The installation of this equipment shall be in accordance with the
regulations of authorities having jurisdiction and all applicable
codes. It is the responsibility of the installer to determine and
follow the applicable codes. Sheet metal parts, self-tapping
screws, clips and such items inherently have sharp edges, and it
is necessary that the installer exercise caution. This equipment
is to be installed only by an experienced installation company
which employs trained personnel.
Inspection
When the equipment is received, all items should be carefully
checked against the bill of lading to be sure all crates and cartons
have been received. All units should be carefully inspected
for damage when received. If any damage is noticed, the
carrier should make the proper notation on the delivery receipt
acknowledging the damage.
The carrier should also ll out a Carrier Inspection Report.
The McQuay International Trafc Department should then be
contacted.
The unit nameplate should be checked to make sure the voltage
agrees with the power supply available.
The Type K Series Comfort Conditioner is designed and built
for through-the-wall installation in either new or existing
buildings. The self-contained refrigerant system delivers cooling
to the desired space. Heating can be accomplished with electric
resistance or hydronic heat. Each conditioner consists of the
following components:
● Cooling Chassis ● Room Cabinet
● Heat Section ● Wall Box
● Control ● Louver
Figure 1: Type K Unit Components
IM 1068 / Page 2 of 32
Model Nomenclature
P KES 2 007 C Z 41 Z 12 AR 14 A I C 1
Model
Product Category
P = PTAC
Product Style
1= 1st Style Change
Product Identier
KES = Type K, Cool Chassis Only
KEI = Type K Cool Chassis Only, IAQ
KEC = Type K Cool Chassis Only,
Corrosion Protection
KHS = Type K Heat Section Only
Design Series
1 = A design
2 = B design
Nominal Capacity - Btuh
007 = 7000
009 = 9000
012 = 12000
019 = 19000
Voltage
A = 115-60-1
C = 208-60-1
G = 230-60-1
J = 277/265-60-1
S = 208-115-60-1
R = 265-115-60-1
SKU
A = Stock
B = Standard Delivery
C = Extended Lead time
Color
I = Antique Ivory
Power Connection
A = Junction Box
Return Air/Outdoor Air
14 = Bottom
Discharge
AR = Flat Top
Controls
12 = Unit Mounted Manual Change Over (MCO)
24 = Unit Mounted Manual Change Over
w/Night Set Back (NSB)
27 = 24V Wall T'stat w/Guest Room Control
(GRC) & Night Set Back (NSB)
32 = 24V Wall T'stat w/Night Set back(NSB)
Hand Orientation
A = Same Hand Left
B = Same Hand Right
N = LH Supply / RH Return
P = RH Supply / LH Return
Z = Not Applicable
Note: Availability of voltages, heating options, and controls may vary amongst unit sizes. Consult your McQuay
representative.
IM 1068 / Page 3 of 32
Wall Opening Requirements
Before installing the unit, check the wall opening to be sure
the wall sleeve will slide in unobstructed. The rough opening
should measure 25'' x 36½'' (635mm x 927mm) indoors and
14½" x 36½" (368mm x 927mm) outdoors for sizes 007–012
and 27¾''x 46¾'' (705mm x 1187mm) indoors and 16⅜" x 46¾"
outdoors (415mm x 1187mm) outdoors for sizes 019 as shown
below. The wall box is designed to be mounted on the oor
but may be located above the oor line to clear obstructions.
Without cabinet modications, the wall box can be placed up to
1'' (25mm) above the oor. The standard adjustable kickplate can
be telescoped to hide the space below the wall box. Complete
wall box installation instructions can found on page 5.
Figure 2: Unit and Wall Box Opening Dimensions
CAUTION
!
Sheet metal parts, self-tapping screws, clips and such items
inherently have sharp edges, and it is necessary that the
installer exercise caution. This equipment is to be installed
only by an experienced installation company which employs
trained personnel.
E
D
LC
A
H
J
K
B
M
F
G
Table 1: Unit Dimension
Dimensions – Inches
Unit Size A B C D E F G H J K L M N P R
007–012 48 2½ Min. 7¼ Min. 36¼ 5¾ 24½ 13019 602½Min.8½Min.46¼6⅞27⅜ 15⅞244-6Adj.39¼5/859½27¾ 46¾
Dimensions – mm
Unit Size A B C D E F G H J K L M N P R
007–012 1219 64 Min. 184 Min. 921 146 648 348 533 89-140 Adj. 44 203 25 1162 635 927019 1524 64 Min. 216 Min. 1175 175 695 403 610 102-152 Adj. 76 235 16 1151 705 1187
11
⁄16 21 31⁄2-5½ Adj. 1¾ 8 1 45¾ 25 36½
IM 1068 / Page 4 of 32
Wall Box Installation
The wall thickness will determine how much, if any, of the
wall box will protrude into the room. Figure 3 shows a typical
installation in a frame and brick wall. These instructions will
vary by depth of wall, but not by wall material. Do not
remove the weather panel at any time during the installation
of the wall box. Premature removal of this panel could
result in improper leveling or sealing. Install the wall box as
follows:
5. Place 2'' (51mm) berglass batt or 1" (25mm) Styrofoam
insulation around the top and sides of the wall box.
6. Locate the wall box in the wall opening with the weather
panel to the outside. Use the top edge of the wall box for
horizontal leveling. The wall box must also be vertically
plumb. Shim the wall box to accomplish this. Recess so
louver is ush with outside wall.
7. Drill four (4) holes in the sides of the wall box and attach
it to the walls securely using appropriate fasteners.
1. If the wall opening has not been made, cut and break
through using care to leave interior and exterior surfaces
undamaged. See wall opening requirements on page 4 for
proper size.
2. Install lintels as shown on the plans and specications.
3. If the wall opening has already been made, measure it to
be certain it has adequate clearance for the wall box. Be
sure to allow extra clearance for insulation around the
wall box to reduce sound and heat transfer. Continue with
step #4.
4. Apply a layer of mortar or roong cement to the bottom
surface of the opening (see Figure 3).
Table 2: Wall Box Dimensions
Dimension “A”
007–012 019
in. mm in. mm in. mm
0 to -1 0 to -25 8
0 to +1 0 to +25 9
1 to 2 25 to 51 10
2 to 3 51 to 76 11
3 to 4 76 to 102 12
4 to 5 102 to 127 13
5 to 6 127 to 152 14
6 to 7 152 to 178 15
7 to 8 178 to 203 16
8 to 9 203 to 229 17
Dimension “C” – Cabinet Depth
1
⁄4 210 — —
1
⁄4 235 81⁄2 216
1
⁄4 260 91⁄2 241
1
⁄4 286 101⁄2 267
1
⁄4 311 111⁄2 292
1
⁄4 327 121⁄2 318
1
⁄4 362 131⁄2 343
1
⁄4 387 141⁄2 368
1
⁄4 413 151⁄2 394
1
⁄4 438 161⁄2 419
Note: Never drill through bottom of wall box.
