McQuay LDD, LDS, LDL, LME, LMH Installation Manual

...
Installation & Maintenance Data IM 439-15
Large Vertical Water Source Heat Pumps
6 thru 25 Tons
Models LDD, LDE, LDL, LDS, LME, LMH, LML, LMS
Group: WSHP Part Number: 106581103
Date: June 2006
©2006 McQuay International
Contents
Model Nomenclature .................................................... 2
Transportation and Storage ......................................... 2
Installation.................................................................. 3-6
Piping ............................................................................ 7
Cleaning and Flushing System ..................................... 8
Start-up ...................................................................... 8-9
Operating Limits ........................................................... 9
Electrical Data ............................................................... 9
Typical Wiring Diagrams ........................................ 10-13
Model Nomenclature
W LDD 1 070 D Z
Product Category
W = WSHP
Product Identifier
See box below
Typical Mark IV/AC units ................................. 10-11
Typical MicroTech units .................................. 12-13
Unit Operation ............................................................ 14
Mark IV Sequence of Operation ................................. 15
Thermostat Connections............................................ 16
Miscellaneous Options on Mark IV Units .............. 17-20
Field Installed Options on MicroTech Units ................ 21
Troubleshooting WSHP .............................................. 22
Maintenance ............................................................... 23
Design Series
1 = A Design 2 = B Deisgn 3 = C Design 4 = D Design 5 = E Design
Nominal Capacity
070 = 70,000 108 = 108,000 121 = 121,000
Coil Options
(None)
Voltage
D= 208-60-3 H= 230-60-3 K= 460-60-3 L= 575-60-3 N= 380-50-3
180 = 180,000 215 = 215,000 290 = 290,000 etc. . .
McQuay Product Identifiers
LDD = Std. Large Vertical/DDC Controls/Std. Range/Less Board LME = Std. Large Verical/Mark IV/Ext. Range LDE = Std. Large Vertical/DDC Controls/Ext. Range LMH = High Static Large Vertical/Mark IV/Std. Range LDL = Std. Large Vertical/DDC Controls/Ext. Range/Less Board LML = High Static Large Vertical/Mark IV/Ext. Range LDS = Std. Large Vertical/DDC Controls/Std. Range LMS = Std. Large Vertical/Mark IV/Std. Range
Page 2 of 24 / IM 439
Note: Installation and maintenance are to be performed only
by qualified personnel who are familiar with local codes and regulations, and are experienced with this type of equipment.
CAUTION
!
Sharp edges are a potential injury hazard. Avoid contact with them.
Transportation and Storage
Upon receipt of the equipment, check unit for visible dam­age. Make a notation on the shipper’s delivery ticket before signing. If there is any evidence of rough handling, the cartons should be opened at once to check for concealed damage. If any damage is found, notify the carrier within 48 hours to establish your claim and request their inspection and a report. The Warranty Claims Department should then be contacted.
Do not stand or transport the machines on end. For storing, each unit must be in the “up” position.
In the event that elevator transfer makes upended position­ing unavoidable, absolutely ensure that the machine is in the normal upright position for at least 24 hours before operating.
Temporary storage at the jobsite must be indoors, com­pletely sheltered from rain, snow, etc. High or low tempera­tures naturally associated with weather patterns will not harm the conditioners. Excessively high temperatures 140°F (60°C) may deteriorate certain plastic materials and cause permanent damage. In addition, the solid-state circuit boards may experience operational problems.
Installation
General
1. To prevent damage, this equipment should not be oper-
ated for supplementary heating and cooling during the
construction period.
2. Inspect the shipping label for any specific tagging numbers
indicated per request from the installing contractor. At this
time the voltage, phase and capacity should be checked
against the plans.
3. Check the unit size against the plans to be sure that the unit
will be installed in the correct location.
4. After removing the packaging material, remove unit from
the skid.
5. Before installation, check the available dimensions versus
the dimensions of the unit.
6. Pay attention to the location and routing of water piping,
condensate drain piping, and electrical wiring. The loca-
tions of these items are clearly marked on submittal
drawings.
7. The installing contractor will find it beneficial to confer with
piping, sheetmetal, ceiling and electrical foremen together
before installing any conditioners.
Note: Check the unit name plate for correct voltage with the
plans before installing the equipment. Also, make sure all electrical ground connections are made in accor­dance with local code.
8. We recommend that the contractor cover the conditioners
with plastic film to protect the machines during finishing of
the building. This is important if spraying fireproofing
material on bar joists, sandblasting, spray painting and
plastering operations have not been completed.
Unit Location
1. Locate the unit in an area that allows for easy removal of the filter and access panels, and has enough space for service personnel to perform maintenance or repair. Pro­vide sufficient room to make water, electrical and duct con­nections
(see Figure 1 for service clearance details)
.
2. The contractor should make sure that access has been provided including clearance for 2" (51 mm) thick filter brack­ets, duct collars and fittings at water and electrical connec­tions.
3. Allow adequate room around the unit for a condensate trap.
4. The unit can be installed “free standing” in an equipment room. Generally, the unit is located in a separate room with the non-ducted return air facing the return air intake. Alter­natively, the unit can have a ducted return air.
5. It is recommended that the unit be located on vibration iso­lators to reduce any vibration
(see Figure 3)
.
6. If optional field installed controls are required (Boilerless System), space must be provided for the enclosure to mount on the side of the unit.
Figure 1. Service clearance
Side B
Fan Motor
Side A
24" (610 mm)
Control Box Location
24"
(610 mm)
Piping
Location
IMPORTANT
1. A 24" (610 mm) minimum clearance is required on the return air, control box and piping sides. However, a 36" (914 mm) clearance allows for easier serviceability.
2. A 12" (305 mm) minimum clearance is required on Side A to gain access to panel to remove locking collar for shaft removal.
3. A 6" (152 mm) clearance is required on Side B to remove screws holding top panel.
4. Top clearance is required for fan shaft removal.
5. Some codes dictate a 60" (1524 mm) clearance above the control box which could be violated with a ducted return. Check your codes.
IM 439 / Page 3 of 24
Unit Arrangement
Two fan discharges and piping arrangements are available. With the return air side defined as the “front” of the unit, the water piping and electrical power connections may be right­hand (side) or left-hand. The main control panel is located in the center of the unit, lower section under the return air filter. Unit sides opposite the control panel and opposite the piping side may be up against walls and still allow for service and maintenance through the remaining access panels.
Filter Access
Each unit is shipped with a filter bracket for side filter removal.
Figure 2. Side view from piping end
M
M
Piping
Control Box Location
Piping
Fan Motor
Vibration Isolation
For minimum sound and vibration transmission, it is recom­mended that the unit be mounted on vibration isolators.
Holes are provided in the bottom panel to facilitate con-
nection of isolators
(see Figure 3 for hole locations)
Isolators supplied by the manufacturer are the type shown in Figures 4 and 5. Four white isolators are used for single compressor units and six green isolators are used for dual compressor units. The holes in the bottom of the unit allow for
3
⁄8" (10 mm) bolt to be secured to the isolator.
a
Figure 4. Single compressor unit — vibration isolators
3" (76 mm)
7
(4)
5
/32"
28
(715 mm)
3" (76 mm)
3" (76 mm)
23
54
/32"
(1390 mm)
.
/16" (11 mm) holes
Figure 3. Isolator
25/8" (61 mm)
7
/16" (11 mm) dia.
