McQuay MWM009J, MWM009JR, MWM015J, MWM015JR, M5WM010J Instruction Manual

...
Wall Mounted Split Systems
Models:
MWM009J/JR MWM015J/JR
M5WM010J/JR M5WM015J/JR
Catalog
MWM - J - 2009
MWM-J-2009 Table of Contents
“McQuay” is a registered trademark of McQuay International. All rights reserved.
© 2009 McQuay International. All rights reserved throughout the world.
Bulletin illustrations cover the general appearance of McQuay International products at the time of publication.
We reserve the right to change design and construction specifi cations at any time without notice.
Table of Contents
Nomenclature......................................................................................................................1
Indoor Unit .....................................................................................................................1
Outdoor Unit ..................................................................................................................2
Product Line-Up .............................................................................................................3
Features...............................................................................................................................7
Application Information .....................................................................................................8
Operating Range ...........................................................................................................8
Refrigerant Circuit Diagram ...........................................................................................9
Controller ....................................................................................................................11
Installation Guideline ...................................................................................................12
Sound Data ........................................................................................................................24
Sound Pressure Level .................................................................................................24
NC Curve .....................................................................................................................25
Engineering & Physical Data ........................................................................................... 27
General Data ...............................................................................................................27
Component Data .........................................................................................................31
Performance Data ............................................................................................................. 35
Calculation Steps .........................................................................................................36
Performance Table ......................................................................................................39
Outline and Dimension ....................................................................................................45
Electrical Data ................................................................................................................... 46
Wiring Diagram ................................................................................................................. 48
Service and Maintenance.................................................................................................50
Troubleshooting ...............................................................................................................52
Exploded View and Part List ...........................................................................................60
Nomenclature MWM-J-2009
1
Nomenclature
Indoor Unit
M 5 WM 010 J R
Brand
M : Mcquay
Refrigerant
“ “
4
5
: Omitted if R22
: R407C
: R410A
Model Name
WM : Wall Mounted
Capacity Index
010
015
: 10,000 Btu/h
: 15,000 Btu/h
Series
G
J
: G Series
: J Series
Model Type
“ “
R
: Omitted if cooling only
: Heatpump
MWM-J-2009 Nomenclature
2
Outdoor Unit
M 5 LC 010 C R
Brand
M : Mcquay
Refrigerant
“ “
4
5
: Omitted if R22
: R407C
: R410A
Model Name
LC : Single Split Condensing Unit
Capacity Index
010
015
: 10,000 Btu/h
: 15,000 Btu/h
Series
C : C Series
Model Type
“ “
R
: Omitted if cooling only
: Heatpump
3
Product Line-Up MWM-J-2009
Product Line-Up
Indoor Unit MWM-J
MWM
Nomenclature
Classifi cation
PCB
