McQuay Type K Incremental Packaged Terminal Air Conditioner, Incremental Packaged Terminal Maintenance Manual

Installation & Maintenance Data
Group: PTAC
Part No.: 669729001
Date: March 2010
Type K Incremental Packaged Terminal Air Conditioner
Incremental™ Room Conditioner with R-410A Refrigerant
IM 1068
© 2010 McQuay International
Table of Contents
Inspection ................................................................................2
Model Nomenclature ...............................................................3
Wall Opening Requirements ....................................................4
Wall Box Installation ................................................................5
Outdoor Louver Installation .....................................................6
Heat Section Installation (Sizes 007-012) .........................6-7
Heat Section Installation (Size 019) .....................................8
Cooling Chassis Installation ................................................9
Electric Power Wiring
Units with Electric Heat (Sizes 007-012 ....................
Units with Hydronic Heat (Sizes 007-012) Units with Hydronic Heat (Size 019)
Room Cabinet and Control Installation .............................14-15
Equipment Start-up .............................................................15
Ventilation .......................................................................
Remote Mounted Thermostat Installation ..............................16
Typical Wiring Diagrams ................................................17-25
Standard Chassis w/Elect Heat & MCO Controls
(Sizes 007–012) .............................................................
Standard Chassis w/Elect Heat & MCO Controls
(Size 019) .......................................................................
.................12-13
...............................13
Installation
The installation of this equipment shall be in accordance with the regulations of authorities having jurisdiction and all applicable codes. It is the responsibility of the installer to determine and follow the applicable codes. Sheet metal parts, self-tapping screws, clips and such items inherently have sharp edges, and it is necessary that the installer exercise caution. This equipment is to be installed only by an experienced installation company which employs trained personnel.
Inspection
When the equipment is received, all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. All units should be carefully inspected for damage when received. If any damage is noticed, the carrier should make the proper notation on the delivery receipt acknowledging the damage.
10-11
16
17
18
Standard Chassis w/Hot Water Heat & MCO Controls
(Sizes 007–012) .............................................................
Standard Chassis w/Hot Water Heat & MCO Controls
(Size 019) .......................................................................
Standard Chassis w/Steam Heat & MCO Controls
(Sizes 007–012) .............................................................
Standard Chassis w/ Steam Heat & MCO Controls
(Size 019) .......................................................................
Standard Chassis w/ Electric Heat & 24V Wall Stat
(Sizes 007–012) .............................................................
Standard Chassis w/Elect Heat & 24V Wall Stat
(Sizes 007–012) .............................................................
Standard Chassis w/Steam Heat & 24V Wall Stat
(Sizes 007–012) .............................................................
Scheduled Maintenance ........................................................26
Recommended Spare Parts ..................................................27
Troubleshooting Chart .....................................................28-29
Approximate Shipping Weights ............................................ 30
19
20
21
22
23
24
25
The carrier should also ll out a Carrier Inspection Report. The McQuay International Trafc Department should then be
contacted.
The unit nameplate should be checked to make sure the voltage agrees with the power supply available.
The Type K Series Comfort Conditioner is designed and built
for through-the-wall installation in either new or existing buildings. The self-contained refrigerant system delivers cooling to the desired space. Heating can be accomplished with electric resistance or hydronic heat. Each conditioner consists of the following components:
● Cooling Chassis ● Room Cabinet
● Heat Section ● Wall Box
● Control ● Louver
Figure 1: Type K Unit Components
IM 1068 / Page 2 of 32
Model Nomenclature
P KES 2 007 C Z 41 Z 12 AR 14 A I C 1
Model
Product Category
P = PTAC
Product Style
1= 1st Style Change
Product Identier KES = Type K, Cool Chassis Only KEI = Type K Cool Chassis Only, IAQ KEC = Type K Cool Chassis Only, Corrosion Protection KHS = Type K Heat Section Only
Design Series 1 = A design 2 = B design
Nominal Capacity - Btuh
007 = 7000 009 = 9000 012 = 12000 019 = 19000
Voltage
A = 115-60-1 C = 208-60-1 G = 230-60-1 J = 277/265-60-1 S = 208-115-60-1 R = 265-115-60-1
Coil Options Z = None
Heating Options
35 = 2.5 kW nominal 41 = 3.5 kW nominal 44 = 4.0 kW nominal 48 = 5.0 kW nominal 50 = 7.7 kW nominal 62 = Hydronic - Normally Open Valve (Hot Water) 63 = Hydronic - Normally Closed Valve (Steam)
SKU A = Stock B = Standard Delivery C = Extended Lead time
Color I = Antique Ivory
Power Connection A = Junction Box
Return Air/Outdoor Air 14 = Bottom
Discharge
AR = Flat Top
Controls
12 = Unit Mounted Manual Change Over (MCO) 24 = Unit Mounted Manual Change Over w/Night Set Back (NSB) 27 = 24V Wall T'stat w/Guest Room Control (GRC) & Night Set Back (NSB) 32 = 24V Wall T'stat w/Night Set back(NSB)
Hand Orientation
A = Same Hand Left B = Same Hand Right N = LH Supply / RH Return P = RH Supply / LH Return Z = Not Applicable
Note: Availability of voltages, heating options, and controls may vary amongst unit sizes. Consult your McQuay representative.
IM 1068 / Page 3 of 32
Wall Opening Requirements
Before installing the unit, check the wall opening to be sure
the wall sleeve will slide in unobstructed. The rough opening should measure 25'' x 36½'' (635mm x 927mm) indoors and 14½" x 36½" (368mm x 927mm) outdoors for sizes 007–012
and 27¾''x 46¾'' (705mm x 1187mm) indoors and 16⅜" x 46¾"
outdoors (415mm x 1187mm) outdoors for sizes 019 as shown
below. The wall box is designed to be mounted on the oor but may be located above the oor line to clear obstructions. Without cabinet modications, the wall box can be placed up to 1'' (25mm) above the oor. The standard adjustable kickplate can be telescoped to hide the space below the wall box. Complete
wall box installation instructions can found on page 5.
Figure 2: Unit and Wall Box Opening Dimensions
CAUTION
!
Sheet metal parts, self-tapping screws, clips and such items inherently have sharp edges, and it is necessary that the installer exercise caution. This equipment is to be installed only by an experienced installation company which employs trained personnel.
E
D
LC
A
H
J
K
B
M
F
G
Table 1: Unit Dimension
Dimensions – Inches
Unit Size A B C D E F G H J K L M N P R
007–012 48 2½ Min. 7¼ Min. 36¼ 5¾ 24½ 13 019 60 2½Min. 8½Min. 46¼ 6⅞ 27⅜ 15⅞ 24 4-6Adj. 3 9¼ 5/8 59½ 27¾ 46¾
Dimensions – mm
Unit Size A B C D E F G H J K L M N P R
007–012 1219 64 Min. 184 Min. 921 146 648 348 533 89-140 Adj. 44 203 25 1162 635 927 019 1524 64 Min. 216 Min. 1175 175 695 403 610 102-152 Adj. 76 235 16 1151 705 1187
11
⁄16 21 31⁄2-5½ Adj. 8 1 45¾ 25 36½
IM 1068 / Page 4 of 32
Wall Box Installation
The wall thickness will determine how much, if any, of the wall box will protrude into the room. Figure 3 shows a typical installation in a frame and brick wall. These instructions will
vary by depth of wall, but not by wall material. Do not
remove the weather panel at any time during the installation of the wall box. Premature removal of this panel could result in improper leveling or sealing. Install the wall box as follows:
5. Place 2'' (51mm) berglass batt or 1" (25mm) Styrofoam
insulation around the top and sides of the wall box.
