hr MBH kCal/Hr kW
1 0.001 0.252 0.293 x 10
-
3
1000 1 252 0.293
3.968 0.004 1 1.162 x 10
-
3
3412 3.412 860.04 1
Pressure
PSI kg/cm
2
W.G. Pascal
(in.) (ft.) (Pa)
1 0.07 27.7 2.309 0.69 x 104
14.22 1 394.08 32.84 9.81 x 104
3.61 x 10
-
2
2.538 x 10
-
3
1 0.083 248.84
1.45 x 10
-
4
0.1 x 10
-
4
0.004 3.349 x 10
-
4
1
Flow Rate
L/s m
3
/hr m3/s U.S. GPM CFM
1 3.6 0.001 15.85 2.119
0.278 1 0.278 x 10
-
3
4.403 0.588
1000 3600 1 15850 2119
0.063 0.227 0.063 x 10
-
3
1 0.1337
0.472 1.7 0.472 x 10
-
3
7.481 1
Temperature Velocity
fps m/s fpm
1 0.305 60
3.281 1 196.9
0.017 0.005 1
Volume
L m
3
U.S. G.P.M. ft3
1 0.001 0.264 0.0353
1000 1 264 35.3
3.785 3.785 x 10
-
3
1 0.134
28.315 0.028 7.48 1
Area
in
2
ft2 m
2
cm2
1 6.94 x 10
-
3
6.452 x 10
-
4
6.452
144 1 0.093 929.03
1550.06 10.764 1 1 x 104
0.155 1.076 x 10
-
3
1 x 10
-
4
1
°F = (1.8 x °C) + 32
8.1
32°=°F
C
MCQUAY Service Guide Book Product Mainboard vs. Handset Matrix
4
3.0 PRODUCT MAINBOARD VS. HANDSET MATRIX
3.1 Product Mainboard vs. Handset Matrix
Type No.
Main Board
Model
L2.0
L2
GSN
L2
08A
R_1_
01A
W_2_
03A
C_2_
01A
2P2065
69-4
U1
SB125
SQ
2.0
VA2.0 VA3.0
Handset
Standard Optional
DX
1 WM - F Series
9
G17 SLM3+AC5300/Netware 3/SLM8
2 WM - G Series
9
G17SLM3+AC5300/Netware 3/SLM8
3 WMS - G Series
9
G17SLM3+AC5300/Netware 3/SLM8
4 WM – J Series
9
GS01 -
5 CK - A/B/C/E Series
9
G17/GS01 SLM3+AC5300/Netware 3/SLM8
6 CE - D Series
9
G17SLM3+AC5300/Netware 3/SLM8
7 CE - E Series
9
G17SLM3+AC5300/Netware 3/SLM8
8 CC - C Series
9
SLM3 Netware 3 / SLM8
9 CC - D Series
9
Netware 3 SLM3
10 SB - B/C Series
SB 75 – 100B/BR
9
SLM3 Netware 3 / SLM8
SB 125 – 150B/BR
9
SLM3 -
SB 125CR
9
SLM3 ­SB 150B2/BR2 – 600B4/BR4
9
SQ-LCD -
11 SB D/ER Series
SB 75 – 100D/ER
9
SLM3 Netware 3 / SLM8
SB 125 – 150D/ER
9
SLM3 ­SB 125D2 – 500D4
9
SQ-LCD ­SB 125ER2 – 600ER4
9
SQ-LCD -
12 RT Series
RT 55 – 120A/AR
9
SLM3 -
RT 150 – 420A/AR
9
SQ-LCD ­5RT 90 – 250BR
9
RT Panel -
13 WMX – F/G Series
9
G17 SLM3 + AC5300
CKX – A/C Series
9
G17 SLM3 + AC5300
CEX – E Series
9
G17 SLM3 + AC5300
CCX C Series
9
SLM3 Netware 3 / SLM8
14 WMY – J Series
9
G17/GS01 -
15 WMY – K Series
9
APJ1 -
16 CKY – E Series
CEY – E Series CCY – C Series
9 9 9
GS01 GS01
Netware 3C
Netware 3C
4
MCQUAY Service Guide Book Product Mainboard vs. Handset Matrix
5
Type
No.
Main Board (IC)
Model
W2 MC1.0 LWS2 APM01CB APM02D
Handset
Standard Optional
CW FCU
13 WM – GW Series
9
G17
SLM3+AC5300/Netware 3/SLM8
14 CK – AW/MWH/CW Series
9
G17
SLM3+AC5300/Netware 3/SLM8
15 CE – DW Series
9
G17
SLM3+AC5300/Netware 3/SLM8
16 CE – EW Series
9
G17
SLM3+AC5300/Netware 3/SLM8
17 CC – CW Series
9
SLM3
Netware 3 / SLM8
18 SB – BW Series
9
N/A
-
Mini Chiller
19 AC – C Series
AC 20 – 60C/CR
9
C. Panel
-
AC 80 – 150C/CR
9
C. Panel
-
5AC 20 – 25C/CR
9
C. Panel
-
5AC 30 – 55C/CR
9
C. Panel
-
WSHP
20 5WMWS – GR
9
G17
SLM3+AC5300/Netware 3/SLM8
21 5CKWS – AR/CR
9
G17
SLM3+AC5300/Netware 3/SLM8
22 5CCWS – CR
9
SLM3
Netware 3 / SLM8
23 WH – B Series
WH 11 – 20B/BR
9
SLM15A
-
WH 25 – 70B/BR
9
APW04A
-
5
MCQUAY Service Guide Book Handset Operating Guide
6
4.0 HANDSET OPERATING GUIDE
4.1 G6
Operation Guide
1. “ON/OFF” Switch
2. Temperature Setting
Press button to increase or decrease the set temperature. Setting range are between 16°C to 30°C setting (60°F to 80°F) (Optional setting from 20°C to 30°C).