8. If face brick is being installed, continue coursing up the
wall until the wall box is completely surrounded and
becomes an integral part of the wall.
9. Caulk interior and exterior perimeter weather tight where
the box meets the wall. Use a non hardening, waterproof
caulk such as silicone.
Note: For rooms with thick carpet, wall box should be
installed 1/2'' (13mm) above concrete oor to facilitate
future chassis installation and removal.
Figure 3: Wall Box End View (Drawing Not To Scale)
NOTICE
Dimension “B” will vary by the thickness of the wall, the louver, the amount
the louver is recessed into the wall (if any) and the amount the wall box extends
into the room. The minimum “B” dimension is 21⁄2'' (64mm). The wall box can
be factory furnished in increments between 21⁄2'' (64mm) and 10'' (254mm).
Wall box extensions in 1'' (25mm) increments can also be provided to attach
to the rear of the wall box.
1. Remove the louver from the shipping carton which also
contains the mounting hardware.
2. Remove the weather panel from the wall sleeve to gain
access to the outside of the wall box. Verify that gap
between exterior wall and wall box is caulked.
3. If an optional louver frame is required, install prior to
louver installation. Caulk that portion of the frame which
will come in contact with the wall. Pass the louver frame
through the wall box opening and from the outside of
the building, slide over the end of the wall box. Position
as desired, then drill holes through the top and sides of
the overlapping wall box and louver frame. Secure to the
wall with screws. Caulk wall box/louver frame joint on
all four sides. Provide additional caulking around outside
wall and louver frame to ensure a weather tight seal.
4. Make a temporary handle by looping a piece of exible
wire or heavy cord through the louver. This will insure
that a rm grasp can be maintained during installation.
5. From a position inside the room, push the louver through
the opening at the rear of the wall box. Line it up with the
wall box and pull it back so the louver studs pass through
the holes of the wall box ange (see Figure 4).
6. Attach the washers and nuts to secure the louver in place.
7. If heat section and cool chassis are not to be immediately
installed, replace the weather panel.
Figure 4: Louver Installation
Heat Section Installation (Sizes 007-012)
The Type K heat section is matched to the Type K cooling
chassis but packaged and shipped separately. Check the
heat section carton label and the unit’s nameplate to ensure
it is correct for the cooling chassis and the space.
The following steps should be followed when installing the
heat section:
1. Remove the heater from the shipping carton and examine
for concealed damage. Report any damage found to the
carrier. The control is packaged with the heat section
in a separate carton. Remove this carton from the heat
section and set it aside until after the heat section is
installed.
2. Manually spin the blowers to make sure there is no
interference. Minor misalignment may have occurred
during shipping and should be corrected. If it can’t be
corrected with minor adjustment, the condition should be
reported to the factory. Do not lubricate room side motor
at this time. Each unit is adequately lubricated before
leaving the factory.
3. Observe the method of installation. The heat section has
side channels that ride on rails in the wall box. At the
back of the wall box towards the top are two hooks
that engage the heat section. Locate these hooks before
sliding the heat section in place. “U”-shaped clips are
included that lock the heat section in place once installed.
“U”-clips can usually be found taped to the wall box
interior.
4. Remove the weather panel from the wall box. If the
louver has not been installed, install it before placing the
heat section into the wall box.
Figure 5: Heat Section Installation
5. Slide the heat section into place so that the holes of the
heat section surround the hooks of the wall box. Lock it
to the wall box using the “U”-shaped clips provided (see
Figure 5). The “U”-shaped clips should be positioned
with the open end pointing down.
IM 1068 / Page 6 of 32
6. The piping for steam or hot water can be supplied from
either the right or left side of the coil. Hot water must be
supplied to the bottom of the coil, and steam to the top of
the coil. See Detail A through H for specics. To simplify
connections to the coil, use 5/8'' O.D. copper tubing
where local codes allow.
7. A shutoff valve is recommended on the supply and return
side of the coil.
8. When steam is used, a trap is required on the return side.
Trap size should be determined by the consulting
engineer or steam trap supplier, depending upon the type
of system and the pressure applied.
When hot water is used, an air vent must be installed
at the highest point in the piping connection. If the vent is
not automatic, it should be piped with easy access for
regular maintenance. Caution: Locate vent so it does
not drip or spray on electrical components.
9. Insulate all exposed water or steam lines that are located
within the room cabinet. Failure to do this may cause
erratic operation of the thermostat.
10. Protect the heat section from damage during
construction. Do not operate the heat section without a
lter or the warranty will be void.
Figure 6: Suggested Piping Arrangements
in.
mm 489 552 540 267 597 514
S T U V W Y
191⁄
213⁄4 211⁄4 101⁄2 231⁄2 201⁄
4
4
Hot Water Supply Steam Supply
Detail A — Hot water supply R.H., return L.H. Detail B — Steam supply R.H., return L.H.
C
L
W
S
T
Return Stub
V
25/8"
(67mm)
2"
(51mm)
Y
C
L
S
T
Return Stub
V
(51mm)
Detail C — Hot water supply R.H., return R.H. Detail D — Steam supply R.H., return R.H.
C
L
U
T
Return
Stub
W
V
1"
(25mm)
C
L
2"
(51mm)
C
L
U
T
Return Stub
Y
V
(51mm)
2"
2"
C
L
C
L
(25mm)
25/8"
(67mm)
1"
Detail E — Hot water supply L.H., return R.H. Detail F — Steam supply L.H., return R.H.
C
L
2"
(51mm)
Return Stub
25/8"
(67mm)
V
Detail G — Hot water supply L.H., return L.H. Detail H — Steam supply L.H., return L.H.
C
2" (51mm)
L
1" (25mm)
Return Stub
W
V
C
1"
(25mm)
L
(51mm)
C
L
Return Stub
2"
2"
(51mm)
Return Stub
Y
C
L
V
S
S
V
U
U
C
L
IM 1068 / Page 7 of 32
Y
25/8"
C
L
W
S
S
U
U
C
L
(67mm)
Heat Section Installation (Size 019)
Figure 7 shows the heat section installed in a standard wall
box. Note that the heat section slides into a wall box on the
slide rails. For heat section installation, proceed as follows:
1. Remove heat section from shipping carton.
2. Visually check for shipping damage and report any
visible damage immediately to the trucker. Spin blower
wheels by hand to assure they do not rub within their
housing. Shipping may have loosened mounts. Adjust as
required.