6. Locate the wall box in the wall opening with the weather
panel to the outside. Use the top edge of the wall box for horizontal leveling. The wall box must also be vertically
plumb. Shim the wall box to accomplish this. Recess so louver is ush with outside wall.
7. Drill four (4) holes in the sides of the wall box and attach
it to the walls securely using appropriate fasteners.
1. If the wall opening has not been made, cut and break through using care to leave interior and exterior surfaces undamaged. See wall opening requirements on page 4 for proper size.
2. Install lintels as shown on the plans and specications.
3. If the wall opening has already been made, measure it to
be certain it has adequate clearance for the wall box. Be
sure to allow extra clearance for insulation around the
wall box to reduce sound and heat transfer. Continue with
step #4.
4. Apply a layer of mortar or roong cement to the bottom
surface of the opening (see Figure 3).
Table 2: Wall Box Dimensions
Dimension “A” 007–012 019
in. mm in. mm in. mm
0 to -1 0 to -25 8 0 to +1 0 to +25 9 1 to 2 25 to 51 10 2 to 3 51 to 76 11 3 to 4 76 to 102 12 4 to 5 102 to 127 13 5 to 6 127 to 152 14 6 to 7 152 to 178 15 7 to 8 178 to 203 16 8 to 9 203 to 229 17
Dimension “C” – Cabinet Depth
1
⁄4 210
1
⁄4 235 81⁄2 216
1
⁄4 260 91⁄2 241
1
⁄4 286 101⁄2 267
1
⁄4 311 111⁄2 292
1
⁄4 327 121⁄2 318
1
⁄4 362 131⁄2 343
1
⁄4 387 141⁄2 368
1
⁄4 413 151⁄2 394
1
⁄4 438 161⁄2 419
Note: Never drill through bottom of wall box.
8. If face brick is being installed, continue coursing up the wall until the wall box is completely surrounded and becomes an integral part of the wall.
9. Caulk interior and exterior perimeter weather tight where
the box meets the wall. Use a non hardening, waterproof caulk such as silicone.
Note: For rooms with thick carpet, wall box should be
installed 1/2'' (13mm) above concrete oor to facilitate
future chassis installation and removal.
Figure 3: Wall Box End View (Drawing Not To Scale)
NOTICE
Dimension “B” will vary by the thickness of the wall, the louver, the amount
the louver is recessed into the wall (if any) and the amount the wall box extends into the room. The minimum “B” dimension is 21⁄2'' (64mm). The wall box can be factory furnished in increments between 21⁄2'' (64mm) and 10'' (254mm). Wall box extensions in 1'' (25mm) increments can also be provided to attach to the rear of the wall box.
Table 3: Wall Box “B” Dimension
Dimensions — inches
Wall Box 007–012 21⁄2 31⁄2 4 5 6 7 8 9 10 “B” Dimension 019 21⁄2 31⁄2 41⁄2 51⁄2 61⁄2 71⁄2 81⁄2 91⁄2 101⁄ 007–012 101⁄2 111⁄2 12 13 14 15 16 17 18
Overall Length
Dimensions — mm
Wall Box 007–012 64 89 102 127 152 178 203 229 254 “B” Dimension 019 64 89 114 140 165 191 216 241 267 007–012 267 292 305 330 356 381 406 432 457
Overall Length
019 113⁄4 123⁄4 133⁄4 143⁄4 153⁄4 163⁄4 173⁄4 183⁄4 193⁄
019 298 324 349 375 400 425 451 476 502
2
4
IM 1068 / Page 5 of 32
Outdoor Louver Installation
1. Remove the louver from the shipping carton which also
contains the mounting hardware.
2. Remove the weather panel from the wall sleeve to gain
access to the outside of the wall box. Verify that gap between exterior wall and wall box is caulked.
3. If an optional louver frame is required, install prior to
louver installation. Caulk that portion of the frame which
will come in contact with the wall. Pass the louver frame through the wall box opening and from the outside of the building, slide over the end of the wall box. Position as desired, then drill holes through the top and sides of the overlapping wall box and louver frame. Secure to the
wall with screws. Caulk wall box/louver frame joint on
all four sides. Provide additional caulking around outside wall and louver frame to ensure a weather tight seal.
4. Make a temporary handle by looping a piece of exible
wire or heavy cord through the louver. This will insure
that a rm grasp can be maintained during installation.
5. From a position inside the room, push the louver through
the opening at the rear of the wall box. Line it up with the
wall box and pull it back so the louver studs pass through
the holes of the wall box ange (see Figure 4).
6. Attach the washers and nuts to secure the louver in place.
7. If heat section and cool chassis are not to be immediately installed, replace the weather panel.
Figure 4: Louver Installation
Heat Section Installation (Sizes 007-012)
The Type K heat section is matched to the Type K cooling
chassis but packaged and shipped separately. Check the
heat section carton label and the unit’s nameplate to ensure it is correct for the cooling chassis and the space. The following steps should be followed when installing the heat section:
1. Remove the heater from the shipping carton and examine for concealed damage. Report any damage found to the
carrier. The control is packaged with the heat section
in a separate carton. Remove this carton from the heat
section and set it aside until after the heat section is installed.
2. Manually spin the blowers to make sure there is no interference. Minor misalignment may have occurred during shipping and should be corrected. If it can’t be corrected with minor adjustment, the condition should be
reported to the factory. Do not lubricate room side motor
at this time. Each unit is adequately lubricated before leaving the factory.
3. Observe the method of installation. The heat section has
side channels that ride on rails in the wall box. At the
back of the wall box towards the top are two hooks
that engage the heat section. Locate these hooks before
sliding the heat section in place. “U”-shaped clips are included that lock the heat section in place once installed. “U”-clips can usually be found taped to the wall box interior.
4. Remove the weather panel from the wall box. If the
louver has not been installed, install it before placing the heat section into the wall box.
Figure 5: Heat Section Installation
5. Slide the heat section into place so that the holes of the
heat section surround the hooks of the wall box. Lock it
to the wall box using the “U”-shaped clips provided (see
Figure 5). The “U”-shaped clips should be positioned
with the open end pointing down.
IM 1068 / Page 6 of 32
6. The piping for steam or hot water can be supplied from either the right or left side of the coil. Hot water must be supplied to the bottom of the coil, and steam to the top of
the coil. See Detail A through H for specics. To simplify connections to the coil, use 5/8'' O.D. copper tubing
where local codes allow.
