McQuay M5WM10F, M5LC15C, M5LC10C, M5WM15F, M5WM20F Installation And Maintenance Manual

...
M5WM Wall Mounted Split Type Air Conditioner (SEER 13)
Indoor Unit
Outdoor Unit
IM-5WMF (SEER13)-0706-McQua
y
Group: Wall Mounted Part Number: R08019028218 Date: July 2006
Wireless Remote Control (Standard)
Wired Wall Control
(Optional)
Table of Contents
General Information……………………………………………….. 3
Safety Precautions………………………………………. 3
Unit Dimensions…………………………………………….……... 4
Indoor Units ……………………………………. ……....4
Outdoor Units …………………………….…….. ……....4
Installation Guidelines……………………………………………... 7
Installation Diagram……………………………………... 7 Installation of Outdoor Unit……………………………... 7
Condensed Water Disposal of Outdoor Unit……. ……....7
Outdoor Unit Clearances…………………………… 7
Installation of the Indoor Unit…………………………… 7
Indoor Unit Clearances …………………………….8
Piping ……………………....................................... 8
Mounting Plate Installation ……………….. ………8 Installing Unit on Mounting Plate ………….………9
Drain Hose Installation .................. .............. ………9
Refrigerant Tubing…………………………………………………. 10
Tubing Length & Elevation………………………………10 Tubing Preparation………………………………………. 10 Tubing Connection To Units …………..………. ………10
Electrical Connections …………………………..………... ………11
Cooling Unit ………………………...…………. ………11
Heat Pump Unit ………………………............... ………11
Wiring Diagrams ……………………………….................. ………12
Vacuuming and Charging………………………………………….. 18
Purging the Piping and the Indoor Unit…………………. 18
Additional Charge……………………………………….. 18
Charge Operation………………………………………... 18
Special Precaution When Dealing with R410A unit……. 19
Model Numbers
Cooling Only
Indoor Unit Outdoor Unit Nominal Cooling – BTUH
M5WM10F M5LC10C 9000 M5WM15F M5LC15C 12,000 M5WM20F M5LC20C 17,500 M5WM25F M5LC25C 23,000
Cooling/Heat Pump
Indoor Unit Outdoor Unit Nominal Cooling - BTUH Nominal Heating - BTUH
M5WM10FR M5LC10CR 9000 8800 M5WM15FR M5LC15CR 12,000 12,000 M5WM20FR M5LC20CR 17,500 18,000 M5WM25FR M5LC25CR 23,000 23,500
Page 2 IM-5WMF(SEER13)-0706
Unit Indicator Lights ……………………………................ 19
IR Signal Receiver ………………...…………… 19
Cooling Only Unit ……………………............... 19
Heat Pump Unit ………………………............... 20
Special Features …………………………………..….......... 21
Dry Mode ……………………………..…........... 21
Heat Mode (Heat Pump Only) ………..………... 21 Air Flow Control ………………………..……… 21 Hot Keep (for Heat Pump Only) ………..……… 21 Overheating Protection (Heat Pump Only) ……... 21 Frost Prevention ………………………………... 21 Fan Speed and Rated Cooling Capacity ……….. 21
Main Filters ……..………………………............ 21
Cooling ……………..………………………….. 21
Electrostatic Air Purifying Filter …………......... 21
Deodorizing Filter ………………………..…….. 21 Filter Replacement ……………………………... 21 Auto Random Re-start Function ……………….. 22
Low Ambient Kit ………………………………. 22 Minimum and Maximum Operating Temperature….. 22 Remote Controller Operation Guide ……………………… 23 Service and Maintenance …………………………………. 25
Maintenance Schedule …………………………. 25
Troubleshooting ………………………………... 25
General Information
IM-5WMF(SEER13)-0706 Page 3
This manual provides the installation procedures so your air conditioner unit operates properly and provides you the service it was designed to provide. Special adjustment may be necessary to suit local requirements. Before using your air conditioner, please read this instruction manual carefully and keep it for future reference.
Safety Precautions
Before installing the air conditioner unit, please read the following safety precautions carefully.
WARNING
The installer must determine and follow all applicable codes and regulations. This equipment presents hazard of electricity, rotating parts, sharp edges, heat and weight. Failure to read and follow these instructions can result in property, severe personal energy or death. This equipment must be installed by experienced, trained personnel only.
