McQuay KZZ Installation Manual

Installation & Maintenance Data IM 254-4
Group: Fan Coil
Part Number: 107133000
Date: June 1999
HiLine Fan-coil Units Type KZZ
Contents
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Riser Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Unit Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3, 4
Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
©1999 McQuay Incorporated
Installation and maintenance are to be performed only by qualified personnel who are familiar with and in compliance with state, local and national codes and regulations, and experienced with this type of equipment.
Caution: Sharp edges and coil surfaces are a potential injury hazards. Avoid contact with them.
Inspection
When the equipment is received, all items must be carefully checked against the bill of lading to be sure all crates and cartons have been received. The units are shipped four to a pallet. Visible or concealed damage should be reported
Riser Installation
(Field Supplied & Installed)
1. It is critical that the coupling stub-outs are properly positioned so that the coil connections will line up when the units are placed in position. See Figure 2. It is recom­mended that a fixture be constructed to maintain dimen­sions shown in Figure 2 during the soldering process.
2. If isolator pads are required, this additional thickness must be considered before installation of risers.
3. Due to expansion or contraction, the unit has provisions for plus or minus one inch vertical movement of risers. If the riser system movement exceeds this value, compen­sating provisions must be provided by the installing con­tractor.
4. Risers must be anchored to the building as there is no provision on the unit to support the weight of the risers.
5. Care must be taken to prevent dirt and other foreign
immediately to the carrier along with the filing of a claim for damage. The electrical nameplate should be checked to be sure it agrees with the power supply available. See Figure 1 below.
matter from entering the risers as clogged lines or valves could result.
6. Close all ball valves on the coupling stub-outs and cement joints to avoid condensation problems.
7. Apply insulation to stub-outs and cement joints to avoid condensation problems.
8. To assure compliance with existing building codes, the installing contractor must restore the original fire resis­tance rating of the structure by sealing the access space around the risers with material having the same fire rating at the structure. This procedure is very important also in assuring that a seal is provided between floors to prevent the passage of warm, humid air which can cause conden­sation on riser insulation. This is most critical in unpres­surized buildings with high infiltration rates.
Figure 1. Uncrating Figure 2. Field riser locations
20" (508 mm) (Cabinet)
11/32" (9 mm) Plaster
1/16"
(2 mm)
Stop
3-1/4"
(83 mm)
(89 mm)
43-1/2"
(1105 mm)
3-1/2"
3-5/8"
(92 mm)
(508 mm)
3-1/2"
(89 mm)
Htg. Supply
2-Pipe
System
20"
Clg. Supply
Htg. Return
3-1/2"
(89 mm)
Clg. Return
3-1/8" (79 mm)
2-3/4" (70 mm)
Page 2
XXX 3/8" (9.5 mm) YYY 3/4" (19 mm)
Floor
Drain
Unit Installation
Riser Blockoffs
Drain Blockoff
Drain Riser
1. The KZZ HiLine fan-coil units have been received with the top plenum and plenum front cover not assembled to the lower cabinet (see Figure 3).
2. Care should be taken when removing the top plenum from the lower cabinet so as not to tear the fiberglass insulation.
3. Remove the plenum front panel from the lower cabinet.
4. The fasteners for assembling the unit, the riser blockoffs, and sight baffle (if required) are located in the base of the lower cabinet. The filter is located above the coil. Re­move these parts from the unit. Remove the valve pack­age supports.
5. For ease of installation, bend out the tabs that support the top plenum to the lower cabinet (see Figure 5).
6. Place the riser blockoffs over the riser stub-outs (see Figure 4).
7. Remove the appropriate riser and drain knockouts in the lower cabinet (see Figure 5).
8. Slit the fiberglass insulation so that the riser valves can be pushed through and into the unit.
9. Position the lower cabinet to the risers. The horizontal stub-outs should be centered in the opening in the cabinet. This is important to allow for riser expansion and contraction of plus or minus one inch.
10. Solder connections if sweat valves have been supplied.
11. Attach plastic drain hose to drain line. Be sure hose clamp is properly installed.
12. With the unit in the final location, check level to insure proper condensate drainage and operation.
13. Fasten the top panel of the plenum by installing the three sheet metal screws “A” (see Figure 6).
14. Install the sight baffle (if required) to the top as shown in Figure 6.
15. Place the top plenum on the lower cabinet (see Figure 6). The top plenum can be installed so that the discharge opening is facing to the left, the right, or to the front. Knockouts are provided for additional discharge ar­rangements. If plenum is to be rotated to the left or right, the thermostat box can be moved to an alternate loca­tion by removing the optional cover plate. When the thermostat is moved to the alternate location the cover plate must be insulated and reinstalled in the previous location. Determine the correct discharge before install­ing the plenum to the lower cabinet.
Although the plenum may be rotated 90° in either
direction, the thermostat box and heat baffle must always be located above the return air grille on units with electric heat.
16. Fasten the top plenum to the lower cabinet with sheet metal screws (see Figure 6).
17. Before fastening the plenum front panel to the plenum wrap, snap the nylon electrical receptacle into the square hole into the back of the thermostat box (see Figure 7).
18. Attach the plenum front panel to the plenum wrap with sheet metal screws enclosed.
19. The thermostat box has been installed in the plenum front panel in the position that will allow plasterboard to be attached directly to the unit. If the installation requires that the wall be furred out away from the unit, the box can be adjusted out 3
7
8" (98 mm) by removing the four screws “A” (see Figure 8) and pulling the box out. Align with holes “C”. Replace screws “A”. If a dimension other than the 3
7
8" (98 mm) or 3⁄8" (10 mm) is required, this can be accomplished by using the angle bracket as a tem­plate and drilling .149" (4 mm) diameter holes in the box at the desired depth.
20. When the plasterboard or other wall material does not fit flat against the face of the unit, extension sleeves must
Figure 3. Unit preparation for field assembly Figure 4. Riser blockoff placement
Lower Cabinet
Serial Plate
Top Front Panel
Top Plenum
Page 3
Loading...
+ 5 hidden pages