7. A shutoff valve is recommended on the supply and return side of the coil.
8. When steam is used, a trap is required on the return side. Trap size should be determined by the consulting engineer or steam trap supplier, depending upon the type
of system and the pressure applied.
When hot water is used, an air vent must be installed at the highest point in the piping connection. If the vent is not automatic, it should be piped with easy access for
regular maintenance. Caution: Locate vent so it does
not drip or spray on electrical components.
9. Insulate all exposed water or steam lines that are located within the room cabinet. Failure to do this may cause erratic operation of the thermostat.
10. Protect the heat section from damage during
construction. Do not operate the heat section without a
lter or the warranty will be void.
Figure 6: Suggested Piping Arrangements
in. mm 489 552 540 267 597 514
S T U V W Y
191⁄
213⁄4 211⁄4 101⁄2 231⁄2 201⁄
4
4
Hot Water Supply Steam Supply Detail A — Hot water supply R.H., return L.H. Detail B — Steam supply R.H., return L.H.
C
L
W
S
T
Return Stub
V
25/8"
(67mm)
2"
(51mm)
Y
C
L
S
T
Return Stub
V
(51mm)
Detail C — Hot water supply R.H., return R.H. Detail D — Steam supply R.H., return R.H.
C
L
U
T
Return
Stub
W
V
1"
(25mm)
C
L
2"
(51mm)
C
L
U
T
Return Stub
Y
V
(51mm)
2"
2"
C
L
C
L
(25mm)
25/8"
(67mm)
1"
Detail E — Hot water supply L.H., return R.H. Detail F — Steam supply L.H., return R.H.
C
L
2"
(51mm)
Return Stub
25/8"
(67mm)
V
Detail G — Hot water supply L.H., return L.H. Detail H — Steam supply L.H., return L.H.
C
2" (51mm)
L
1" (25mm)
Return Stub
W
V
C
1"
(25mm)
L
(51mm)
C
L
Return Stub
2"
2"
(51mm)
Return Stub
Y
C
L
V
S
S
V
U
U
C
L
IM 1068 / Page 7 of 32
Y
25/8"
C
L
W
S
S
U
U
C
L
(67mm)
Heat Section Installation (Size 019)
Figure 7 shows the heat section installed in a standard wall box. Note that the heat section slides into a wall box on the slide rails. For heat section installation, proceed as follows:
1. Remove heat section from shipping carton.
2. Visually check for shipping damage and report any visible damage immediately to the trucker. Spin blower wheels by hand to assure they do not rub within their housing. Shipping may have loosened mounts. Adjust as required.
3. Check voltage rating on data plate fastened to heat
section. This must conform to voltage supplied for the equipment.
4. Locate slide rails on each side of wall box and insert
heater section into the wall box. Slide to the rear until it
is rmly seated.
5. Screw in the heat section lock screws as shown in Figure
7. (Screws are shipped with the heat section.)
Figure 7: Heat Section Installed in Wall Box
WARNING
!
If the heat section is used for heating an area during construction,
specicallyplastering,precautionsmustbetakentoprotectthe
equipment by using covers of corrugated board, sheet metal or
plywood.Iftheinstallationspeciesheatonly,besuretoinstall permanentweatherpanelandlteradapter(see“Installationof
Heating Only Option”). Failure to heed this warning can cause malfunction of the equipment.
Figure 8: Rough-in Piping Connections Locations
Figure 9: Hot Water Coil
Steam or Hot Water Application (Size 019)
When the heat section requires steam or hot water, the installation varies. See Figures 9 and 10 for suggested piping arrangements.
1. Supply and return piping for steam or hot water is supplied from right-hand side only. Hot water must be supplied to the bottom of the coil, and steam to the top of the coil.
2. To simplify the steam or hot water connections to the
coil, use 5/8'' O.D. copper tubing where local codes
permit. See Figure 8 for rough-in dimensions.
3. When hot water is to be used, an air vent must be put in at the highest point in the piping connection. See Figure
9. If the air vent used is not of the automatic type, it should be piped so that it may be easily opened.
4. A shutoff valve is recommended on the supply and return
side of the coil. A steam trap is required on the return
side when steam is used for heating. See Figure 10.
5. All steam or hot water lines which are located within the
room cabinet should be insulated.
IM 1068 / Page 8 of 32
Figure 10: Steam Coil
Cooling Chassis Installation
1. Remove the cooling chassis from the shipping carton and examine it for damage. Do not rest it on end. Check the
plate rating against the power supply to make sure that they are the same (Figure 11). Also check the size
(capacity) to make sure that it coincides with the heat section; e.g., Size 009 cooling.
2. The cooling chassis is supplied with an internal spring mounted compressor. The hold-down nuts on the
compressor mountings should not be loosened.
3. Manually spin the condenser fan wheel to be sure that there is no interference or looseness. If it is loose, tighten
the setscrew located over the center of the at on the
motor shaft. Do not lubricate condenser fan motor at time
of installation.
Figure 11: Cooling Chassis Details
4. Slide the chassis into the wall box. Chassis must be
square in the box so that all the rubber seals are pressed
tight. Check bottom seal between chassis and wall box to
ensure that it has not been unseated from slot during
chassis installation.
5. For unit size 019, there is a “J” bolt on each side that holds the chassis in place. Thread the “J” bolts through the holes supplied in the chassis and tighten until
the chassis is rmly seated in the wall box.
IM 1068 / Page 9 of 32
Electric Power Wiring
Before making any electrical connections, observe the
following precautions:
1. Check the nameplate rating of the heat section and
cooling chassis to make sure the equipment is connected to the proper power supply and that proper fusing is used.
a. By installing a remote double-pole switch in the
conditioner’s power line within sight of the unit.
b. By installing a double pole, single throw “on-off”
switch located in a convenient position within the
room cabinet.
After all these precautions are observed, proceed as follows:
2. In cases where a number of conditioners are to be installed, single circuits should be provided for each machine.
3. A separate disconnect is recommended for each
conditioner in addition to individual fusing. This can be accomplished in several ways:
Figure 12: Electric Heat Section (Sizes 007 through 012)
A
H
M
J
E
K
Notes:
Guest room control, low voltage or master-slave wiring connection made at
control box.
4" × 24" (102mm × 51mm) wall space for electrical conduits except behind
junction box.
Junction box with knockouts for 1/2'' (12mm) 3/4'' (19mm) conduit.
See Table 5 for dimension B.
D
Front View
Units With Electric Heat (Sizes 007–012)
A 4" x 4" electrical junction box is located on the left side of the heat section. Field wiring should be brought to this point for power to the unit. See Figure 12 & 13.