Improper installation can cause equipment damage, service personnel injury or death.
Do not allo w flammable fumes near unit or areas sharing ventilation.
Installation and maintenance must be performed by qualified persons who are familiar with local code and regulations, and experienced with this type of appliance.
All field wiring must be done in accordance with industry standards and local codes.
Inspect the unit nameplate to be certain the voltage is the same as the voltage that will be delivered to the unit. Improper electrical wiring can cause property damage, severe personal energy or death.
The unit must be GROUNDED.
Make sure wiring does not touch refrigerant
piping, compressor, or any moving parts of the fan motors.
Confirm that the power supply is switched OFF before installing or servicing the unit.
WARNING
Hazardous Voltage!
Disconnect all electrical power including remote disconnects before servicing. Failure to disconnect power before servicing can cause severe personal
CAUTION
Use copper conductors only. Unit terminals are not designed to accept other types of conductors. Failure to do so may cause damage to the equipment.
CAUTION
Do no install in a laundry room. Humidity and laundry
chemicals can corrode unit components.
Do not install the unit where leakage of flammable gas may occur. If gas leaks and accumulates ar ound the unit, it may cause a fire.
Connect drainage piping properly. If drainage piping is not connected properly, water leakage can cause property damage.
Do not overcharge the unit. This unit is factor y pre­charged. Overcharge will cause over-current or damage to the compressor.
Keep panel closed. Unsecured panels will cause the unit to operate noisily.
NOTICE
This product was carefully packed and thoroughly inspected before leaving the factory. Responsibility for its safe delivery was assumed by the carrier upon acceptance of the shipment. Claims for loss or damage sustained in transit must therefore be made upon the carrier, as follow:
VISIBLE LOSS OR DAMAGE
Any external evidence of loss or damage must be noted on the freight bill or carrier’s receipt, and signed by the carrier’s agent. Failure to adequately describe such external evidence of loss or damage may r esult i n the carrier’s refusing to honor a damaged claim. The form required to file such a claim will be supplied by the carrier.
CONCEALED LOSS OR DAMAGE
Concealed loss or damage means loss or damage which does not become apparent until the product has been unpacked. The contents may be damaged in transit due to rough handling even though the carton may not show external damages. When the damage is discovered upon unpacking, make a written request fo r inspection by the carrier’s agent within fifteen (15) days of the delivery date. File a claim with the carrier since such damage is the carrier’s responsibility.
Unit Dimensions
Model: M5WM10F, 10FR – Indoor Unit
Model: M5WM15F, 15FR, 20F, 20FR – Indoor Unit
Page 4 IM-5WMF(SEER13)-0706
Model: M5WM25F, 25FR – Indoor Unit
Model: M5LC10C, 10CR, 15C, 15CR – Outdoor Unit
IM-5WMF(SEER13)-0706 Page 5
Dimension
A B C D E F G H 10C/CR 33-5/8” 24-3/4” 12-7/8” 7/8” 2-5/8” 23-3/4” 5” 15-3/8” 15C/CR 33-5/8” 28-3/4” 12-7/8” 7/8” 2-5/8” 23-3/4” 5” 15-3/8”
Dimension
I J K L M
10C/CR
5/8” 14-1/4” 6-1/2” 3” 2-7/8”
15C/CR
5/8” 14-1/4” 6-1/2” 3” 2-7/8”
Model: M5LC20C, 20CR, 25C, 25CR – Outdoor Unit
Page 6 IM-5WMF(SEER13)-0706
Installation Guidelines
Installation Diagram
Condensate Disposal of Outdoor Unit (Heat Pump Unit Only)
There are 2 holes on the base of outdoor unit
for condensed water to flow out. Insert the drain elbow to one of the holes.
To install the drain elbow, first insert one
portion of the hook to the base (portion A), then pull the drain elbow in the direction shown by the arrow while inserting the other portion to the base. After installation, check to ensure that the drain elbow clings to base firmly.
If the unit is installed where the condensate
may freeze in the base, remove plug at the bottom of unit for better drainage
See Figure 2.
Figure 2. Condensate Disposal of Outdoor Unit (Heat Pump Unit Only)
Installation of the Indoor Unit
Indoor Unit Clearance
The indoor unit must be installed in a manner to prevent mixing the discharged air with the return air. Please follow the installation clearances shown in Figure 3. Do not place the indoor unit in direct sunlight. The location must be suitable for piping and drainage, and be away from doors or windows.
