The information in this manual supersedes and replaces previous catalogues with regards to McQuay Water Source Heat Pump products.
Illustrations cover the general appearance of McQuay International products at the time of publication and McQuay International reserves the
right to make changes in design and construction at anytime without notice.
™®The following are trademarks or registered trademarks of their respective companies: LonTalk from Echelon Corporation, BACnet from ASHRAE, Protocol
Selectability, and MicroTech II from McQuay International.
Catalog 1109-1 McQuay Large Vertical Water Source Heat Pumps Page 3 of 56
Large Vertical Water Source Heat
Pumps - Models LVC & LVW
Sizes 072 - 290 (6 to 25 Tons)
Model LVC (Standard Range: 55°F to 110°F)
Model LVW (Geothermal Range: 30°F to 110°F)
Large Vertical Water Source Heat Pump units are easily
located in equipment rooms or oor-by-oor installations.
They can be applied to all building types where it is
advantageous to extend the water source heat pump concept
to larger or core areas.
Each heat pump is factory assembled and run tested for
reliability. Service is accomplished through multiple front,
back and side access panels. Access is available to all serviceable components. Each unit ships on a wooden skid and
covered with plastic to facilitate moving with a fork truck.
Two unique frame sizes make up our 6- through 25-ton
product line - each with a consistent shape for easy layout
of the ductwork, water piping, condensate piping and electrical connections.
Units are constructed of heavy gauge G-60 galvanized
steel. The interiors of all framework and panels are covered
with 1/2" thick, 1½ lb. dual-density berglass insulation.
Electrical components are located in the lower section,
adjacent to the compressor(s). Knockouts are provided
on both sides of the unit to facilitate main power and low
voltage wiring through separate holes. Each unit is rated
to accept time delay fuses for branch circuit overcurrent
protection. Each unit is listed with CETL.
The control box is accessible through the compressor
section access panel. The control box houses the major
operating electrical controls, including the control circuit board(s), transformer, compressor contactor(s), fan
contactor(s) and terminal block. Each component is accessible for service or replacement.
The standard control for all large capacity units is the
MicroTech™ III controller. The unit controller receives its
power from the 75VA control transformer. A LonWorks®
or BACnet® communication module is available as a
selectable option.
Standard 1" lters are supported by factory-mounted brackets for side removal in either direction.
Nomenclature
W LVC 1 215 B L Y S Y Y F
Product Category
W = WSHP
Product Identier
LVC = Large Vertical - Standard Range
LVW = Large Vertical - Geothermal
Design Series
1 = A Design 4 = D Design
2 = B Design 5 = E Design
3 = C Design
Filter - Standard 1" factory-installed lter rack with 1" throw-
away lter. Optional 2" lter rack with duct collar for eld
-installation.
4
Refrigerant Circuit - All units have a dual refrigerant circuit
with scroll compressors, thermal expansion valve, coaxial heat
exchanger, nned tube airside coil and reversing valve.
5
Compressor Vibration Isolators - Standard feature for all units,
reduces vibration sound levels during compressor operation.
6
Schrader Connections - Four Schrader valves are located inside
the end access panel – one on the low side and one on the high
side of the refrigeration circuit – for charging and servicing.
All valves are 7/16" SAE ttings.
onWorks®
I/O Expansion
Module
7
MicroTech® III Controllers – Designed for exibility, the control
L
Communication
Module
BACnet®
Communication
Module
board is used in standalone applications in conjunction with
the I/O expansion module for control of the second refrigerant
circuit. A separate L
onWorks® or BACnet® communication
module can be easily snapped onto the board to allow communication with a building automation system. The control
system accomodates the use of a two-stage heat/two-stage
cool 7-day programmable or non-programmable wall-mounted
thermostat, offered as a eld-installed option.
Electrical
- The control enclosure includes fan relay, compres-
sor relays, 24-volt control transformer, reversing valve solenoid coil, lockout circuits and control circuit board.
8
LED Annunciator – External LED status lights display fault
conditions to provide easy troubleshooting and diagnosis, visible without removing access panel.
9
External Pipe Connections – Supply and return pipe connec-
tions located outside the cabinet make pipe connections easy
without removing access panels.
Safety
Controls (Not Shown) - Low and high refrigerant pressure
switches and low refrigerant suction temperature
(freezestat) sensor.
Catalog 1109-1 McQuay Large Vertical Water Source Heat Pumps Page 5 of 56
LVC & LVW Features & Options
Large vertical water source heat pump units are easily
located in small equipment rooms or oor-by-oor installations. They can be applied to all building types where it is
advantageous to extend the water source heat pump concept
to larger or core areas.
Each heat pump is factory assembled and run tested for
reliability. Service is accomplished through multiple front,
back and side access panels. Access is available to all serviceable components. Each unit ships on a wooden skid and
covered with plastic to facilitate moving with a fork truck.
Two unique frame sizes make up our 6- through 25-ton
product line - each with a consistent shape for easy layout
of the ductwork, water piping, condensate piping and electrical connections.
Units are constructed of G-60 galvanized steel. The
interiors of all framework and panels are covered with 1/2"
thick, 1½ lb. dual-density berglass insulation. Closed-cell
foam (IAQ) insulation is available as a selectable option, suitable for berglass-free applications. Multiple 1" lters are
supported by factory-mounted brackets for side removal in
either direction.
Electrical components are located in the lower section,
adjacent to the compressor(s). Knockouts are provided on
both sides of the unit to facilitate main power and low voltage
wiring through separate holes. Each unit is rated to accept time
delay fuses for branch circuit overcurrent protection. Each unit
is listed with CETL and CE.
The control box is accessible through the compressor section access panel. The control box houses the major operating electrical controls, including the control circuit board(s),
transformer, compressor contactor(s), fan contactor(s) and
terminal block. Each component is accessible for service or
replacement.
Figure 1: Front View with Access Panel Removed
The reversing valve is energized in the heating mode
and will “fail-safe” to the cooling mode, which is the predominant mode of operation.
Both heat exchanger components incorporate advanced-
heat transfer technologies. The coaxial heat exhanger has a
copper inner tube and steel outer tube. The large face area
coil has copper tubes and aluminum ns. Geothermal units
include coil and piping insulation to protect against conden-
sation in low temperature applications.
Safety controls on each refrigerant circuit include a suc-
tion line temperature sensor, low refrigerant pressure and
high pressure switches to lock out compressor operation at
extreme conditions. The safety controls can only be reset
from the main disconnect switch to prevent unauthorized
reset. Each circuit has high and low side refrigerant service
valves for refrigerant circuit diagnostics and charging.
Thermal Expansion Valve
Units include a Thermal Expansion Valve (TXV) for
refrigerant metering. The TXV allows the unit to operate at
optimum efciency with uid temperatures ranging from
25°F to 110°F, and entering air temperatures ranging from
40°F to 90°F. The TXV precisely meters the exact amount
of refrigerant ow through the system to meet the load and
deliver rated heating and cooling capacity.
Fan Section
The fan section includes a belt-driven fan assembly,
multiple DWDI forward curved fan wheels, solid fan shaft,
steel ball bearings, three phase fan motor, adjustable motor
sheave, adjustable motor base, fan pulley and insulated
divider panel between the compressor section. Unit sizes
072 through 120 have two fan assemblies and unit sizes
180 through 290 have three fan assemblies. The fan motor
is always located at the piping end, but may be relocated to
the opposite side in the eld.