AA
3" (76 mm)
1
/
4
2"
(51 mm)
Section A-A
3
" (114 mm)
2
1
" (140 mm)
2
/
5
7
/16" (11 mm)
/8" (10 mm) TAP
21/2" (64 mm)
1
/4" (6 mm)
Figure 5. Dual compressor unit — vibration isolators
2" (51 mm)
1
/8"
30
(765 mm)
2" (51 mm)
1
3
/4" (83 mm)
Page 4 of 24 / IM 439
3
80
/8"
(2042 mm)
(6) 3/8" (10 mm) holes
3
/16"
40
(1021 mm)
1
/4" (83 mm)
3
Air Balancing
All units are supplied with a variable pitch motor sheave to aid in airflow adjustment. They are typically set at the low end of the rpm range for field adjustment to the required airflow.
When the final adjustments are complete, the current draw of the motors should be checked and compared to the full load current rating of the motors. The amperage must not exceed the service factor stamped on the motor nameplate.
Upon completion of the air balance, it is a common industry recommendation that the variable pitched motor sheave be replaced with a properly sized fixed sheave. A matching fixed sheave will provide longer belt and bearing life and vibration free operation. Initially, it is best to have a variable pitched motor sheave for the purpose of air balancing, but once the balance has been achieved, fixed sheaves maintain balancing and alignment more effectively.
Adjustment (See Figure 6)
1. All sheaves should be mounted on the motor or driving
shaft with the setscrew “A” toward the motor.
2. Be sure both driving and driven sheaves are in alignment
and that shafts are parallel.
3. Fit internal key “D” between sheave and shaft, and lock
setscrew “A” securely in place.
4. Put on belts and adjust belt tension to 4 lbs. ± 0.7 lbs. (18 ± 3N) for a
1
2" to 3⁄4" (13 mm to 19 mm) belt deflection
height.
5. To determine the deflection distance from normal position, use a straightedge or stretch a cord from sheave to sheave to use as a reference line. On multiple-belt drives an adjacent undeflected belt can be used as a reference.
6. Future adjustments should be made by loosening the belt tension and increasing or decreasing the pitch diameter of the sheave by half or full turns as required. Readjust belt tension before starting drive.
7. Be sure that all keys are in place and that all setscrews are tight before starting drive. Check setscrews and belt tensio n after 24 hours service.
8. When new V-belts are installed on a drive, the initial tension will drop rapidly during the first few hours. Check tension frequently during the first 24 hours of operation. Subsequent retensioning should fall between the mini­mum and maximum force.
Figure 7. Drive belt adjustment
Adjusting:
1. Loosen setscrews “B” and “C” in moving parts of sheave and pull out external key “E”. (This key projects a small amount to provide a grip for removing.)
2. Adjust sheave pitch diameter for desired speed by open­ing moving parts by half or full turns from closed position.
Do not open more than five full turns.
3. Replace external key “E” and securely tighten setscrews “B” over key and setscrews “C” into keyway in fixed half of the sheave.
Figure 6.
“A”
“B”
“E”
“D”
Span Length (t)
Deflection
Force
D
h
d
C
t
h=
64
t= C2 –
Where:
t= Span length, inches (mm) C= Center distance, inches (mm) D= Larger sheave diameter, inches (mm)
d= Smaller sheave diameter, inches (mm) h= Deflection height, inches (mm)
Note: The ratio of deflection to belt span is 1:64.
D-d
()
2
Single Groove
“C”
Key “E” projects to provide a grip for removing.
IM 439 / Page 5 of 24
Ductwork and Attenuation
Discharge ductwork is normally used with these conditioners. Return air ductwork may also be required but will require field installation of a return air duct collar.
All ductwork should conform to industry standards of good
practice as described in ASHRAE Systems Guide.
The discharge duct system will normally consist of a flex­ible connector at the unit, a transition piece to the final duct size, a short run of duct, an elbow without vanes and a trunk duct tee’d into branch ducts with discharge diffusers as shown in Figure 10. Transition piece must not have angles totalling more than 30 degrees or severe loss of air performance can result.
All units have multiple fan outlets. A single duct can en­close all the openings as shown in Figure 10; however, the preferred method for minimum static pressure loss would be individual ducts at each outlet connected to a larger duct down­stream.
For minimum noise transmission, the metal duct material should be internally lined with acoustic fibrous insulation.
The ductwork should be laid out so that there is no line of sight between the conditioner discharge and the distribution diffusers.
Return air ducts can be brought in adjacent to the return air of the conditioner. T ypically, the equipment room becomes the common return air plenum.
Do not insert sheetmetal screws directly into the unit cabi­net for connection of supply or return air ductwork, especially return air ductwork which can hit the drain pan or the air coil.
Ventilation Air
Outside air may be required for ventilation. The temperature of the ventilation air must be controlled so that mixture of out­side air and return air entering the conditioner does not ex­ceed conditioner application limits. It is also general practice to close off the ventilation air system during unoccupied peri­ods (night setback).
The ventilation air system is generally a separate build­ing subsystem with distribution ductwork. Simple introduction of the outside air into each return air plenum chamber rea­sonably close to the conditioner air inlet is not only adequate, but recommended. Do not duct outside air directly to the con­ditioner inlet. Provide sufficient distance for thorough mixing of outside and return air
(see Operating Limits on page 9).
Optional Duct Collar and 2" (51 mm) Filter Rack
The optional duct collar kit is used to facilitate connection of return air duct to the unit. The duct collar kit can be used in conjunction with the standard 1" (25 mm) thick filter rack or the optional 2" (51 mm) filter rack.
The 2" (51 mm) filter rack facilitates the installation of 2" (51 mm) thick filters for side removal. The 2" (51 mm) filter rack replaces the existing 1" (25 mm) filter rack and does not require the use of the optional return air duct collar.
The kits are installed as follows:
1. Remove all filters, filter racks and brackets. Save all
screws. Discard bracket end.
2. Attach top duct collar in conjunction with top filter rack
with truss head screws.
3. Attach bottom duct collar and filter rack.
4. On single compressor units, attach two flanges using four
(4) #8 truss head screws provided.
5. Attach center support in original location.
6. Locate and attach center filter racks using screws pro-
vided.
7. Attach duct collar sides using eight (8) #10 sheetmetal
8. No point in the drain system may be above the drain
connection of any unit.
9. Automatic flow controlled devices must not be installed
prior to system cleaning and flushing.
10. A high point of the piping system must be vented.
11. Check local code for the need of dielectric fittings.
Figure 8. Assembly detail
Filter Rack
Duct Collar
Duct Collar Side
Figure 9.
Center Support
Chassis
Page 6 of 24 / IM 439
Side Flanges
Door End
Top Duct Collar
Duct Collar Side
Top Filter Rack
Center Filter Racks
Filters
Piping
CAUTION
!
Do not overtorque fittings. The maximum torque without damage to fittings is 30 foot pounds. If a torque wrench is not available, use as a rule of thumb, finger-tight plus one quarter turn. Use two wrenches to tighten the union, one to hold the line and one for simultaneous tightening of the nut.
1. All units are recommended to be connected to supply and return piping in a two-pipe reverse return configuration. A reverse return system is inherently self-balancing and re­quires only trim balancing where multiple quantities of units with different flow and pressure drop characteristics are connected to the same loop. A simple way to check for proper water balance is to take a differential temperature reading across the water connections. To insure proper water flow, the dif ferential should be 10°F to 14°F (5°C to 8°C) in the cooling mode of operation.
A direct return system may also be made to work ac­ceptably , but proper water flow balancing is more difficult to achieve and maintain, and may require flow control devices.