Figure 3. Indoor Unit Minimum Clearances
Installation of Outdoor Unit
Outdoor Unit Clearances
Install the outdoor unit in a manner to prevent mixing hot discharged air with return air flow. Also the unit should be a suitable distance from obstructions See Figure 1 for installation clearances. Double the dimensions shown if surroundings are more than 72” tall, or if there is an obstruction on top. Select the coolest possible place where intake air temperature is not greater than the outside air temperature (maximum 113ºF).
Figure 1. Outdoor Unit Minimum Clearances
IM-5WMF(SEER13)-0706 Page 7
Indoor Unit
Room Cabinet
Remove side plate when connecting the piping and power supply
Page 8 IM-5WMF(SEER13)-0706
Piping
The refrigerant piping can enter the indoor unit at several different locations. Use the knock outs provided in the room cabinet. See Figure 4.
Figure 4. Indoor Unit
Bend the pipes carefully to prevent kinks and r estrictions. It’s best to use a tube bender. The condensation drain hose can be taped to the pipes. See Figure 5.
Figure 5. Rear View of Indoor Unit
Mounting Plate Installation
The mounting plate ships attached to the back of the indoor unit. To detach for mounting on wall, remove plastic rivet from bottom (pry loose with a knife blade) and unhook.
The wall must be strong enough to suppor t the weight of the unit. If necessary, reinforce the wall. Drill holes in plate to align with wall studs and attach with four (4) screws.
If the refrigerant piping is going thru the wall behind the indoor unit, provide a 2-1/2” hole that is slightly pitched to the outside. See Figure 6. Hole must be located in alignment with the arrows on the mounting plate . See
Figure 7. Figure 6. Wall Opening for Piping
Figure 7. Mounting Plate/Wall Opening
IM-5WMF(SEER13)-0706 Page 9
Installing Unit on Mounting Plate
Hook the indoor unit onto the upper portion of th e mounting plate (engage the two hooks at the rear top of the indoor unit with the upper edge of the plate). Properly seat the hooks and replace the plastic rivet at the bottom.
Figure 8. Installing Unit on Mounting Plate
Drain Hose Installation
The condensate drain hose (20” long) come factory attached to the indoor unit. It is gravity flow. Avoid situations that could restrict drainage. See Figure 9.
Figure 9. Drain Hose Installation
Page 10 IM-5WMF(SEER13)-0706
Refrigerant Tubing
Tubing Length & Elevation
Copper tubing to connect the indoor and outdoor units is supplied by others or it can be ordered from the factory. See Table 1 for requirements. Cover b oth tubes in dividually with 3/8” wall foam insulation.
Table 1. Refrigeration Tubing Requirements
Model 10 15 20 25
Maximum length, ft., L
40 40 50 50
Max. elevation, ft., H
16 16 26 26
Max. number of bends
10 10 10 10
Liquid tube size – OD
¼” ¼” ¼” ¼”
Gas tube size - OD
3/8” ½” ½” 5/8”
Note: The refrigerant pre-charged in the outdoor unit is for tubing length up to 25ft. See Table 5, page 18 for additional R410A refrigerant required on longer runs.
Figure 10. Tubing Length and Elevation
Tubing Preparation
Do not use contaminated or damaged copper tubing. Do not remove plastic, rubber plugs and brass nuts from the valves, fittings, tubings and coils until you are ready to connect suction or liquid line into valves or fittings.
If any brazing work is required, ensure that the nitrogen gas is passed through coil and joints while the brazing work is done. This will eliminate soot formation on the inside wall of the copper tubing.
Cut the copper tubing with a tube cutter. See Figure 11.
Remove burrs from cut ends by holding tubing
downwards to prevent metal chips from entering the tubing.
Slide the flar e nuts, for both the indoor unit and outdoor unit onto the copper tubing.
Flare the tubing as shown in Figure 11, Figure 12 and Table 2.
The flare must be even and not cracked or scratched.
Figure 11. Cutting and Flaring Tube
Table 2: Tube Flaring Dimensions
Tube Diameter - OD X (in.)
Inch Imperial Rigid
¼ .051 .028
3/8 .063 .039
½ .075 .051
5/8 .087 .067
Tubing Connection To Units
Connect the copper tubing to both the indoor and outdoor units. See Figure 12.