Press ▲ or button simultaneously will toggle the temperature setting between °C and °F.
3. Automatic Air Swing
The swing angle ranging from horizontal to 25° to bottom.
4. “SLEEP” MODE
This function can be activated in COOL, HEAT & AUTO mode operation. If it is activated in “COOL” mode, the set temperature will be increase 0.5°C after 30 minutes, 1°C after 1 hour and 2°C after 2 hours. Whereas in “HEAT” mode, the set temperature will decrease by 1°C after 30mins, 2°C after 1 hour and 3°C after 2 hours.
5. Timer Setting
Press button to activate the timer setting
(from 1 hour to 15 hour) of the air conditioning unit. To cancel the timer setting, press the button continuously until the timer display goes off.
6. Operation Modes
Cooling only unit : Cool Dry   → Fan
Heatpump unit : Auto Cool  Dry Fan Heat    
7. Fan Speed and Ventilation Mode Selection
8. Signal Transmission Indication
Blink to confirm the last setting has been
send to the unit.
MCQUAY Service Guide Book Handset Operating Guide
7
4.2 G7
Operation Guide
1. Transmission Source
2. Signal Transmission Indication
Blink to confirm the last setting has been send to the unit.
3. On/Off Button
4. Temperature Setting
The temperature setting range is from 16°C to 30°C (Optional setting 18°C to 30°C).
Press both buttons simultaneously to toggle the temperature setting between °C and °F.
5. Operation Mode
Cooling only unit: COOL, DRY & FAN.
Heatpump unit: AUTO, COOL, DRY,
FAN & HEAT.
6. Fan Speed Selection
7. On Timer Setting
8. Off Timer Setting
9. Automatic Air Swing (Optional)
Press button to activate the automatic air swing function. Press again to stop the louver at the desired direction.
10. Sleep Mode Setting
This function is available under COOL, HEAT & AUTO mode.
When it is activated in COOL mode, the set temperature will be increased
0.5°C after 30mins, 1°C after 1 hour and 2°C after 2 hours.
When it is activated in HEAT mode, the set temperature will be decreased 1°C after 30mins, 2°C after 1 hour and 3°C after 2 hours.
11. Clock Time Setting
Press button + or - to increase or decrease the clock time.
12. Turbo Function (Optional-Only Applicable To Inverter Unit)
Press button for fast cooling or heating operation.
The temperature will be increased internally if it is in the HEAT mode, decreased if in COOL or DRY mode. Fan speed will be increased if it is not at maximum speed.
The temperature & fan speed will resume to user setting if the button is pressed again or after 20mins.
Available under HEAT, COOL & DRY
modes only.
MCQUAY Service Guide Book Handset Operating Guide
8
4.3 G11
Operation Guide
1. “ON/OFF” Button
2. Temperature Setting
The temperature setting range is from 16°C to 30°C.
Press both buttons simultaneously to toggle and from °C to °F setting.
3. Operation Mode
Cooling only unit: COOL (
), DRY ( )
and FAN (
).
Heat pump unit: AUTO, COOL (
), DRY
(
), FAN ( ) and HEAT ( ).
4. Fan speed selection
Press the button continuously will toggle the fan speed in the following order: Low
( ) –––: Med ( ) –––: High ( ) –––: Auto
5. ON Timer Setting
6. OFF Timer Setting
7. Automatic Air Swing
Press the SWING (
) button to activate the automatic air swing function. Press again to stop the louver at the desired direction.
8. Sleep Mode Setting
This function is available under COOL, HEAT and AUTO mode.
When the unit is operating under cooling mode, the set temperature is increased by 0.5°C after 30 minutes, 1°C after an hour, and 2°C after 2 hours.
When the unit is operating under heating mode, the set temperature is decreased by 1°C after 30 minutes, 2°C after an hour and 3°C after 2 hours.
9. Clock Time Setting
Press + button to increase the clock time.
Press – button to decrease the clock
time.
10. Turbo Mode
Press the TURBO (
) button to achieve the required set temperature in a short time.
11. Ionizer
Press the Ionizer (
) button to activate the negative Ion function, which will refresh the indoor air effectively.
12. Personalize Setting
Press button and hold for 3s to initiate personalized setting
Set the individual setting e.g. MODE, SET TEMP or FAN SPEED and leave for 4s to save the setting into the program.
2 groups of settings are allowed to store in the handset. Press once to activate the P1 setting, press again to cycle between P1 and P2.
Press any key to deactivate the personalize setting.
MCQUAY Service Guide Book Handset Operating Guide
9
4.4 G17
Operation Guide
1. Transmission Source
2. Signal Transmission Indication
Blink to confirm that the last setting has been transmitted to the unit.
3. Temperature Setting
Temperature setting range is from 16°C to 30°C (optional setting 20°C to 30°C).
4. Personalize Setting
Press and hold for 3s, then will blink. Press again to cycle between and .
Set the desire setting, then leave the handset for 4s without pressing any key and it will save the setting into the program.
Press
once to activate the P1 setting,
press again to cycle between P1 and P2.
Press any key to deactivate the personalize setting.
5. Automatic Air Swing (optional)
Press the SWING
button to activate the automatic air swing function. Press again to stop the louver at the desired direction.
6a. Silent Function (For WM – J Series only)
Press
for quiet operation.
Fan speed turn to minimum speed.
