McQuay Mark IV-AC Installation Manual

Operation & Maintenance Data OM 120-2
Mark IV/AC Controller For
Water Source Heat Pump Units
Group: WSHP Part Number: 578993Y
Date: May 1999
Contents
Features of the Mark IV Controller ................................ 2
Initial Power Up................................................................2
General Use and Information ......................................... 2
Occupied Operation ........................................................ 3
Thermostat Inputs (G, Y1, W1, and W2)........................3
Control Inputs (HP, LT, COF, U, L, E, O) 3
Control Outputs (A and P)..............................................3
Fan Operation................................................................. 3
Cooling Mode ................................................................. 3
Heating Mode.................................................................3
Unoccupied Operation....................................................3
Thermostat Inputs (G, Y1, W1, and W2)........................3
Control Inputs (HP, LT, COF, U, L, E, O) 3
Control Outputs (A and P)..............................................3
Fan Operation................................................................. 4
Cooling Mode ................................................................. 4
Heating Mode.................................................................4
Additional Operating Modes .......................................... 4
Load Shed ......................................................................4
©1999 AAF-McQuay Incorporated OM 120-2 (Rev. 5/99)
Remote Shutdown.......................................................... 4
High/Low Pressure Faults..............................................4
Low Temperature Faults ................................................5
Condensate Overflow..................................................... 5
Tenant Override.............................................................. 5
Operation of the Fan during most Modes, Faults &
Shutdowns ..................................................................5
Operation with High Speed Jumper ..............................5
Priority of Faults and Modes..........................................5
LED Status and Fault Output Status .............................6
14-PositionTerminal Strip...............................................6
Trouble Shooting the Mark IV/AC Control Board ........ 6
Interfacing the Mark IV/AC Controller
to External Equipment .................................................7
Typical Mark IV/AC Unit Wiring Diagram...................... 8
Features of the Mark IV/AC Controller
The Mark IV/AC controller incorporates features which improve the operation and safety of AAF-McQuay heat pumps. These features include:
1. Compressor short cycle protection
2. Brownout protection with time delays for the fan and com­pressor to prevent damage due to low voltage conditions
3. Condensate overflow protection
4. Refrigerant high / low pressure protection
5. Low temperature protection with automatic condenser defrost cycle
6. Random start delay compressor to prevent high building electrical demands when multiple units are simultaneously switched on during power-up, return from brownouts, return from load shed, etc.
7. LED’s to indicate operational status and fault indication
8. Controlled delay of the reversing valve to reduce annoy­ing “swish” noise
9. High speed test jumper (TP) used to reduce compres­sor short cycle and reversing valve delay times to speed system check out and repair.
10. Load shed control input for energy management systems
11. Remote shutdown control input for remote shutdown of unit
*
12. Unoccupied control input for night setback control
13. Inputs for both standard (W1) and night setback (W2) thermostats
Initial Power Up
When power is first applied to the unit, the following events occur:
1. The board executes a reset routine which sets up the microcontroller for normal operation. During this routine the following occurs:
a. The reversing valve may click on and off. b. The A output goes low for a fraction of a second. c. The GREEN LED will flash at
approximately 1
d. A new random start delay time between 0 and 32
seconds is generated. A new short-cycle timer is also generated by adding 180 to the new start delay time for a total time delay between 180 and 212 seconds. Once these numbers are generated, the same time delays will be used until the next power cycle.
2. The microcontroller then checks for the following condi­tions in the following order:
a. High pressure fault b. Low temperature fault c. Load shed signal on d. Brownout or remote shutdown condition e. Condensate fault f. Unoccupied signal on If any of these conditions are true, the microcontroller
executes the appropriate routine. For example, if the high pressure switch is open upon power up, the compressor will not start and the RED LED will flash.
3. If none of the above signals or faults are detected during start up, the unit will go into normal operation.
1
2 seconds.
1
2 second intervals for
14. Fault output for remote fault indication
15. Operation of the fan during most faults and load shed to increase comfort
16. Tenant override input to manually switch from unoccu­pied mode (U) to occupied mode (O)
17. Control board inputs U, L, E, Y1, W1, G, W2, and O have been designed to operate by connecting to the units 24vac, 24vdc, or chassis ground
The remote shutdown input (E) should not be the sole
*
means of ensuring equipment status when used as a part of a life-safety control system as the unit fan may operate during some fault conditions.
CAUTION
The Mark IV/AC circuit board incorporates static sensitive devices. A static charge from touching the device can damage the electronic components. To prevent damage during service, AAF-McQuay Incorporated recommends the use of static discharge wrist straps which are grounded to the heat pump chassis through a one mega ohm resistor.
For replacement of a Mark IV/AC circuit board:
1. Connect wrist strap to unit.
2. Remove faulty board and place on static protected surface.
3. Remove replacement board from static protected bag.
Do not touch circuit board; hold by edges.
4. Holding board in grounded hand, install board in unit.
5. Insert faulty board in empty static bag for return.
General Use and Information
The Mark IV/AC control board is provided with three drive terminals, R (24vac), F (24vdc), and C (0vac) that can be used by the end user to drive the thermostat inputs (G, Y1, W1, and W2) and control inputs (U, L, E, and O). Any combination of or single board drive terminal (R, F, or C) may be used to operate the Mark IV/AC boards control or thermostat inputs. However, only one drive terminal (R, F, or C) can be con­nected to any individual input terminal or damage will occur. Some of the control inputs are used within the Water Source Heat Pump and not accessible to the end user. For example HP, LT, and COF are not available for use by the end user.
Typically the Mark IV/AC board’s R (24vac) terminal is used to drive the board’s thermostat inputs and control inputs by connecting it to the R terminal of an industry standard thermostat. The control outputs of the standard thermostat are then connected to the Mark IV/AC board thermostat inputs and control inputs as needed. Any remaining board input(s) may be operated by additional thermostat outputs or remote relays (dry contacts only).