Torque each flare nut to specifications. See Table 3.
Cover both tubes individually with 3/8” minimum wall foam insulation.
Table: Flare Nut Torque Specifications
Tube Size (in.) Torque (ft./lb.)
¼ 13.3
3/8 31.0
½ 40.6
5/8 48.0
Figure 12. Flare Tubing Connections
H L
Outdoor Unit
IM-5WMF(SEER13)-0706 Page 11
Electrical Connections
Wiring must be in accordance with all applicable electrical codes.
Wires must not touch the refrigerant piping, compressor or any moving part.
All electrical field wiring must be clamped at both the indoor unit and the outdoor unit. See Figure 14 for typical clamp.
See Table 4, figure 13 and Figure 15 for the number of wires, wire gauge and fuse/circuit breaker size required.
Table 4: Wire and Fuse/Breaker Requirements
10/15
Unit Size
Indoor Outdoor
20/25
Voltage-1Ph/60Hz
115V 208/230V 208/230V
Power supply wire size Number of wires
14 ga.
2 + gnd.
14 ga.
2 + gnd.
12ga.
2 + gnd.
Connecting wire size Number of wires – A/C Number of wires - HP
14 ga.
2 4
14 ga. 3 + gnd. 5 + gnd.
Fuse/Breaker size
15 amp 15 amp 20 amp
* Not including the Outdoor Coil Sensor Cable.
Figure 13. Cooling Only Size 10 & 15
Indoor Unit Outdoor Unit Terminal Block Connecting Wires Terminal Block
COMP
N2
N1
L
NEC requires an approved electrical disconnect within sight of the unit so that anyone working on the unit can turn the power off and see that its not accidentally turned back on. This will require two disconnects, one by the outdoor unit and one by the indoor unit.
COMP
N2 N1
L
Power supply
208/230V
!
L2
L1
N L1
Power supply 115V
Figure 14. Terminal Block and wire Clamp
Figure 15. Heat Pump Unit Size 10 & 15
4WV
OF
Comp
N2 N1
L
4WV
OF
Comp
N2 N1
L
!
Power supply
208/230V
L2
L1
N L1
Power supply 115V
Outdoor coil sensor, 2 conductor cable, (26 feet long) shipped with the indoor unit. Extend with 22 ga. low voltage wire if not long enough to reach outdoor unit.
Indoor Unit Terminal Block
Outdoor Unit Terminal Block
Connecting Wires
NEC requires an approved electrical disconnect within sight of the unit so that anyone working on the unit can turn the power off and see that its not accidentally turned back on. This will require two disconnects, one by the outdoor unit and one by the indoor unit
WARNING
Improper installation can cause severe personal injury or death. Wiring must be done by a qualified electrician in compliance with local codes. Model 10F, 10FR, 15F and 15FR are using two separate power supply. Indoor unit powered by 115V/1Ph/60Hz. Outdoor unit powered by 208­230V/1Ph/60Hz.
Page 12 IM-5WMF(SEER13)-0706
Indoor Unit Outdoor Unit Terminal Block Connecting Wires Terminal Block
COMP
N2
N1
L
NEC requires an approved electrical disconnect within sight of the unit so that anyone working on the unit can turn the power off and see that its not accidentally turned back on. This will require two disconnects, one by the outdoor unit and one by the indoor unit.
COMP
L1 L2
L1 L2
!
Power supply
208/230V
L2
L1
4WV
OF
Comp
N2 N1
L
!
Power supply
208/230V
L2
L1
Outdoor coil sensor, 2 conductor cable, (26 feet long) shipped with the indoor unit. Extend with 22 ga. low voltage wire if not long enough to reach outdoor unit.