Figure 2: Belt-Driven Fan Assembly Compartment
Refrigeration System
All Large Vertical unit sizes have dual independent circuits. Each circuit includes a scroll compressor, reversing
valve, water to- refrigerant coaxial heat exchanger, electronic expansion valve, airside coil, sightglass and safety
controls.
The compressor is located adjacent to the compressor
access panel and isolated from a bottom panel with rubber
isolators.
Page 6 of 56 McQuay Large Vertical Water Source Heat Pumps Catalog 1109-1
Factory Installed Options
Optional high static fan motors are available on each
unit size to handle increased CFM and static pressure
applications.
Control Features – Control Choices And Added Functionality
The control enclosure houses the major operating electri-
cal controls including the MicroTech® III controller and I/O
expansion module, control transformer, compressor relays
and fan relay. Each component is easily accessed for service
or replacement.
Three unique control choices are offered with the Micro-
Tech III control system:
■ Standalone operation using a MicroTech III controller and
I/O expansion module
■ MicroTech III controller and I/O expansion module with a
LonWorks® communication module
■ MicroTech III controller and I/O expansion module with a
BACnet® communication module
Each option features direct quick-connect wiring to all
unit-controlled components for “clean” wiring inside the
control box. Each control circuit board receives power from
a 75VA transformer.
Table 1: Control Options
Control Description Application Protocol
MicroTech III
(Standalone)
The MicroTech III controller is a standalone microprocessor-based control
board conveniently located in the unit
control enclosure for easy accessibility.
The board is designed to provide ther-
mostat
control of a Water Source Heat
Pump using a two-stage wall thermostat. The unit controller provides unitwide control of the WSHP and control
of the rst refrigerant circuit.
Each unit controller is factory programmed, wired,
and tested for complete control of single zone, standalone operation of your McQuay Water Source Heat
Pump.
Unit Controller
with
I/O Expansion
Module
The I/O Expansion Module is an exten-
s
ion of the Microtech III controller and
provides control of the second refrigerant circuit. External
display fault conditions to provide easy
troubleshooting and diagnosis of the
second circuit.
LED status lights
Allows for:
•
Control of second refrigeration circuit.
U n i t- m o un te d
or wall-mounted
thermostat
Wa l l- mo un t e d
t
her mos tat or
sensor
LonWorks
Communication
Module
BACnet
Communication
Module
T
he MicroTech III control system
accepts a plug-in L
nication module to provide network
c
ommunications and added functional-
ity to easily integrate with an existing
BAS. The communication module can
be factory- or field-installed and is
tested with all logic required to monitor
and control the unit.
The
MicroTech III controller accepts
a plug-in BACnet communication
module to provide network commu-
ications and added functionality to
n
easily integrate with an existing BAS.
The communication module can be
factory- or eld-installed and is tested
with all logic required to monitor and
control the unit.
onWorks commu-
Designed to be linked with a centralized building
automation system (BAS) through a LonWorks com-
munications network for centralized scheduling and
management of multiple heat pumps.
Designed to be linked with a centralized building
automation system (BAS) through a BACnet communications network for centralized scheduling and
management of multiple heat pumps.
Lo nMa rk 3 .4
certied
BACnet
MS/TP
Catalog 1109-1 McQuay Large Vertical Water Source Heat Pumps Page 7 of 56
Control Features – MicroTech® III Controller
The MicroTech III Controller is a microprocessor-based
control board conveniently located in the unit control box for
easy access through a removable access panel. The standalone
unit controller is a hard wired interface and provides all the
necessary eld connections. The board can be wired for 24volt AC output to the wall thermostat by using terminals R
& C. An LED annunciator is located on the front of the unit
chassis to allow quick check of the unit operating status.
MicroTech III Operating Features
Assumes cycle fan operation-not continuous fan operation:
■ Start-up – The unit will not operate until all the inputs
and safety controls are checked for normal conditions.
■ Cooling mode – On a call for cooling from the wall ther-
mostat, the controller will energize the fan relay and stage
compressors to satisfy the space temperature setpoint.
When the load is satised, the controller will disable the
compressor and fan.
■ Heating Mode – On a call for heating from the wall
thermostat, the controller will enable the fan, energize
circuit one reversing valve and circuit 1 compressor to
satisfy the space heating setpoint. If the space temperature
setpoint is not satiseld, circuit two reversing valve and
circuit 2 compressor will be energized and run until the
heating setpoint at the thermostat is satised.
■ Random Start Power-up Delay Timer – In the event of
a building power outage, this feature prevents multiple
units from starting simultaneously upon building power
restoration.
■ Unoccupied Mode – A simple “grounded” signal between
terminals U and C (no power source required), puts the
unit into the unoccupied mode for night setback operation.
■ Interstaging Timer – A default value of 5 minutes be-
tween staging of compressors, this feature minimizes short
cycling of compressors and improves comfort.
■ Override Mode – A switch on the deluxe automatic
changeover thermostat can be activated during the unoccupied mode to put the unit back into the occupied mode
for two hours for after-hours heating or cooling.
■ Motorized Valve/Pump Restart – The IV/PR (H8) ter-
minals on the The MicroTech III unit controller are used
to energize (open) a motorized valve or start a water pump
to get water circulating prior to starting the compressor on
call for heating or cooling. The IV/PR (H8) terminal may
be “daisy chained” between a maximum of 200 units.
■ Brownout Protection – The MicroTech III unit controller
measures the input voltage and will suspend compressor and fan operation if the voltage falls below 80% of
the unit nameplate rated value. A unique LED status is
generated.
■ Unit Shutdown – A simple grounded signal puts the unit
into the shutdown mode. Compressor and fan operations
are suspended. A unique LED status is generated.
■ Condensate Overow Protection – The
MicroTech III
controller incorporates a liquid sensor at the top of the
drain pan. Upon sensing water ow, cooling operation is
suspended. A unique LED status is generated.
■ Remote Reset of Automatic Lockouts – The Remote
Reset feature provides the means to remotely reset auto-
matic lockouts generated by high-pressure and/or lowtemperature faults. When the MicroTech III controller is
in automatic lockout due to one of these faults, and the
cause of the fault condition has been alleviated, energizing the O-terminal for 10 seconds or more will force the
control board to clear the lockout. A unit power cycle can
also be used to clear an automatic lockout if the conditions
causing the fault have been alleviated.
■ Intelligent Reset – The Fault Retry feature helps to
minimize nuisance trips of automatic lockouts caused by
high-pressure and/or low-temperature faults. This feature
clears faults the rst two times they occur within a 24-hour
period and triggers an automatic lockout on the 3rd fault.
The retry count is reset to zero every 24 hours.
■ Equipment Protection Control – The MicroTech III
controller receives separate input signals from the refrig-
erant high-pressure switch and the low suction line temperature sensor. In a high-pressure situation, compressor
operation is suspended. In a low temperature situation,
the unit goes into a defrost cycle where the unit is put
into cooling operation for 60 seconds until the coaxial
heat exchanger is free of ice. Each switch generates its
own unique LED status.