2. The piping can be steel, copper or PVC.
3. Supply and return runouts are usually connected to the unit by short lengths of high pressure flexible hose which are sound attenuators for both unit operating noise and hydraulic pumping noise. One end of the hose should have a swivel fitting to facilitate removal for service. Hard pip­ing can also be brought directly to the unit although it is not recommended since no vibration or noise attenuation can be accomplished. The hard piping must have unions to facilitate unit removal
setup)
.
(see Figure 10 for typical piping
Figure 10.
Branch Duct
Trunk Duct
4. Supply and return shutoff valves are required at each con­ditioner. The return valve is used for balancing and should have a “memory stop” so that it can always be closed off but can only be reopened to the proper position for the flow required.
5. No unit should be connected to the supply and return pip­ing until the water system has been cleaned and flushed completely. After the cleaning and flushing has taken place, the initial connection should have all valves wide open in preparation for water system balancing.
6. Condensate piping can be steel, copper or PVC. Each unit is supplied with a FPT threaded fitting.
7. The condensate disposal piping must have a trap and the piping must be pitched away from the unit not less than
1
⁄4" per foot (21 mm per meter). Generally , the condensate trap is made of copper. A complete copper or PVC conden­sate system can also be used. Union fittings in the copper lines should be applied to facilitate removal.
8. No point in the drain system may be above the drain con­nection of any unit.
9. Automatic flow controlled devices must not be installed prior to system cleaning and flushing.
10. A high point of the piping system must be vented.
11. Check local code for the need of dielectric fittings.
Cleaning and Flushing System
1. Prior to first operation of any conditioner, the water cir-
culating system must be cleaned and flushed of all con­struction dirt and debris.
If the conditioners are equipped with water shutoff valves, either electric or pressure operated, the supply and return runouts must be connected together at each con­ditioner location. This will prevent the introduction of dirt into the unit. Additionally, pressure operated valves only open when the compressor is operating
(see Figure 1 1)
.
Main Duct
Transition Duct
Flexible Connector
Flexible Hose with Brass Pipe Fittings
Supply
Return
Balancing Valve with Close-off
Condensate
Figure 11.
Return Runout
Supply Runout
Rubber Hose
Runouts Initially Connected Together
Mains
IM 439 / Page 7 of 24
Cleaning and Flushing System (Continued)
2. The system should be filled at the city water makeup connection with all air vents open. After filling, vents should be closed.
The contractor should start main circulator with pres­sure reducing valve makeup open. Vents should be checked in sequence to bleed off any trapped air to as­sure circulation through all components of the system.
Power to the heat rejector unit should be off, and the supplementary heat control set at 80°F (27°C).
While circulating water, the contractor should check and repair any leaks in the piping. Drain at the lowest point(s) in the system should be opened for initial flush and blowdown, making sure city water fill valves are set to make up water at the same rate. Check the pressure gauge at pump suction and manually adjust the makeup to hold the same positive steady pressure both before and after opening the drain valves. Flush should con­tinue for at least two hours, or longer if required, to see clear, clean drain water.
3. Supplemental heater and circulator pump should be shut off. All drains and vents should be opened to completely drain down the system. Short circuited supply and re­turn runouts should now be connected to the conditioner supply and return connections. Teflon tape is recom­mended over pipe dope for pipe thread connections. Use no sealers at the swivel flare connections of hoses.
4. Trisodium phosphate was formerly recommended as a cleaning agent during flushing. However, many states and localities ban the introduction of phosphates into their sewage systems. The current recommendation is to sim­ply flush longer with warm 80°F (27°C) water.
5. Refill the system with clean water. Test the litmus paper for acidity, and treat as required to leave the water slightly alkaline (pH 7.5 to 8.5). The specified percentage of anti­freeze may also be added at this time. Use commercial grade anti-freeze designed for HVAC systems only. Do not use automotive grade anti-freeze.
6. Set the system control and alarm panel heat add setpoint to 70°F (21°C) and the heat rejection setpoint to 85°F (29°C). Supply power to all motors and start the circulat­ing pumps. After full flow has been established through all components including the heat rejector (regardless of season) and air vented and loop temperatures stabilized, each of the conditioners will be ready for check, test and start-up and for air and water balancing.
Start-up
1. Open all valves to full open position and turn on power to the conditioner.
2. Set thermostat for Fan Only operation by selecting Off at the system and On at the fan switch. If Auto fan operation were selected, the fan would cycle with the compressor. Check for proper air delivery.
3. All units have variable pitch motor sheaves. Reset for correct airflow.
4. Set thermostat to Cool. If the thermostat is an automatic changeover type, simply set the cooling temperature to the coolest position. On manual changeover types addi­tionally select Cool at the system switch.
Again, many conditioners have time delays which protect the compressor against short cycling. After a few minutes of operation, check the discharge grilles for cool air delivery. Measure the temperature difference between entering and leaving water. It should be approximately
1
1
2 times greater than the heating mode temperature difference. For example, if the cooling temperature dif­ference is 15°F (8°C), the heating temperature difference should have been 10°F (5°C).
Without automatic flow control valves, a cooling tem­perature difference of 10°F to 14°F (5°C to 8°C) is about right. Adjust the combination shutoff/balancing valve in the return line to a water flow rate which will result in the 10°F to 14°F (5°C to 8°C) degree difference in cooling.
5. Set thermostat to Heat. If thermostat is the automatic changeover type, set system switch to the Auto position and depress the heat setting to the warmest selection. Some conditioners have built-in time delays which pre­vent the compressor from immediately starting. With most control schemes, the fan will start immediately. After a few minutes of compressor operation, check for warm air delivery at discharge grille. If this is a “cold building” start-up, leave unit running until return air to the unit is at least 65°F (18°C).
Measure the temperature difference between enter­ing and leaving air and entering and leaving water. With entering water of 60°F to 80°F (16°C to 27°C), leaving water should be 6°F to 12°F (3.3°C to 6.6°C) cooler, and the air temperature rise through the machine should not exceed 35°F (19°C). If the air temperature exceeds 35°F (19°C), the airflow rate is probably inadequate.
If the water temperature difference is less than 6°F (3.3°C) degrees, the water flow rate is excessive. If the water temperature difference exceeds 12°F (6.6°C), then the water flow rate is inadequate.
6. Check the elevation and cleanliness of the condensate line. If the air is too dry for sufficient dehumidification, slowly pour enough water into the condensate pan to ensure proper drainage.
7. If the conditioner does not operate, the following points should be checked: a. Is proper voltage being supplied to the machine? b. Is the proper type of thermostat being used? c. Is the wiring to the thermostat correct?
8. If the conditioner operates but stops after a brief period, check for: a. Is there proper airflow? Check for dirty filter, incorrect
fan rotation (3-phase fan motors only), or incorrect ductwork.
b. Is there proper water flow rate within temperature limits?
Check water balancing; backflush unit if dirt-clogged.
9. Check the unit for vibrating refrigerant piping, fan wheels, etc.
10. Do not lubricate the fan motor during the first year of operation as it is prelubricated at the factory.
Page 8 of 24 / IM 439
Operating Limits
CAUTION
!
Electrical Data
Environment
This equipment is designed for indoor installation only. Shel­tered locations such as attics, garages, etc., generally will not provide sufficient protection against extremes in tem­perature and/or humidity, and equipment performance, reli­ability, and service life may be adversely affected.