3. Check voltage rating on data plate fastened to heat
section. This must conform to voltage supplied for the
equipment.
4. Locate slide rails on each side of wall box and insert
heater section into the wall box. Slide to the rear until it
is rmly seated.
5. Screw in the heat section lock screws as shown in Figure
7. (Screws are shipped with the heat section.)
Figure 7: Heat Section Installed in Wall Box
WARNING
!
If the heat section is used for heating an area during construction,
Heating Only Option”). Failure to heed this warning can cause
malfunction of the equipment.
Figure 8: Rough-in Piping Connections Locations
Figure 9: Hot Water Coil
Steam or Hot Water Application (Size 019)
When the heat section requires steam or hot water, the
installation varies. See Figures 9 and 10 for suggested piping
arrangements.
1. Supply and return piping for steam or hot water is
supplied from right-hand side only. Hot water must be
supplied to the bottom of the coil, and steam to the top of
the coil.
2. To simplify the steam or hot water connections to the
coil, use 5/8'' O.D. copper tubing where local codes
permit. See Figure 8 for rough-in dimensions.
3. When hot water is to be used, an air vent must be put in
at the highest point in the piping connection. See Figure
9. If the air vent used is not of the automatic type, it
should be piped so that it may be easily opened.
4. A shutoff valve is recommended on the supply and return
side of the coil. A steam trap is required on the return
side when steam is used for heating. See Figure 10.
5. All steam or hot water lines which are located within the
room cabinet should be insulated.
IM 1068 / Page 8 of 32
Figure 10: Steam Coil
Cooling Chassis Installation
1. Remove the cooling chassis from the shipping carton and
examine it for damage. Do not rest it on end. Check the
plate rating against the power supply to make sure that
they are the same (Figure 11). Also check the size
(capacity) to make sure that it coincides with the heat
section; e.g., Size 009 cooling.
2. The cooling chassis is supplied with an internal spring
mounted compressor. The hold-down nuts on the
compressor mountings should not be loosened.
3. Manually spin the condenser fan wheel to be sure that
there is no interference or looseness. If it is loose, tighten
the setscrew located over the center of the at on the
motor shaft. Do not lubricate condenser fan motor at time
of installation.
Figure 11: Cooling Chassis Details
4. Slide the chassis into the wall box. Chassis must be
square in the box so that all the rubber seals are pressed
tight. Check bottom seal between chassis and wall box to
ensure that it has not been unseated from slot during
chassis installation.
5. For unit size 019, there is a “J” bolt on each side
that holds the chassis in place. Thread the “J” bolts
through the holes supplied in the chassis and tighten until
the chassis is rmly seated in the wall box.
IM 1068 / Page 9 of 32
Electric Power Wiring
Before making any electrical connections, observe the
following precautions:
1. Check the nameplate rating of the heat section and
cooling chassis to make sure the equipment is connected
to the proper power supply and that proper fusing is used.
a. By installing a remote double-pole switch in the
conditioner’s power line within sight of the unit.
b. By installing a double pole, single throw “on-off”
switch located in a convenient position within the
room cabinet.
After all these precautions are observed, proceed as follows:
2. In cases where a number of conditioners are to be
installed, single circuits should be provided for each
machine.
3. A separate disconnect is recommended for each
conditioner in addition to individual fusing. This can be
accomplished in several ways:
Figure 12: Electric Heat Section (Sizes 007 through 012)
A
H
M
J
E
K
Notes:
Guest room control, low voltage or master-slave wiring connection made at
control box.
4" × 24" (102mm × 51mm) wall space for electrical conduits except behind
junction box.
Junction box with knockouts for 1/2'' (12mm) 3/4'' (19mm) conduit.
See Table 5 for dimension B.
D
Front View
Units With Electric Heat (Sizes 007–012)
A 4" x 4" electrical junction box is located on the left side of
the heat section. Field wiring should be brought to this point
for power to the unit. See Figure 12 & 13.
8"
(203mm)
Long Control
Box
Table 4: Electric Heat Section Dimensions
A D E F G H J K M
in.
mm 1162 940 451 622 348 581 254 233 38
Room Cabinet
B
Room Cabinet
Mounting Holes (4)
1
⁄2''
(12mm)
Wall Box
1
⁄4''
(6mm)
Heat Section
Power Cord
Cooling Chassis
Power Cord
Side View
453⁄4 37 173⁄4 241⁄2 1311⁄16 227⁄8 10 93⁄16 11⁄
G
2
F
Table 5: Wall Box “B” Dimensions
Wall Box Size21⁄2" 31⁄2"
“B” Dimension 007–01264 mm 89 mm 102 mm 127 mm 152 mm 178 mm 203 mm 229 mm 254 mm
IM 1068 / Page 10 of 32
4" 5" 6" 7" 8" 9" 10"
Figure 13: Electric Heat Section (Size 019)
A
H
Control Box
Room Cabinet
Main Power Cord
Heat Chassis
Power Cord
Room
Cabinet
Mounting
Holes (4)
Cool Chassis
Power Cord
D
4" x 4" Junction Box
Front View
(Mounted by Others)
Field Mounted to L.H. Edge of Wall Box
Table 6: Electric Heat Section Dimensions
in.
mm 1511 1175 695 403 749
Notes:
Guest room control, low voltage or master-slave wiring connection made at
See Table 7 for dimension B.
A D F G H
591⁄
461⁄4 273⁄8 157⁄8 291⁄
2
control box.
2
Long
Control Box
Cool
Chassis
Power
Cord
Heat Section
Power Cord
91/4"
(203 mm)
B
F
G
Wall Box
(End View
w/o Cabinet)
Side View
Table 7: Wall Box “B” Dimensions
Wall Box Size 21⁄2" 31⁄2"
“B” Dimension 01964 mm 89 mm 102 mm 127 mm 152 mm 178 mm 203 mm 229 mm 254 mm
4" 5" 6" 7" 8" 9" 10"
IM 1068 / Page 11 of 32
Units With Hydronic Heat (Sizes 007–012)
The hydronic heat section can be supplied with a short (4¼''
high) control box or a long (13½'' high) control box
depending on the number of options selected. Observe the
control box to determine which one was supplied for the job.
Long Control Box
1. If the long control box was provided, make electrical
connections to a eld supplied junction box that should
be fastened to the oor beneath the control
(Figure 15).
Short Control Box
If the short control box was supplied, eld wiring should be
brought into the 2'' x 4'' junction box which is located on the
right-hand side of the heat section (Figure 14.)
2. Locate the long control box. The power wires for the
control extend through the piece of exible conduit that
exits from the bottom of the control. These wires should
be connected to the incoming power at the junction box
installed in Step 1.