Note: Most unit fault conditions are the result of operating
the equipment outside the unit specications.
Table 2: MicroTech III Controller LED & Fault Outputs
Mode / Fault
Occupied, Bypass,
Standby
Override
Unoccupied On On Off Energized
Condensate Overow On Off Off De-energized
High Pressure 1 Fault
Low Pressure 1 Fault Off Off On De-energized
Low Temperature 1 Fault Flash Off Off De-energized
Brownout
Emergency Shutdown
Room/Return
Temp Sensor 1 Failure
Service Test Mode
Enabled
Serial EEPROM
Corrupted
Network “Ofine”
Received
1
Compressor relay/compressor terminal is labeled COMP, switched line of
the same electric input as any of the L1 terminals.
Status LED’s
, or Tenant Off On Off Energized
Air or Low
1
Y
ellow Green Red Output-Terminal “A”
Off Off Flash De-energized
Off Flash Off De-energized
Off Flash Off De-energized
Flash Flash On De-energized
Flash Flash Flash De-energized
On On On De-energized
Off Off Off De-energized
Thermostat
Alarm Light
Page 8 of 56 McQuay Large Vertical Water Source Heat Pumps Catalog 1109-1
Control Features – I/O Expansion Module
I/O Expansion Module
The I/O Expansion Module is factory-installed for control
of the second refrigeration circuit.
The I/O Expansion Module has an independent LED an-
nunciator to identify operational fault conditions for the
electric heater.
Table 3: I/O Expansion Module LED & Fault
Outputs
Invalid Conguration
Jumper Setting
Base Board
Communication Fail
High Pressure #2 Fault Off Off Flash De-energized
Low Pressure #2 Fault Off Off On De-energized
Low Suction Temp #2 Fault Flash Off Off De-energized
Sensor Failures Low Suction
Low Suction
1
EWT (w/ Boilerless EH only)
2
Service Test Mode Enabled Flash Flash Flash De-energized
Unoccupied Mode On On Off Energized
Occupied, Bypass,
Standby, or Tenant
Override Modes
Normal Operation
Note: Mode / Faults are listed in order of priority.
1
Boilerless electric heat only
2
Alarm/fault LED indications take precedence over service test mode LED
indication. The controller shall use service test mode if the service test
mode jumper is installed, even if the LED’s indicate an alarm/fault.
/ Fault
Mode
Yellow Green Red
Temp #2, Flash Flash On De-energized
Off On Off De-energized
Status LED's
Terminal “A”
Flash Flash Off De-energized
Off Flash Flash N/A
Off On Off Energized
Thermostat Alarm
Light Output
Figure 3: I/O Expansion Module Conguration
Jumper Terminals
Jumper Terminals
JP1 shorted in units with
2 compressors
JP1 through JP8 not
used with 2 circuit units.
Catalog 1109-1 McQuay Large Vertical Water Source Heat Pumps Page 9 of 56
Control Features – MicroTech III with Communication Module
MicroTech® III Controller with LonWorks® or
®
BACnet
Each Ennity Large Vertical and Horizontal Water
Source Heat Pump can be equipped with a LonWorks or
BACnet communication module. The LonWorks module is
LonMark 3.4 certied and designed to communicate over a
LonWorks communications network to a Building Automation System (BAS). The BACnet module is designed to
communicate over a BACnet MS/TP communications network to a building automation system. Both controllers are
microprocessor-based and can be factory or eld-installed.
The control modules are programmed and tested with all
the logic required to monitor and control the unit. Optional
wall sensors may be used with the communication modules
to provide limited local control of the Horizontal Water
Source Heat Pump. The MicroTech III controller monitors
water and air temperatures and passes information to the
communication module. The module communicates with
the BAS, to provide network control of the Water Source
Heat Pump.
MicroTech III LonWorks Communication Module
The LonWorks communication module is designed for
units that are integrated into a LonWorks communication
network for centralized scheduling and management of
multiple heat pumps.
Communication Module
MicroTech III Controller with Communication
Modules Features
The MicroTech III Controller with LonWorks or BACnet
Communication Module orchestrates the following unit
operations:
Enable heating and cooling to maintain space
temperature setpoint based on a room sensor setting
Enable fan and compressor operation
Monitors all equipment protection controls
Monitors room and discharge air temperatures
Monitors leaving water temperature
Relays status of all vital unit functions
An amber, on-board status LED indicates the status of the
MicroTech III LonWorks or BACnet module.
The MicroTech III Controller Includes:
A unit-mounted return air sensor
A unit-mounted discharge air sensor
A leaving water temperature sensor
The communication modules provide network access to
setpoints for operational control
Available Wall Sensors Include:
Room sensor
MicroTech III BACnet Communication Module
Designed to be linked with a centralized building automation system (BAS) through a BACnet communications
network for centralized scheduling and management of
multiple heat pumps.
Room sensor with LED status and tenant override
button
Temperature sensor with LED status, timed-override
button, and ±3°F setpoint adjustment
Room sensor with LED status, timed-override
button, 55° to 90°F setpoint adjustment
Page 10 of 56 McQuay Large Vertical Water Source Heat Pumps Catalog 1109-1
Unit Location
Control Box
Location
Piping
Location
Fan Motor
24"
(610 mm)
Side B
Side A
24" (610 mm)
Large Vertical Water Source Heat Pump units are easily
located in equipment rooms or oor-by-oor installations.
They can be applied to all building types where it is
advantageous to extend the water source heat pump concept
to larger or core areas.
Locate the unit in an area that allows for easy removal
of the lter and access panels, and has enough space for
service personnel to perform maintenance or repair. Provide
sufcient room to make water, electrical and duct connections.
Figure 4: Service Clearances
Applications
The main control panel is located in the center front of
the unit. The fan discharge is top front, and the fan motor
is always located at the piping end. Unit sides opposite
the control panel and opposite the piping side may be up
against walls and still allow for service and maintenance
through the remaining access panels.
Figure 5: Fan Deck Arrangements
The contractor should make sure that access has been
provided including clearance for 2" (51 mm) thick lter
brackets, duct collars and ttings at water and electrical
connections. Allow adequate room around the unit for a
condensate trap. The unit can be installed “free standing”
in an equipment room. Generally, the unit is located in a
separate room with the non-ducted return air facing the
return air intake.
Alternatively, the unit can have a ducted return air. It is
recommended that the unit be located on vibration isolators
to reduce any vibration (see Figure 6, page 12).
IMPORTANT
1. A 24" (610 mm) minimum clearance is required on the
return air, control box and piping sides. However, a 36"
(914 mm) clearance allows for easier serviceability.
2. A 12" (305 mm) minimum clearance is required on Side
A to gain access to panel to remove locking collar for shaft
removal.
3. A 6" (152 mm) clearance is required on Side B to remove
screws holding top panel.
4. Top clearance is required for fan shaft removal.
5. Some codes dictate a 60" (1524 mm) clearance above
the control box which could be violated with a ducted
return. Check your local codes.