Press again to deactivate the function.
6b. Ionizer Function (For WM - G series only)
Press
button to activate the negative ion function, which will refresh the indoor air effectively.
7. Sleep Mode Setting
This function is available under COOL, HEAT and AUTO mode.
When under cooling mode, the set temperature is increased by 0.5°C after 30 minutes, 1°C after an hour, and 2°C after 2 hours.
When under heating mode, the set temperature is decreased by 1°C after 30 minutes, 2°C after an hour, and 3°C after 2 hours.
8. Operating Mode
Press the MODE button to select the type of operating mode.
For cooling only unit, the available modes are: COOL, DRY and FAN.
9. Fan Speed Selection
Press the button continuously will toggle the fan speed in the following order:
Low Med High Auto
Stop pressing when the desired fan speed appears on the display screen.
10. “ON/OFF” Button
11. Timer Cancel
12. OFF Timer Setting
13. ON Timer Setting
14. Turbo Function
Press for fast cooling.
Fan speed turn to maximum speed.
Press again to deactivate the function.
15. Clock Time Setting
Press
and hold to set the clock time.
MCQUAY Service Guide Book Handset Operating Guide
10
4.5 GS01
Operation Guide
1. Transmission Source
2. Signal transmission indication
Blink to confirm that the last setting has been transmitted to the unit.
3. ON/OFF Button
4. Fan Speed selection
Press the
button continuously will
toggle the fan speed.
5. Operation mode
For cooling only unit: COOL
, DRY
and FAN
.
For heat pump unit: AUTO
, COOL
, DRY , FAN and HEAT .
The AUTO
mode is unavailable for
chilled water system.
6. Automatic air swing
Press the SWING
button to activate the automatic air swing function. Press again to stop the louver at the desired direction.
Swing mode selection (for CK-E model)
Press SWING
button for 4 seconds to
enter field setting mode.
While in field setting mode, it will only show SWING MODE
.
Press temperature button to select SWING MODE
rotation from Swing
Mode 1 to Swing Mode 3.
There are 3 different SWING MODE, which are:
Mode 1 Mode 2 Mode 3
SWING MODE will not activate unless SWING is activated.
If no mode changes within 4 seconds, unit will operate According to the selected
SWING MODE
.
7. Turbo function (model dependent)
Press
for fast cooling or heating
operation.
Fan speed turn to maximum speed for 15 minutes.
Press again to deactivate the function.
Available under HEAT, COOL and DRY
modes only.
1
2
3
4
5
6
7
8
9
10
11
12
13
MCQUAY Service Guide Book Handset Operating Guide
11
Any change of fan speed will deactivate this function.
The Turbo function
is unavailable for
chilled water system and remote control with SWING MODE function.
8. OFF timer setting
9. Quiet function (model dependant)
Press for quiet operation.
Fan speed turn to minimum speed.
Press again to deactivate the function.
Any change of fan speed will deactivate
this function.
The Silent function is unavailable for chiller water system.
10. Clock time setting
Press and hold
button to set the clock
time.
11. ON timer setting
12. Sleep mode setting
This function is available under COOL, HEAT and AUTO mode.
When under cooling mode, the set temperature is increased by 0.5°C after the first half an hour, another 0.5°C after the second half an hour and 1°C after the following 1 hour.
When under heating mode, the set temperature is decreased by 1°C after the first half an hour, another 1°C after second half an hour and 1°C after the following hour.
13. Temperature setting
The temperature setting range is from 16°C to 30°C (Optional setting 20°Cto 30°C).
Press both buttons and simultaneously to toggle from °C to °F setting.
MCQUAY Service Guide Book Handset Operating Guide
12
4.6 APJ1
Operation Guide
1. Transmission Source
2. LCD Display
3. ECONO button
ECON operation is a function which enables efficient operation by limiting the maximum power consumption value.
This function is useful for cases which attention should be paid to ensure a circuit breaker will not trip when the product runs along side other appliances.
Press
button to start ECONO
operation. The symbol
is displayed on
the LCD.
Press
button to cancel ECONO
operation. The symbol
button
disappears from the LCD.
4. POWERFUL Button
POWERFUL operation quickly maximizes the cooling / heating effect in any operation mode.
To start POWERFUL operation, press
button. is displayed on the LCD. POWERFUL operation ends in 20 minutes. Then the system automatically operates again with the previous settings which were used before POWERFUL operation.
To cancel POWERFUL operation, press button again. disappears
from the LCD.
5. Temperature Settings.
6. ON/ OFF button
7. Mode Selector Button
It selects the operation mode (AUTO/
DRY/ COOL/ HEAT/ FAN).
Press MODE button to select operation
mode. Each pressing of the button advances the mode setting in sequence.
8. FAN Operation
5 levels of airflow rate setting from
to
plus & are available.
When the airflow is set to
, the noise
from the indoor unit will become quieter.
9. SWING Operation
To start auto swing, press
button
and the symbol
is displayed on the
LCD.
1
2
4
5
6
7
8
9
10
11
12
13
3
MCQUAY Service Guide Book Handset Operating Guide
13
The flap (horizontal blade) will begin to swing.
To set the flap at desired position, press
button when the flap has reached
the desired position. The flap will stop moving. The symbol
disappeared from
the LCD.
10. COMFORT AIRFLOW Operation
When COMFORT is enable, the flow of air will be upward direction while in COOL operation and in the downward direction while in HEAT operation, which will provide a comfortable wind that will not come in direct contact with people.
To start COMFORT AIRFLOW operation, press COMFORT
button. The flap will change, preventing air from blowing directly on the occupants of the room. The
symbol
is displayed on the LCD.
