A : 50Hz / 1Ph / 220-240V
F : 50Hz / 3Ph / 380-415V
Model
“ ”: Cooling Only
R: Heat Pump
M5MSY_(i)Nomenclature
Product Line-Up
Indoor Unit
M5WMY-L Series/J Series
Classifi cation
M5WMY
10LRACBDDXXXXXXX
15LRACBDDXXXXXXX
10JRACLADXXXXX
15JRACLADXXXXX
HEATPUMP
20JRACLTCXXXXX
Indoor Unit
M5CKY-C Series
Nomenclature
GS01
Handset
PCB
W_2_03A
Air
Purifi cation
Saranet Filter
Bio Antibody Filter
Classifi cation
Marking
Titanium Apatite
Filter
CE
Others
Auto Restart
Handset
M5CKY
Nomenclature
GS01
10CRACOAXXX
15CRACOAXXX
20CRACOAXXX
HEATPUMP
PLCKYCRNGS01XXX
PCB
C_2_01A_M
Air
Purifi cation
Saranet Filter
Negative Ionizer
Nano Technology Air
Filtration
CE
Marking
Others
Auto Restart
2
Nomenclature M5MSY_(i)
Indoor Unit
M5CCY-C Series
Classifi cation
M5CCY
10CRACPAXXXXX
15CRACPAXXXXX
HEAT-
PUMP
20CRACPAXXXXX
Indoor Unit
M5CMY-E Series
Nomenclature
Netware 3C
Handset
Handset
PCB
C_2_01A_M
PCB
Air
Purifi cation
Saranet Filter
Negative Ionizer
Classifi cation
Air
Purifi cation
Nano Technology Air
Filtration
CE
Marking
Marking
Others
Auto Restart
Others
M5CMY
Nomenclature
GS01
15ERACAAXXXXX
20ERACAAXXXXX
HEAT-
PUMP
C_2_01A_M
Saranet Filter
Negative Ionizer
Nano Technology Air
Filtration
CE
Auto Restart
3
M5MSY_(i) Nomenclature
Outdoor Unit
M5MSY-BR
Classifi cation
Refrigerant
M5MSY
18BRACDOA
20BRACDOA
25BRACDOA
30BRACDOA
HEATPUMP
Nomenclature
Cap Tube
Control
EXV
XXXXX
XXXXX
XXXXX
XXXXX
Fin
Gold coated
Blue coated
Bare
ContactorHPLP
Safety
Devices
Compressor
DC Inverter SwingCEDrain Elbow
Marking
Others
* Remark : M5MSY18BR is not recommended to couple with M5WMY10/15 JR (for Wall Mounted series).
M5MSY18BR is recommended to couple with M5WMY10/15 LR (for Wall Mounted series).
4
Application Information M5MSY_(i)
Application Information
Operating Range
Ensure the operating temperature is in allowable range.
Heatpump - M5MSY20/25/30BR
Heating
18
10
Outdoor temp. (°CWB)
-16
1520
Indoor temp. (°CDB)
Heatpump - M5MSY18BR
Heating
18
27
Standard
point
Cooling
46
43
Outdoor temp. (°CDB)
0
122319
Indoor temp. (°CWB)
Cooling
10
Outdoor temp. (°CWB)
-16
1520
Indoor temp. (°CDB)
27
Indoor temp. (°CWB)
Caution :
The use of your air conditioner
outside the range of working
temperature and humidity can result
in serious failure
.
5
M5MSY_(i) Application Information
Refrigerant Circuit Diagrams
Model: M5MSY18BR
M5MSY20BR
Model: M5MSY25BR
M5MSY30BR
6
Application Information M5MSY_(i)
Installation Guideline
Installation of Outdoor Unit
• The outdoor unit must be installed in such a way, so as to prevent short circuit of the hot discharged air or
obstruction to the smooth air fl ow. Please follow the installation clearance shown in the fi gures below. Select
the coolest possible place where intake air temperature is not greater than the outside air temperature
(maximum 45°C/113°F)
• Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airfl ow, follow the installation
guidelines below.
• For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less.