Rear (or Top)
Discharge
Right-Hand Piping
(Upblast-Rear)
Front (or Top)
Discharge
Right-Hand Piping
(Upblast-Front)
Fan
Motor
Front (or Top)
Discharge
Left-Hand Piping
(Upblast-Front)
Fan Deck Arrangements
Six fan discharge arrangements and two piping arrangements are available. With the return air side dened as the
Rear (or Top)
Discharge
Left-Hand Piping
(Upblast & Rear)
Straight Horizontal
Discharge
Left-Hand Piping
(Top-Horizontal Discharge)
Straight Horizontal
Discharge
Right-Hand Piping
(Top-Horizontal Discharge)
“front” of the unit, the water piping connections may be
right-hand (side) or left-hand. All units have a single supply
and return water connection with a copper FPT type tting
that protrudes through the unit casing for easy connection.
The condensate connection is also a copper FPT type and is
located on both sides of the unit. The unused connection is
plugged.
Catalog 1109-1 McQuay Large Vertical Water Source Heat Pumps Page 11 of 56
Notes:
1. The hand of unit is determined by looking at the return air
(lter) side. The piping and electrical connections are always
made on the “hand” side of the unit. The return air (lter) side is
considered the “front” of the unit.
2. The fan motor is always located at the piping/electrical
connection (hand) side of the unit.
3" (76 mm)
3"
(76 mm)
3" (76 mm)3" (76 mm)
Section A-A
2"
(51 mm)
AA
28
5
/32"
(715 mm)
(4)
7
/16" (11 mm) holes
7
/16"
(11 mm)
1
/4"
(6 mm)
54
23
/32"
(1390 mm)
2"
(51 mm)
2" (51 mm)
30
1
/8"
(765 mm)
3
1
/4" (83 mm)
3
1
/4" (83 mm)
(6)
3
/8" (19 mm) holes
80
3
/8"
(2042 mm)
40
3
/16"
(1021 mm)
4½" (114 mm)
5½" (140 mm)
2½" (64 mm)
2⅝" (61 mm)
7/16" (11 mm)
3/8" (10 mm) TAP
Applications
Vibration Isolators
Figure 6: Vibration Isolator Dimensions
For minimum sound and vibration transmission, it is recommended that the unit be mounted on vibration isolators.
Holes are provided in the bottom panel to facilitate con-
nection of isolators (see Figures 7-8 for hole locations).
Isolators supplied by the manufacturer are the type
shown in Figures 6. Four white isolators are used for single
compressor units and six green isolators are used for dual
compressor units. The holes in the bottom of the unit allow
for a 3⁄8" (10 mm) bolt to be secured to the isolator.
Figure 7: Vibration Isolators Locations - Single Compressor Unit
Figure 8: Vibration Isolators Locations - Dual Compressor Unit
Page 12 of 56 McQuay Large Vertical Water Source Heat Pumps Catalog 1109-1
Ductwork and Attenuation
Discharge ductwork is normally used with these conditioners. Return air ductwork may also be required but will
require eld installation of a return air duct collar.
All ductwork should conform to industry standards of
good practice as described in ASHRAE Systems Guide.
The discharge duct system will normally consist of a
exible connector, a transition piece to the nal duct size, a
short run of duct, an elbow without vanes and a trunk duct
tee’d into branch ducts with discharge diffusers. Transfor-
mation duct must not have angles totalling more than 30
degrees or severe loss of air performance can result.
All units have multiple fan outlets. The preferred
method for minimum static pressure loss would be indi-
vidual ducts at each outlet connected to a larger main duct
downstream (Figure 9).
Figure 9: Suggested Supply Ducting per ASHRAE and SMACNA Publications
For minimum noise transmission, the metal duct material should be internally lined with acoustic brous insulation. The ductwork should be laid out so that there is no
line of sight between the conditioner discharge and the
distribution diffusers.
Return air ducts can be brought in adjacent to the return
air of the conditioner. Typically, the equipment room becomes the common return air plenum.
Do not insert sheetmetal screws directly into the unit
cabinet for connection of supply or return air ductwork,
especially return air ductwork which can hit the drain pan
or the air coil.
Notes:
1. Transformations to supply duct have maximum slope of 1" to 7".
2. Square elbows with double thickness vanes may be substituted.
3. Do not install ducts so that the air ow is counter to fan rotation.
If necessary, turn fan deck assembly and motor.
4. Transformations and units shall be adequately supported so no
weight is on the exible connection.
Applications
Flexible
Connector
Fan Rotation
(See Note
Branch Duct
Note 2
Note 1
Note 1
3)
Note 1
Flexible
Connector
Fan Rotation
(See Note
Main Duct
3)
Transformation Duct
Flexible Connector
Note 2
Flexible Connector
Fan Rotation
(See Note 3)
Note 2
Note 2
Fan Rotation
(See Note
3)
Distribution
Diffuser
Trunk Duct
Catalog 1109-1 McQuay Large Vertical Water Source Heat Pumps Page 13 of 56
Applications
Typical Cooling and Heating Refrigeration Cycles – Dual Compressors
Note: Typical temperature readings are at full load conditions at ISO-13256 for boiler-tower applications.
Figure 10: Cooling Refrigeration Cycle
When the wall thermostat calls for COOLING, the reversing valve (de-energized) directs the ow of the refrigerant,
a hot gas, from the compressor to the water-to-refrigerant
heat exchanger (coaxial heat exchanger). There, the heat is
removed by the water, and the hot gas condenses to become
a liquid. The liquid then ows through a thermal expansion
valve to the air-to-refrigerant heat exchanger coil (evaporator). The liquid then evaporates and becomes a gas, at the
same time absorbing heat and cooling the air passing over the
surfaces of the coil. The refrigerant then ows as a low pressure gas through the reversing valve and back to the suction
side of the compressor to complete the cycle.
Figure 11: Heating Refrigeration Cycle
When the wall thermostat calls for HEATING, the
reversing valve (energized) directs the ow of the refrigerant, a hot gas, from the compressor to the air-to-refrigerant
heat exchanger coil (condenser). There, the heat is removed
by the air passing over the surfaces of the coil and the hot
gas condenses and becomes a liquid. The liquid then ows
through a thermal expansion valve to the water-to-refrigerant
heat exchanger (evaporator). The liquid then evaporates and
becomes a gas, at the same time absorbing heat and cooling
the water. The refrigerant then ows as a low pressure gas
through the reversing valve and back to the suction side of
the compressor to complete the cycle.
Page 14 of 56 McQuay Large Vertical Water Source Heat Pumps Catalog 1109-1
Applications – Systems
Water source heat pump systems are one of the most ef-
cient, environmentally friendly systems available for heating
and cooling buildings. High-efciency, self contained units
(sizes 7,000 btuh to 290,000 btuh) can be placed in virtually
any location within a building. Each unit responds only to
the heating or cooling load of the individual zone it serves.
This permits an excellent comfort level for occupants, better
control of energy use for building owners and lower seasonal
operating costs. The Air-Conditioning Refrigeration Institute
(ARI) and the International Standards Organization (ISO)
publish standards so that water source heat pumps are rated
for specic applications. The ARI/ISO loop options shown in
this catalog are typical water source heat pump loop choices
available in today’s market. These systems offer benets ranging from low cost installation to the highest energy efciency
available in the market today.
Boiler / Tower Applications: ARI 320 / ISO
13256-1
A “Boiler/Tower” application uses a simple two-pipe
water circulating system that adds heat, removes heat or
transfers rejected heat to other units throughout the building. The water temperature for heating is generally maintained between 65ºF – 70ºF and is usually provided by a
natural gas or electric boiler located in a mechanical room.