Air flow rate is set to AUTO. COOL/ DRY: The flap will go up. HEAT: The flap will go down.
To cancel COMFORT AIRFLOW operation, press COMFORT
button again. The flap will return to the memorized position before the COMFORT AIRFLOW operation.
The symbol
will disappear from the
LCD.
11. ON TIMER Operation
To use ON TIMER operation, press button.
is displayed on the LCD. Each
pressing of
advances the time setting by 1 hour. The timer can be set between 1 to 12 hours.
To cancel ON TIMER operation, press
button. will disappear from the
LCD.
12. OFF TIMER Operation
To use OFF TIMER operation, press button.
is displayed on the LCD. Each
pressing of
advances the time setting by 1 hour. The timer can be set between 1 to 9 hours.
To cancel OFF TIMER operation, press
button. will disappear from the
LCD.
13. CANCEL Button
MCQUAY Service Guide Book Handset Operating Guide
14
4.7 SLM3
Operation Guide
1. “
ON/OFF” Switch
2. Temperature Setting
Setting range are between 16°C to 30°C (60°F to 80°F).
3. Operation Modes
Press the “mode” button for select the type of operating mode.
-Cooling Only: COOL, DRY, FAN
-Heat Pump: AUTO, COOL, DRY, HEAT, FAN
AUTO mode is represented by both COOL and HEAT LED light on.
4. Fan Speed Selection
Press the button until the desired fan speed is achieved.
5. Timer
Press the set button to select the switch timer of the air conditioner unit (the setting range is between 1 to 15 hours).
6. “SLEEP” Mode
This function can only be activated under “cool” or heating mode operation. When it is activated under “cool” mode operation, the set temperature will increase 0.5°C
after 30 minutes, 1°C after 1 hour and 2°C after 2 hours. If it is activated under “HEAT” mode operation, the set temperature will be decreased 0.5°C after 30 minutes, 1°C after 1 hour and 2°C after 2 hours.
7. Air Swing
Press button to activate the automatic air swing function.
8. Sensor
Infra red sensor to receive signals from wireless controller.
9. LED Display
To display the set temperature (in °C) and timer delay setting (in hours).
10. Transmission Source
MCQUAY Service Guide Book Handset Operating Guide
15
4.8 SLM8
No. KEY No. KEY
1 MODE 8 OFF TIMER 2 TURBO 9 ON TIMER 3 SWING 10 DELAY TIMER 4 QUEIT 11 FAN 5 SET TEMP UP 12 ON/OFF 6 SET TEMP
DOWN
13 REAL TIME
CLOCK (RTC)
7 SLEEP
Operation Guide
1. MODE Button
Press the MODE button to switch operation from COOL, HEAT, DRY*, FAN. DRY mode is available for selected models only.
2. TURBO Fan Speed
Press the TURBO key once to activate Turbo fan speed. Turbo symbol will be shown. To disable Turbo fan speed and BACK to previous fan speed, press the Turbo key once again. If user presses the FAN button or QUIET button or turn off the unit, the turbo speed will be disabled. This speed is only valid during COOL mode for selected models.
3. Automatic Air Swing
Press the SWING
button to activate the automatic air swing function. Press again to stop the louver at the desired direction.
Swing mode selection (for selected model)
Press SWING
button for 4 seconds to
enter field setting mode.
While in field setting mode, it will only show SWING MODE
.
Press temperature button to select SWING MODE
rotation from Swing
Mode 1 to Swing Mode 3.
There are 3 different SWING MODE, which are:
Mode 1 Mode 2 Mode 3
SWING MODE will not activate unless SWING is activated.
If no mode changes within 4 seconds, unit will operate According to the selected
SWING MODE
.
4. Quiet Fan Speed
Press the QUIET key once to activate Quiet fan speed. QUIET symbol will be shown.
To disable Quiet fan speed and BACK to previous fan speed, press the QUIET key again.
If user presses the FAN button or TURBO button or turn off the unit, the quiet speed will be disabled. This speed is only valid during COOL mode for selected models.
5. Temperature Setting
Press the temperature button and set the temperature of your choice by pressing “ ” or “ ” button once, temperature changes by 1°C or 1°F. The default temperature setting range is from 16°C to 30°C (60°F to 86°F).
Pressing both keys simultaneously will toggle the temperature setting between ºC and ºF.
No temperature setting is allowed during FAN mode (No set temperature display). There is no room temperature display.
6. SLEEP Function
Press the SLEEP button to activate the sleep mode. SLEEP function is not available in DRY mode and FAN mode.
7. ON TIMER and OFF TIMER
The unit has 2-event timer, namely Timer 1 and Timer 2, each event has an ON TIMER and an OFF TIMER.
All timers are event-triggered timers and can be overridden by the ON/OFF button and Override function.
MCQUAY Service Guide Book Handset Operating Guide
16
Set Event 1 and Event 2 Timers
Process for Timer ON and Timer OFF is the same.
Press and hold Timer ON/OFF key for 3 seconds to go into timer setting mode. (Icon ON 1 or OFF 1 will blink)
Press UP or DOWN to select Timer 1 or Timer 2 to set. (‘1’ blinking indicate that Timer 1 is currently selected, ‘2’ blinking indicate that Timer 2 is currently selected)
Press Timer ON/OFF key again to confirm. (Day will blink next)
Press UP or DOWN to select the day.
Press Timer ON/OFF key again to confirm
the day. (Hour will blink next)
Press UP or DOWN to change the hour.
Press Timer ON/OFF key again to confirm
the hour. (Minute will blink next)
Press UP or DOWN to change the minute.