Indoor Unit Terminal Block
Outdoor Unit Terminal Block
Connecting Wires
NEC requires an approved electrical disconnect within sight of the unit so that anyone working on the unit can turn the power off and see that its not accidentally turned back on. This will require two disconnects, one by the outdoor unit and one by the indoor unit
A
4WV
OF
COMP
L1 L2
L1 L2
Figure 17. Heat Pump Unit Size 20 & 25 Figure 16. Cooling Only Size 20 & 25
Wiring Diagrams
INDOOR UNIT MODEL: M5WM 10F – 15F
OUTDOOR UNIT MODEL: M5LC 10C – 15C
Page 13
IM-5WMF(SEER13)-0607
115V
208/230V
INDOOR UNIT
MODEL :M5WM 20F
OUTDOOR UNIT MODEL: M5LC 20C – 25C
IM-5WMF(SEER13)-0706
Page 14
OUTDOOR UNIT MODEL: M5LC 20C
INDOOR UNIT
MODEL: M5WM 25F
Page 15
IM-5WMF(SEER13)-0706
OUTDOOR UNIT: MODEL: M5LC 25C
INDOOR UNIT
MODEL: M5WM 10FR – 15FR
OUTDOOR UNIT MODEL:
M5LC 10CR – 15CR
IM-5WMF(SEER13)-0706
Page 16
INDOOR UNIT MODEL: M5WM 20FR
IM-5WMF(SEER13)-0706 Page 17
OUTDOOR UNIT MODEL: M5LC 20CR
INDOOR UNIT MODEL: M5WM 25FR
IM-5WMF(SEER13)-0706
Page 18
OUTDOOR UNIT: MODEL: M5LC 25CR
Vacuuming and Charging
Purging the Piping and the Indoor Unit
Except for the outdoor unit which is pre-charged with refrigerant, the indoor unit and the refr igerant connection pipes must be air-purged because the air containing moisture that remains in the refrigerant cycle may cause malfunction of the compressor.
Remove the caps from the valve and the service port.
Connect the center of the charging gauge to the
vacuum pump.
Connect the charging gauge to the service port of the 3-way valve. (See Figure 18.)
Start the vacuum pump. Evacuate for approximately 30 minutes. The evacuation time varies with different vacuum pump capacity. Confirm that the charging gauge needle has moved towards -760mmHg
(-29.9”Hg).
Caution:
If the gauge needle does n ot move to -760mmHg, be sure to check for gas leaks (using the refrigerant detector) at flare type connection of the indoor and outdoor unit and repair the leak before proceeding to the next step.
Close the valve of the charging gauge and stop the vacuum pump.
On the outdoor unit, open the suction valve (3 way) and liquid valve (2 way) (in anti-clockwise direction) with 4mm key for hexagon sacked screw.
Figure18. 3-way Suction Valve on Outdoor Unit
Additional Charge
The refrigerant is pre-charged in the outdoor unit. If the tubing length between the indoor and outdoor unit is no more than 25ft. than an additional charge after evacuation is not necessary. If the tubing length is more than 25ft., use additional R410A as indicated in Table 5.
Table 5. Additional R410A ounces (when tubing length is
more than 25 feet
Model 26’ -33’ 34’ – 40’ 41’ – 50’
10F 1.2 2.0 ­15F 1.2 2.0 ­20F 1.2 2.0 3.5
25F 2.8 5.3 9.4 10FR 1.6 2.8 ­15FR 1.6 2.8 ­20FR 2.0 3.5 5.8 25FR 4.0 7.0 11.8
Charge Operation
This operation must be done by using a gas cylinder and a precise weighing machine. The additional charge is topped-up into the outdoor unit using the suction valve via the service port. See Figure 20.
Remove the service port cap.
Connect the low pressure side of the charging gauge
to the suction service port center of the cylinder tank and close the high pressure side of the gauge. Purge the air from the service hose.
Start the air conditioner unit.
Open the gas cylinder and low pressure charging
valve.
Whe n the required re frigerant quantity is pumpe d into the unit, close the low pressure side and the gas cylinder valve.
Disconnect the service hose form service port.
Put
back the service port cap.
Figure 19. Vacuuming Schematic
Figure 20. Charging Schematic
Page 19
IM-5WMF(SEER13)-0706
Special Precautions When Dealing With R410A Unit
R410A is a new HFC refrigerant which does not damage the ozone layer. The working pressure of this new refrigerant is 1.6 times higher than conventional refrigerant (R22), thus proper installation/servicing is essential.
Never use refrigerant other than R410A in an air­conditioner which designed to operat e with R410A.
POE oil is used as lubricant for R410A compressor, which is different from the mineral oil used for R22 compressor. During installation or servicing, extra precaution must be taken not to expose the R410A system too long to moist air. Residual POE oil in the piping and components can absorb moisture from the air.
To prevent mischarging, the diameter of the service port on the flare valve is different from that of R22.
Use tools and materials exclusively for refrigerant R410A. Tools exclusively for R410A are manifold valve, charging hose, pressure gauge, gas leak detector, flare tools, torque wrench, vacuum pump and refrigerant cylinder.