The condensing water temperature, during cooling months,
is maintained between 85ºF and 95ºF and requires the use
of a cooling tower to dissipate waste heat. Cooling towers can be located on the roof, or inside or adjacent to the
building. This application can be the lowest cost of the loop
options available.
Note: ASHRAE 90.1 standards require that circulating
pumps over 10 HP will require use of “variable frequency
drive” equipment and pipe insulation to be used whenever
water temperatures are below 60 degrees and above 105
degrees. See ASHRAE 90.1 Standards for details.
Open Loop Well Water Applications: ARI
325 / ISO 13256-1
“Open Loop” well water systems use ground water
to remove or add heat to the interior water loop. The
key benet of an open loop system is the constant water
temperature, usually 50ºF to 60ºF, which provides efcient
operation at a low rst cost. Most commercial designers
incorporate a heat exchanger to isolate the building loop
from the well water. Using heat exchangers can reduce
maintenance issues while still allowing the transfer of heat
from unit to unit as with the “Boiler/Tower System”. A successful design provides an ample amount of groundwater
(approximately 2 GPM per ton) and adequate provisions
for discharging water back to the aquifer or surface. Open
Loop applications are commonly used in coastal areas
where soil characteristics allow reinjection wells to return
the water back to the aquifer. Note that some states have requirements on the depths of return water reinjection wells,
and such wells must be approved by the United States Environmental Protection Agency. Also, bad water quality can
increase problems with heat exchanger scaling. Suspended
solids can erode the heat exchanger. Strainers can be used
to contain suspended solids.
Figure 13: Open Loop Well Application
Figure 12: Boiler/Tower Application
Catalog 1109-1 McQuay Large Vertical Water Source Heat Pumps Page 15 of 56
Applications – Systems
Closed Loop Geothermal Applications ARI
330/ISO 13256-1
“Vertical Closed Loop” applications are installed by
drilling vertical bore holes into the earth and inserting
a plastic polyethylene supply/return pipe into the holes.
The vertical wells are connected in parallel reverse return
fashion to allow the water from the building to circulate
evenly throughout the boreeld. The circulating uid dissipates heat to the ground in a similar manner as a “tower”
and adds heat back to the loop like a boiler. If properly
designed, the loop eld can maintain the loop temperatures
necessary to condition the building without the use of a
boiler or a tower. Loop temperatures usually range from
37ºF to 95ºF in Northern climates. Southern applications
can see temperatures ranging from 40ºF to 100ºF. The
number of bore holes and their depth should be determined
by using commercial software that is specically designed
for vertical geothermal applications. Typical bore depths
of a vertical loop range from 150 to 400 feet and generally
require about 250 feet of surface area per ton of cooling.
Figure 14: Vertical Loop Application
Figure 15: Horizontal Loop Application
A “Surface Water” or “Lake” closed loop system is a
geothermal loop that is directly installed in a lake or body
of water that is near the building. In many cases, the body
of water is constructed on the building site to meet drainage
or aesthetic requirements. Surface loops use bundled
polyethylene
as a vertical or horizontal loop using a parallel reverse
return design. The size and the depth of the lake is critical.
Commercial design services should be used to certify that a
given body of water is sufcient to withstand the building
loads. Loop temperatures usually range from 35ºF to 90ºF
and prove to be the best cooling performer and lowest
cost loop option of the three geothermal loops. Some
applications may not be good candidates due to public
access or debris problems from ooding.
coils that are connected in the same manner
Figure 16: Surface Water Loop Application
A closed loop “Horizontal” geothermal application
is similar to a vertical loop application with the exception
that the loops are installed in trenches approximately 5
feet below the ground surface. The piping may be installed
using a “four-pipe” or “six-pipe” design and could require
1,500 to 2,000 square feet of surface area per ton of
cooling. Loop temperatures for a commercial application
can range from 35ºF to 95ºF in Northern climates. Southern
climates can see temperatures ranging from 40ºF to
100ºF. Horizontal loops are generally not applied in urban
areas because land use and costs can be prohibitive. New
advances
assembly time of horizontal loops while keeping the rst
cost lower than a vertical loop.
Page 16 of 56 McQuay Large Vertical Water Source Heat Pumps Catalog 1109-1
Catalog 1109-1 McQuay Large Vertical Water Source Heat Pumps Page 31 of 56
Operating Limits
Table 8: Air Limits - °F (English units)
Standard Range Geothermal RangeUnits Units
Cooling
Min. Ambient Air 50ºF 50ºF 40ºF 40ºF
Normal Ambient Air 80ºF 70ºF 80ºF 70ºF
Max Ambient Air 100ºF 85ºF 100ºF 85ºF
Min. Entering Air
Normal Entering Air db/wb 80/67ºF 70ºF 80/67ºF 70ºF
Max Entering Air db/wb
1,2
50ºF 50ºF 50ºF 40ºF
1,2
100/83ºF 80ºF 100/83ºF 80ºF
Heating Cooling Heating
Table 9: Air Limits - °C (SI units)
Standard Range Geothermal Range
Units Units
Cooling
Min. Ambient Air 10ºC 10ºC 5ºC 5ºC
Normal Ambient Air 27ºC 21ºC 27ºC 21ºC
Max Ambient Air 38ºC 29ºC 38ºC 29ºC
Min. Entering Air
Normal Entering Air db/wb 27/19ºC 21ºC 27/19ºC 21ºC
Max Entering Air db/wb
1,2
10ºC 10ºC 10ºC 5ºC
1,2
38/28ºC 27ºC 38/28ºC 27ºC
Heating Cooling Heating
Table 10: Water - °F (English units)
Standard Range Geothermal Range
Units Units
Cooling
Min. Entering Water
Normal Entering Water 85ºF 70ºF 77ºF 40ºF
Max Entering Water 110ºF 90ºF 110ºF 90ºF
1,2
55ºF 55ºF 30ºF 20ºF
Heating Cooling Heating
Environment
This equipment is designed for indoor installation only.
Sheltered locations such as attics, garages, etc., generally
will not provide sufcient protection against extremes in
temperature and/or humidity, and equipment performance,
reliability, and service life may be adversely affected.
Power supply
A voltage variation of +/-10% of nameplate voltage is
acceptable. Three-phase system imbalance shall not exceed
2%.
Additional information for initial
start-up only
Standard range units:
Units are designed to start in an ambient of 50ºF (10ºC),
with entering air at 50ºF (10ºC), with entering water at 70ºF
(21ºC), with both air and water at the ow rates used in the
ISO 13256-1 rating test, for initial start-up in winter.
Note: This is not a normal or continuous operating
condition. It is assumed that such a start-up is for the
purpose of bringing the building space up to occupancy
temperature.
Table 11: Water - °C (SI units)
Standard Range Geothermal Range
Units Units
Cooling
Min. Entering... Water
Entering Water 29ºC 21ºC 25ºC 4ºC
Normal
Max Entering Water 43ºC 32ºC 43ºC 32ºC
1 At ARI ow rate
2 Maximum and minimum values may not be combined. If one value is
at maximum or minimum, the other two conditions may not exceed the
normal condition for standard units. Extended range units may combine
any two maximum conditions, but not more than two, with all other
conditions being normal conditions.