8"
(203mm)
Long Control
Box
Table 4: Electric Heat Section Dimensions
A D E F G H J K M
in. mm 1162 940 451 622 348 581 254 233 38
Room Cabinet
B
Room Cabinet Mounting Holes (4)
1
⁄2''
(12mm)
Wall Box
1
⁄4''
(6mm)
Heat Section
Power Cord
Cooling Chassis Power Cord
Side View
453⁄4 37 173⁄4 241⁄2 1311⁄16 227⁄8 10 93⁄16 11⁄
G
2
F
Table 5: Wall Box “B” Dimensions
Wall Box Size 21⁄2" 31⁄2" “B” Dimension 007–012 64 mm 89 mm 102 mm 127 mm 152 mm 178 mm 203 mm 229 mm 254 mm
IM 1068 / Page 10 of 32
4" 5" 6" 7" 8" 9" 10"
Figure 13: Electric Heat Section (Size 019)
A
H
Control Box
Room Cabinet
Main Power Cord
Heat Chassis
Power Cord
Room
Cabinet Mounting Holes (4)
Cool Chassis
Power Cord
D
4" x 4" Junction Box
Front View
(Mounted by Others) Field Mounted to L.H. Edge of Wall Box
Table 6: Electric Heat Section Dimensions
in. mm 1511 1175 695 403 749
Notes:
Guest room control, low voltage or master-slave wiring connection made at
See Table 7 for dimension B.
A D F G H
591⁄
461⁄4 273⁄8 157⁄8 291⁄
2
control box.
2
Long Control Box 
Cool
Chassis
Power
Cord
Heat Section
Power Cord
91/4"
(203 mm)
B
F
G
Wall Box
(End View
w/o Cabinet)
Side View
Table 7: Wall Box “B” Dimensions
Wall Box Size 21⁄2" 31⁄2" “B” Dimension 019 64 mm 89 mm 102 mm 127 mm 152 mm 178 mm 203 mm 229 mm 254 mm
4" 5" 6" 7" 8" 9" 10"
IM 1068 / Page 11 of 32
Units With Hydronic Heat (Sizes 007–012)
The hydronic heat section can be supplied with a short (4¼'' high) control box or a long (13½'' high) control box depending on the number of options selected. Observe the control box to determine which one was supplied for the job.
Long Control Box
1. If the long control box was provided, make electrical
connections to a eld supplied junction box that should
be fastened to the oor beneath the control
(Figure 15).
Short Control Box
If the short control box was supplied, eld wiring should be
brought into the 2'' x 4'' junction box which is located on the right-hand side of the heat section (Figure 14.)
2. Locate the long control box. The power wires for the control extend through the piece of exible conduit that
exits from the bottom of the control. These wires should
be connected to the incoming power at the junction box
installed in Step 1.
Remote Control — For units with remote mounted
thermostat, refer to page 14.
Figure 14: Hydronic Heat Section with Short Control Box (Sizes 007-012)
The short control box is used with standard unit mounted manual changeover control, and unit mounted manual changeover with emergency standby (ESB) power supply.
A
H
M
J
E
K
L
Hydronic Coil
Short
Control Box
Room Cabinet
Room Cabinet Mounting Holes (4)
8"
(203mm)
B
P
N
Wall Box
G
F
1
D
Front View
Junction Box
Room Cabinet Removed
⁄2''
(12mm)
Side View
Table 8: Hydronic Heat Section with Short Control Box Dimensions
in. mm 1162 940 648 622 348 581 254 406 114 38 375 44
Notes:
See Detail A, B, C, D, E. F, G, or H on page 7 for dimensions of factory installed valve and return piping stub. Junction box 7/8" (22mm) diameter knockouts for 1/2" (12mm) conduit. See Table 9 for dimension B.
A D E F G H J K L M N P
453⁄
37 251⁄2 241⁄2 1311⁄16 227⁄8 10 16 41⁄2 11⁄2 143⁄4 13⁄
4
4
Table 9: Wall Box “B” Dimensions
Wall Box Size 21⁄2" 31⁄2" “B” Dimension 007–012 64 mm 89 mm 102 mm 127 mm 152 mm 178 mm 203 mm 229 mm 254 mm
4" 5" 6" 7" 8" 9" 10"
1
⁄4''
(6mm)
IM 1068 / Page 12 of 32
Figure 15: Hydronic Heat Section with Long Control Box (Sizes 007-012)
The long control box is used with optional special controls such as Guest Room Control (GRC), Night Setback (NSB), and remote thermostats. Note: Left-hand piping must be used with the long control box design.
A
H
M
E
J
K
L
Hydronic Coil
D
Front View
Cool Chassis Power Cord
Junction Box (By Others)
Table 10: Hydronic Heat Section with Long Control Box Dimensions
A D E F G H J K L M
453⁄
in. mm 1162 940 648 622 348 581 254 406 114 38
Notes:
See details G and H on page 7 for dimensions of factory installed valve and return piping stub. See Table 9 on page 12 for dimension B.
37 251⁄2 241⁄2 1311⁄16 227⁄8 10 16 41⁄2 11⁄
4
2
Long
Control Box
Room Cabinet
Room Cabinet Mounting Holes (4)
Heat Chassis
Power Cord
Flexible Conduit Power Supply Cord
8"
(203mm)
B
Wall Box
1
⁄2''
(12mm)
1
⁄4'' (6mm)
Side View
Room Cabinet Removed
F
G
Unit with Hydronic Heat (size 019)
1. Only one size control box is available for size 019. Make all electrical connections to a factory supplied
junction box located on the L.H. side of the wall box
(Figure 16).
Figure 16: Units with Hydronic Heat (Size 019)
Control Box
Room Cabinet
Main Power Cord
Heat Chassis
Power Cord
Room
Cabinet
Mounting
Holes (4)
Cool Chassis
Power Cord
Front View
4" x 4" Junction Box (Mounted by Others) Field Mounted to L.H. Edge of Wall Box
Notes:
 RefertoTable7onpage11for“B”dimension.
Coil Stubs for Field Piping
Long
Control
Box
Cool
Chassis
Power
Cord
Heat Chassis
Power Cord
B
Wall Box
(End View
w/o Cabinet)
Side View
IM 1068 / Page 13 of 32
Room Cabinet and Control Installation
The depth of the room cabinet varies by the amount the wall
box extends into the room. Check the unit tagging against the
room cabinet tagging to be sure they match. Installation of the control box should be done at the same time as the room cabinet.
1. Remove the cabinet from the carton and inspect it for
damage. If any is found, contact the carrier immediately. The room cabinet is made up of six pieces: a cabinet, a removable front panel, a discharge grille, two (2) end plates, and a kickplate. Make sure all pieces are included with the room cabinet (Figure 18).
Remove the front panel by lifting it slightly and pulling
forward, then upwards and out from the surrounding cabinet. Unit size 019 utilizes safety chains that must be disconnected from the room cabinet in order to remove the front panel.
If necessary, remove the tie bar located at the bottom of
the front panel, unlock the latch at each end and lift the bar out (Figure 17)
Figure 18: Unit Cabinet Assembly Details
4. Fasten the two (2) end plates to the room cabinet using the wing nuts supplied. These end plates are adjustable
and should be positioned to set at on the nished oor
(Figure 19).