Table 1. Air and water limits
All UNITS
Cooling Heating
Min. Ambient Air 40°F/5°C40°F/5°C
Normal Ambient Air 80°F/27°C70°F/21°C
Max. Ambient Air 100°F/38°C85°F/29°C
Min. Ent. Air
Normal Ent. Air, 80/67°F70°F
Max. Ent. Air, 100/83°F80°F
➀➁
db/wb 27/19°C21°C
➀➁
db/wb
50°F/10°C40°F/5°C
38/28°C27°C
Table 2. Water enthalpy
Min. Ent. Air Normal Ent. Air 85°F/29°C70°F/21°C85°F/29°C70°F/21°C Max. Ent. Air
At ARI flow rate.Maximum and minimum values may not be combined. If one value is at
maximum or minimum, the other two conditions may not exceed the normal condition for standard units. Extended range units may combine any two maximum or minimum conditions, but not more than two, with all other conditions being normal conditions.
➀➁
➀➁
Cooling Heating Cooling Heating
55°F/13°C55°F/13°C40°F/5°C40°F/5°C
110°F/43°C90°F/32°C 110°F/43°C90°F/32°C
Additional Information
1. All units
Unit will start up in an ambient of 40°F (5°C), with entering air at 40°F (5°C), with entering water at 40°F (5°C), with both air and water at flow rates used in the ARI Standard 320-86 rating test, for initial start-up in winter.
General
1. Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electrical Code, whichever is applicable.
2. Apply correct line voltage to the unit. Each unit is supplied with a 3-lug terminal block in the main control for three­phase main power. Multiple knockouts on the sides of the unit facilitate conduit connections on the unit for line and low voltage. A disconnect switch near the unit is required by code. Power to the unit must be sized correctly and be fused with Class RK5 dual element fuses.
Minimum and Maximum Voltage
Nameplate 208/60/3: Min. 187 volts, Max. 229 volts Nameplate 230/60/3: Min. 207 volts, Max. 253 volts Nameplate 460/60/3: Min. 414 volts, Max. 506 volts Nameplate 575/60/3: Min. 515 volts, Max. 632 volts Nameplate 380/50/3: Min. 360 volts, Max. 418 volts
Three-phase system unbalance should not exceed 2%. Voltages listed are to show voltage range. However, units operating with overvoltage and undervoltage for extended periods of time will experience premature component failure.
Note: This is not a normal or continuous operating
condition. It is assumed that such a start-up is for the purpose of bringing the building space up to occupancy temperature.
IM 439 / Page 9 of 24
L3 L2
32
36
34
35
1
L1
Junction
Box
Term
Board
Comp
19
3
BK
YE
YE
RD
RD
BK
BK
L1
L2
L3
GND
RD
YE
2
18
Crankcase
Heater
30
24
23
22
17
YE
BK
16
YE
BK
21
15
Fan
Motor
GN
GND
YE
RD
BK
Common
Comp
Fan
Mark IV/AC
Board
Compressor
Contactor
36
35
21
L1
37
37
Breaker
(Optional)
OR 230V
RD 208V
BK/RD 460V
BK
BK
YE
GND
Xformer
REV Valve Solenoid
COF
LT
LT
HP
HP
14
46
43
42
BR
BR
BL
High
Press
Switch
Low
Press
Switch
Low
Temp
Switch
Ring
Terminal
(Condensate
Overflow)
Thermistor
V
RV
RV
44
29
BL
C
R
W
2
W
1
Y
1
GOFELUAPVRC
28
26
27
WH
WH
Electric
Expansion
Valve
BK
BK
061093503 Rev. A
Ty pical Wiring Diagrams
Figure 12. Typical Mark IV/AC unit — single compressor
Page 10 of 24 / IM 439
L1
L2
L3
COMMON
COMP
FAN
O
W
G
WY
FELUAPVRC
211
COMMON
COMP
FAN
O
W
G
WY
FELUAPVRC
211
Fan
Motor
Electric
Expan Valve
Optional
Crankcase
Heater
Compr. 2 Compr. 1
Chassis Control
RD7
BK12
RD6
BK92
BK93
Compr.
Cont. 1
Compr. Cont. 2
BK82
BK83
}
YE14
Optional
Positive
Staging
Relay
GR/YE
YE13YE13
BK11
BK
RD
YE
WH
WH56
WH
WH57
WH55
Circuit 2
Thermistor
Thermistor
Electric
Expan Valve
WH
WH46
WH
WH47
WH45
Low T emp
Circuit 1
2
1
2
1
Circuit
1
Circuit
2
High Press
Switch
Low Press
Switch
Reversing Valve
Solenoid
(not required on cooling only)
<<
<<
<<
<<
<<
<<
<<
<<
High Press
Switch
Low Press
Switch
BK
WH
BK
WH
BR
BR
BL
BL
BR53
Low T emp
BR
BR
BL
BL
RD54
BR52
BK51
BL50
BL40
BK41
BR43
RD44
BR42
BK51
BL50
BL40
BK41
YE
<<
<<
Condensate
Overflow
Sensor
BK30
BK49
RD48
BK
BK
BK59
RD58
BK
BK
1
2
5
3
4
BR87
RD88
PK89
WH85
WH86
BK83
BL18
YE13
BK11
BK82
BK31
YE8
BK4
BK
WH
RD
OR
YE14
BK12
BK92
BK32
YE9
BK5
WH
RD
OR
BK93
BL17
BK
BK
RD
YE
BK10
RD208
OR240
RD208
OR240
BL
YE
BK
BL
YE
BK
WH16
YE28
YE23
WH16
BK34
BL19
Control 1
BR42
BR43
BK41
BK40
BK30
BK29
WH66
BL50
BK51
COF
LT
LT HP HP
BK24
BK25
RV
RV
V
R
C
Red
3
1
2
4
Red
Red
Red
3
1
2
4
Control 2
BR52
BR53
COF
LT
LT
BK20
RV
RV
V
R
C
HP HP
BK19
WH56
PK21
YE23
WH64
RD22
WH55
BK59
RD59
BR53
BK51
BL50
BK29
PK89
BR87
RD88
WH46
PK26
YE28
WH65
RD27
WH45
BK49
RD48
WH15
BL17
BK33
GND
Breaker 3A (optional)
Field
Line
Voltage
WH15
YE3
BK10
RD2
BK1
BK34
BK33
YE3
YE8
YE9
RD7
RD2
RD6
BK4
BK1
BK5
BK
YE
RD
BL
BL
RD27
RD22
Figure 13. Typical Mark IV/AC unit — dual compressor
IM 439 / Page 11 of 24
Figure 14. Typical MicroTech unit — single compressor
GR/Y E
LEGEND
Component Wire Connector
Heater Crankcase Heater
R1 & R2 Relay
T1 & T2 Transformer
Thermistor
Optional Wiring
LP1 Low pressure Switch
HP1 High Pressure Switch
LT1 Low Temperature Switch
RV Reversing Valve Solenoid M2 Compressor Contactor M1 Fan Starter
V1 Expansion Valve
TB Terminal Block Connection
Fan Mtr.
22 23
24
T1
Compr.
T2
Mtr.
T3
1
Heater
( Ext. Rng. Only)
Circuit
Breaker
T1 T2 T3
16
17 18
(optional)
Gnd.