1,2
13ºC 13ºC -1ºC -6ºC
Heating Cooling Heating
Geothermal range units:
Geothermal range heat pump conditioners are designed
to start in an ambient of 40ºF (5ºC), with entering air at
40ºF (5ºC), with entering water at 40ºF (5ºC), with both air
and water at the ow rates used in the ISO 13256-1 rating
test, for initial start-up in winter.
Note: This is not a normal or continuous operating
condition. It is assumed that such a start-up is for the
purpose of bringing the building space up to occupancy
temperature.
Page 32 of 56 McQuay Large Vertical Water Source Heat Pumps Catalog 1109-1
Page 34 of 56 McQuay Large Vertical Water Source Heat Pumps Catalog 1109-1
Performance Data
2.5
0
.5
1.0
1.5
2.0
6,0005,0004,0003,0002,0001,000
600 RPM
800 RPM
1000 RPM
1200 RPM
1400 RPM
1
1
⁄
2
HP
2 HP
EXTERNAL STATIC PRESSURE (INCHES OF WATER)
CFM
0
2.5
0
.5
1.0
1.5
2.0
6,0005,0004,0003,0002,0001,000
800 RPM
1000 RPM
1200 RPM
1400 RPM
2 HP
3 HP
EXTERNAL STATIC PRESSURE (INCHES OF WATER)
CFM
0
Figure 17: Large Vertical Size 072, 096 (Includes allowance for dry coil and lter)
Note: For wet coil face velocity (cfm ÷ coil face area, sq. ft.). Add the following static to the external static pressure for the
corresponding face velocity: 300 fpm = .20"; 400 fpm = .31"; 500 fpm = .44". Re-enter table at the increased external static
pressure to determine nal cfm.
Motor and Drive Selections:
1.5 hp: 790-107
Unit Size 072 Unit Size 096
3 RPM 1.5 hp: 677-960 RPM Do Not Select
2 hp: 1006-1330 RPM 2 hp: 1006-1330 RPM
Figure 18: Large Vertical Size 120 (Includes allowance for dry coil and lter)
Note: For wet coil face velocity (cfm ÷ coil face area, sq. ft.). Add the following static to the external static pressure for the
corresponding face velocity: 300 fpm = .27"; 400 fpm = .41"; 500 fpm = .58". Re-enter table at the increased external static
pressure to determine nal cfm.
Motor and Drive Selections:
2 hp: 790-107
Unit Size 120
3 RPM Do Not Select
3 hp: 1006-1330 RPM
Catalog 1109-1 McQuay Large Vertical Water Source Heat Pumps Page 35 of 56
Performance Data
2.5
0
.5
1.0
1.5
2.0
12,00010,0008,0006,0004,0002,000
600 RPM
800 RPM
1000 RPM
1200 RPM
1400 RPM
5 HP
EXTERNAL STATIC PRESSURE (INCHES OF WATER)
CFM
0
3 HP
2.5
0
.5
1.0
1.5
2.0
12,00010,0008,0006,0004,0002,000
800 RPM
1000
RPM
1200 RPM
1400 RPM
7
1
⁄
2
HP
10 HP
EXTERNAL STATIC PRESSURE (INCHES OF WATER)
CFM
0
Figure 19: Large Vertical Size 180, 215
Note: For wet coil face velocity (cfm ÷ coil face area, sq. ft.). Add the following static to the external static pressure for the
corresponding face velocity: 300 fpm = .20"; 400 fpm = .31"; 500 fpm = .44". Re-enter table at the increased external static
pressure to determine nal cfm.
Motor and Drive Selections:
3
Unit Size 180 Unit Size 215
hp: 912-1098 RPM 3 hp: 825-993 RPM Do Not Select
5 hp: 1085-1307 RPM 5 hp: 963-1160 RPM
Figure 20: Large Vertical Size 290
Note: For wet coil face velocity (cfm ÷ coil face area, sq. ft.). Add the following static to the external static pressure for the
corresponding face velocity: 300 fpm = .27"; 400 fpm = .41"; 500 fpm = .58". Re-enter table at the increased external static
pressure to determine nal cfm.
Motor and Drive Selections:
7.5 hp: 1005-1299 RPM
Unit Size 290
10 hp: 1195-1395 RPM
Do Not Select
Page 36 of 56 McQuay Large Vertical Water Source Heat Pumps Catalog 1109-1
Figure 21: Large Vertical – Size 072
Dimensional Data
Front View
Left Hand Piping
Overall Unit Dimensions: 54⅝" W × 55¾" H × 28" D
Right Hand Piping
Electrical
Knockouts
Figure 22: Large Vertical – Size 096
Left Hand Piping
Overall Unit Dimensions: 54⅝" W × 55¾" H × 28" D
Front View
Right Hand Piping
Electrical
Knockouts
Catalog 1109-1 McQuay Large Vertical Water Source Heat Pumps Page 37 of 56
Dimensional Data
Figure 23: Large Vertical – Size 120
Front View
Left Hand Piping
Overall Unit Dimensions: 54⅝" W × 55¾" H × 28" D
Right Hand Piping
Electrical
Knockouts
Figure 24: Large Vertical – Size 180
Left Hand Piping
Overall Unit Dimensions: 80⅜" W × 67" H × 30" D
Front View
Right Hand Piping
Page 38 of 56 McQuay Large Vertical Water Source Heat Pumps Catalog 1109-1
Figure 25: Large Vertical – Size 215
Dimensional Data
Left Hand Piping
Overall Unit Dimensions: 80⅜" W × 67" H × 30" D
Front View
Right Hand Piping
Figure 26: Large Vertical – Size 290
Left Hand Piping
Overall Unit Dimensions: 80⅜" W × 67" H × 30" D
Front View
Right Hand Piping
Catalog 1109-1 McQuay Large Vertical Water Source Heat Pumps Page 39 of 56
Accessories
Optional 2" Filter Rack & Return Air Duct Collar
The optional 2" lter rack and duct collar accepts 2" (51
mm) thick lters for side removal. It replaces the existing
1" (25 mm) lter rack and duct collar.
The optional 2" return air duct collar kit is used to facilitate connection of return air duct to the unit. A duct collar
kit can be used in conjunction with the standard 1" thick
lter rack or the optional 2" lter rack.
Figure 27: 2" Return Air Filter Rack
*2⅛"
Figure 28: 2" Return Air Duct Collar and Filter Rack
Dimensions Unit Sizes 072-120
501/16"
6"
30⅞"
Figure 29: 2" Return Air Duct Collar and Filter Rack
Dimensions Unit Sizes 180-290
1
/16"
74
6"
3
38
/16"
Page 40 of 56 McQuay Large Vertical Water Source Heat Pumps Catalog 1109-1
Catalog 1109-1 McQuay Large Vertical Water Source Heat Pumps Page 41 of 56
Accessories
Supply and Return Water Hoses
Available as re rated construction in 2 or 3 foot (610
mm or 914 mm) lengths. Fire rated hoses have a synthetic
polymer core with an outer rated covering of stainless
steel. Fittings are steel. Assembly is “re rated” and tested
according to UL 94 with a VO rating and ASTM 84. Each
hose has MPT connections. Hoses have a swivel connection
at one end and are available in 1¼" (32 mm) to match the
FPT ttings on unit sizes 072 through 120. Unit sizes 180
through 290 have 1½" (38 mm) FPT ttings.