Figure 17: Release Concealed Latch
2. For unit sizes 007–012: Place the cabinet around the installed wall box, heat
section and cool chassis and push the cabinet rmly
against the wall. The discharge grille seals should rest on the discharge opening of the heat section.
For unit size 019: Position the room cabinet over the heat section so that the
two studs on each side are positioned over the matching slots in the heat section. Set the cabinet down on the heat section, push tight against the wall and secure using wing nuts supplied. See Figure 18.
Figure 19: Unit Cabinet Assembly Details
5. Locate the kick plate and clip it into the slots provided in the end plates so that the ange is toward the oor.
6. Take the control box and escutcheon plate out of the carton for attachment to the room cabinet.
7. There are two anges beneath the control door that support the control box (Figure 20). Remove the two
screws in the control box that hold the escutcheon plate
in place. Remove the thermostat knob and escutcheon
plate.
3. Fasten the cabinet to the wall using appropriate fasteners.
The back anges of the room cabinet have factory
furnished holes for securing the cabinet to the wall.
IM 1068 / Page 14 of 32
Figure 20: Remove the Escutcheon Plate and Control Knob
8. While holding the control box in position, set the
escutcheon plate in place on the anges beneath the
control door.
9. Using the two screws removed in Step 7, secure the control box and escutcheon plate to the room cabinet.
10. Replace the thermostat control knob.
11. Connect the power cord from the heat section to the
bottom of the control box. Plug in the cord from the control box to the receptacle in the cooling chassis.
12. Move the thermostat bulb to the cooling chassis and
secure it to the snap clips provided. Inspect the lter to be
sure it is securely in place.
13. Loosen the wing nuts on the nose piece that is attached
to the heat section. Slide the nose piece toward the room cabinet until it makes contact. Tighten wing nuts to secure the nose piece in place. This nose piece prevents air from leaking back into the cabinet and giving the thermostat a false reading.
14. Before replacing the front panel, replace the tie bar (if it
has been removed) and lock the latches. Then retrieve the front panel and replace it by sliding it in and downward
into the room cabinet. See gure 21.
Note: Tie bar latches must be in and locked before installing the front panel.
15. Wipe cabinet with a soft cloth to remove smudges. If required, use a mild, nonabrasive cleanser.
Figure 21: Unit Cabinet Assembly Details
Equipment Start-up
Initial start-up of the McQuay equipment by an experienced person is usually the responsibility of the installing contractor. This consists of inspecting and operating the equipment for all functions at the time of initial installation, and making adjustments as necessary. It also includes demonstrating its proper operation to the owners or their agents.
Note: That unless otherwise specically agreed to in writing, there is no eld labor or start-up service
included in the price of the equipment.
The Type K unit is furnished with a concealed fan cycle
rocker switch on the control box. Before start-up, open the
front panel and place this switch in the “cycle” position.
Continue start-up procedures as follows:
1. Check the main power supply to be sure there is power to
the unit.
2. Open the control access door and press the button labeled F-Fan. The indoor fans should be energized.
3. Move the fan speed rocker switch from “Low Fan”
to “High Fan” and back again. The fan speed should change.
4. Depress the button marked H-Heat. Turn the thermostat
knob completely counterclockwise. The electric heat elements or the hydronic valve should become energized and noticeable heat should be felt at the discharge grille.
5. Depress the C-Cool button and move the thermostat
completely clockwise. The compressor and condenser fan should come on and the air from the discharge should
feel cold.
6. Depress the S-Stop button and all functions of the unit
should stop.
CAUTION
!
The stop button does not disconnect power to the unit. Before servicing the equipment, disconnect the unit from the power source.
IM 1068 / Page 15 of 32
Ventilation
The introduction of outside air is controlled by an automatic
damper. During normal operation, the damper will be open whenever the Heat, Cool, or Fan control buttons are
depressed. If the indoor fan is not energized, the damper will be closed. A concealed cutoff switch is provided so that the damper can be kept closed. This switch is located at the front left-hand side of the cooling chassis (Figure 12). It can be reached by removing the front panel.
The master unit is furnished with a 50 VA transformer that is capable of handling up to 7 slave units. If
additional slave units are to be added, a larger eld
supplied transformer must be mounted external to the unit. The master and slave units draw 5.6 VA each. Furnish a transformer to handle the number of slaves installed, plus the master unit.
2. When using a programmable wall thermostat, connect the common terminal of the thermostat to terminal A of the
unit terminal board. Refer to the instructions furnished
with the thermostat to locate the common terminal.
Remote Mounted Thermostat Installation (Sizes 007–012 Only)
Units that are furnished with remote mounted thermostats should be wired as shown in Figure 22. The connections for
Note: It may be necessary to reduce the number of
slave units connected to the master or eld supply
a larger transformer when using a programmable thermostat.
eld wiring are on a seven-position terminal board located on
the face of the control box. Other considerations for remote mounted thermostat are as follows:
Check the VA draw of the chosen thermostat, plus the
VA draw of the master and slave units to be sure the total doesn’t exceed 50 VA power draw. Slave units are
1. If slave units are to be employed, remove the jumper
connected as described in #1 above.
from terminals A to C of the slave unit. Connect terminal
A of the master unit to the corresponding terminal A of the slave unit as shown in Figure 22.
Figure 22: Remote Mounted Thermostat Wiring Connections
Manual Changeover Thermostat Automatic Changeover Thermostat Thermostat Part No. 0046736101 Thermostat Part No. 0060685101
Subbase Part No. 0046742100 Subbase Part No. 0002005963
IM 1068 / Page 16 of 32
TC1 Room Thermostat
TC2 Night Setback Thermostat (NSB)
TC3 Heat Fan Lockout
TC4 Low Ambient Lockout
VM Valve Motor
WN Wire Nut
R4 Relay, Guest Room Control (GRC)
R5 Relay, Hot Water Valve
R6 Relay, Control
R7 Relay, Night Setback (NSB)
S1 Control Switch
S2 Fan Speed Switch
S3 Fan Cycle Switch
S4 Damper Switch
T1 Transformer
TB1 Terminal Block, Control Box
C1 Capacitor, Indoor Fan
C2 Capacitor, Outdoor Fan
C3 Capacitor, Compressor
GRC Guest Room Control
HL High Limit
HTR Heater
MP Motor Protector
NSP Night Setback Control
P1 Plug, Control Box/Heat Section
to Cool Section
TB2 Terminal Board (24V), Control Box
TB3 Terminal Board, Heat Section
TB4 Terminal Board, Cool Section
TB6 Terminal Box
R1 Relay, Heat
R2 Relay, Cool
R3 Relay, Night Setback (NSB)
Typical Wiring Diagrams
Standard Chassis With Electric Heat & MCO Controls (Sizes 007—012)
COOL SECTION CONTROL BOX HEAT SECTION
S1 Switch Contact Positions
Unit Mounted Manual Changeover
Catalog 1068 / Page 17 of 32
TC1 Room Thermostat
TC2 Night Setback Thermostat (NSB)
TC5 Freezestat
VM Valve Motor
WN Wire Nut
Note: Large heat shown. Refer to unit diagram for
details of small or medium heat.