Lug
PB 1
T1
L2L1 L3
T2 T3
123
M 1
L1 L2 L3
T1 T2 T3
BL
9190
1 2
3
L1 L2
7
7 8
12
9 13 BK
BK/RD 460V
OR 230V RD 208V
BK 575V VT 400V
24V
>>
WH
92
BK
T1 (50VA)
YE
V1
93
M 2
L3
12
13
>>
WH
Page 12 of 24 / IM 439
Condensate
Overflow
32
76
3
LT1
2
> >
> >
32
30
31
J4
Condensate
Lo Temp. SRC
MicroTech
Controller
34
LP1
34
33
Lo Press SIG
Lo Press SRC
Low Temp. SIG
RV
35
37
36
RV Com
Hi Press SRC
M2
59
BR
BR
38
39
RV Out
Comp Com
C
C
C1
M1
> >
C2
41
HP1
42
> >
43
40
234567891011121314 6
1
J5
24VAC
Fan Out
24V Gnd
Fan Com
Comp Out
Spare Relay NO
Spare Relay Com
Spare Relay NC
Remote D1 SRC
Remote D1 SIG
1
Tenant Override
RM Sensor LED
64
63
62
1234567 Terminal Board #1
Air
Water
Disch.
53
55
54
56
Water Out Com
Discharge Air In
Discharge Air Com
Lon Talk
Lon Talk
RM Sensor Com
RM Sensor In
111098765432
65
66
67
68
52
44
45
46
Out
Water Out In
Aux Module DC +
Aux Module DC Com
24VAC Com
12
J2J1
47
Aux Module SEL 1
Aux Module SEL 2
69 70 71 72
73
48
49
50
23457891011
1
J6
Aux Module CLK
Aux Module RCV
Aux Module XMT
51
J2
1 2
1 2 3 4 5
(Optional)
6
Auxiliary Module
7
J1
E L U P C
Terminal Board #2
Figure 15. Typical MicroTech unit — dual compressor
GR/Y
E
LEGEND
Component Wire Connector
Heater Crankcase Heater
V1 & V2 Expansion Valve
R1, R2 & R3 Relay
M2 & M3 Compressor Contactor
T1 & T2 Transformer RV1 & RV2 Reversing Valve Solenoid LP1 & LP2 Low pressure Switch HP1 & HP2 High Pressure Switch
LT1 & LT2 Low Temperature Switch
M1 Fan Starter
TB Terminal Block Connection
Thermistor
Optional Wiring
Condensate
Overflow
32
76
LT1
>>
>>
30
31
J4
34
LP1
35
32
34
33
BK
Fan Mtr.
Compr.
Compr.
M2
59
RV1
BR
HP1
BR
37
36
38
39
78910 561
T1
RD
T2
YE
T3
T1
T2
Mtr.
T3
1
Heater
(Ext. Rng. Only)
T1
T2
Mtr.
T3
2
Heater
(Ext. Rng. Only)
Circuit
(optional)
Breaker
90
44
C
C
C2
M1
>>
4
41
42
>>
43
40
234
L2 L3
L1
PB1
M1
L1 L2 L3
M2 16 17
18
19
20 21
77
L1
T1
L2
T2
L3
T3
12
13
M3
T1
L1
T2
L2
T3
L3
14
15
BL
CKT1
>>
91
CKT 2
94
3
LT2
2
78
81
1234 1234
T1 T2 T3
123
1 2 3
7 8
12
9
13
4
4 5
14
6
15
BK
BK/RD 460V
OR 230V RD 208V BK 575V VT 400V
>>
WH
WH
WH
>>>>
81
LP2
RV2
79
82
80
83
4321 4321
V2
J8
Auxiliary
Module
234 567
21
1
J2 J1
44
56
J5 J6
45
Air
Disch
55
46
47
48
Out
Water
53
54
49
50
51
BK
T1 (50VA)
YE 93
V1
9695
45
60
BR
C
M3
C
HP2
BR
84
85
J10J11J4
52
123456789101111121314
Gnd Lug
>>>>
Condensate
Lo Temp SIG
Lo Press SIG
Lo Temp SRC
Lo Press SRC
MicroTech Controller
RV Out
RV Com
Hi Press SIG
24VAC
Fan Out
24V Gnd
Fan Com
Comp Out
Comp Com
Spare Relay NO
Remote D1 SIG
Remote D1 SRC
12345 6789101112
J1 J2
RM Sensor LED
Spare Relay NC
Spare Relay Com
63
62
12345678
Terminal Board #1
Discharge Air Com
Discharge Air Water
Tenant Override
Lon Talk
RM Sensor In
RM Sensor Com
65
66
64
67
Water Out In
Water Out Com
Aux Module DC Com
24VAC Com
Lon Talk
68
9
Aux Module CLK
Aux Module RCV
Aux Module DC +
Aux Module SEL 2
Aux Module SEL 1
69 70 71 72 73
Aux Module XMT
E L U P C
Terminal Board #2
IM 439 / Page 13 of 24
Unit Operation
General
Each unit has a printed circuit board control system. The low voltage output from the low voltage terminal strip on the control board is always 24 volts DC (direct current). Terminals C and R on the low voltage terminal strip supply 24 volts AC power. The unit has been designed for operation with a 24 volt mercury bulb type wall thermostat or a microelectronic wall thermostat selected by the manufacturer. Do not operate the unit with any other type of wall thermostat.
Mark IV/AC Control Units
Single compressor units have a single Mark IV/AC circuit board and dual compressor units have two Mark IV/AC circuit boards. The refrigerant circuits on dual compressor units operate totally independent from each other and allow for total independent operation of each circuit.
The Mark IV/AC circuit board has built-in features such as random start, compressor time delay, night setback, load shed, shutdown, condensate overflow protection, defrost cycle, brownout, and LED/fault outputs.
The 24 volt low voltage terminal strip on each board is set up so R-G energizes the fan, R-Y1 energizes the compressor for cooling operation, R-W1 energizes the compressor and reversing valve for heating operation. The reversing valve is set up to be energized in the heating mode. The circuit board has a fan interlock circuit to energize the fan whenever the compressor is on if the thermostat logic fails to do so.
The Mark IV/AC control board has a lockout circuit to stop compressor operation if any one of its safety switches opens (high pressure switch and low pressure switch). If the low temperature switch opens, the unit will go into the cooling mode for 60 seconds to defrost any slush in the water-to­refrigerant heat exchanger. After 60 seconds the compressor is locked out. If the condensate sensor detects a filled drain pan, the compressor operation will be suspended only in the cooling mode. The unit is reset by opening and closing the disconnect switch on the main power supply to the unit in the event the unit compressor operation has been suspended due to low temperature (freezestat) switch, high pressure switch or low pressure switch. The unit does not have to be reset on a condensate overflow detection.
The Mark IV/AC control board has a fault output signal to an LED on a wall thermostat. Table 3 shows for which functions the fault output is “on” (sending a signal to the LED).
units; day heating and cooling operation is locked out. R-W2 energizes the compressor and reversing valve for heating operation. Night setback operation can be overridden for two hours by toggling the fan switch (intermittently closing the R to O terminals) on the Deluxe Auto Changeover thermostat. Day thermostat setpoints then control the heating and cool­ing operation. The Mark IV/AC control system is also set up for load shed and shutdown operation on receipt of a “grounded” signal to the “L” and “E” terminals, respectively, on the low voltage terminal strip (see Figure 16).
Figure 16.
Unit
1
To activate the unoccupied mode for units on the same clock schedule, a single wire can be “daisy chained” between units and simply grounded through the timeclock contacts. The same system can also be done to activate the load shed and emergency shutdown modes by running additional wires between units to ground.