Wall facing two sidesWall facing one side
More than 100
Side View
More than 350
1200
or less
More than 50
More
than 100
More than 350
More than 50
Top Vie w
Wall facing three sides
More than 100
More than 50
More than 350
Top View
Unit : mm
• Before installing the piping and connecting cord, please remove the access panel and plastic valve cover for
easy access. Refer to fi gures shown below.
PLEASE REMOVE
ACCESS PANEL &
PLASTIC VALVE
COVER WHEN
CONNECTING
THE PIPING AND
CONNECTING
CORD.
PUSH & PULL UP
• There are 2 holes on the base of Outdoor Unit for
condensed water to fl ow out. Insert the drain elbow
to one of the holes.
• To install the drain elbow, fi rst insert one portion
of the hook to the base (portion A), then pull the
drain elbow in the direction shown by the arrow
while inserting the other portion to the base. After
installation, check to ensure that the drain elbow
clings to base fi rmly.
• If the unit is installed in a snowy and chilly area,
condensed water may freeze in the base. In such
case, please remove plug at the bottom of unit to
smooth the drainage.
7
BASE
Plug
A
DRAIN
ELBOW
DRAIN
ELBOW
M5MSY_(i) Application Information
Installation Diagram
Wall Mounted
Indoor Unit
Cut thermal insulation
pipe to an appropriate
length and wrap it with
tape, making sure that no
gap is left in the insulation
pipe's cut line.
Wrap the insulation pipe with
the finishing tape from bottom
to top.
Front panel
50mm or more from walls
(on both sides)
30mm or more from ceiling
Caulk pipe
hole gap
with putty.
Air filter
Air-Purifying Filter with
bacteriostatic virustatic function (2)
Air-Purifying Filter with
bacteriostatic virustatic
function
Filter frame
Tab
Air filter
Outdoor Unit
M4 x 12L
Opening service lid
Service lid
Service lid is opening/closing
type.
Opening method
1) Remove the service lid
screws.
2) Pull out the service lid
diagonally down in
the direction of the arrow.
1) Pull down.
250mm from wall
Caution
Before installing the unit, ensure that the power supply matches the power requirement of the air conditioner.s
Installation of Indoor Unit
Service Space
Install the indoor unit at a location with the following requirements
• Location is suitable for wiring, piping and drainage.
• No obstruction of air fl ow into and out of unit where cooler air can be evenly distributed.
• Ensure that air discharge is not short circuited with air intake.
• Ensure that wall is suffi ciently strong, rigid, fl at, perpendicular and vibration free.
• Where air fi lter cassette can be slided in or out easily.
• Where there is no danger of fl ammable gases.
• Where there is no direct sunlight on unit.
Air flow
(Indoor)
min. 50
(Space for
maintenance)
Required space
min. 50
(Space for
maintenance)
rofecapS(
03.nim
)ecnamrofrep
8
Application Information M5MSY_(i)
Ceiling Cassette
Front Panel
Air Filter
(behind the grille)
Air Discharge Louver
Drain Piping
Thermal Insulation
Wrap the insulated pipe with the
finishing tape from bottom to top
Air Intake Grille
Preliminary Site Survey
• Electrical supply and installation is to confi rm to local authority’s (e.g. National Electrical Board) codes and
regulations.
• Voltage supply fl uctuation must not exceed ± 10% of rated voltage. Electricity supply lines must be
independent of welding transformers which can cause high supply fl uctuation.
• Ensure that the location is convenient for wiring, piping and drainage.
• The indoor unit must be installed in such that free from any obstacles in path of cool air discharge and
warm air return, and must allow spreading or air throughout the room (near the centre of the room).
• Clearance must be provided for the indoor unit from the wall and obstacles as shown in the fi gure.
Beam
Min 0.5 mMin 0.5 m
Min 1.0 m
Obstacles
Max 3.0 m
Floor
• The installation place must be strong enough to support a load of 4 times the indoor unit weight to avoid
amplifying noise and vibration.
• The installation place (handling ceiling surface) must be level and the height in the ceiling is 350mm or
more.