Handset
Air Purifi cation
Grille
Marking
Others
LGSN
G17
Saranet Filter
Bio Filter
A
CE
COOLING
ONLY
009J
ACBAA X X X X X X
009J
ACLAA X X X X X
015J
ACBAA X X X X X X
015J
ACLAA X X X X X
HEATPUMP
009JR
ACBAA X X X X X X
009JR
ACLAA X X X X X
015JR
ACBAA X X X X X X
015JR
ACLAA X X X X X
4
MWM-J-2009 Product Line-Up
Indoor Unit M5WM-J
M5WM
Nomenclature
Classifi cation
PCB
Handset
Air Purifi cation
Grille
Marking
Others
LGSN
G17
Saranet Filter
Bio Filter
A
CE
COOLING
ONLY
010J ACBAA X X X X X X
010J ACLAA X X X X X
015J ACBAA X X X X X X
015J ACLAA X X X X X
HEATPUMP
010JR ACBAA X X X X X X
010JR ACLAA X X X X X
015JR ACBAA X X X X X X
015JR ACLAA X X X X X
5
Product Line-Up MWM-J-2009
Outdoor Unit MLC
MLC
Nomenclature
Classifi cation
PCB
Refrigerant
Control
FIN
Safety Devices
Compressor
Marking
Others
Cap Tube
EXV
Gold Coated
Blue Coated
Bare
Contactor HPLP
Rotary
CE
Drain Elbow
Low Ambient Kit
COOLING
ONLY
009C ACPOH X X X X
015C ACPOH X X X X
HEATPUMP
009CR ACPOH X X X X X
015CR ACPOJ X X X X X
6
MWM-J-2009 Product Line-Up
Outdoor Unit M5LC
M5LC
Nomenclature
Classifi cation
PCB
Refrigerant
Control
FIN
Safety Devices
Compressor
Marking
Others
Cap Tube
EXV
Gold Coated
Blue Coated
Bare
Contactor HPLP
Rotary
CE
Drain Elbow
Low Ambient Kit
COOLING
ONLY
010C ACPGG X X X X X
010C ACPOG X X X X
015C ACPGG X X X X X
015C ACPOG X X X X
HEATPUMP
010CR ACPOG X X X X
015CR ACPOG X X X X
7
Features MWM-J-2009
Features
Air Filtration with Bio Antibody Filter and Photo-catalytic Deodorizing Titanium Apatite Filter
Bio Antibody Filter is effective against various airborne infectious viruses while Titanium Apatite Filter is able to trap microscopic particles as well as break down and decompose odors. The fi lter can be used for approximately 3 years without replacement if wash about once every six months.
Self Diagnosis
The microprocessor provides the possibility to detect and diagnose any fault or malfunction that occurs in the system. The error will be refl ected by the blinking of the LED lights.
On / Off Button on Indoor Unit
On/Off button is provided on the front panel of the unit. It can be used when the remote controller is missing or if its battery has run out. (Note: This button can also be used for forced operation mode)
Auto Random Restart
Auto random restart function allows the unit to automatic restart as the last setting condition when the power supply is resumed after power failure. However, the compressor will restart randomly if more than one unit is installed and sharing the same phase of power.
Wireless Remote Controller
The compact LCD transmitter is able to operate the air conditioner unit within the distance of 8 meters. Fan speed can be set at high / medium / low / super low or automatic. Sleep mode auto control will gradually increase or decrease the setting temperature to provide a comfortable surrounding for sleeping. Air fl ow direction can be controlled automatically. Room temperature is controlled by electronic thermostat. The real time timer allows the air conditioner to be switched On and Off automatically based on user settings. Turbo mode function is available to enables the required set temperature to be achieved in a short time. Personalized Setting allows user to preset and store 2 groups of personal settings (including timer setting) in the handset.
Energy Effi ciency
Using a more effi cient compressor and superior R410A refrigerant, M5WM10JR series achieves the highest European Energy Rating of A/A. This ensures higher energy savings is accomplished especially during daily usage. M5WM-J series participates in the Eurovent Certifi cation Programme under category of Comfort Air Conditioners rated below 12kW cooling capacity (AC1). The certifi ed data for the certifi ed models are listed in the Eurovent Directory.
8
MWM-J-2009 Application Information
Application Information
Operating Range
Ensure the operating temperature is in allowable range.
Cooling only
Note :
Standard operating range.
With Low ambient kit. (Optional item) Please refer to local dealer for unit of this specification.
Indoor temp. (°CDB)
Cooling
Outdoor temp. (°CDB)
Indoor temp. (°CWB)
Outdoor temp. (°CDB)
Indoor temp. (°CWB)
Heating
Outdoor temp. (°CWB)
-9
16 21
6
30
-5
19
35
14
46
23
Standard
point
Low ambient kit
18
-5
19
35
14
46
23
Low ambient kit
Standard
point
Standard
point
! Caution :
The use of your air conditioner outside the range of working temperature and humidity can result in serious failure.