Press Timer ON/OFF key again to confirm
the minute.
Each timer (Timer 1 ON or Timer 1 OFF or Timer 2 ON or Timer 2 OFF) will only be set separately, if there is no key operation for 5 seconds during setting the timer, it will automatically exits from setting mode and no changes will be made.
ON/OFF timer will be checked every 1 minute. It is not advisable to set ON TIMER and OFF TIMER to have same values. Shall these occur, the effective timer will be treated with priority as stated in Table below:
Table: Timer Priority Priority Timer 1 (Highest) ONTMR2 2 OFFTMR2 3 ONTMR1 4 (Lowest) OFFTMR1
Upon IR reception, IR wireless remote controller will override ON TIMER 2 and OFF TIMER 2 settings.
Example: ON TMR 2 setting : DAY TUE, TIMER 5.00pm OFF TMR 1 setting: DAY TUE, TIMER 5.00pm
Outcome when RTC reaches 5.00pm on TUE:
when unit is on, no respond.
when unit is off, unit will turn on.
8. DELAY TIMER Function
Press the DELAY TIMER key once will activate the delay timer function for 1 hour. An indicator “OVERRIDE” will show on the LCD.
Press the same key again will increase the setting to 2 hours. An indicator “OVERRIDE” will be shown. Subsequent press will deactivate the delay timer function.
After the delay timer is completed, the delay timer function is deactivated and the logo is OFF. All other timers will be resumed.
9. FAN Speed
Fan speed can be changed via pressing the FAN key: Low > Med > High > Auto >
FAN speed is not available in DRY mode.
10. ON/OFF Button
11. Real-time Clock Display
RTC is shown on screen during the unit ON or OFF except for power failure or error code.
Set RTC Setting
Press RTC key one time will activate RTC setting mode. (Day will blink)
Press UP or DOWN to select the day.
Press RTC again to confirm the day.
(Hour will blink next)
Press UP or DOWN to change the hour.
Press RTC again to confirm the hour.
(Minute will blink next)
Press UP or DOWN to change the minute.
Press RTC again to confirm the minute.
RTC will only be set after all 7 steps, if
there is no key operation for 5 seconds during setting the RTC, it will automatically exits from setting mode and no changes will be made.
12. Key Lock
Press and hold both TURBO and QUIET keys for 5 seconds will activate/deactivate the key lock function; “KEYLOCK” will be shown/disappear on LCD. Upon all the keys are locked, only ON/OFF, TURBO and QUIET (to unlock) can be pressed.
MCQUAY Service Guide Book Handset Operating Guide
17
4.8 Sequential Controller
Operating Guide
1. “ON/OFF” Switch
Caution: In the case when the ON/OFF
key is pressed immediately after the operation is stopped, the unit will not restart until 3 minutes later to protect the compressor.
2. Selecting Operating Mode
Press the MODE key to select the type of
operating mode. Consecutive press of the
key switches the operation over “COOL”, HEAT”, “AUTO” and “FAN
3. SAVE Mode
Press the SAVE key to select the energy
saving function. This option is only
available for “COOL”, “HEAT” and “AUTO”
modes.
4. Auxiliary Electric Heater
If the “HEAT” mode provides insufficient
heating to a room even at the highest temperature setting (30°C), press the HEATER key to activate the auxiliary electric heater. For models with two heaters, consecutive press of the key allows the selection of one or both heaters active.
5. Temperature Setting
To set the desired room temperature, press or to increase or decrease the set temperature in the range of 16°C to 30°C.
Press both and simultaneously to toggle between °C and °F setting.
6. Time Setting
Real time clock
Press the CLOCK key once to activate
set clock mode.
Press again to disable set clock mode.
Under set clock mode, the time of the
present day can be set by pressing the
respective MINUTE, HOUR and DAY key.
7 days timer
Press the ON TIMER key to activate auto
ON timer mode. Under this mode, press
the respective MINUTE, HOUR and DAY
key to select the time of the week when the air-conditioning unit is to automatically
start running. Press ON TIMER key again to save the setting.
Press the OFF TIMER key to activate
auto OFF timer mode. Under this mode,
press the respective MINUTE, HOUR and DAY key to select the time of the week
when the air-conditioning unit is to
automatically stop running. Press the ON TIMER key again to save the setting.
Then to activate the 7 days timer, press
the HOLD key until the word “TIMER
ACTIVE” appears on the LCD screen. Repeat the same step to disable the 7
days timer.
7. Other Function
Key Lock
Press the MINUTE key 3 times
consecutively to activate the key lock. A “KEY LOCK” symbol will appear on the LCD screen. At this point, only the
ON/OFF key is valid.
To disable the key lock, again press the
MINUTE key 3 times consecutively.
Test Run
Press the TEST RUN key 2 times
consecutively to test run the unit.
4.9 Netware 3 / Netware 3C
A : Time F : Energy saving mode B : Error indication G : Compressor defrost C : Comp. running cycle (up to 4 comps.) (up to 4 comps.) H : Operation mode D : Key lock I : Temperature set E : Heater (up to 2 heaters)
MCQUAY Service Guide Book Handset Operating Guide
18
Differences between Netware 3 & Netware 3C:
Netware 3 Netware 3C
Compatibility
Non-inverter / X-inverter
Series
Y-inverter Series
Casing Color Dark Silver White
Retrieve Last State Error No Yes
Pump Down No Yes
Applicable model All except A(5)WM-J/JR
For MCK-E, only applicable
with nomenclature ACOBB
All except M5WMY-J/JR
NIM/G-WAY Yes
For MCK-E, only applicable
with nomenclature ACOBB
No
Operating Guide
1. “ON/OFF” Switch
Caution: In the case when the ON/OFF
key is pressed immediately after the operation is stopped, the unit will not restart until 3 minutes later to protect the compressor.