Remote Control — For units with remote mounted
thermostat, refer to page 14.
Figure 14: Hydronic Heat Section with Short Control Box (Sizes 007-012)
The short control box is used with standard unit mounted manual changeover control, and unit mounted manual changeover with
emergency standby (ESB) power supply.
A
H
M
J
E
K
L
Hydronic Coil
Short
Control Box
Room
Cabinet
Room Cabinet
Mounting Holes (4)
8"
(203mm)
B
P
N
Wall Box
G
F
1
D
Front View
Junction Box
Room Cabinet Removed
⁄2''
(12mm)
Side View
Table 8: Hydronic Heat Section with Short Control Box Dimensions
in.
mm 1162 940 648 622 348 581 254 406 114 38 375 44
Notes:
See Detail A, B, C, D, E. F, G, or H on page 7 for dimensions of factory installed valve and return piping stub.
Junction box 7/8" (22mm) diameter knockouts for 1/2" (12mm) conduit.
See Table 9 for dimension B.
Wall Box Size21⁄2" 31⁄2"
“B” Dimension 007–01264 mm 89 mm 102 mm 127 mm 152 mm 178 mm 203 mm 229 mm 254 mm
4" 5" 6" 7" 8" 9" 10"
1
⁄4''
(6mm)
IM 1068 / Page 12 of 32
Figure 15: Hydronic Heat Section with Long Control Box (Sizes 007-012)
The long control box is used with optional special controls such as Guest Room Control (GRC), Night Setback (NSB), and remote
thermostats.
Note: Left-hand piping must be used with the long control box design.
A
H
M
E
J
K
L
Hydronic Coil
D
Front View
Cool Chassis
Power Cord
Junction Box (By Others)
Table 10: Hydronic Heat Section with Long Control Box Dimensions
A D E F G H J K L M
453⁄
in.
mm 1162 940 648 622 348 581 254 406 114 38
Notes:
See details G and H on page 7 for dimensions of factory installed valve and return piping stub.
See Table 9 on page 12 for dimension B.
37 251⁄2 241⁄2 1311⁄16 227⁄8 10 16 41⁄2 11⁄
4
2
Long
Control Box
Room
Cabinet
Room Cabinet
Mounting Holes (4)
Heat Chassis
Power Cord
Flexible Conduit
Power Supply Cord
8"
(203mm)
B
Wall Box
1
⁄2''
(12mm)
1
⁄4'' (6mm)
Side View
Room Cabinet Removed
F
G
Unit with Hydronic Heat (size 019)
1. Only one size control box is available for size 019.
Make all electrical connections to a factory supplied
junction box located on the L.H. side of the wall box
(Figure 16).
Figure 16: Units with Hydronic Heat (Size 019)
Control Box
Room Cabinet
Main Power Cord
Heat Chassis
Power Cord
Room
Cabinet
Mounting
Holes (4)
Cool Chassis
Power Cord
Front View
4" x 4" Junction Box
(Mounted by Others)
Field Mounted to L.H. Edge of Wall Box
Notes:
RefertoTable7onpage11for“B”dimension.
Coil Stubs for Field Piping
Long
Control
Box
Cool
Chassis
Power
Cord
Heat Chassis
Power Cord
B
Wall Box
(End View
w/o Cabinet)
Side View
IM 1068 / Page 13 of 32
Room Cabinet and Control Installation
The depth of the room cabinet varies by the amount the wall
box extends into the room. Check the unit tagging against the
room cabinet tagging to be sure they match. Installation of the
control box should be done at the same time as the room
cabinet.
1. Remove the cabinet from the carton and inspect it for
damage. If any is found, contact the carrier immediately.
The room cabinet is made up of six pieces: a cabinet, a
removable front panel, a discharge grille, two (2) end
plates, and a kickplate. Make sure all pieces are included
with the room cabinet (Figure 18).
Remove the front panel by lifting it slightly and pulling
forward, then upwards and out from the surrounding
cabinet. Unit size 019 utilizes safety chains that must be
disconnected from the room cabinet in order to remove
the front panel.
If necessary, remove the tie bar located at the bottom of
the front panel, unlock the latch at each end and lift the
bar out (Figure 17)
Figure 18: Unit Cabinet Assembly Details
4. Fasten the two (2) end plates to the room cabinet using
the wing nuts supplied. These end plates are adjustable
and should be positioned to set at on the nished oor
(Figure 19).
Figure 17: Release Concealed Latch
2. For unit sizes 007–012: Place the cabinet around the installed wall box, heat
section and cool chassis and push the cabinet rmly
against the wall. The discharge grille seals should rest on
the discharge opening of the heat section.
For unit size 019: Position the room cabinet over the heat section so that the
two studs on each side are positioned over the matching
slots in the heat section. Set the cabinet down on the heat
section, push tight against the wall and secure using wing
nuts supplied. See Figure 18.
Figure 19: Unit Cabinet Assembly Details
5. Locate the kick plate and clip it into the slots provided in
the end plates so that the ange is toward the oor.
6. Take the control box and escutcheon plate out of the
carton for attachment to the room cabinet.
7. There are two anges beneath the control door that
support the control box (Figure 20). Remove the two
screws in the control box that hold the escutcheon plate
in place. Remove the thermostat knob and escutcheon
plate.
3. Fasten the cabinet to the wall using appropriate fasteners.
The back anges of the room cabinet have factory
furnished holes for securing the cabinet to the wall.
IM 1068 / Page 14 of 32
Figure 20: Remove the Escutcheon Plate and Control Knob
8. While holding the control box in position, set the
escutcheon plate in place on the anges beneath the
control door.
9. Using the two screws removed in Step 7, secure the
control box and escutcheon plate to the room cabinet.
10. Replace the thermostat control knob.
11. Connect the power cord from the heat section to the
bottom of the control box. Plug in the cord from the
control box to the receptacle in the cooling chassis.
12. Move the thermostat bulb to the cooling chassis and
secure it to the snap clips provided. Inspect the lter to be
sure it is securely in place.
13. Loosen the wing nuts on the nose piece that is attached
to the heat section. Slide the nose piece toward the room
cabinet until it makes contact. Tighten wing nuts to
secure the nose piece in place. This nose piece prevents
air from leaking back into the cabinet and giving the
thermostat a false reading.
14. Before replacing the front panel, replace the tie bar (if it
has been removed) and lock the latches. Then retrieve the
front panel and replace it by sliding it in and downward
into the room cabinet. See gure 21.
Note: Tie bar latches must be in and locked before
installing the front panel.
15. Wipe cabinet with a soft cloth to remove smudges. If
required, use a mild, nonabrasive cleanser.
Figure 21: Unit Cabinet Assembly Details
Equipment Start-up
Initial start-up of the McQuay equipment by an experienced
person is usually the responsibility of the installing contractor.