As an R410A air conditioner incurs higher pressure than R22 units, it is essential to choose the copper pipes correctly. Never use copper pipes thinner than
0.8mm even though they are available in the market.
If the refrigerant gas leakage occurs during installation/servicing, be sure to ventilate fully. If the refrigerant gas comes into contact with fire, a poisonous gas may occur.
When installing or removing an air conditioner, do not allow air or moisture to remain in the refrigerant cycle.
Unit Indicator Lights
IR Signal Receiver
When an infrared remote control operating signal is transmitted, the signal receiver on the indoor unit beeps to confirm acceptance of the signal transmission.
Figure 21. Indicator Lights Location – Indoor Unit
Cooling Only Unit
Table 6 shows the LED indicator lights for the cooling only unit under normal operation and fault conditions. The LED indicator lights are located at the bottom right side of the indoor unit. (See Figure 21 and Figure 22).
Figure 22. LED Indicator Lights for Cooling Only Unit
Table 6. LED Indicator Lights: Normal Operation and Fault
Conditions for Cooling Only Unit
Power
Sleep
Timer
Dry
Mode
or
Fault
Action
Timer -
Sleep -
Dry -
Once every 2 sec.
Room air
sensor contact loose/short
Repair or replace
Twice every 2 sec.
Indoor coil
sensor contact loose/short
Repair or replace
3 times every 2 sec.
Sensor coil
problem, compressor overload protection trip or gas leak.
Check circuit breaker, check for gas leak
CAUTION
R410A must be charged as liquid. Usually R410A
cylinder is equipped with a dip-pipe for liquid withdrawal. If there is no dip-pipe, the cylinder should be inverted so as to withdraw liquid R410A from the valve.
Do not top-up when servicing leak, as this will
reduce the unit performance. Vacuum the unit thoroughly and then charge the unit with fresh R410A according to the amount rec ommended in the specification.
Do not touch the compressor or refrigerant piping
when the chiller is running. If necessary wear protective gloves.
ON / ON or OFF Blinking
Page 20
IM-5WMF(SEER13)-0706
Heat Pump Unit
Table 7 shows the LED indicator lights for the heat pump unit under normal operation and fault conditions. The LED indicator lights are located at the bottom right side of the indoor unit.
The heat pump units are equipped to maintain selected room temperature by switching automatically to either “cool” or “heat” mode.
Figure 23. LED Indicator Lights: Normal Operation and
Fault Conditions for Heat Pump Unit
Table 7. LED Indicator Lights: Normal Operation and Fault Conditions for Heat Pump Unit
Cool
Dry
Fan
Heat
Sleep
Mode or Fault Action
/
Cooling -
Dry -
Fan -
/
Heat -
/
Auto mode in heating operation. *
-
/
Auto mode in cooling operation. *
-
Compressor cycling on
overload
Low outdoor air flow, defective compressor or overload.
Indoor coil sensor loose or defective
Attach or replace.
Outdoor coil sensor
loose or defective
Attach or replace.
Room air sensor loose
or defective
Attach or replace.
Unit Malfunctions If in AUTO or SLEEP mode, switch to
Heat, turn SLEEP off, unplug power cord and plug back in. If both lights blink with unit in Heat or Cool and SLEEP off, the problem may be coil sensor, compressor has tripped or low refrigerant.
ON / ON or OFF Blinking
* Unit has 10 minutes delay before it will switch between modes.
IM-5WMF(SEER13)-0706
Page 21
Special Features
Dry Mode
Select this mode when the standard Cool mode does not provide sufficient dehumidification. The compressor and indoor low fan will cycle together and will operate for longer periods of time to provide the increa sed rate of dehumidification. As a result, the room temperature differential may increase slightly.
Heat Mode (Heat Pump Only)
When the unit is switched on from cold start or defrosting cycle, the indoor fan will start to operate only after the indoor coil becomes warmer.
When the set temperature is achieved, the indoor fan will stop as the indoor coil starts to cool.
Air Flow Control
For more effective air circulation, you can manually adjust the air discharge grille to the left or right.
During cool and dry mode operation, do not direct the air discharge louver downwards as it may cause condensate to drip. (See figure 24).