R3 Relay, Cooling
R4 Relay, Indoor Fan Motor
R5 Relay Heating 1st Stage
R6 Relay, Heating 2nd Stage
R7 Relay, Night Setback (NSB)
R9 Relay, Hot Water Valve
S1 Control Switch
S4 Damper Switch
T1 Transformer
TB2 Terminal Box
TB3 Terminal Box
TB4 Terminal Box
TB5 Terminal Box
TB6 Terminal Box
C1 Capacitor, Indoor Fan
C2 Capacitor, Outdoor Fan
C3 Capacitor, Compressor
F1 Fuse
HL High Limit
HTR Heater
MP Motor Protector
P1 Plug, Heat Section to Cool Section
P2 Plug, Heat Section to Control Box
P3 Plug, PC Board
P4 Plug, on Master Wire Harness
P5 Plug, on Master Wire Harness
R1 Relay, Run
R2 Relay, Outdoor Fan Motor
Standard Chassis With Electric Heat & MCO Controls (Size 019)
COOL SECTION CONTROL BOX HEAT SECTION
Catalog 1068 / Page 18 of 32
S1 Switch Contact Positions
Unit Mounted Manual Changeover
TC1 Room Thermostat
TC2 Night Setback Thermostat (NSB)
TC3 Heat Fan Lockout
TC4 Low Ambient Lockout
VM Valve Motor
WN Wire Nut
R4 Relay, Guest Room Control (GRC)
R5 Relay, Hot Water Valve
R6 Relay, Control
R7 Relay, Night Setback (NSB)
S1 Control Switch
S2 Fan Speed Switch
S3 Fan Cycle Switch
S4 Damper Switch
T1 Transformer
TB1 Terminal Block, Control Box
C1 Capacitor, Indoor Fan
C2 Capacitor, Outdoor Fan
C3 Capacitor, Compressor
GRC Guest Room Control
HL High Limit
HTR Heater
MP Motor Protector
NSP Night Setback Control
P1 Plug, Control Box/Heat Section
to Cool Section
TB2 Terminal Board (24V), Control Box
TB3 Terminal Board, Heat Section
TB4 Terminal Board, Cool Section
TB6 Terminal Box
R1 Relay, Heat
R2 Relay, Cool
R3 Relay, Night Setback (NSB)
Standard Chassis With Hot Water Heat & MCO Controls (Sizes 007—012)
COOL SECTION HEAT SECTION CONTROL BOX
S1 Switch Contact Positions
Unit Mounted Manual Changeover
Catalog 1068 / Page 19 of 32
TC1 Room Thermostat
TC2 Night Setback Thermostat (NSB)
TC5 Freezestat
VM Valve Motor
WN Wire Nut
R3 Relay, Cooling
R4 Relay, Indoor Fan Motor
R5 Relay Heating 1st Stage
R6 Relay, Heating 2nd Stage
R7 Relay, Night Setback (NSB)
R9 Relay, Hot Water Valve
S1 Control Switch
C1 Capacitor, Indoor Fan
C2 Capacitor, Outdoor Fan
C3 Capacitor, Compressor
F1 Fuse
HL High Limit
HTR Heater
MP Motor Protector
S4 Damper Switch
T1 Transformer
TB2 Terminal Box
TB3 Terminal Box
TB4 Terminal Box
TB5 Terminal Box
TB6 Terminal Box
P1 Plug, Heat Section to Cool Section
P2 Plug, Heat Section to Control Box
P3 Plug, PC Board
P4 Plug, on Master Wire Harness
P5 Plug, on Master Wire Harness
R1 Relay, Run
R2 Relay, Outdoor Fan Motor
Standard Chassis With Hot Water & MCO Controls (Size 019)
COOL SECTION CONTROL BOX HEAT SECTION
Catalog 1068 / Page 20 of 32
S1 Switch Contact Positions
Unit Mounted Manual Changeover
TC1 Room Thermostat
TC2 Night Setback Thermostat (NSB)
TC3 Heat Fan Lockout
TC4 Low Ambient Lockout
VM Valve Motor
WN Wire Nut
R4 Relay, Guest Room Control (GRC)
R5 Relay, Hot Water Valve
R6 Relay, Control
R7 Relay, Night Setback (NSB)
S1 Control Switch
S2 Fan Speed Switch
S3 Fan Cycle Switch
S4 Damper Switch
T1 Transformer
TB1 Terminal Block, Control Box
C1 Capacitor, Indoor Fan
C2 Capacitor, Outdoor Fan
C3 Capacitor, Compressor
GRC Guest Room Control
HL High Limit
HTR Heater
MP Motor Protector
NSP Night Setback Control
P1 Plug, Control Box/Heat Section
to Cool Section
TB2 Terminal Board (24V), Control Box
TB3 Terminal Board, Heat Section
TB4 Terminal Board, Cool Section
TB6 Terminal Box
R1 Relay, Heat
R2 Relay, Cool
R3 Relay, Night Setback (NSB)
Standard Chassis With Steam Heat & MCO Controls (Sizes 007—012)
COOL SECTION HEAT SECTION CONTROL BOX
S1 Switch Contact Positions
Unit Mounted Manual Changeover
Catalog 1068 / Page 21 of 32
TC1 Room Thermostat
TC2 Night Setback Thermostat (NSB)
TC5 Freezestat
VM Valve Motor
WN Wire Nut
R3 Relay, Cooling
R4 Relay, Indoor Fan Motor
R5 Relay Heating 1st Stage
R6 Relay, Heating 2nd Stage
R7 Relay, Night Setback (NSB)
R9 Relay, Hot Water Valve
S1 Control Switch
C1 Capacitor, Indoor Fan
C2 Capacitor, Outdoor Fan
C3 Capacitor, Compressor
F1 Fuse
HL High Limit
HTR Heater
MP Motor Protector
S4 Damper Switch
T1 Transformer
TB2 Terminal Box
TB3 Terminal Box
TB4 Terminal Box
TB5 Terminal Box
TB6 Terminal Box
P1 Plug, Heat Section to Cool Section
P2 Plug, Heat Section to Control Box
P3 Plug, PC Board
P4 Plug, on Master Wire Harness
P5 Plug, on Master Wire Harness
R1 Relay, Run
R2 Relay, Outdoor Fan Motor
Standard Chassis With Steam Heat & MCO Controls (Size 019)
COOL SECTION CONTROL BOX HEAT SECTION
Catalog 1068 / Page 22 of 32
S1 Switch Contact Positions
Unit Mounted Manual Changeover
Standard Chassis With Electric Heat & 24V Wall Stat (Sizes 007—012)
TC2 Night Setback Thermostat (NSB)
TC3 Heat Fan Lockout
TC4 Low Ambient Lockout
VM Valve Motor
WN Wire Nut
R4 Relay, Guest Room Control (GRC)
R5 Relay, Hot Water Valve
R6 Relay, Control
R7 Relay, Night Setback (NSB)
S2 Fan Speed Switch
S3 Fan Cycle Switch
S4 Damper Switch
T1 Transformer
TB1 Terminal Block, Control Box
TB2 Terminal Board (24V), Control Box
C1 Capacitor, Indoor Fan
C2 Capacitor, Outdoor Fan
C3 Capacitor, Compressor
GRC Guest Room Control
HL High Limit
HTR Heater
MP Motor Protector
NSP Night Setback Control
P1 Plug, Control Box/Heat Section
to Cool Section
TB3 Terminal Board, Heat Section
TB4 Terminal Board, Cool Section
TB6 Terminal Box
TC1 Room Thermostat
R1 Relay, Heat
R2 Relay, Cool
R3 Relay, Night Setback (NSB)
COOL SECTION CONTROL BOX HEAT SECTION
Catalog 1068 / Page 23 of 32
TC1 Room Thermostat
TC2 Night Setback Thermostat (NSB)
TC3 Heat Fan Lockout
TC4 Low Ambient Lockout
VM Valve Motor
WN Wire Nut
R4 Relay, Guest Room Control (GRC)
R5 Relay, Hot Water Valve
R6 Relay, Control
R7 Relay, Night Setback (NSB)
S1 Control Switch
S2 Fan Speed Switch
S3 Fan Cycle Switch
S4 Damper Switch
T1 Transformer
TB1 Terminal Block, Control Box
C1 Capacitor, Indoor Fan
C2 Capacitor, Outdoor Fan
C3 Capacitor, Compressor