Unit
2
Time
Clock
Unit
3
Ground
To
Additional
Units
The P and C terminals of the Mark IV/AC board are used for pump restart. These terminals pass a voltage signal whenever the unit’s compressor is turned on. This signal is detected by a Pump Restar t Relay board (P/N 898-613703X01) providing a N.O. or N.C. set of contacts for heat pump loop circulation pump control. When used with the Loop Water Controller, the relay operation accommodates turning off circulation pumps during unoccupied periods with a safety override dependent on, at minimum, one WSHPs need. The P and C terminals may be “daisy chained” between 200 units
(see page 18).
Table 3.
INDICATION
Normal Mode Off On Off Off High Pressure Fault Off Off Flash On Low Temperature Fault* Flash Off Off On Condensate Overflow On Dim Off On Brown-out Off Flash Off On Load Shed Off Off On Off Unoccupied Mode On On Off Off Unit Shutdown Off Flash Off On
*In heating mode only.
Yellow Green Red
LEDs
The Mark IV/AC control board has built-in night setback operation. A “grounded” signal to the “U” terminal on the low voltage terminal strip puts the unit into the unoccupied mode for night setback operation. The fan shuts off and the unit is put under control from the night setback terminal on the thermo­stat, W2 on single compressor and W3 on dual compressor
Page 14 of 24 / IM 439
FAULT
OUTPUT
Mark IV/AC Sequence of Operation
14-Position Terminal Strip
Pin Designation Description
1CTransformer ground (Ovac) 2RTransformer supply (24vac) 3V-DC power connection 4PPump request output 5A Alarm fault output 6UUnoccupied input 7LLoad shed input 8ERemote shutdown input
9F+DC power connection 10 Y1 Occupied cooling mode input 11 W1 Occupied heating mode input 12 G Fan only input 13 W2 Unoccupied heating mode input 14 O Tenant override input
LED Status and Fault Output Status
Board Status LED’s Fault Output
Mode Yellow Green Red Terminal A
Occupied Off On Off Energized Unoccupied On On Off Energized Load Shed Off Off On Energized Condensate Overflow On Dim Off De-Energized High/Low Pressure Fault Off Off Flash De-Energized Low T emperature Fault* Flash Off Off De-Energized Brownout Off Flash Off De-Energized Emergency Shutdown Off Flash Off De-Energized
*in heating mode only
Note: The fault output is energized when no faults exist. The fault output is
de-energized during faults and when unit power is off.
Remote Reset of Manual Lockouts – The Remote Reset feature provides the means to remotely reset automatic lockouts generated by high-pressure and/or low-temperature (in heating) faults. When the Mark IV board is in automatic lockout due to one of these faults, and the cause of the fault condition has been alleviated, energizing the O-terminal for 10 seconds or more will force the Mark IV board to clear the lockout. A unit power cycle can also be used to clear an automatic lockout if the conditions causing the fault have been allevi­ated.
Fault Retry To Minimize Nuisance Trips – The Fault Retry feature
helps to minimize nuisance trips of automatic lockouts caused by high-pressure and/or low-temperature (in heating) faults. This feature clears faults the first two times they occur within a 24-hour period and triggers an automatic lockout on the 3rd fault. The retry count is reset to zero every 24 hours.
General Use and Information
The Mark IV/AC control board is provided with three drive terminals, R(24vac), F(24vdc), and C(Ovac) that can be used by the end user to drive the thermostat inputs (G, Y1, W1, and W2) and control inputs (U, L, E, and O). Any combination of a single board drive terminal (R, F, or C) may be used to operate the Mark IV/AC boards control or thermostat inputs. However, only one drive terminal (R, F, or C) can be connected to any individual input terminal or damage will occur. Some of the control inputs are used within the Water Source Heat Pump and not accessible to the end user. For example, HP, LT, and COF are not available for use by the end user.
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Flash Yellow L ED
Turn On Red LED
Read Outputs
Check Timers
Hi
Pres. Sw ?
No
Brown Out ?
No
Low Temp Sw ?
No
Lo Shed ?
No
N S B ?
Cond. Overflow?
No
R - W 1 ?
No
R -Y 1 ?
No
Stop Comp.
Flash Red LED
Stop Comp.
Stop Fan
Flash Green LED
Stop Comp.
Htg Mode?
Yes
Stop Comp.
No
No
Typically the Mark IV/AC board’s R(24vac) terminal is used to drive the board’s thermostat inputs and control inputs by connecting it to the R terminal of an industry standard thermostat. The control out­puts of the standard thermostat are then connected to the Mark IV/ AC board thermostat inputs and control inputs as needed. Any re­maining board input(s) may be operated by additional thermostat out­puts or remote relays (dry contacts only).
All Mark IV/AC board inputs must be operated by dry contacts pow­ered by the control board’s power terminals. No solid state devices (Triacs) may be used to operate Mark IV/AC board inputs. No outside power sources may be used to operate Mark IV/AC board inputs.
Using Drive Using Drive Using Drive
Terminal R (24vac) Terminal F (vd c) Terminal C (ground)
De-energized Energized De-energized Energized De-energized Energized
Place the Meters
Red (+) Lead on
Input to be
checked
U, L, E, Y1, W1,
G, W2, O 14vac 26vac
Place the Meters Place the Meters Place the Meters
on Black (-) Lead Black (-) Lead Black (-) Lead
on C on V on R
10 to 22 to
0vdc
30 to 10 to 22 to
33vdc
14vac 26vac
R - W 2 ?
Start Comp.
Cooling Mode
Turn On Yellow LED
Stop Comp.
Reversing Valve On
Time Delay
Start Comp.
Start Comp.
No
Yes
No
IM 439 / Page 15 of 24
Thermostat Connection Diagrams
Mark IV/AC Units – Unit Sizes 070 to 121
7-Day Programmable Electronic Thermostat (P/N 107095901)
WSHP Mark IV/AC Board Low Voltage Terminal Strip (Circuit1)
OW2GW1Y1 F E L U A P V R C
Thermostat Terminals
RCW1Y1 W2 Y2 G
Non-Programmable Electronic Thermostat (P/N 668054201)
WSHP Mark IV/AC Board Low Voltage Terminal Strip (Circuit1)
OW2GW1Y1 F E L U A P V R C
Includes Thermostat and Wall Plate.
Refer to the installation, operation & application guide (LIA217) for thermostat 107095901 installation details
Thermostat Terminals
RCW1Y1 W2 Y2 G
Includes Thermostat and Wall Plate.
Refer to the installation, operation & application guide (LIA204-4) for thermostat 668054201 installation details
Page 16 of 24 / IM 439
Mark IV/AC Units – Unit Sizes 180 to 290
7-Day Programmable Electronic Thermostat – 2 Circuits (P/N 107095901)
WSHP Mark IV/AC Board Low Voltage Terminal Strip (Circuit 1)
OW2GW1Y1 F E L U A P V R C
Thermostat Terminals
RCW1Y1 W2 Y2 G
WSHP Mark IV/AC Board Low Voltage Terminal Strip (Circuit 2)
OW2GW1Y1 F E L U A P V R C
Includes Thermostat and Wall Plate.
Refer to the installation, operation & application guide (LIA217) for thermostat 107095901 installation details
Non-Programmable Electronic Thermostat – 2 Circuits (P/N 107095901)
WSHP Mark IV/AC Board Low Voltage Terminal Strip (Circuit 1)
OW2GW1Y1 F E L U A P V R C
WSHP Mark IV/AC Board Low Voltage Terminal Strip (Circuit 2)
OW2GW1Y1 F E L U A P V R C
Thermostat Terminals
RCW1Y1 W2 Y2 G
Optional Remote Sensor (P/N 667720401)
1. Remove cover from remote sensor housing.
2. Select an appropriate location for mounting the remote sensor.
3. Mount remote sensor unit using hardware provided.
4. Install two strand shielded wire between remote sensor and thermostat. Shielded wire must be used.
Do not run remote sensor wire in conduit with other wires.