Hot Keep (For Heat Pump Only)
With the Hot Keep switch OFF, the indoor fan will stop when coil temperature drops to 86ºF. With the switch ON, the fan will not stop unless coil temperature drops below 65ºF. With the switch in INTERNAL, and the unit is not heating, the fan is on for 30 seconds and off for 2 min. (See Figure 24).
In cool mode, fan runs continuous at selected speed.
The switch is located on front of the indoor unit, above
the ON/OFF switch (See Figure 24).
Figure 24
Overheating Protection (Heat Pump Only)
If the indoor coil temperature exceeds 145ºF because of high ambient conditions, dirty air filter, etc., the compressor will turn off.
Frost Prevention
If the indoor coil starts to frost in cooling mode, the compressor will stop.
If the outdoor coil becomes frosted, heating will stop for a few minutes while the unit goes into defrost.
Fan Speed and Rated Cooling Capacity
The rated cooling capacity is provided at the maximum fan speed.
The cooling capacity is slightly lower when the unit is operating at MEDIUM and LOW fan speed.
Main Filters – Permanent and Washable
Air filters must be cleaned at regular intervals. Twice annually may be adequate in some areas, while twice monthly may be required in others. Areas with high dirt and lint content or heavy usage of units require more frequent filter maintenance than those areas of relative ly clean operating or low usage conditions. Unit malfunction will occur if air filters are not kept clean. Vacuum the filters from the dirty side or wash with hot water and a mild detergent. Allow the filters to dry thoroughly before replacing them. See Figure 25.
Electrostatic Air Purifying Filter
Pre-charged electrostatic polypropylene filter removes microscopic dust, smoke and small invisible particles to keep the room air clean.
Deodorizing Filter
Activated carbon filter removes unwanted smells and odors in the air and keeps the room air fresh.
Page 22
IM-5WMF(SEER13)-0706
Figure 25. Installing Filters
Filter Replacement
Replace the electrostatic air purifying and deodorizing filters every 6 months or sooner if th ey turn brown.
Replacement filters can be purchased from your sales representative or distributor.
Use the new filter immediately once it has been removed from the package.
Auto Random Re-start Function
If there is a power loss to the building, the units will randomly restart when the power is restored. Control will restart at the last setting regardless of how long the power was off.
Low Ambient Kit
With this option, the unit can cool down to 32ºF outdoor temperature. (Standard units only cool down to 66ºF). To install, wire the Fan Speed Control Module (FSCM) in the outdoor unit per wiring diagram supplied with the kit. Attach the Outdoor Coil Sensor to the return bend as shown in Figure 26. Wrap sensor and return bend with insulating tape to promote accurate sensing of the refrigerant temperature. Refer also to the instructions supplied with the kit.
Figure 26 Low Ambient Location
Minimum and Maximu m Operating Temperature
Cooling
Temperature Ts ºF Th ºF
Minimum Indoor 67 57 Maximum Indoor 80 67 Minimum Outdoor *66 57 Maximum Outdoor 115 75
Heating (Heat Pump Only)
Temperature Ts ºF Th ºF
Minimum Indoor 50 ­Maximum Indoor 80 ­Minimum Outdoor 16 16 Maximum Outdoor 75 65
Ts = Dry Bulb Temperature, Th = Wet Bulb Temperature
* 32ºF with optional Low Ambient Kit
WARNING
!
Disconnect the main power supply before opening the return air grille. DO NOT restore power until the grille is closed.
IM-5WMF(SEER13)-0706
Page 23
Remote Controller Operation Guide
1) Transmission Source
The source where the sign al is transm itted.
2) Signal Transmission Indication
Blinks to confirm the last setting has been transmitted to the unit.
3) “ON/OFF” Button
Press once to start the unit.
Press again to stop the unit.
4) Temperature Setting
To set the desired room temperature, press the + or – button to increase or decrease the set temperature.
The temperature setting range is from 60ºF to 86ºF (Optional setting 68ºF to 86ºF).
Press both bu ttons simultaneously to toggle + and – from ºC to ºF setting.
5) Operation Mode
Press the MODE button to select the type of operating mode.
For cooling only unit, the available modes are: COOL, DRY and FAN.
For heat pump unit, the available modes are: AUTO, COOL, DRY, FAN and HEAT.
6) Fan Speed Selection
Press the
button continuously to toggle the fan speed in the following order: Low Med High Auto
Stop pressing when the desired fan speed appears on the display screen.
7) Turbo Function
Press
for fast cooling or heating operation.