2. Selecting Operating Mode
Press the MODE key to select the type of
operating mode. Consecutive press of the key switches the
operation over “COOL”, “HEAT”, “AUTO”, DRY” and “FAN
3. Fan Speed Selection
Press the FAN key until the desired fan
speed is achieved.
4. Sleep Mode Setting
Press the SLEEP key to activate sleep
mode. Available under COOL, HEAT & AUTO mode.
When it is activated in COOL mode, the
set temperature will be increased 0.5°C after 30mins, 1°C after 1 hour and 2°C after 2 hours.
Jumper
20 - 30
Application
SET Set temp range : 20°C ~ 30°C OFF Set temp range : 16°C ~ 30°C
1. Time display
2. Key lock display
3. Error indication
4. Fan speed display
5. Operation mode display
6. Sleep mode display
7. Air swing display
8. Temperature set display
MCQUAY Service Guide Book Handset Operating Guide
19
When it is activated in HEAT mode, the
set temperature will be decreased 1°C after 30mins, 2°C after 1 hour and 3°C after 2 hours.
5. Temperature Setting
To set the desired room temperature, press or to increase or decrease the set temperature in the range of 16°C to 30°C.
Press both and simultaneously to toggle between °C and °F setting.
6. Air Swing
Press the SWING key to activate the
automatic air swing function.
7. Time Setting
Real time clock
Press the CLOCK key to activate set
clock mode. Press again to disable set clock mode.
Under set clock mode, the time of the present day can be set by pressing the
respective MINUTE, HOUR and DAY key.
7 days timer
The unit has 3 event functions; each event has an ON TIMER and an OFF TIMER. Press the timer key (ON TIMER/OFF TIMER) will enable Event 1 timer setting mode. Press same key again will enable Event 2 timer setting mode. Press the 3rd times will enable the Event 3 (Event handset) timer setting mode. Subsequent key pressed the unit will quit from timer setting mode.
Set Event 1 and Event 2 Timers
Under timer setting mode, “SET TIMER” will be shown on LCD and blink at 0.5 sec interval. For Event 1 Timer setting, ‘ON’ or ‘OFF’ indication will appear and digit “1” will be displayed on the top left corner of the LCD. ‘ON’ or ‘OFF’ indication and digit “2” will be displayed during Event 2 timer setting. The timer setting can be changed through pressing the DAY key, HOUR key or MINUTE key. If there is no further time related (DAY, HOUR and MINUTE) key is pressed, the unit will quit from the timer setting mode.
Set Event 3 Timer via remote control (Optional)
This timer can be controlled separately through remote control as well as ON TIMER or OFF TIMER keys. Timer 3 can be set like timers 1 and 2 like above except the DAY setting is not provided as this timer setting is valid everyday. An indicator ‘3’ will display during the Event 3 timer setting mode. ‘ON’ or ‘OFF’ will blink at 0.5 sec interval during the timer setting. If there is no further time related (DAY, HOUR and MINUTE) key is pressed, the unit will quit from the timer setting mode.
Activating and canceling timers
These timers will not trigger if the timer is not active. To activate the timers, press
the TIMER ACTIVE key unit “TIMER
ACTIVE” appears on LCD. This symbol is to indicate Event 1, Event 2 and/or Event 3 timers are active. Pressing the same steps will deactivate the timers and “TIMER ACTIVE” symbol will disappear.
Another method to cancel the timers setting is changed all the hour setting of the timers to null, the LCD display --:--, then this respective timer will be disable.
8. Other Function
Key Lock
Press the MINUTE key 3 times
consecutively to activate the key lock. A “KEY LOCK” symbol will appear on the LCD screen. At this point, only the
ON/OFF key is valid.
To disable the key lock, again press the
MINUTE key 3 times consecutively.
Fan Lock
When the DAY key is press 3 times consecutively within 1.5 sec, the fan symbol will disappear and fan key will be inhibited. Press the DAY key 3 times to cancel the fan lock function.
4.10 Rooftop Panel
MCQUAY Service Guide Book Handset Operating Guide
20
Operating Guide
1. LCD Display
Upon power up of the unit, the LCD displays the main display screen
2000/01/0 [SAT] 12:00am
Status : OFF Mode : Heating Set Temp : 24°C
2. “ON/OFF” Switch
Press the ON/OFF button for 1 second to switch on the unit if the status shows OFF. The status will change to ON. The ON/OFF LED will light up.
3. HEAT Button
Press the HEAT button for 1 second if heating is required.
4. COOL Button
Press the COOL button for 1 second if cooling is required.
5. ALARM Button
Press the ALARM button to view or clear the alarm history.
The panel can keep up to 20 faults/alarm warning records.
6. ECS Button
7. Downward Button
Press the button once to view the
Compressor(s) On, Off or Defrost Status.
Press the button again to view the temperature for Return Air and Outdoor Air.
Press the button again to view the
Selected Type for Unit, Number of Compressor used, Indoor Fan Option, Model and EEPROM version.
8. Upward Button
Press the button to return to previous screen(s)
9. ENTER Button
Press the button to enter [Main Menu].
There are 6 sub menus in [Main Menu].
Operation Menu > Setting Menu > Timer Menu > Alarm Menu > Warning Menu > Display Menu.
Press
or to select sub menus, press ENTER to enter into the sub menu or press ESC to exit to main display screen.