This consists of inspecting and operating the equipment for
all functions at the time of initial installation, and making
adjustments as necessary. It also includes demonstrating its
proper operation to the owners or their agents.
Note: That unless otherwise specically agreed to
in writing, there is no eld labor or start-up service
included in the price of the equipment.
The Type K unit is furnished with a concealed fan cycle
rocker switch on the control box. Before start-up, open the
front panel and place this switch in the “cycle” position.
Continue start-up procedures as follows:
1. Check the main power supply to be sure there is power to
the unit.
2. Open the control access door and press the button labeled
F-Fan. The indoor fans should be energized.
3. Move the fan speed rocker switch from “Low Fan”
to “High Fan” and back again. The fan speed should
change.
4. Depress the button marked H-Heat. Turn the thermostat
knob completely counterclockwise. The electric heat
elements or the hydronic valve should become energized
and noticeable heat should be felt at the discharge grille.
5. Depress the C-Cool button and move the thermostat
completely clockwise. The compressor and condenser fan
should come on and the air from the discharge should
feel cold.
6. Depress the S-Stop button and all functions of the unit
should stop.
CAUTION
!
The stop button does not disconnect power to the unit. Before
servicing the equipment, disconnect the unit from the power
source.
IM 1068 / Page 15 of 32
Ventilation
The introduction of outside air is controlled by an automatic
damper. During normal operation, the damper will be open
whenever the Heat, Cool, or Fan control buttons are
depressed. If the indoor fan is not energized, the damper will
be closed.
A concealed cutoff switch is provided so that the damper
can be kept closed.
This switch is located at the front left-hand side of the
cooling chassis (Figure 12). It can be reached by removing
the front panel.
The master unit is furnished with a 50 VA transformer
that is capable of handling up to 7 slave units. If
additional slave units are to be added, a larger eld
supplied transformer must be mounted external to the
unit. The master and slave units draw 5.6 VA each.
Furnish a transformer to handle the number of slaves
installed, plus the master unit.
2. When using a programmable wall thermostat, connect the
common terminal of the thermostat to terminal A of the
unit terminal board. Refer to the instructions furnished
with the thermostat to locate the common terminal.
Manual Changeover Thermostat Automatic Changeover Thermostat
Thermostat Part No. 0046736101 Thermostat Part No. 0060685101
Subbase Part No. 0046742100 Subbase Part No. 0002005963
IM 1068 / Page 16 of 32
TC1 Room Thermostat
TC2 Night Setback Thermostat (NSB)
TC3 Heat Fan Lockout
TC4 Low Ambient Lockout
VM Valve Motor
WN Wire Nut
R4 Relay, Guest Room Control (GRC)
R5 Relay, Hot Water Valve
R6 Relay, Control
R7 Relay, Night Setback (NSB)
S1 Control Switch
S2 Fan Speed Switch
S3 Fan Cycle Switch
S4 Damper Switch
T1 Transformer
TB1 Terminal Block, Control Box
C1 Capacitor, Indoor Fan
C2 Capacitor, Outdoor Fan
C3 Capacitor, Compressor
GRC Guest Room Control
HL High Limit
HTR Heater
MP Motor Protector
NSP Night Setback Control
P1 Plug, Control Box/Heat Section
to Cool Section
TB2 Terminal Board (24V), Control Box
TB3 Terminal Board, Heat Section
TB4 Terminal Board, Cool Section
TB6 Terminal Box
R1 Relay, Heat
R2 Relay, Cool
R3 Relay, Night Setback (NSB)
Typical Wiring Diagrams
Standard Chassis With Electric Heat & MCO Controls (Sizes 007—012)
COOL SECTION CONTROL BOX HEAT SECTION
S1 Switch Contact Positions
Unit Mounted Manual Changeover
Catalog 1068 / Page 17 of 32
TC1 Room Thermostat
TC2 Night Setback Thermostat (NSB)
TC5 Freezestat
VM Valve Motor
WN Wire Nut
Note: Large heat shown. Refer to unit diagram for
details of small or medium heat.
R3 Relay, Cooling
R4 Relay, Indoor Fan Motor
R5 Relay Heating 1st Stage
R6 Relay, Heating 2nd Stage
R7 Relay, Night Setback (NSB)
R9 Relay, Hot Water Valve
S1 Control Switch
S4 Damper Switch
T1 Transformer
TB2 Terminal Box
TB3 Terminal Box
TB4 Terminal Box
TB5 Terminal Box
TB6 Terminal Box
C1 Capacitor, Indoor Fan
C2 Capacitor, Outdoor Fan
C3 Capacitor, Compressor
F1 Fuse
HL High Limit
HTR Heater
MP Motor Protector
P1 Plug, Heat Section to Cool Section
P2 Plug, Heat Section to Control Box
P3 Plug, PC Board
P4 Plug, on Master Wire Harness
P5 Plug, on Master Wire Harness
R1 Relay, Run
R2 Relay, Outdoor Fan Motor
Standard Chassis With Electric Heat & MCO Controls (Size 019)
COOL SECTION CONTROL BOX HEAT SECTION
Catalog 1068 / Page 18 of 32
S1 Switch Contact Positions
Unit Mounted Manual Changeover
TC1 Room Thermostat
TC2 Night Setback Thermostat (NSB)
TC3 Heat Fan Lockout
TC4 Low Ambient Lockout
VM Valve Motor
WN Wire Nut
R4 Relay, Guest Room Control (GRC)
R5 Relay, Hot Water Valve
R6 Relay, Control
R7 Relay, Night Setback (NSB)
S1 Control Switch
S2 Fan Speed Switch
S3 Fan Cycle Switch
S4 Damper Switch
T1 Transformer
TB1 Terminal Block, Control Box
C1 Capacitor, Indoor Fan
C2 Capacitor, Outdoor Fan
C3 Capacitor, Compressor
GRC Guest Room Control
HL High Limit
HTR Heater
MP Motor Protector
NSP Night Setback Control
P1 Plug, Control Box/Heat Section
to Cool Section
TB2 Terminal Board (24V), Control Box
TB3 Terminal Board, Heat Section
TB4 Terminal Board, Cool Section
TB6 Terminal Box
R1 Relay, Heat
R2 Relay, Cool
R3 Relay, Night Setback (NSB)
Standard Chassis With Hot Water Heat & MCO Controls (Sizes 007—012)
COOL SECTION HEAT SECTION CONTROL BOX
S1 Switch Contact Positions