Heatpump
9
Application Information MWM-J-2009
70034 049971
Refrigerant Circuit Diagram
Model: MWM009J - MLC009C M5WM010J - M5LC010C MWM015J - MLC015C M5WM015J - M5LC015C
70034 023154
Model: MWM009JR - MLC009CR M5WM010JR - M5LC010CR M5WM015JR - M5LC015CR
10
MWM-J-2009 Application Information
70034 095236
Model: MWM015JR - MLC015CR
11
Application Information MWM-J-2009
Controller
G17
Operation Guide
1 Transmission Source
The source where the signal will be transmitted.
2 Signal Transmission Indication
Blink to confi rm that the last setting has been transmitted to the unit.
3 Temperature Setting
To set the desired room temperature, press the v or V button to increase orde crease the set temperature. The temperature setting range is from 16°C to 30°C (optional setting 20°C to 30°C).
4 Personalize Setting
Press
and hold for 3s, then will blink. Press again to cycle between and Set the desire setting, then leave the hand set for 4s without pressing any key and it will save the setting into the programme. Press once to activate the P1 setting, press again to cycle between P1 and P2. Press any key to deactivate the personalize setting.
5 Automatic Air Swing (optional)
Press the SWING
button to activate the automatic air
swing function. To distribute the air to a specifi c direction, press the SWING button and wait until the louver move to the desired direction and press the button once again.
6 Silent Function
Press
for quiet operation. Fan speed turn to minimum speed. Press again to deactivate the function.
7 Sleep Mode Setting
Press the SLEEP button will activate the sleep mode function. This function is available under COOL, HEAT and AUTO mode. When the unit is operating under cooling mode, the set temperature is increased by 0.5°C after 30 minutes, 1°C after an hour, and 2°C after 2 hours. When the unit is operating under heating mode, the set temperature is decreased by 1°C after 30 minutes, 2°C after an hour, and 3°C after 2 hours.
8 Operating Mode
Press the MODE button to select the type of operating mode. For cooling only unit, the available modes are: COOL (7), DRY (6) and FAN (
).
9 Fan Speed Selection
Press the
button continuously will toggle the fan speed in the following order: Low p Med p High p Auto Stop pressing when the desired fan speed appears on the display screen.
10 “ON/OFF” Button
Press one to start the air conditioner unit. Press again to stop the unit.
11 Timer Cancel
Press the TIMER CANCEL button to cancel the on timer setting.
12 OFF Timer Setting
Press the OFF TIMER button will activate the off timer function. Set the desired off time by pressing the OFF TIMER button continuously.
13 ON Timer Setting
Press the ON TIMER button will activate the on timer function. Set the desired on time by pressing the ON TIMER button continuously. If the timer is set to 7.30am, the air conditioner will turn on at 7.30am sharp.
14 Turbo Function
Press
for fast cooling. Fan speed turn to maximum speed. Press again to deactivate the function.
15 Clock Time Setting
Press
and hold to set the clock time.
MODE
P1 P2
SLEEP
SET
CANCEL
ON TIMER
SET
CANCEL
OFF TIMER
6a 6b
12
15
11
13
14
7
4
3
10
9
2
1
8
5
12
MWM-J-2009 Application Information
Installation Guideline
Safety Precautions
WARNING
CAUTION
Installation and maintenance should be performed by qualifi ed persons who are familiar with local code and regulation, and experienced with this type of appliance.
All fi eld wiring must be installed in accordance with the national wiring regulation.
Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring work according to the wiring diagram.
The unit must be GROUNDED to prevent possible hazard due to insulation failure.
All electrical wiring must not touch the refrigerant piping or any moving parts of the fan motors.
Confi rm that the unit has been switched OFF before installing or servicing the unit.
Disconnect from the main power supply before servicing the air conditioner unit.
DO NOT pull out the power cord when the power is ON. This may cause serious electrical shocks which may result in fi re hazards.
Keep the indoor and outdoor units, power cable and transmission wiring, at least 1m from TVs and radios, to prevent distorted pictures and static. {Depending on the type and source of the electrical waves, static may be heard even when more than 1m away}.