•Wire 1 should run between the S1 terminal on the thermostat and the S1 terminal on the remote sensor
•Wire 2 should run between the S2 terminal on the thermostat and the S2 terminal on the remote sensor
• Connect the shielding of the wire to the S2 terminal on the thermostat
5. Disable the main sensor (R12) on the thermostat by cutting it from the circuit board.
Cut R12 from
circuit board
Includes Thermostat and Wall Plate.
Refer to the installation, operation & application guide (LIA204-4) for thermostat 668054201 installation details
Thermostat
S1
S2
Wire 2
Wire 1
Remote Sensor
S2
S1
IM 439 / Page 17 of 24
Miscellaneous Options on Mark IV Units
Pump Restart Relay Kit P/N 061419001
Used as an option with the Mark IV/AC board, the pump restart relay kit provides a means to alert the loop water controller that water flow is required by a WSHP so that the system pump can be started. This option is typically used in installations where the pump may be shut off when there is no need for water flow (i.e. temperature OK, etc.). Typically only one pump restart relay kit is required per installation as up to 200 Mark IV/AC boards can be “daisy-chained” to­gether.
The Mark IV/AC “P” terminal is used to determine WSHP compressor operation. Wired as shown below, when com­pressor operation is required, the Mark IV/AC “P” terminal
will change state causing a contact closure between terminal 58 and 64 signaling the loop water control (LWC) panel to restart the loop pump if Off.
The pump restart relay kit is typically mounted within one WSHP or within the LWC panel, whichever is more conve­nient, diagrams are provided below for each location. To install the relay, remove the cover on the double-faced tape provided on the relay and attach the relay either to the inside of the LWC panel (adjacent to circuit breaker CB1 and terminal block TB3) or in the WSHP control box (in a conve­nient location), then wire as shown below.
Wiring Pump Restart Relay when Installed within the LWC Panel
WSHP Mark IV/AC Board Low Voltage Terminal Strip (Circuit 1)
Wiring Pump Restart Relay when Installed within a WSHP Control Box
WSHP Mark IV/AC Board Low Voltage Terminal Strip (Circuit 1)
OW2GW1Y1F E LUAPVRC
Daisy chain to other Mark IV/AC board “P” and “C” terminals
Power by
others
Pump
Restart
Relay
Note: Make all wiring connections to circuit one (1) board when adding this option to a dual circuit machine.
Page 18 of 24 / IM 439
7 6 5 4 3 2 1
Motorized Valve & Relay for Large Vertical Units
Wired as shown below the motorized valve will open on a call for compressor operation. These 1­are power-open power-close. Valve and auxiliary relay are purchased separately.
1
4˝ and 1-1⁄2˝ valves
Note: The wiring shown below can only be used when the “P” terminal is not being used as a pump restart signal to other equipment. If the “P” terminal must be used as a pump restart signal to other equipment, then wire the auxiliary relay’s yellow wire to “Y1”, white wire to “W1”, and orange wire to “C”, then the valve will open on a call for occupied heating or cooling from the thermostat.
11/4" or 11/2" Valve
66" (1676 mm)
Lead Length
Conduit
Anti-Short Bushing
P/N 061201002 - 1-1/4" Valve Kit (070-120) P/N 061201102 - 1-1/2" Valve Kit (180-290) P/N 061201202 - Valve Relay
WSHP Mark IV/AC Board Low Voltage Terminal Strip (Circuit1)
OW2GW1Y1 F E L U A P V R C
Orange
Yellow
White
BL
BK
1
2
3
Auxiliary Relay
GN
Pin, Male
Plug
1 2 3 4 5
Black to 1 Red to 2 White to 3
Yellow to 4
Orange to 5
Time Clock (by others)
Daisy-chain to additional Mark IV/AC board “U” terminals
45231
Valve
RD
OR
COMP Spade
Terminal (On
Circuit 1 Mark
IV/AC Board)
COMMON
Spade Terminal
(On Circuit 1 Mark IV/AC)
OR
Compressor
Contactor (Circuit 1)
RD
Typical Motorized Valve Installation
Return Water Connection
Flexible Hose
Motorized Valve Assembly
Conduit Assembly
To Main System
Shutoff Valve
To Low Voltage
Hole on Unit
Note: Wire motorized valve relay to Circuit one (1) on all dual circuit machines, sizes 180, 215 and 290, as illustrated above.
IM 439 / Page 19 of 24
Boilerless System Kit (BSK)
P/N 062522204 for sizes 070 - 108 and 121 & P/N 0061251501 for sizes 180, 215 and 290
Wire Ends to be Field
Connected to the
Mark IV/AC Board
WSHP Mark IV/AC Board Low Voltage Terminal Strip
OR
GR GR
Orange
Yellow
White
4-pin
Plug
OR
RD WH
BK
Boilerless
System
Board
Normal
OR
WH
Control Box
Boilerless System Kit
RD
43 Ohm
BR
WH
RD
1
2 3
Auxiliary Relay
WH YE
Pot 1
Override
12345
Water
Temperature
Sensor
Signal to remote duct heater control circuit
The BSK field installed kits include the sheet metal enclosure with cover, wire harness, boilerless system board, auxiliary relay, and water temperature sensor. When used, one BSK is required for each unit. To use the BSK kit you attach the sheet metal enclosure to the unit as shown, route the 4-wire harness through knockouts and connect to the Mark IV/AC board, mount and connect and insulate the water tempera­ture sensor on the water supply line, and then connect the duct heater control contacts to the duct heater control circuit.
If night setback (U-terminal) is used, the duct heater will respond to the occupied W1 thermostat signal. The load shed input (L-terminal) cannot be used for other control functions when being used with the BSK.
The BSK is a DC voltage device, when the BSK is used the thermostat must be wired for VDC operation, one example is provided below. This example is for a 2-circuit WSHP, R1 is a field supplied 24vdc relay. R1 is not required on 1-circuit units.
Wire ends
from
Boilerless
System Kit
WSHP Mark IV/AC Board Low
Voltage Terminal Strip
OR
BR RD
43 Ohm
WH
+
R1
Strip
OW2GW1Y1 F E L U A P V R C
The BSK option for use with the Mark IV/AC control board provides the capability to control a remote duct heater. The duct heater must be provided with a low voltage control circuit that only requires a set of dry contacts for operation.
The contacts shown on the Boilerless System board (termi­nals 1, 2, and 3) are used to control the remote duct heater, the N.O. contacts will close on a call for duct heater heat. POT1 provides a means to manually adjust the water tem­perature setpoint (adjustment range is 43
O
F to 60OF). The Normal/Override switch provides a means to manually force electric heat to always be used in place of heat pump heat when in the override position (default position is normal - heat pump heat).
When the water temperature drops below the value of POT1, then the duct heater will be used instead of heat pump heat on a call for heat from the low voltage thermostat (not included).