Unit Mounted Manual Changeover
Catalog 1068 / Page 19 of 32
TC1 Room Thermostat
TC2 Night Setback Thermostat (NSB)
TC5 Freezestat
VM Valve Motor
WN Wire Nut
R3 Relay, Cooling
R4 Relay, Indoor Fan Motor
R5 Relay Heating 1st Stage
R6 Relay, Heating 2nd Stage
R7 Relay, Night Setback (NSB)
R9 Relay, Hot Water Valve
S1 Control Switch
C1 Capacitor, Indoor Fan
C2 Capacitor, Outdoor Fan
C3 Capacitor, Compressor
F1 Fuse
HL High Limit
HTR Heater
MP Motor Protector
S4 Damper Switch
T1 Transformer
TB2 Terminal Box
TB3 Terminal Box
TB4 Terminal Box
TB5 Terminal Box
TB6 Terminal Box
P1 Plug, Heat Section to Cool Section
P2 Plug, Heat Section to Control Box
P3 Plug, PC Board
P4 Plug, on Master Wire Harness
P5 Plug, on Master Wire Harness
R1 Relay, Run
R2 Relay, Outdoor Fan Motor
Standard Chassis With Hot Water & MCO Controls (Size 019)
COOL SECTION CONTROL BOX HEAT SECTION
Catalog 1068 / Page 20 of 32
S1 Switch Contact Positions
Unit Mounted Manual Changeover
TC1 Room Thermostat
TC2 Night Setback Thermostat (NSB)
TC3 Heat Fan Lockout
TC4 Low Ambient Lockout
VM Valve Motor
WN Wire Nut
R4 Relay, Guest Room Control (GRC)
R5 Relay, Hot Water Valve
R6 Relay, Control
R7 Relay, Night Setback (NSB)
S1 Control Switch
S2 Fan Speed Switch
S3 Fan Cycle Switch
S4 Damper Switch
T1 Transformer
TB1 Terminal Block, Control Box
C1 Capacitor, Indoor Fan
C2 Capacitor, Outdoor Fan
C3 Capacitor, Compressor
GRC Guest Room Control
HL High Limit
HTR Heater
MP Motor Protector
NSP Night Setback Control
P1 Plug, Control Box/Heat Section
to Cool Section
TB2 Terminal Board (24V), Control Box
TB3 Terminal Board, Heat Section
TB4 Terminal Board, Cool Section
TB6 Terminal Box
R1 Relay, Heat
R2 Relay, Cool
R3 Relay, Night Setback (NSB)
Standard Chassis With Steam Heat & MCO Controls (Sizes 007—012)
COOL SECTION HEAT SECTION CONTROL BOX
S1 Switch Contact Positions
Unit Mounted Manual Changeover
Catalog 1068 / Page 21 of 32
TC1 Room Thermostat
TC2 Night Setback Thermostat (NSB)
TC5 Freezestat
VM Valve Motor
WN Wire Nut
R3 Relay, Cooling
R4 Relay, Indoor Fan Motor
R5 Relay Heating 1st Stage
R6 Relay, Heating 2nd Stage
R7 Relay, Night Setback (NSB)
R9 Relay, Hot Water Valve
S1 Control Switch
C1 Capacitor, Indoor Fan
C2 Capacitor, Outdoor Fan
C3 Capacitor, Compressor
F1 Fuse
HL High Limit
HTR Heater
MP Motor Protector
S4 Damper Switch
T1 Transformer
TB2 Terminal Box
TB3 Terminal Box
TB4 Terminal Box
TB5 Terminal Box
TB6 Terminal Box
P1 Plug, Heat Section to Cool Section
P2 Plug, Heat Section to Control Box
P3 Plug, PC Board
P4 Plug, on Master Wire Harness
P5 Plug, on Master Wire Harness
R1 Relay, Run
R2 Relay, Outdoor Fan Motor
Standard Chassis With Steam Heat & MCO Controls (Size 019)
COOL SECTION CONTROL BOX HEAT SECTION
Catalog 1068 / Page 22 of 32
S1 Switch Contact Positions
Unit Mounted Manual Changeover
Standard Chassis With Electric Heat & 24V Wall Stat (Sizes 007—012)
TC2 Night Setback Thermostat (NSB)
TC3 Heat Fan Lockout
TC4 Low Ambient Lockout
VM Valve Motor
WN Wire Nut
R4 Relay, Guest Room Control (GRC)
R5 Relay, Hot Water Valve
R6 Relay, Control
R7 Relay, Night Setback (NSB)
S2 Fan Speed Switch
S3 Fan Cycle Switch
S4 Damper Switch
T1 Transformer
TB1 Terminal Block, Control Box
TB2 Terminal Board (24V), Control Box
C1 Capacitor, Indoor Fan
C2 Capacitor, Outdoor Fan
C3 Capacitor, Compressor
GRC Guest Room Control
HL High Limit
HTR Heater
MP Motor Protector
NSP Night Setback Control
P1 Plug, Control Box/Heat Section
to Cool Section
TB3 Terminal Board, Heat Section
TB4 Terminal Board, Cool Section
TB6 Terminal Box
TC1 Room Thermostat
R1 Relay, Heat
R2 Relay, Cool
R3 Relay, Night Setback (NSB)
COOL SECTION CONTROL BOX HEAT SECTION
Catalog 1068 / Page 23 of 32
TC1 Room Thermostat
TC2 Night Setback Thermostat (NSB)
TC3 Heat Fan Lockout
TC4 Low Ambient Lockout
VM Valve Motor
WN Wire Nut
R4 Relay, Guest Room Control (GRC)
R5 Relay, Hot Water Valve
R6 Relay, Control
R7 Relay, Night Setback (NSB)
S1 Control Switch
S2 Fan Speed Switch
S3 Fan Cycle Switch
S4 Damper Switch
T1 Transformer
TB1 Terminal Block, Control Box
C1 Capacitor, Indoor Fan
C2 Capacitor, Outdoor Fan
C3 Capacitor, Compressor
GRC Guest Room Control
HL High Limit
HTR Heater
MP Motor Protector
NSP Night Setback Control
P1 Plug, Control Box/Heat Section
to Cool Section
TB2 Terminal Board (24V), Control Box
TB3 Terminal Board, Heat Section
TB4 Terminal Board, Cool Section
TB6 Terminal Box
R1 Relay, Heat
R2 Relay, Cool
R3 Relay, Night Setback (NSB)
Standard Chassis With Hot Water Heat & 24V Wall Stat (Sizes 007—012)
COOL SECTION CONTROL BOX HEAT SECTION
Catalog 1068 / Page 24 of 32
TC1 Room Thermostat
TC2 Night Setback Thermostat (NSB)
TC3 Heat Fan Lockout
TC4 Low Ambient Lockout
VM Valve Motor
WN Wire Nut
R4 Relay, Guest Room Control (GRC)
R5 Relay, Hot Water Valve
R6 Relay, Control
R7 Relay, Night Setback (NSB)
S1 Control Switch
S2 Fan Speed Switch
S3 Fan Cycle Switch
S4 Damper Switch
T1 Transformer
TB1 Terminal Block, Control Box
C1 Capacitor, Indoor Fan
C2 Capacitor, Outdoor Fan
C3 Capacitor, Compressor
GRC Guest Room Control
HL High Limit
HTR Heater
MP Motor Protector
NSP Night Setback Control
P1 Plug, Control Box/Heat Section
to Cool Section
TB2 Terminal Board (24V), Control Box
TB3 Terminal Board, Heat Section
TB4 Terminal Board, Cool Section
TB6 Terminal Box
R1 Relay, Heat
R2 Relay, Cool
R3 Relay, Night Setback (NSB)
Standard Chassis With Steam Heat & 24V Wall Stat (Sizes 007—012)
COOL SECTION CONTROL BOX HEAT SECTION
Catalog 1068 / Page 25 of 32
Scheduled Maintenance
Incremental conditioners are built to last. With proper care,
the unit should provide uninterrupted service for many years.