Please take note of the following important points when installing.
Do not install the unit where leakage of fl ammable gas may occur.
If gas leaks and accumulates around the unit, it
may cause fi re ignition.
Ensure that drainage piping is connected properly.
If the drainage piping is not connected properly,
it may cause water leakage which will dampen the furniture.
Do not overcharge the unit.
This unit is factory pre-charged. Overcharge will cause over-current or damage to the compressor.
Ensure that the unit’s panel is closed after service or installation.
Unsecured panels will cause the unit to operate
noisily.
Sharp edges and coil surfaces are potential locations which may cause injury hazards. Avoid from being in contact with these places. Before turning off the power supply, set the remote controller’s ON/OFF switch to the “OFF” position to prevent the nuisance tripping of the unit. If this is
not done, the unit’s fans will start turning automatically when power resumes, posing a hazard to service personnel or the user.
Do not operate any heating apparatus too close to the air conditioner unit. This may cause the plastic panel to
melt or deform as a result of the excessive heat.
Ensure the color of wires of the outdoor unit and the terminal markings are same to the indoors respectively. IMPORTANT : DO NOT INSTALL OR USE THE AIR CONDITIONER UNIT IN A LAUNDRY ROOM. Do not use joined and twisted wires for incoming power supply.
NOTICE
Disposal requirements
Your air conditioning product is marked with this symbol. This means that electrical and electronic products shall not be mixed with unsorted household waste. Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment of the refrigerant, of oil and of other parts must be done by a qualifi ed installer in accordance with relevant local and national legislation. Air conditioners must be treated at a specialized treatment facility for re-use, recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential negative consequences for the environment and human health. Please contact the installer or local authority for more information. Batteries must be removed from the remote controller and disposed of separately in accordance with relevant local and national legislation.
13
Application Information MWM-J-2009
Installation Diagram
Indoor Unit
Air filter
M4 x 12L
Air-Purifying Filter with bacteriostatic virustatic function (2)
Front panel
30mm or more from ceiling
Outdoor Unit
50mm or more from walls (on both sides)
Air filter
Air-Purifying Filter with bacteriostatic virustatic function
Filter frame
Tab
Caulk pipe hole gap with putty.
Cut thermal insulation pipe to an appropriate length and wrap it with tape, making sure that no gap is left in the insulation pipe's cut line.
Wrap the insulation pipe with the finishing tape from bottom to top.
Service lid
Opening service lid
Service lid is opening/closing type.
Opening method
1) Remove the service lid screws.
2) Pull out the service lid diagonally down in thedirection of the arrow.
1) Pull down.
250mm from wall
Caution
Before installing the unit, ensure that the power supply matches the power requirement of the air conditioner.
Installation of Indoor Unit
Service Space
Install the indoor unit at a location with the following requirements
Location is suitable for wiring, piping and drainage. No obstruction of air fl ow into and out of unit where cooler air can be evenly distributed. Ensure that air discharge is not short circuited with air intake. Ensure that wall is suffi ciently strong, rigid, fl at, perpendicular and vibration free. Where air fi lter cassette can be slided in or out easily. Where there is no danger of fl ammable gases. Where there is no direct sunlight on unit.
min. 50
(Space for maintenance)
Air flow (Indoor)
min. 50
(Space for maintenance)
03.n
im
rofecap
S(
)ecn
am rof rep
Required space
14
MWM-J-2009 Application Information
Routing of Piping
The refrigerant piping can be routed to the unit in one of 5 directions, by using the cut outs in the unit casing (refer to Figure 1).
1
2
3
4
5
Figure 1
Carefully bend the pipes to the required position to align with the hole. For right hand and rear side draw out, hold the bottom of the piping and fi x direction before shaping it to the desired position (refer to Figure 2).
Right & Rear Side Routing
Right-back piping
Bind coolant pipe and drain hose together with insulating tape.