Details please refer to Rooftop Panel Operation Manual.
Press to exit to previous Menu.
MCQUAY Service Guide Book Handset Operating Guide
21
4.11 Chiller Panel
Operating Guide
1. LCD Display
Upon power up of the unit, the LCD displays the main display screen
01/01/2003 12:00am
Status : OFF Mode : Cooling Set Temp : 12°C
[00]
2. “ON/OFF” Switch
Press the ON/OFF button for 1 second to switch on the unit if the status shows OFF. The status will change to ON. The ON/OFF LED will light up.
The Set Temp refers to water in temperature and the factory setting is 12°C for cooling and 40°C for heating.
[00] refers to the factory setting for panel
ID.
3. HEAT Button
Press the HEAT button for 1 second if heating is required.
4. COOL Button
Press the COOL button for 1 second if cooling is required.
5. ALARM Button
Press the ALARM button to view or clear the alarm history.
The panel can keep up to 20 faults/alarm
warning records.
6. ECS Button
Press to exit to previous Menu.
7. Downward Button
Press the button once to view the Compressor(s) On or Off status.
Press the button twice to view the temperature for Water In, Water Out, Outdoor Air and Controller Panel.
Press the button again to view the Air Conditioning Model, Number of Compressor used and Unit Number.
8. Upward Button
Press the button to return to previous screen(s)
9. ENTER Button
Press the button to enter [Main Menu].
There are 6 sub menus in [Main Menu].
Operation Menu > Setting Menu > Timer Menu > Alarm Menu > Display Menu.
Press
or to select sub menus, press ENTER to enter into the sub menu or press ESC to exit to main display screen.
Details please refer to Chiller Panel Operation Manual.
MCQUAY Service Guide Book Handset Operating Guide
22
4.12 MC301
Operating Guide
1. ON/OFF Operation
Press “ON/OFF” key, the unit will be ON or OFF, and “ON” or “OFF” will display on the LCD.
2. Temperature Setting
Use “” or “” keyboard to increase or decrease by 1 °C/°F, temperature range is 16-30 °C (61-86°F).
Press “FAN” for 5s to alter between °C and °F.
3. Fan Speed Setting
Press “FAN” key to adjust fan speed follows by: HighAutoLow→Medium→High.
When the mode is “Fan”, there is no “Auto” speed. Single-speed fan motor has no this function.
4. Mode Setting
Press the “MODE” button, the current mode is twinkling. Press again to change mode as follows: When the outdoor unit is OFF:
- Heat pump:
COOLHEATFANDRY
- Cooling only:
COOLFANDRY
When the outdoor unit is Cooling:
COOL→FAN→DRY
When the outdoor unit is Heating:
HEAT→FAN
5. Swing Setting
Press “HEATER/SWING” key to active swing function (Only for swing unit). “SWING” will display on LCD.
6. Auxiliary Heater Setting
Under “HEAT” or “FAN” mode, press “HEATER/SWING” key to active heater. (Only for heater unit). “HEATER” will display on LCD.
7. Sleep Setting
Press “SLEEP” key, “SLEEP” will display on LCD, which means this function is active.
8. Keyboard Lock
Press “SLEEP” for 5s, the keyboard will be changed between locked and unlocked.
When it is locked, the lock icon will be shown on the LCD. During the locked stage, only the ON/OFF key is valid.
9. Real Time Clock Setting
Press “CLK” to enter, firstly is “week setting”; press “” or “” to change from Sunday to Saturday. If there is no any press for 5s on any key, it will exit to the displaying status.
Press “CLK” again is the “CLOCK SET” icon will display and the current real time clock is twinkling. At this time, press “▲” to increase the hour, press
” to increase minutesif there is not any press for 5s, it will exit without saving
the changed real time. If you want to confirm the new setting, you need to press “CLK” once again within 5s.
During the setting process, only “▲”, “▼” and “CLK” are valid. If other key is press, it will exit to the normal status.
MCQUAY Service Guide Book Handset Operating Guide
23
10. Reset
This key is used to reset the unit.
11. Timer Setting
Week timer setting: Include total 28 on/off timers, 7 days every week and 4 timers every day.
Single timer setting: It is active only on the same day that timer set when power on. It is inactive when timer is set at AM 00:00. It can be set at AM 00:00 if you want to cancel some timer setting.
Press “FAN” and “MODE” at one time, all timers setting can be cancelled.
Timer display: The current timer setting will display every 2s.
The third bit of the K1(micro-switch) of PCB board must be set ON if PCB has clock chip and battery, otherwise the real time clock will not be activated once power is shut off.
A) Week Timer Setting
Press “TIMER” “WEEK SET” and “TIMER SET” will display on the left and
bottom of LCD panel, press “” or “” to select a day (Sunday to Saturday), press “TIMER” again, the day is selected, the timer’s states of the selected day will display on LCD Panel.
Enter first timer setting, the timer ON or OFF icon will display on the left and bottom of LCD panel, the timer sequence number “1” will display on the top of LCD, press “”or “ ” to select timer sequence number, press “TIMER”, the timer sequence number is selected.
Enter timer ON and timer OFF setting, press “” or “” to select timer ON or timer OFF, “TIMER ON” or “TIMER OFF” is twinkling, Press “TIMER”, timer ON or timer OFF is selected.
Enter timer setting, “TIMER SET” and “CLOCK SET” will display on the left and bottom of LCD panel, press “” to set hour and press “” to set minute, press “TIMER” again to finish setting and enter next timer setting, repeat above procedures to finish others timer setting.