Scheduled maintenance of this equipment, as described
below, is the key to the equipment’s longevity.
Air lters must be cleaned at regular intervals. Twice
annually may be adequate in some areas while twice monthly
may be required in others. Areas with high dirt and lint
content or heavy usage of units require more frequent lter
maintenance that those areas of relatively clean operating or
low usage conditions. Unit malfunction may occur if air
lters are not kept clean.
The standard lter supplied with the Type K unit is a
permanent wire mesh type. This type of lter should be rinsed
with hot water and a mild detergent. Let dry and oil lightly to
enhance dust collecting ability.
The Type K is also available with a carbon lter, a zeolite
lter or electrostatic lter. The electrostatic lter is renewable
by rinsing with hot water and replacing in the unit once dry.
The carbon or zeolite lters must be discarded and replaced.
The frequency of this replacement depends on the air quality
of the room being ltered. Rooms with heavy smoke or
ammonia content will require more frequent lter changes
than rooms with minimal degrees of smoke or ammonia.
3. Unplug the chassis from the control box and remove the
chassis from the wall sleeve. Replace with spare chassis
or weatherplate.
4. Move chassis to maintenance area and check all seals,
wires, and insulation and repair as required.
5. Cover motor and protect all electrical components before
washing dirt from chassis.
6. Clean condensate drain and clear weep holes.
7. Dry equipment thoroughly, especially electric parts and
insulation.
8. Clean any rust spots with steel wool and paint with rust
inhibiting paint.
9. Check all fasteners and tighten if necessary.
10. Check the motor nameplate for routine oiling
instructions.
11. Test run chassis before reinstalling or returning to spare
parts stock.
Note: When replacing the standard lter with an
optional carbon, electrostatic, or zeolite lter, compress
the lter brackets slightly. The optional lters are slightly
thinner than the standard lter and will stay in place
better if the brackets are squeezed slightly.
It is recommended that the chassis be removed every year
for a thorough check-up. The heat section need not be
removed but should be inspected or cleaned if necessary.
Should the heat section blowers or motor need service, the
entire fan board can be easily removed from the unit for
service.
To access the unit for cleaning or service, proceed as
follows:
WARNING
!
Residential and institutional cleaning compounds can cause
permanent damage to the packaged terminal unit. To avoid
damage to unit controls and heat transfer surfaces, do not
spray cleaning compounds onto the return air opening or unit
controls.
Normal cleaning can be accomplished by wiping the unit
surface with a damp cloth. When using cleaning compounds on
An advantage of the Incremental system is that failure of any
one part affects only one Incremental conditioner and does
not interrupt the operation of the rest of the system. A further
advantage is that a failed part can be quickly and easily
replaced, thus minimizing the inoperative time of the
equipment. This is so, however, only if a replacement part is
quickly available. In order to replace a failed part quickly and
keep all Incremental conditioners in good operating
condition, McQuay International recommends that at the time
Incremental conditioners are purchased, owners arrange for
a small stock of replacement parts.
Where an owner carries such a stock, immediate replacement
of a defective part is possible. The defective part can
then be returned to McQuay International or one of its
authorized service stations. So long as it is still in warranty, it
is repaired or replaced and returned to the owner without cost
for shop labor and material. Thus, the stock of replacement
parts is constantly replenished. To the right is listed the kind
of parts which McQuay International recommends be carried
in stock, together with the quantity of parts recommended per
100 Incremental conditioners installed.
Touch-up Paint (1 Pt. Spray Can) ...................................1
For the current spare parts list, and applicable prices, see our
McQuay representative or write McQuayService, P.O Box
1551, Minneapolis, MN 55440.
IM 1068 / Page 27 of 32
Troubleshooting Chart
These items should be checked by a qualied service technician only.
Trouble Cause Cure
1. Blowers won't
operate on Cool.
2. Blowers operate on
Cool, but compressor
does not start.
3. Blowers run on Cool
and compressor
starts, but stops after
a short interval.
a. No power.
b. Faulty push-button switch.
c. Loose connections at push-button switch.
a. Thermostat set too high.
b. Heat valve is open and heat is on.
c. Low voltage.
d. Faulty push-button switch.
e. Faulty connection at push-button switch.
f. Defective wiring to thermostat.
g. Loose connections at compressor terminals.
h. Wiring to compressor terminals defective.
i. Loose connections in compressor overload device.
j. Starting capacitor malfunctions (open circuited, short
circuited or loss of capacity).
k. Defective compressor motor (short circuited, open circuited,
grounded).
a. Operation of overload device due to overloaded
compressor motor.
a. Check supply line fuses, circuit breakers, and be sure
the power is on. Blown fuses would indicate circuit overloading,
a short circuit, or a grounded condition in the circuit.
Voltage supply to the equipment should be checked. Voltage
under load must be within 10% of voltage given on
data plate.
b. Replace.
c. Tighten.
a. Adjust.Rotatecontrolknobto“Cooler.”
b. Close heat valve.
c. Check as above.
d. Replace.
e. Tighten.
f. Replace.
g. Tighten.
h. Replace.
i. Tighten
j. Replace.
k. *Ship cooling chassis prepaid to nearest McQuay authorized
warranty station.
a. Check voltage supply. Clean condenser inside and out.
Check at outside face of condenser for recirculation of
to make sure condenser blower/fan is operating properly.
Check compressor for short circuit. If defective, *ship cooling
chassis to nearest McQuay authorized warranty station.
4. Blowers run on Cool
and compressor
starts and runs, but
compressor
occasionally stops
(on overload device).