Right-bottom piping
Remove pipe port cover here for right-bottom piping
Right-side piping
Remove pipe port cover here for right-side piping
Remove pipe port cover here for left-bottom piping
Remove pipe port cover here for left-side piping
Left-back piping
Left-side piping
Left-bottom piping
Figure 2
Mounting Installation Plate
Paste the installation plan provided on the desired location on the wall and marks the holes location accordingly. Ensure the wall is strong enough to withstand the weight of the unit. Otherwise, it is necessary to reinforce the wall with plates, beams or pillars. Ensure the levelness of the installation plate, and fi x with 5 suitable screws.
Mounting plate
Mounting plate fixing screw
15
Application Information MWM-J-2009
Fix the installation plate fi rmly to the wall, without tilting to left or right. Use a plumb line, if available.
Through the wall hole Ø 65mm
Drain hose position
Recommended mounting plate retention spots (5 spots in all)
Use tape measure as shown. Position the end of a tape measure at
Gas pipe end
Liquid pipe end
166
184
181.7
55554.5
153.8 263
51.9 800
45.9
42.2
288
42.2
45.9
42.2
All dimensions are in mm
In case of rear piping drawings out, drill a hole 65mm in diameter with a cone drill, slightly lower on the outside wall.
Inside
Caulking
Outside Wall embedded pipe (Field supply)
Wall hole cover (Field supply)
Wall embedded pipe (Field supply)
Ø65
Hole with cone drill
Mounting Unit onto the Installation Plate
Hook the indoor unit onto the upper portion of the installation plate (engage the two hooks at the rear top of the indoor unit with the upper edge of the installation plate). Ensure the hooks are properly seated onto the installation plate by moving it to the left and right. To attach the indoor unit, hook the claws of the bottom frame to the mounting plate. If the claws are diffi cult to hook, remove the front grille. To remove the indoor unit, push the marked area (at the lower part of the front grille) to release the claws. If it is diffi cult to release, remove the front grille.
Mounting plate
Clip
Mark (rear side)
Bottom frame
Front grille
Mounting plate
Interconnecting wires
Hang indoor unit's hook here.
Wire guide
When stripping the ends ofinterconnecting wires in advance, bind right endsof wires with insulating tape.
16
MWM-J-2009 Application Information
Water Drainage Piping
The indoor drain pipe must be downward gradient for smooth drainage. Avoid situation as shown in fi gure below.
End dipped into water
Water leaking
Water leaking
Water leaking
Wrong
Wrong
Wrong
Drain
Water Drainage
Water Retention
Correct
Installation of Outdoor Unit
Condensed Water Disposal of Outdoor Unit (Heat Pump Unit Only)
There are 2 holes on the base of outdoor unit for condensed water to fl ow out. Insert the drain elbow to one of the holes. To install the drain elbow, fi rst insert one portion of the hook to the base (portion A), the pull the drain elbow in the direction shown by the arrow while inserting the other portion to the base. After installation, check to ensure that the drain elbow clings to base fi rmly. If the unit is installed in a snowy and chilly area, condensed water may freeze in the base. In such case, please remove plug at the bottom of unit to smooth the drainage.
A
17
Application Information MWM-J-2009
As condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to achieve maximum cooling capacity, the location selected for outdoor unit should fulfi ll the following requirements:
Install the condensing (outdoor) unit in a way such that hot air distributed by the outdoor condensing unit cannot be drawn in again (as in the case of short circuit of hot discharge air). Allow suffi cient space for maintenance around the unit.
Ensure that there is no obstruction of air fl ow into or out of the unit. Remove obstacles which block air intake or discharge. The location must be well ventilated, so that the unit can draw in and distribute plenty of air thus lowering the condensing temperature.
A place capable of bearing the weight of the outdoor unit and isolating noise and vibration. A place protected from direct sunlight. Otherwise use an awning for protection, if necessary.
The location must not be susceptible to dust or oil mist.
Installation Clearance
Outdoor units must be installed such that there is no short circuit of the hot discharge air or obstruction to smooth air fl ow. Select the coolest possible place where intake air should not be hotter than the outside temperature (max. 45˚C).