Min 0.5 m
Max 3.0 m
9
M5MSY_(i)Application Information
Unit Installation
15.0
38.0
505.0
32.0
580.0 ~ 610mm (CEILING OPENING MEASUREMENT)
538.0
18.0
)TNEMERUSAEMGNINEPOGNILIEC(mm016~0.085
88.0448.0
19.0529.0
M5CKY-C
• The indoor unit must be away from heat and steam sources (avoid installing it near an entrance).
• Measure and mark the position for the hanging rod. Drill the hole for the angle nut on the ceiling and fi x
the hanging rod.
• The installation template is extended according to temperature and humidity. Check on dimensions in
using.
• The dimensions of the installation template are same as those of the ceiling opening dimensions.
• Before ceiling laminating work is completed, be sure to fi t the installation template to the indoor unit.
Note: Be sure to discuss the ceiling drilling work with the installers concerned.
Unit Hanging
Indo or U nit
Ceiling
Bo
ard
30.0mm
M5CKY-C/E
• Confi rm the pitch of the hanging rod is 770mm x 622mm sharp (M5CKY-E)
• Hold the unit and hand it on the hanging rod with the nut and washer.
• Adjust the unit height to 35.0mm between the indoor unit bottom surface and the ceiling surface.
• Confi rm with a level gauge that the unit is installed horizontally and tighten the nut and bol to prevent unit
falling and vibration.
Open the ceiling board along the outer edge of the paper installation template.
•
10
Application Information M5MSY_(i)
Ceiling Concealed
Hanger
Return duct
Supply duct
Wrap the insulated pipe with the
finishing tape from bottom to top
Ceiling
Drain
piping
Thermal insulation
Preliminary Survey
• Electrical supply and installation is to confi rm to local authority’s (e.g. National Electrical Board) codes and
regulations.
• Voltage supply fl uctuation must not exceed ± 10% of rated voltage. Electricity supply lines must be
independent of welding transformers which can cause high supply fl uctuation.
• Ensure that the location is convenient for wiring, piping and drainage.
• The indoor unit must be installed in such that free from any obstacles in path of cool air discharge and
warm air return, and must allow spreading or air throughout the room (near the centre of the room).
• Clearance must be provided for the indoor unit from the wall and obstacles as shown in the fi gure.
• Use the hanger supplied with the unit.
• Ensure the support is strong enough to withstand the weight of the unit.
• Use the supplied drain socket to connect the drain pipe
11
Install the unit in such a way that
the condensate water can flow
out smoothly.
M5MSY_(i) Application Information
The diagrams below show the screws position for duct work connection.
12
Application Information M5MSY_(i)
Ceiling Convertible
Preliminary Site Survey
• Electrical supply and installation is to confi rm to local authority’s (e.g. National Electrical Board) codes and
regulations.
• Voltage supply fl uctuation must not exceed ± 10% of rated voltage. Electricity supply lines must be
independent of welding transformers which can cause high supply fl uctuation.
• Ensure that the location is convenient for wiring, piping and drainage.
Standard Mounting
Ensure that the overhead supports are strong enough to hold the weight of the unit. Position the hanger rods
(wall mounting bracket for fl oor standing), and check for its alignment with the unit as shown in Fig. below.
Also,check that the hangers are secured and the base of the fan coil unit is leveled in both horizontal
directions, taking into account the gradient for drainage fl ow as recommended under section Piping and
Drain Hose Installation.
13
M5MSY_(i)Application Information
Please ensure that the following steps are taken:
• Check the gradient for drainage fl ow as recommended in Figure A.
• Provide clearance for easy servicing and optimal air fl ow as shown in Figure B.
• The indoor unit must be installed such that there is no short circuit of the cool discharge air with the warm
return air.
• Do not install the indoor unit where there is direct sunlight shining on the unit. The location should be suitable for piping and drainage installation. The unit must be a large distance away from the door.