Figure 32: Supply and Return Water Hoses
Condensate Hose Kit
Available as a long clear plastic hose with the necessary
clamps and a MPT hose tting for connection to the FPT
eld piping.
Figure 33: Condensate Hose Kit
Hose Specifications
Inner Tube: Fire retardant TRP (Thermosplastic Rubber)
tested to UL-94 with V-O rating.
Outer Braid: Stainless steel wire (ANSI 302/304)
Temperature range: 40°F to 200°F
Page 42 of 56 McQuay Large Vertical Water Source Heat Pumps Catalog 1109-1
Accessories
Combination Balancing and Shutoff (Ball)
Valves
Constructed of brass and rated at 400 psig (2758 kPa)
maximum working pressure. Valves have a built-in adjustable memory stop to eliminate rebalancing. Valves have
FPT connections on both ends for connection to the water
hose and to the eld piping.
Figure 34: Shut off Ball Valve
Motorized Valve
Used in variable pumping type applications, the valve
actuator is wired and typically piped in the return water
line. On a call for heating or cooling, the valve will open
prior to the compressor starting. The 24VAC valve actuator
must be wired directly to terminal block H8 on the
MicroTech III controller. The valve is rated for 300
psig (2070 kPa).
Multiple Unit Control Panel (MUCP)
Figure 36: Multiple Unit Control Panel and Board
The Multiple Unit Control Panel (MUCP) is an acces-
sory used when up to 3-units are controlled from a single
thermostat. The MUCP must be eld-installed in a remote
location, typically close to the units and convenient for
service access.
A maximum of 2 boards may be used together if up to
6-units must be connected and controlled from a single
thermostat.
Figure 37: Multiple Unit Control Panel Ciruit Board
Figure 35: 2-Way Motorized Valve
Field Installed Controls
The 2-way motorized water valve kit includes the valve
body, actuator and wire harness. The valve will only open
on a call for heating or cooling. The valve is rated for 300
psig (2070 kPa).
A multiple unit control panel allows a single thermostat
to control up to three units in parallel.
The multiple unit control board provides the compo-
nents necessary to protect the MicroTech III unit controller
from electrical damage that may occur when using standard
off-the-shelf relays.
This version of the board uses VAC relays and should
not be used in combination with any other accessories or
equipment that require VDC connections to the “G”, “W1”,
or “Y1” terminals.
Catalog 1109-1 McQuay Large Vertical Water Source Heat Pumps Page 43 of 56
Accessories
These easy-to-operate comfort command centers bring
you a complete range of deluxe features. Features that
enable you to match temperature programming to your application, provide added convenience, and help save energy
and money. All packed into an extra rugged, highly reliable
design that will look and perform like new for years to
come.
HP Circuit 1 High Pressure Switch
HP2 Circuit 2 High Pressure Switch
IOEXP I/O Expansion Board / Harness
LED1 LED Annunciator / Harness
LED2 LED Annunciator / Harness
*RAT Return Air Temperature
*LWT Leaving Water Temp Sensor
LP Circuit 1 Low Pressure Switch
LP2 Circuit 2 Low Pressure Switch
SLTS Circuit 1 Suction Line Temp Sensor
SLTS2 Circuit 2 Suction Line Temp Sensor
R1 Fan Motor Starter
RV Circuit 1 Reversing Valve Solenoid
RV2 Circuit 2 Reversing Valve Solenoid
TB1 Power Terminal Block
X1 75 VA Transformer
*DAT Discharge Air Temp Sensor
*EWT Entering Water Temp Sensor
Notes:
1. “Run/Prg” Jumper to be in “Run” position
for normal operation
* Optional with Communication Module
Page 50 of 56 McQuay Large Vertical Water Source Heat Pumps Catalog 1109-1
Engineering Specications – Model LVC, LVW
General
Contractor shall furnish and install Water Source Heat Pumps as indicated on plans. Each unit shall be CETL Listed. Units
less than 135,000 Btu/hr. total cooling capacity shall be ISO rated per Standard 13256-1. Each unit shall be fully run tested at
the factory. Each unit shall be shipped on a wooden skid and covered with plastic.
Casing and Cabinet
The casing shall be constructed of heavy-gauge G-60 galvanized steel corner posts and steel panel construction with heavy
gauge steel base pan. The base pan shall have holes to accept eld installation of rubber or spring isolators. The interior shall
be lined with 1/2" thick, 1½ lb. density glass ber. Multiple panels on front, back and sides shall provide access to compressor,
control box, fan motor and fan assembly. Unit shall have a galvanized steel painted drain pan with a drain connection extending
through the unit casing. Insulated drain pan shall act as a divider panel between the compressor and fan sections. Units shall have
as standard a factory installed 1" thick lter brackets for side lter removal. Unit shall have multiple 1" thick throwaway lters.
Cabinets shall have knockouts for entrance of line voltage and low voltage control wiring. Supply return water and condensate
connections shall be copper FPT ttings and protrude through the casing.
R-410A Refrigerant Circuit
Units shall be dual circuit design containing scroll compressors, electronic expansion valve, water-to-refrigerant coaxial
heat exchanger, reversing valve, nned tube heat exchanger, and safety controls. Non-ozone depleting R-410A refrigerant must
be used.
Compressor(s) shall be scroll type with thermal overload protection and external rubber vibration isolation mounts. Air
coil shall be aluminum ns bonded to copper tubes. The coaxial heat exchanger shall be copper inner tube and steel outer tube
with a U.L. Listing and a 400 psig water side rating and a 450 psig refrigerant side rating. Optional Cupro-nickel Coax coil for
geothermal units.
High and low side service valves shall be provided on each refrigerant circuit for measuring and charging of the refrigerant
circuit.
Safety controls shall include a low suction temperature (freezestat), high refrigerant pressure and low refrigerant pressure
switches. Units shall be capable of being reset only by interrupting the power supply to the unit and not from the wall thermostat.
Unit shall be capable of starting in an ambient of 40º F with entering water at 55º F standard range, 20º F extended range, with
both air and water ow rates at the ISO rating conditions.
Electrical
A control enclosure shall be located within the unit and shall contain controls for compressor(s), reversing valves(s) and
fan motor operation. A terminal block shall facilitate main power wiring connection. A 75 VA transformer shall supply the low
voltage control circuit.
Unit shall be nameplated to accept time delay fuses for branch overcurrent protection of the power conductors.
Unit control system shall provide one or two stage cooling and heating as required by the setpoints of the wall thermostat.
The unit shall be capable of providing an output signal to a unit-mounted LED annunciator to indicate a “fault” condition.
The control system shall be microprocessor based and provide the following:
■ Stand-alone operation
■ LonWorks communication capabilities (Must be LonMArk 3.4 certied)
■ BACnet communication capabilities (BACnet MS/TP Network)
Fan and Motor Assembly
Units shall have a belt driven centrifugal fan. The fan housing shall protrude through the cabinet to facilitate eld duct connection.