ALL MODELS A B C D
Minimum Distance 300 mm 1000 mm 300 mm 500 mm
CAUTION : If the condensing unit is operated in an atmosphere containing oils (including machine oils), salt (coastal area), sulphide gas (near hot spring, oil refi nery plant), such substances may lead to failure of the unit.
18
MWM-J-2009 Application Information
Wiring
Electrical Connections
Wiring regulations on wire diameters differ from country to country. Please refer to your LOCAL ELECTRICAL CODES for fi eld wiring rules. Be sure that installations comply with the rules and regulations.
General Precautions
Ensure that the rated voltage of the unit corresponds to the name plate before carrying out proper wiring according to the wiring diagram. Provide a power outlet to be used exclusively for each unit. A power supply disconnects and a circuit breaker for over-current protection should be provided in the exclusive line. The unit must be GROUNDED to prevent possible hazards due to insulation failures. All wiring must be fi rmly connected. All wiring must not touch the hot refrigerant piping, compressor or any moving parts of fan motors.
Refrigerant Piping
Piping Length and Elevation
When the pipe length becomes too long, both the capacity and reliability drop. As the number of bends increases, system piping resistance to the refrigerant fl ow increases, thus lowering the cooling capacity, and as the result the compressor may become defective. Always choose the shortest path and follow the recommendation as tabulated below:
Outdoor Unit
Indoor Unit
LH
Model
Indoor
MWM009J/JR
M5WM010J/JR
MWM015J/JR
M5WM015J/JR
Outdoor
MLC009C/CR
M5LC010C/CR
MLC015C/CR
M5LC015C/CR
Min. Allowable Length, m (L) 3 3
Max. Allowable Length, m (L) 15 15
Max. Allowable Height, m (H) 10 10
Liquid, mm/in 6.35 / 1/4 6.35 / 1/4
Suction, mm/in 9.52 / 3/8 12.70 / 1/2
* Be sure to add the proper amount of additional refrigerant. Failure to do so may result in reduced performance
Remark: The refrigerant pre-charged in the outdoor unit is for piping length up to 7.6m/25ft.
19
Application Information MWM-J-2009
Piping Works
Do not use contaminated or damaged copper tubing. Do not remove plastic, rubber plugs and brass nuts from the valves, fi ttings, tubings and coils until you are ready to connect suction or liquid line into valves or ttings. If any brazing work is required, ensure that the nitrogen gas is passed through coil and joints while the brazing work is being done. This will eliminate soot formation on the inside walls of the copper tubings. Cut the connection pipe with a pipe cutter.
Cutting copper tube
1/4t
Remove burrs from cut edges of the pipes with remover. Hold the end of the pipe downwards to prevent metal chips from entering the pipe.
Remove burr
Insert the fl are nuts, mounted on the connection parts of both the indoor unit and outdoor unit onto the copper pipes. Flare the pipe with extra length above the fl aring tool as shown in the table. The fl ared edge must be even and not cracked or scratched.
Ø Tube,
D (mm / in)
A (mm)
Imperial Die Rigid Die
6.35 / 1/4 1.3 0.7
9.52 / 3/8 1.6 1.0
12.70 / 1/2 1.9 1.3
15.88 / 5/8 2.2 1.7
19.05 / 3/4 2.5 2.0
Swaging block
Copper tube
Piping Connection to the Units
Align the center of the piping and tighten the fl are nut suffi ciently with fi ngers. Finally tighten the fl are nut with torque wrench unit the wrench clicks. When tightening the fl are nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.
Pipe Size (mm/in) Torque (Nm)
6.35 (1/4) 18
9.52 (3/8) 42
12.70 (1/2) 55
15.88 (5/8) 65
19.05 (3/4) 78
Indoor piping
Flare nut
Flared tube
Flare joint
Spanar
Torque wrench
Loading...
+ 50 hidden pages