GRC Guest Room Control
HL High Limit
HTR Heater
MP Motor Protector
NSP Night Setback Control
P1 Plug, Control Box/Heat Section
to Cool Section
TB2 Terminal Board (24V), Control Box
TB3 Terminal Board, Heat Section
TB4 Terminal Board, Cool Section
TB6 Terminal Box
R1 Relay, Heat
R2 Relay, Cool
R3 Relay, Night Setback (NSB)
Standard Chassis With Hot Water Heat & 24V Wall Stat (Sizes 007—012)
COOL SECTION CONTROL BOX HEAT SECTION
Catalog 1068 / Page 24 of 32
TC1 Room Thermostat
TC2 Night Setback Thermostat (NSB)
TC3 Heat Fan Lockout
TC4 Low Ambient Lockout
VM Valve Motor
WN Wire Nut
R4 Relay, Guest Room Control (GRC)
R5 Relay, Hot Water Valve
R6 Relay, Control
R7 Relay, Night Setback (NSB)
S1 Control Switch
S2 Fan Speed Switch
S3 Fan Cycle Switch
S4 Damper Switch
T1 Transformer
TB1 Terminal Block, Control Box
C1 Capacitor, Indoor Fan
C2 Capacitor, Outdoor Fan
C3 Capacitor, Compressor
GRC Guest Room Control
HL High Limit
HTR Heater
MP Motor Protector
NSP Night Setback Control
P1 Plug, Control Box/Heat Section
to Cool Section
TB2 Terminal Board (24V), Control Box
TB3 Terminal Board, Heat Section
TB4 Terminal Board, Cool Section
TB6 Terminal Box
R1 Relay, Heat
R2 Relay, Cool
R3 Relay, Night Setback (NSB)
Standard Chassis With Steam Heat & 24V Wall Stat (Sizes 007—012)
COOL SECTION CONTROL BOX HEAT SECTION
Catalog 1068 / Page 25 of 32
Scheduled Maintenance
Incremental conditioners are built to last. With proper care, the unit should provide uninterrupted service for many years. Scheduled maintenance of this equipment, as described below, is the key to the equipment’s longevity.
Air lters must be cleaned at regular intervals. Twice
annually may be adequate in some areas while twice monthly may be required in others. Areas with high dirt and lint
content or heavy usage of units require more frequent lter
maintenance that those areas of relatively clean operating or low usage conditions. Unit malfunction may occur if air
lters are not kept clean. The standard lter supplied with the Type K unit is a permanent wire mesh type. This type of lter should be rinsed with hot water and a mild detergent. Let dry and oil lightly to
enhance dust collecting ability.
The Type K is also available with a carbon lter, a zeolite lter or electrostatic lter. The electrostatic lter is renewable
by rinsing with hot water and replacing in the unit once dry.
The carbon or zeolite lters must be discarded and replaced.
The frequency of this replacement depends on the air quality
of the room being ltered. Rooms with heavy smoke or ammonia content will require more frequent lter changes
than rooms with minimal degrees of smoke or ammonia.
3. Unplug the chassis from the control box and remove the
chassis from the wall sleeve. Replace with spare chassis
or weatherplate.
4. Move chassis to maintenance area and check all seals, wires, and insulation and repair as required.
5. Cover motor and protect all electrical components before
washing dirt from chassis.
6. Clean condensate drain and clear weep holes.
7. Dry equipment thoroughly, especially electric parts and
insulation.
8. Clean any rust spots with steel wool and paint with rust
inhibiting paint.
9. Check all fasteners and tighten if necessary.
10. Check the motor nameplate for routine oiling
instructions.
11. Test run chassis before reinstalling or returning to spare parts stock.
Note: When replacing the standard lter with an optional carbon, electrostatic, or zeolite lter, compress the lter brackets slightly. The optional lters are slightly thinner than the standard lter and will stay in place
better if the brackets are squeezed slightly.
It is recommended that the chassis be removed every year for a thorough check-up. The heat section need not be removed but should be inspected or cleaned if necessary. Should the heat section blowers or motor need service, the entire fan board can be easily removed from the unit for service. To access the unit for cleaning or service, proceed as follows:
WARNING
!
Residential and institutional cleaning compounds can cause permanent damage to the packaged terminal unit. To avoid damage to unit controls and heat transfer surfaces, do not spray cleaning compounds onto the return air opening or unit controls. Normal cleaning can be accomplished by wiping the unit surface with a damp cloth. When using cleaning compounds on
carpets,oorsorwalls,turntheunitofftoavoiddrawingpotentially
damaging vapors into the package terminal unit.
1. Disconnect power to the unit.
2. Remove the front panel and the kickplate.
IM 1068 / Page 26 of 32
Recommended Spare Parts
An advantage of the Incremental system is that failure of any one part affects only one Incremental conditioner and does not interrupt the operation of the rest of the system. A further advantage is that a failed part can be quickly and easily replaced, thus minimizing the inoperative time of the equipment. This is so, however, only if a replacement part is quickly available. In order to replace a failed part quickly and keep all Incremental conditioners in good operating condition, McQuay International recommends that at the time Incremental conditioners are purchased, owners arrange for a small stock of replacement parts. Where an owner carries such a stock, immediate replacement of a defective part is possible. The defective part can then be returned to McQuay International or one of its authorized service stations. So long as it is still in warranty, it is repaired or replaced and returned to the owner without cost for shop labor and material. Thus, the stock of replacement parts is constantly replenished. To the right is listed the kind of parts which McQuay International recommends be carried in stock, together with the quantity of parts recommended per 100 Incremental conditioners installed.