The temperature will be increased internally if it is in HEAT mode, decreased if in COOL and DRY mode.
Fan speed will be increased if it is not at maximum speed.
The temperature and fan speed will resume to user setting if
is pressed again or after 20 minutes.
Available under HEAT, COOL and DRY modes only .
8) ON Timer Setting
Press the SET button will activate the on timer function.
Set the desired on time by pressing the SET button continuously. If the timer is set to 7.30am, the air
conditioner will turn on at 7.30am sharp.
Press the CLR button to cancel the on timer setting.
9) OFF Timer Setting
Press the SET button w ill activate the off timer function.
Set the desired of time by pressing the SET button continuously.
Press the CLR button to cancel the off timer setting.
10) Automatic Air Swing (optional)
Press the SWING button to activate the auto matic air swing function.
To distribute the air to a specific direction, press the SWING button and wait until the louver move to the
desired direction and press the button once again.
Page 24
IM-5WMF(SEER13)-0706
11) Sleep Mode Setting
Press the SLEEP button will activate the sleep mode function.
This is an energy saving option. When the unit is operating under cooling mode, the set temperature is increased
by 0.5ºC after the first half an hour, another 0.5ºC after the second half an hour and 1ºC after the following 1 hour. This function will prevent excessive cooling during summer season.
When the unit is operating under heating mode, the set temperature is decreased by 1ºC after the first half an hour, another 1ºC after the second half an hour and 1ºC after the following 1 hour. This function will prevent night sweat during summer season.
This function is available under COOL, HEAT and AUTO mode.
Figure 27 Sleep Mode Setting
12) Clock Time Setting
Press + button to increase the clock time.
Press – button to decrease the clock time.
13) Personalize Setting
Press and hold for 3 seconds, then will blink. Press again to cycle between and .
P1 P1 P2
Set the desired setting, then leave the handset for 4 seconds without pressing any key and it will save the setting into the program.
Press once to activate the P1 setting, press again to cycle between P1 and P2.
Press any key to deactivate the personalize setting.
14) Ionizer Setting (optional)
Press will activate the ionizer function.
Press again to deactivate the function.
Symbol Identification
IM-5WMF(SEER13)-0706
Page 25
Service and Maintenance
Maintenance Schedule
Item Maintenance Procedures Frequency Indoor Air Filters
Lift the return air grille and remove the filters (See Figure 23). Clean the filters by using a vacuum cleaner or wash in lukewarm water and soap. Rinse and dry before reinstalling.
As required to prevent restriction of air flow.
Indoor Cabinet
Remove any dust on the grille or panel by wiping it with a soft cloth soaked in lukewarm water (below 40ºC / 104ºF) and a mild detergent.
As required to maintain appearance.
Outdoor Unit
Clean the louvers and coil. Be careful not to bend or flatten the aluminium fins. DO NOT use cleaning fluids that might corrode the coil.
As required to prevent restriction of air flow.
Troubleshooting
If any malfunction of the unit is noted, immediately switch off the power supply.
Check the following chart for possible causes/treatments. If the trouble persists, please call your local
dealer/serviceman.
Trouble Possible Cause/Treatment
The compressor does not operate.
Protection against frequent starting. Wait for 3 to 4 minutes for the compressor to start
operating. Fans and compressor do not operate.
Power failure.
Check fuse or circuit breaker.
Power supply disconnect off.
Delay timer may be set
incorrectly. Adjust timer setting
by using remote controller. Air flow too low or insufficient cooling/heating capacity.
Dirty air filters.
Open doors or window.
Adjust thermostat setting. Discharge air flow has bad odor.
Smoke, perfume, etc. may
have collected on the indoor
coil.
Clean coil. Condensation on the return air grille of the indoor unit.
Use dry mode. High humidity in
conditioned space.
Set temperature too low.
Increase temperature setting
and operate unit at high fan
speed. Condensate leaking into room.
Condensate drain plugged. Hissing sound from
the unit during operation.
Refrigerant fluid flowing into the
evaporator coil. Operate for a
while to see if sound goes
away.
CAUTION
Disconnect the electrical power supply before performing any service, maintenance or troubleshooting.
Page 26
IM-5WMF(SEER13)-0706
This document contains the most current product information as of this printing. The manufacturer reserves the right to revise any of the specification and design contain herein at any time without prior notification.
Loading...