R1
WSHP Mark IV/AC Board Low
Voltage Terminal Strip
OW2GW1Y1 F E L U A P V R C
Strip
Thermostat Terminals
RCW1Y1 W2 Y2 G
Page 20 / IM 439
Auxilliary Relay (P/N 03005073)
The auxiliary relay is designed to interface external equip­ment with the Mark IV/AC board. The auxiliary relay has been provided with the components necessary to protect from electrical damage that may occur to the Mark IV/AC board when using standard off-the-self relays. The auxiliary relay
WSHP Mark IV/AC Board Low Voltage Terminal Strip
OW2GW1Y1 F E LUAPVRC
1
Operation: In this example the auxiliary relay contacts can be used to indicate a fault condition. With the auxiliary relay connected as shown, the normally open contacts will close during a fault condition.
WSHP Mark IV/AC Board Low Voltage Terminal Strip
can be used to provide fault signals, unit operation signals, or to provide a means for remote equipment to control the Mark IV/AC board. The orange, yellow, and white connec­tions are short flying leads pre-attached to the board. The diagrams shown are some connection examples.
2 3
Auxiliary Relay
Orange
Yellow
White
OW2GW1Y1 F E L U A P V R C
Operation: In this example the auxiliary relay contacts can be used to signal WSHP fan operation to another device. In this example when the thermostat energizes the “G” terminal the auxiliary relay normally open contacts will close.
WSHP Mark IV/AC Board Low Voltage Terminal Strip
OW2GW1Y1 F E L U A P V R C
1
2 3
1
2 3
Orange
Yellow
White
Orange
Yellow
White
Auxiliary Relay
Operation: In this example the auxiliary relay is used to interface other control devices to the Mark IV/AC board. Using the Orange (-) and White (+) wires, and 24vac or 24vdc, another device could be used to start and stop the WSHP heating sequence.
Auxiliary Relay
IM 439 / Page 21
Field Installed Options of MicroTech 2000 Units
MicroTech 2000 units can provide up to 4-outputs, that can be configured for any of the following output control signals:
1) Scheduled Output When using a Network Master Panel (NMP) these outputs can be assigned to one of 32 available schedules. The output will energize when the assigned schedule is occu­pied and de-energize when in unoccupied. These outputs could be used to control lights, etc.
2) Auxiliary Heat (Skin Heat) When using a Loop Water Controller (LWC) the MicroTech 2000 receives loop water temperature information from the LWC and will use the Auxiliary Heat output for heating when loop water temperature is inappropriate for heat pump heating. These outputs provide a signal that can be used to control a remote electric heater. The output will energize on a call for electric heat and de-energize when not required.
3) Fresh Air Damper These outputs provide a signal that can be used to control a remote fresh air damper. The output will energize when the unit fan is energized and de-energize when the unit fan is de-energized.
4) Motorized Water Valve These outputs provide control for a motorized water valve that can be used to stop or divert flow away from the WSHP when compressor operation is not needed. The output will be energized when compressor operation is required.
If more than one of the above control signals is required on a single WSHP, the MicroTech 2000 Auxiliary Module Kit (107239001) must be used and these additional output control signals will be connected to the Auxiliary board. The Auxiliary board is provided in all 2-circuit units. 1-circuit units can provide up to 4-outputs while 2-circuit units only have 3­outputs available. The 4
th
control signal output shown in the
diagrams below is not available on 2-circuit units. If the Auxiliary board is added in the field to provide additional
outputs it will need to be mounted within the WSHP control box so that J1 on the Auxiliary board can be connected to J6 on the MicroTech 2000 board without exceeding a maximum wire length of 10".
Also, each output is by default configured to “none” and must be field set to one of the four signal types listed above using the Monitor software, cable, and a PC communicating to the unit through an MCG panel.
3rd Control Signal Output
Terminals Located on
MicroTech 2000 Auxiliary Board
2nd Control Signal Output
MicroTech 2000 Auxiliary Board
4th Control Signal Output
MicroTech 2000 Auxiliary Board
J7
Use contacts as needed for option
Terminals Located on
J6
Pilot Duty Relay
Use contacts as needed for option
Terminals Located on
J10
Pilot Duty Relay
24VAC
Pilot Duty Relay
(by others)
24VAC
(by others)
24VAC
(by others)
1st Control Signal Output
(Located externally on the WSHP chassis)
IMPORTANT:
To use onboard 24VAC, change the jumper PF1 on the MicroTech 2000 controller from factory default pins 1 and 2 to pins 2 and 3.
Terminal Boards
24VAC
Pilot Duty Relay
(by others)
Page 22 of 24 / IM 439
Use contacts as needed for option
Troubleshooting Water Source Heat Pump
WARNING
!
To avoid electrical shock, personal injury or death, be sure that field wiring complies with local and national fire, safety, and electrical codes, and voltage to the system is within the limits shown in the job-specific drawings and unit electrical data plate(s). Power supply to unit must be disconnected when making field connections. To avoid electrical shock, personal injury or death, be sure to rigorously adhere to field wiring procedures regarding proper lockout and tagout of components.
Low Voltage, check power supply voltage
Check wiring - loose or broken and check for bad connection
Check relays and contacts, also capacitor and wiring
Check high pressure switch and low temperature switch to see if unit is cycling on the safety
Check to see if the reversing valve is not hung up and is operating correctly
Check condensate overflow switch in cool mode of operation
Fuse may be blown, circuit breaker is open
Compressor runs in short cycle
Compressor attempts to start but does not
Wires may be loose or broken. Replace or retighten wires
Neither Fan, nor Compressor Runs
Unit
Insufficient cooling or heating
Fan operates, Compressor does not
Unit Control, check thermostat for correct wiring or bad thermostat
Check capacitor
Check wiring - loose or broken and check for bad connection
Hi pressure lockout ­A. Cool mode, check water flow B. Heating mode, check air flow C. Check reversing valve for proper valve position
Check compressor overload make sure it is closed
Check compressor to ground, or for internal short to ground.
Compressor winding may be open. Check continuity with ohm meter
Check compressor wiring for defective wiring or loose connection
Check for defective compressor internal windings with ohm meter
Check for bad compressor capacitor
Check for lock rotor amp draw
Check thermostat for improper location
Check for proper air flow. Filter could be dirty
Check blower assembly for dirt or bad fan motor capacity
Check for low refrigerant charge
Check amp draw on blower assembly
IM 439 / Page 23 of 24
Maintenance
1. Normal maintenance on all conditioners is generally lim­ited to filter changes and fan motor lubrication. Lubrica­tion of the fan motor should be performed in accordance with the instruction label on the conditioner. Be sure to use non-detergent electric motor oil.
2. Filter changes are required at regular intervals. The time period between changes will depend upon the project requirements. Some applications such as motels produce a lot of lint from carpeting and linen changes, and will require more frequent filter changes. It is suggested that the filter be checked at 60-day intervals for the first year until experience is acquired. If light cannot be seen through the filter when held up to sunlight or a bright light, it should be changed. A more critical standard may be desirable.
3. The condensate drain pan should be checked annually and cleaned and flushed as required.
4. Recording of performance measurements of volts, amps, and water temperature differences (both heating and cooling) is recommended. A comparison of logged data with start-up and other annual data is useful as an indica­tor of general equipment condition.
5. Periodic lockouts almost always are caused by air or water problems. The lockout (shutdown) of the conditioner is a normal protective result. Check for dirt in the water system, water flow rates, water temperatures. If the lockout occurs in the morning following a return from night set­back, entering air below machine limits may be the cause.
Warranty
All McQuay equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local McQuay Representative for warranty details. Refer to Form 933-43285Y. To find your local McQuay Representative, go to www.mcquay.com.
This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.mcquay.com.
Products Manufactured in an ISO Certified Facility.
®
©2006 McQuay International • www.mcquay.com • 800-432-1342 IM 439-15 (6-06)
Loading...