Catalog 1109-1 McQuay Large Vertical Water Source Heat Pumps Page 51 of 56
Engineering Specications – Model LVC, LVW
Solid-State Control System
MicroTech III Control System - Unit shall have a microprocessor- based control system. The unit control logic shall pro-
vide heating and cooling operation as required by the wall thermostat set point. The control system shall provide the following
for stand-alone operation:
1. The use of standard non-programmable or programmable wall thermostats.
2. Fan operation simultaneous with the compressor (fan interlock) regardless of thermostat logic.
3. Time delay compressor operation.
4. Delayed de-energizing of the reversing valve for quiet reversing valve operation.
5. Compressor short cycle protection of a minimum of three minutes before restart is possible.
6. Random unit start-up after coming off on unoccupied mode.
7. Single grounded wire connection for activation of the unoccupied or unit shutdown modes.
8. Night setback temperature setpoint input signal from the wall thermostat.
9. Override signal from wall thermostat to override unoccupied mode for 2 hours.
10. Brownout protection to suspend unit operation if the supply voltage drops below 80% of normal.
11. Condensate overow protection to suspend cooling operation in an event of a full drain pan.
12. Suspended compressor operation upon activation of the refrigerant pressure switch(es).
13. Cooling operation activated for 60 seconds upon activation of the low suction temperature sensor -
defrost cycle.
14. Method of defeating compressor, reversing valve and fan time delays for fast service diagnostics.
15. Remote reset - Provides means to remotely reset automatic lock-outs generated by high/low pressure faults and/or
low temperature faults.
16. Fault Retry clears faults the 1st two times they occur within a 24-hour period and triggers automatic lock-out on
3rd fault.
MicroTech® III Control with I/O Expansion Module – I/O Expansion Module connects directly to the main MicroTech
III controller to provide control of the second refrigeration circuit.
MicroTech® III Control with LonWorks® Communication Module – Unit shall have a microprocessor-based control
system. The unit control logic shall communicate over a LonMark communications network. The unit controller is factory
programmed [LonMark ® 3.4 certied Application Code the current standard for new applications] and tested with all the logic
required to monitor and control heating and cooling operation. The controller sets the unit mode of operation, monitors water
and air temperatures, and can communicate fault conditions via a LonMark communications network. Units with the Micro-
Tech III and LonWorks communication module include return air, discharge air and leaving water temperature sensors. Space
temperature sensor options include a set-point adjustment, tenant override button, and the capability of substituting the return
air sensor with a wall-mounted room sensor.
Microtech III Control w/ BACnet® Communication Module – Unit shall have a microprocessor-based control system.
The unit control logic shall communicate over a BACnet communications network. The BACnet communication module shall
incorporate an Atmel ARM7 Thumb series MCU and be capable of supporting a full MSTP BACnet implementation. The
microprocessor shall also support SPI compatible communications with the MCU of the Microtech III controller. The physical interface to a BACnet BAS network shall be through an industry standard RS-485 transceiver capable of existing on an
RS-485 network of up to 64 nodes. The unit controller is factory programmed and tested with all the logic required to monitor
and control heating and cooling operation. The controller sets the unit mode of operation, monitors water and air temperatures,
and can communicate fault conditions via a BACnet communications network. Units outtted with Microtech III and BACnet
Communication modules include return air, discharge air and leaving water temperature sensors. Space temperature sensor
options include a set-point adjustment, tenant override button, and the capability of substituting the return air sensor with a
wall-mounted room temperature sensor.
Each communicating unit controller performs the following unit operations:
■ Enable heating and cooling to maintain space temperature set point at the room sensor
■ Enable fan and compressor operation
■ Monitor all safety controls
■ Monitor discharge and return air temperature
■ Monitor leaving water temperature
■ Relay status of all vital unit functions
■ Support optional control outputs
Page 52 of 56 McQuay Large Vertical Water Source Heat Pumps Catalog 1109-1
Engineering Specications – Model LVC, LVW
Unit mounted LED annunciators aid in diagnosing unit operation by indicating the water source heat pump operating mode
and alarm conditions. If there are no current alarm conditions, a green LED on the annunciator board will indicate normal unit
operating mode. If an alarm condition exists, the Microtech III controller will send the fault condition to the LED annunciator,
which will assist in troubleshooting the unit. LED Annunciator shall be visible without removing access panel. Heat pumps
with the MicroTech III Controller with a LonWorks Communication Module is designed to be linked with a centralized Build-
ing Automation System (BAS) through a LonMark communications network for centralized scheduling and management of
multiple heat pumps.
Wall-mounted room sensors are available to control the heating and cooling operation of each MicroTech III Water Source
Heat Pump.
Available room sensors include:
■ Room Sensor with timed override button and LED;
■ Room temperature sensor with timed-override button and set point adjustment (55 to 95 deg F);
■ Room sensor with timed-override button and set point adjustment (-3 to +3 deg F);
■ Room sensor (no options, sensor only).
Warranty
An optional 4-year extended compressor warranty covers the compressor for 5 years from the date at which the unit ships
from the factory.
An optional 4-year extended refrigeration circuit warranty covers the entire refrigeration circuit and related components for
5 years.
Field Installed Accessories
Wall Thermostat Options
■ Programmable Electronic Thermostat Two-stage heat/Two-stage cool, 7-day programmable. Subbase shall have
system "Mode/Prog" and fan "Auto/On" switches. Thermostat shall have the option of an Optional Remote Sensor.
■ Non-programmable, auto or manual changeover Two-stage heat/Two-stage cool, night setback override. Subbase
shall have system "Cool/Off/Heat/Auto" and fan "Auto/On switches. Thermostat shall have the option of an Optional
Remote Sensor.
Wall Temperature Sensor Options:
■ Wall Sensor with timed-override button.
■ Wall Sensor with timed-override button and set point adjustment (55 to 95 deg F), fan mode switch (auto/on), operational mode button (Heat/Cool/Auto) and status LED to display fault condition.
■ Wall Sensor with timed-override button and set point adjustment (-3 to +3 deg F), fan mode switch (auto/on), operational mode button (Heat/Cool/Auto) and status LED to display fault condition.
Hose Kits:
Two re-rated exible hoses with ASTM ratings of Flame Spread 25, Fuel Contribution 25 and Smoke Density 50 for con-
nection to unit and eld piping. Hose shall be covered with stainless steel braiding to prevent damage.
Valve Options:
■ Combination water balancing and shutoff valve with adjustable memory stop.
■ Optional 2-way, Normally Open (N.O.) or Normally Closed (N.C.) motorized water valves.
Catalog 1109-1 McQuay Large Vertical Water Source Heat Pumps Page 53 of 56
McQuay Water Source Heat Pumps
Quality Products, Flexible Congurations
Stacking Units
3
Large Vertical Units
6 to 25 Ton
/4 to 3 Ton
Large Horizontal Units
6 to 10 Ton
Console Units
3/4 to 1
Rooftop Units 3 to 35 Ton
1
/2 Ton
Water to Water Source Heat
Pump Units
3
Ennity Vertical &
Horizontal Units
1/2 to 6 Ton
to 35 Ton
Warranty
All McQuay equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local McQuay Representative for warranty details. Refer to Form
9
33-43285Y. To find your local McQuay Representative, go to www.mcquay.com.
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.mcquay.com.
Products Manufactured in an ISO Certified Facility.