All Mark IV/AC board inputs must be operated by dry contacts powered by the control board’s power terminals. No solid state devices (Triacs) may be used to operate Mark IV/AC board inputs. No outside power sources may be used to operate Mark IV/AC board inputs.
Page 2 / OM 120-2
Occupied Operation
Board LED Status
Yellow Green Red
Off On Off
Thermostat Inputs (G, Y1, W1, and W2)
Thermostat inputs used during occupied operation are G, Y1, and W1, which when energized will activate the Fan Only, Cooling Mode, and Heating Mode respectively. Input W2, unoccupied Heating Mode has no effect during occupied mode.
The Mark IV/AC board is configured so that when either the Y1 or W1 input is energized the unit fan will also be activated with Cooling or Heating Modes. In other words, energizing Y1 and G together will have the same effect as energizing just Y1.
The W1 input has priority over the Y1 input. In situations when both inputs W1 and Y1 become energized (unlikely) in any order the unit will go into the Heating Mode as described below:
1. For example, if the unit is in Cooling Mode, Y1 energized, and W1 becomes energized and remains energized, the follow­ing will occur:
l The compressor will be de-energized l The reversing valve will energize 1 minute later (Heating
Mode position)
l The compressor will restart between 180 and 212
seconds (short-cycle timer)
2. If the unit is in Cooling Mode, Y1 energized, and W1 becomes energized momentarily the controller will de-energize the compressor for 180 to 212 seconds (short-cycle timer) and then return to the cooling mode.
3. However, if the unit is in Heating Mode, W1 energized, and Y1 becomes energized the unit will remain in Heating Mode.
The board will be in occupied mode if the unoccupied terminal (U) is de-energized.
3. The P control output is de-energized when the compressor is energized
When the Y1 terminal is then de-energized, the following will occur:
1. The compressor is de-energized immediately
2. The fan is de-energized immediately, unless the G terminal is energized
3. The P control output is energized when the compressor is de-energized
Compressor time delays may be longer than indicated above as the short-cycle timer (180 to 212 seconds) will be used as needed to prevent adverse compressor cycling.
Heating Mode
The W1 terminal controls occupied Heating Mode operation. When the W1 terminal is energized the following will occur:
1. The reversing valve will be energized immediately
2. The fan will be energized immediately
3. The compressor will be energized after 0 to 32 seconds (start delay timer)
4. The P control output is de-energized when the compressor is energized
When the W1 terminal is then de-energized the following will occur:
1. The compressor will be de-energized immediately
2. The fan will be de-energized immediately, unless the G terminal is energized
3. The reversing valve de-energizes after 1-minute
4. The P control output is energized when the compressor is de-energized
Compressor time delays may be longer than indicated above as the short-cycle timer (180 to 212 seconds) will be used as needed to prevent adverse compressor cycling.
Control Inputs (HP, LT, COF, U, L, E, O)
The control inputs are High / Low Pressure (HP), Low Tempera­ture (LT), Condensate Overflow (COF), Unoccupied (U), Load Shed (L), and Remote Shutdown (E). The control inputs will all be in their normal states during occupied mode. The state of each control in occupied mode during normal operation is as follows: l High / Low Pressure (HP): energized, switch is closed (no
fault)
l Low Temperature (LT): energized, switch is closed (no fault) l Condensate Overflow (COF): sensing no condensate water
(no fault)
l Unoccupied (U): de-energized (no signal) l Load Shed (L): de-energized (no signal) l Remote Shutdown (E): de-energized (no signal) l Tenant Override (O): has no effect in occupied mode
Control Outputs (A and P)
The control outputs are Alarm Fault (A) and Pump Request (P). The operation of the control outputs during occupied mode is as follows:
l Alarm Fault (A): energized (no fault) l Pump Request (P): energized when the compressor is off,
and de-energized when the compressor is on.
Fan Operation
The G terminal controls Fan Only operation. The fan will start when the G terminal is energized. De-energizing the G terminal will cause the fan to stop unless the W1 or Y1 terminals are energized.
Unoccupied Operation
Board LED Status
Yellow Green Red
On On Off
Thermostat Inputs (G, Y1, W1, and W2)
The only thermostat input used during unoccupied operation is W2, which when energized will activate Heating Mode. Inputs G, Y1, and W1 have no effect during unoccupied mode.
Control Inputs (HP, LT, COF, U, L, E, O)
The control inputs are High / Low Pressure (HP), Low Tempera­ture (LT), Condensate Overflow (COF), Unoccupied (U), Load Shed (L), and Remote Shutdown (E). The state of each control input during unoccupied mode during normal operation is as follows:
l High / Low Pressure (HP): energized, switch is closed (no fault) l Low Temperature (LT): energized, switch is closed (no fault) l Condensate Overflow (COF): sensing no condensate water
(no fault)
l Unoccupied (U): energized (signal provided) l Load Shed (L): de-energized (no signal) l Remote Shutdown (E): de-energized (no signal) l Tenant Override (O): see section “Tenant Override Mode”
The board will be in unoccupied mode if the unoccupied terminal (U) is energized.
Cooling Mode
The Y1 terminal controls Cooling Mode operation. When the Y1 terminal is energized, the following will occur:
1. The fan will be energized immediately
2. The compressor will be energized after 0 to 32 seconds (start delay timer)
Control Outputs (A and P)
The control outputs provided by the Mark IV/AC board are Alarm Fault (A) and Pump Request (P). The operation of the control outputs during unoccupied mode is the same as in occupied mode. See occupied operation.
OM 120-2 / Page 3
Loading...
+ 5 hidden pages