Fig.A
Under ceiling type
Floor standing type
Fig.B
14
Application Information M5MSY_(i)
Under Ceiling Installation
Install the Suspension Bolts
1. Install the suspension bolts so that it can support the indoor unit.
2. Adjust the distance to ceiling before installation.
3. Refer to the dimension given to install the unit.
Install the Indoor Unit
1. Insert the suspension bolts into the fi ttings of the hanger bracket.
2. Set the nuts and washer on the both side of the metal fi ttings.
3. Secure it with nuts.
4. Attach the hanger cover (4 pcs) to the units.
15
M5MSY_(i) Application Information
Floor Standing Installation
1. Refer to the dimension as illustrated when installing the mounting bracket.
2. Determine the pipe hose position using the rear piping hole. Drill the pipe hole at the slight downward
slant to the outdoor side.
MOUNTING BRACKET
HOCK THE UNIT ON THE
MOUNTING BRACKET
WALL
16
Application Information M5MSY_(i)
REFRIGERANT PIPING
Piping Length & Elevation
If the pipe is too long, both capacity and reliability of the unit will drop. As the number of bends increases,
resistance to the fl ow of refrigerant system increases, thus lowering cooling capacity. As a result, the
compressor may become defective. Always choose the shortest path and not exceed the maximum piping
length as tabulated below.
Single Indoor
Maximum
Piping
Length(m)
Maximum
height
Difference(m)
Pre-charged
Total Piping
length (m)
Outdoor Unit
Pre-charged
(kg)
1.220
L ≤ 25H ≤ 15302.620
4
L ≤ 25H ≤ 15302.620
Amount of
Additional
Charge (g/m)
Model
M5MSY18BR
(2 Ports)
M5MSY20BR
(2 Ports)
M5MSY25BR
(3 Ports)
M5MSY30BR
(4 Ports)
Maximum
Total Piping
Length (m)
L
+ L2 ≤ 30L ≤ 20H ≤ 1515
1
L1+ L2 ≤ 50L ≤ 25H ≤ 15302.020
L
+ L2+ L3 ≤
1
60
L
+ L2+ L3+ L
1
≤ 60
VERTICAL HEIGHT
DIFFERENCE MAX. H
INDOOR UNIT
OUTDOOR UNIT
* Remark : Applicable for Wall Mounted, Ceiling Cassette, Ceiling Concealed, Ceiling Convertible unit.
17
M5MSY_(i) Application Information
Piping Connection To The Units
• The outdoor unit is equipped with two to four sets of fl are joints depending on O/D unit model. Refer to the
table below for fl are joint size and location.
ModelPipeABCD
M5MSY18BR
M5MSY20BR
M5MSY25BR
M5MSY30BR
18
ELECTRICAL WIRING CONNECTION
IMPORTANT: The fi gures shown in the table are for information purpose only. They should be checked and
selected to comply with the local/national codes of regulations. This is also to the type of
installation and conductors used.
Liquid1/4”1/4”--
Gas3/8”3/8”--
Liquid1/4”1/4”--
Gas1/2”1/2”--
Liquid1/4”1/4”1/4”-
Gas3/8”1/2”1/2”-
Liquid1/4”1/4”1/4”1/4”
Gas3/8”3/8”1/2”1/2”
Indoor Unit AIndoor Unit BIndoor Unit CIndoor Unit D
12 SIG NL
SIGNLNLNLNLNL
0
There must be a double pole switch with a minimum 3 mm contact gap and fuse/ circuit breaker as
SIG
12 SIG NL12 SIG NL
SIGSIG
12 SIG NL
DCBA
Power
Supply
Power Supply
recommended in the fi xed installation circuit.
• All wiring must be connected accordingly to the diagram
above, with reference to the piping connection. Mismatch
any wiring with different piping will cause severe damage
to the system.
• All wires must be fi rmly connected.
• All wires must not touch the refrigerant piping, compressor
or any moving parts of the fan motor.
• The connecting wires between the indoor unit and the
outdoor unit must be clamped on the wire clamps and the
cable tie (push releasable) at the indoor unit and outdoor
unit respectively as shown in the fi gures.
• The power supply cord must be equivalent to H07RN-F
(245IEC57) or higher.
• Remove the detachable part of the access cover to allow
wire routing.
• All wires must not be clamped by the access panel cover.
Detachable part
Wires
mustn't be
clamped
Wire Clamp
Interconnection
Cable
18