B) Single Timer Setting
Press “TIMER” key for 5s, enter single timer setting (When the unit is ON, it can only be set to OFF; When the unit is OFF, it can only be set to ON), the “TIMER SET” will display on LCD panel, press “▲” to set hour and press “”to set minute, press “TIMER” to finish the single timer setting.
Exit timer setting: If there is no press on
any key within 5s or press any key except “”, “”, “TIMER” and “ON/OFF” key, it will exit the timer setting.
MCQUAY Service Guide Book Handset Operating Guide
24
4.13 MC303
Operating Guide
1. Address Register
After communication wire is completely connected, press “SETUP” key for 5s. Address will be automatically registered and a number from 60 to 0 will be shown on the display LCD.
2. View Actual Address
Press “MODE” key for 5s then press “▲” or “” to view all the units.
Actual address has four figures; first two where show on minute previously are for outdoor unit, last two where show error previously at the right bottom corner are for indoor unit.
3. Single/Group Unit Setting
Press “UNIT No.” key to enter the unit
setting, then press “” or “” to choose the unit number to be set and press “ENTER” to confirm choosing.
When LCD panel show “_ _”, press “ENTER” to confirm enter group setting.
4. ON/OFF Operation
Press “ON/OFF” key to RUN or STOP the unit operation.
For Group On/Off, press “ON/OFF” key for 5s and the unit number is twinkling, “[ ]” is displayed on LCD panel. Then press “ON/OFF” key to turn on/off all units.
5. Mode Setting
Press the “MODE” button, the current mode is twinkling. Press again to change mode as follows: When the outdoor unit is OFF:
- Heat pump:
COOL→HEAT→FANDRY
- Cooling only:
COOLFANDRY When the outdoor unit is Cooling: COOLFANDRY When the outdoor unit is Heating: HEAT→FAN
6. Temperature Setting
Use “” or “” keyboard to increase or decrease by 1 °C/°F, temperature range is 16-30 °C (61-86°F).
Press “FAN” for 5s to alter between °C and °F.
7. Fan Speed Setting
Press “FAN” key to adjust fan speed follows by: High→Auto→Low→Medium→High
When the mode is “Fan”, there is no “Auto” speed. Single-speed fan motor has no this function.
8. Swing Setting
Press “SWING” key to active swing function. “SWING” will display on LCD.
9. Sleep Setting
Press “SLEEP” key, “SLEEP” will display on LCD, which means this function is active.
MCQUAY Service Guide Book Handset Operating Guide
25
10. Indoor unit lock/unlock
Press “UNIT No.” key to enter the unit
setting, then press “” or “” to choose the unit number to be set or choose “_ _” for group setting and press “ENTER” to confirm. After that, press “SLEEP” key 5s
to lock the chosen unit, the symbol “
” will display on LCD panel, any operation by LCD panel or remote controller is invalid.
To unlock the unit, press “SLEEP” key 5s, the symbol “
” will disappear.
11. Real Time Clock Setting
Press “CLK” to enter, firstly is “week setting”; press “” or “” to change from Sunday to Saturday. If there is no any press for 5s on any key, it will exit to the displaying status.
Press “CLK” again is the “CLOCK SET” icon will display and the current real time clock is twinkling. At this time, press “▲” to increase the hour, press “ ” to
increase minutes if there is not any press for 5s, it will exit without saving the
changed real time. If you want to confirm the new setting, you need to press “CLK” once again within 5s.
During the setting process, only “▲”, “▼” and “CLK” are valid. If other key is press, it will exit to the normal status.
12. Timer Setting A) Single Timer Setting
Single timer setting: It is active only on the
same day that timer set when power on. It is inactive when timer is set at AM 00:00. It can be set at AM 00:00 if you want to cancel some timer setting.
Press “TIMER” key for 5s, enter single
timer setting (When the unit is ON, it can only be set to TIMER OFF; When the unit is OFF, it can only be set to TIMER ON), the “TIMER SET” will display on LCD panel, press “” to set hour and press “”to set minute, press “TIMER” to finish the single timer setting.
B) Week Timer Setting
Week timer setting: Include total 28 on/off
timers, 7 days every week and 4 timers every day.
Press “TIMER” “WEEK SET” and
“TIMER SET” will display on the left and bottom of LCD panel, press “” or “” to select a day (Sunday to Saturday), press “TIMER” again, the day is selected, the timer’s states of the selected day will display on LCD Panel.
Enter first timer setting, the timer ON or OFF icon will display on the left and bottom of LCD panel, the timer sequence number “1” will display on the top of LCD, press “”or “” to select timer sequence number, press “TIMER”, the timer sequence number is selected.
Enter timer ON and timer OFF setting, press “” or “▼” to select timer ON or timer OFF, “TIMER ON” or “TIMER OFF” is twinkling, Press “TIMER”, timer ON or timer OFF is selected.
Enter timer setting, “TIMER SET” and “CLOCK SET” will display on the left and bottom of LCD panel, press “” to set hour and press “” to set minute, press “TIMER” again to finish setting and enter next timer setting, repeat above procedures to finish others timer setting.
Press “SWING” for 5s, all week timer setting in EEPROM will be deleted.
Exit timer setting: If there is no press on any key within 5s or press any key except “”, “”, “TIMER” and “ON/OFF” key, it will exit the timer setting.
13. Lock/unlock LCD Panel
Press “HEATER” and “SLEEP” key for 5s, the symbol “
” will twinkles on LCD panel, MC303 is locked. Any key of MC303 is invalid until “HEATER” and “SLEEP” key is pressed for 5s again.
While LCD panel is locked, MC303 still
checks and displays each indoor’s unit status.