5. Compressor starts
and runs on Cool, but
blowers do not run.
6. Compressor starts
and runs on Cool, but
fan motor starts, then
stops.
7. Equipment gives
electrical shock.
8. Insufcientcooling
capacity.
a. Low voltage due to overloaded circuits within building or
throughout the local power system. Due to varying power
demands, this condition might exist only at certain times
during the day or on very hot days.
usually occurs at low load periods of the day.
c. Partial short circuit in compressor motor. Under normal
loading, a compressor with a partial short circuit might
a. Faulty push-button switch.
b. Open circuited blower motor.
c. Blower rubbing against its housing.
d. Bearings on blower motor seized.
e. Loose connection at push-button switch.
a. Operation of the internally connected overload device due
to a short circuit in blower motor.
b. Windings, rubbing of blower motor or lack of lubrication in
blower motor bearings.
a. Grounded electrical circuit.
a. Equipment standing too long without being run.
b.Insufcientairowthroughcondenserdueto:
1) Dirty condenser.
2) Obstructed louvers on outer cabinet or wall box.
3) Condenser blower/fan not running.
4) Condenser blower/fan not up to speed.
5) Condenser blower/fan slipping on motor shaft.
6) Recirculation of condenser air.
c. Insufcientairowthroughevaporatordueto:
1) Dirty evaporator.
2) Ice on evaporator coils.
3)Dirtyairlter.
4) Obstructed discharge grilles.
5) Evaporator blower motor not running.
6) Evaporator blower motor not up to speed.
7) Evaporator motor slipping on motor shaft.
a. Run separate electric line to equipment. Consult local
power company.
a. Replace.
b. Replace.
c. Adjust blower motor or blower wheel position.
d. Lubricate motor with SAE #10 oil. (It may be necessary to
remove blower assembly to do this.)
e. Tighten.
a. Adjust blower/fan wheel on shaft or blower motor mounting.
Lubricate with SAE #10 oil (see above).
b. Adjust blower wheel or motor or replace wheel.
a. Eliminate ground.
a. If the air conditioner is allowed to stand for an extended
length of time without being run on Cool, it is possible for all
the refrigerant to become absorbed in the oil inside the
compressor and refrigeration circuit. If this should happen,
there will be no cooling until the necessary working
pressures have been established. This will take about 5
minutes of continuous running.
b.
1) Clean.
2) Remove obstructions.
3) Correct as in #5.
4) Check for correct voltage. Oil blower motor if necessary.
5) Adjust blower position and tighten setscrew.
6) Correct as in #3.
c.
1) Clean.
2) Turn equipment off to let ice melt.
3) Clean or replace.
4) Remove obstructions.
5) Correct as in #1.
6) Check for correct voltage. Oil motor is necessary.
7) Adjust blower wheel position and tighten setscrew.
*If equipment is in warranty.
IM 1068 / Page 28 of 32
Troubleshooting Chart
These items should be checked by a qualied service technician only.
Trouble Cause Cure
8. Insufcientcoolingcapacity
(continued).
9. Too much cooling.
10.“Sweating”
11. Blowers won't operate
on Heat.
12. **Equipment is noisy.
13.Insufcientornoheat
d. Heat load in room exceeds capacity of equipment.
e. Windows and doors in room are open.
f. Compressor not pumping, indicated by:
1) Low wattage.
2) Condenser not warm, evaporator only partially cool, or not at all.
g. Restricted capillary tube or strainer, indicated by:
1) Frost on capillary tube or strainer.
2) Low wattage.
3) Condenser not warm.
4) Evaporator partially frosted, only partially cool, or not at all.
a. Thermostat set too low.
b. Defective thermostat.
a. Condensate drain from evaporator to condenser plugged.
b. Insulating seals on equipment damaged.
c. Evaporator blower motor not up to speed.
d. Evaporator blower incorrectly positioned.
a. No power.
b. Heat is off (equipment with heat fan lockout).
c. Faulty push-button switch.
d. Loose connections at push-button switch.
e. Thermostat set too low.
a. Blower rubbing against enclosure.
b. Blower motor bearings are dry.
c. Loose blower hold-down nuts on motor-bracket assembly.
d. Refrigerant absorbed in compressor oil after extended shutdown.
e. Equipment improperly installed.
f. Damper solenoid hums.
g. Loose terminal box cover on side of compressor.
h. Loose electrical components.
i. Copper tubing vibrating.
j. Harmonics.
k. Loose sheet metal parts.
a. No steam or hot water being applied.
b. No Power.
c. Faulty push-button switch.
d. Loose connection at push-button switch.
e. Thermostat set too high.
f. Thermostat faulty.
g. No power output on transformer secondary.
h. In-operative valve.
e. Close them.
f. * Ship cooling chassis prepaid to nearest McQuay authorized
warranty station.
g. * Ship cooling chassis prepaid to nearest McQuay authorized war
ranty station.
a. Adjust.
b. Replace.
a. Removeobstructionstowaterow.
b. Adjust or replace.
c. Check for correct voltage. Oil motor if necessary.
d. Adjust.
a. Correct as in #1.
b. Open heat valve or turn on heating system.
c. Replace.
d. Tighten.
e. Adjust–rotatecontrolknobto“Warmer”.
a. Adjust fan position on motor shaft to reposition fan motor bracket
assembly.
b. Lubricate with SAE #19 oil or replace motor.
c. Align blower assembly and tighten nuts.
d. Noise will disappear after equipment runs awhile.
e. Make necessary adjustments to components.
f. Check for proper adjustment. Apply silicone oil or grease to gap
between solenoid and armature.
g. Tighten.
h. Fasten securely.
I. Adjust by bending or applying tape.
j. Occasionally equipment will have noisy operation for no apparent
reason. Inspect ion has revealed no loose components that might
be the source of the noise. Due to the action of the compressor, it
is possible to have internal noise develop if the refrigerant tubing
has become bent even slightly. To distinguish this condition from
the simple rattle producing vibration caused by loose screws, nuts,
and other components, grasp the refrigerant tubing at various points
throughout the system until a point is found where the noise is
eliminated or reduced. Bend the copper tubing very gently until the
noise disappears.
k. Tighten.
a. Contact building management.
b. Check power supply line fuses, circuit breakers. Blow fuses would
indicate circuit overloading, a short circuit, or a grounded condition in
the circuit.
c. Replace.
d. Replace wire or tighten.
All McQuay equipment is sold pursuant to its standard terms and conditions of sale, including Limited
Product Warranty. Consult your local McQuay Representative for warranty details. Refer to Form
933-43285Y. To find your local McQuay Representative, go to www.mcquay.com.
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.mcquay.com.
Products Manufactured in an ISO Certified Facility.