Qty. Per Part Name 100 Units
Cooling Chassis ..............................................................1
Compressor Overload Device .........................................1
Compressor Running Capacity .......................................1
Indoor Fan Motor ............................................................1
Outdoor Fan Motor .........................................................1
Outdoor Fan Motor Capacitor .........................................1
Push button Switch .........................................................2
Damper Switch ................................................................2
Thermostat ......................................................................2
Knob for Thermostat .......................................................6
Control Relay ..................................................................2
Damper Motor .................................................................2
Hydronic Valve ...............................................................4
Spare Filter ....................................................................10
Touch-up Paint (1 Pt. Spray Can) ...................................1
For the current spare parts list, and applicable prices, see our
McQuay representative or write McQuayService, P.O Box
1551, Minneapolis, MN 55440.
IM 1068 / Page 27 of 32
Troubleshooting Chart
These items should be checked by a qualied service technician only.
Trouble Cause Cure
1. Blowers won't operate on Cool.
2. Blowers operate on Cool, but compressor does not start.
3. Blowers run on Cool and compressor starts, but stops after a short interval.
a. No power.
b. Faulty push-button switch. c. Loose connections at push-button switch.
a. Thermostat set too high. b. Heat valve is open and heat is on. c. Low voltage. d. Faulty push-button switch. e. Faulty connection at push-button switch. f. Defective wiring to thermostat. g. Loose connections at compressor terminals. h. Wiring to compressor terminals defective. i. Loose connections in compressor overload device. j. Starting capacitor malfunctions (open circuited, short circuited or loss of capacity). k. Defective compressor motor (short circuited, open circuited, grounded).
a. Operation of overload device due to overloaded compressor motor.
a. Check supply line fuses, circuit breakers, and be sure the power is on. Blown fuses would indicate circuit overloading, a short circuit, or a grounded condition in the circuit. Voltage supply to the equipment should be checked. Voltage under load must be within 10% of voltage given on data plate. b. Replace. c. Tighten.
a. Adjust.Rotatecontrolknobto“Cooler.”
b. Close heat valve. c. Check as above. d. Replace. e. Tighten. f. Replace. g. Tighten. h. Replace. i. Tighten j. Replace.
k. *Ship cooling chassis prepaid to nearest McQuay authorized warranty station.
a. Check voltage supply. Clean condenser inside and out. Check at outside face of condenser for recirculation of
 condenserair.Putair“splitters”in,ifmissing.Check
to make sure condenser blower/fan is operating properly. Check compressor for short circuit. If defective, *ship cooling chassis to nearest McQuay authorized warranty station.
4. Blowers run on Cool and compressor starts and runs, but compressor occasionally stops (on overload device).
5. Compressor starts and runs on Cool, but blowers do not run.
6. Compressor starts and runs on Cool, but fan motor starts, then stops.
7. Equipment gives electrical shock.
8. Insufcientcooling
capacity.
a. Low voltage due to overloaded circuits within building or throughout the local power system. Due to varying power demands, this condition might exist only at certain times during the day or on very hot days.
b. Highvoltageduetouctuationsinlocalpowersystem;
usually occurs at low load periods of the day. c. Partial short circuit in compressor motor. Under normal loading, a compressor with a partial short circuit might
 appeartobeoperatingallright;increasedcondensingair
temperature might then cause a short.
a. Faulty push-button switch. b. Open circuited blower motor. c. Blower rubbing against its housing. d. Bearings on blower motor seized.
e. Loose connection at push-button switch.
a. Operation of the internally connected overload device due to a short circuit in blower motor. b. Windings, rubbing of blower motor or lack of lubrication in blower motor bearings.
a. Grounded electrical circuit.
a. Equipment standing too long without being run.
b.Insufcientairowthroughcondenserdueto:
1) Dirty condenser.
2) Obstructed louvers on outer cabinet or wall box.
3) Condenser blower/fan not running.
4) Condenser blower/fan not up to speed.
5) Condenser blower/fan slipping on motor shaft.
6) Recirculation of condenser air.
c. Insufcientairowthroughevaporatordueto:
1) Dirty evaporator.
2) Ice on evaporator coils.
 3)Dirtyairlter.
4) Obstructed discharge grilles.
5) Evaporator blower motor not running.
6) Evaporator blower motor not up to speed.
7) Evaporator motor slipping on motor shaft.
a. Run separate electric line to equipment. Consult local power company.
b. Consult local power company.
c. Ifconrmed,*shipcoolingchassisprepaidtonearestMcQuay
authorized warranty station.
a. Replace. b. Replace. c. Adjust blower motor or blower wheel position. d. Lubricate motor with SAE #10 oil. (It may be necessary to remove blower assembly to do this.) e. Tighten.
a. Adjust blower/fan wheel on shaft or blower motor mounting. Lubricate with SAE #10 oil (see above). b. Adjust blower wheel or motor or replace wheel.
a. Eliminate ground.
a. If the air conditioner is allowed to stand for an extended length of time without being run on Cool, it is possible for all the refrigerant to become absorbed in the oil inside the compressor and refrigeration circuit. If this should happen, there will be no cooling until the necessary working pressures have been established. This will take about 5 minutes of continuous running. b.
1) Clean.
2) Remove obstructions.
3) Correct as in #5.
4) Check for correct voltage. Oil blower motor if necessary.
5) Adjust blower position and tighten setscrew.
6) Correct as in #3. c.
1) Clean.
2) Turn equipment off to let ice melt.
3) Clean or replace.
4) Remove obstructions.
5) Correct as in #1.
6) Check for correct voltage. Oil motor is necessary.
7) Adjust blower wheel position and tighten setscrew.
*If equipment is in warranty.
IM 1068 / Page 28 of 32
Troubleshooting Chart
These items should be checked by a qualied service technician only.
Trouble Cause Cure
8. Insufcientcoolingcapacity
(continued).
9. Too much cooling.
10.“Sweating”
11. Blowers won't operate on Heat.
12. **Equipment is noisy.
13.Insufcientornoheat
d. Heat load in room exceeds capacity of equipment. e. Windows and doors in room are open. f. Compressor not pumping, indicated by:
1) Low wattage.
2) Condenser not warm, evaporator only partially cool, or not at all. g. Restricted capillary tube or strainer, indicated by:
1) Frost on capillary tube or strainer.
2) Low wattage.
3) Condenser not warm.
4) Evaporator partially frosted, only partially cool, or not at all.
a. Thermostat set too low. b. Defective thermostat.
a. Condensate drain from evaporator to condenser plugged. b. Insulating seals on equipment damaged. c. Evaporator blower motor not up to speed. d. Evaporator blower incorrectly positioned.
a. No power. b. Heat is off (equipment with heat fan lockout). c. Faulty push-button switch. d. Loose connections at push-button switch. e. Thermostat set too low.
a. Blower rubbing against enclosure.
b. Blower motor bearings are dry. c. Loose blower hold-down nuts on motor-bracket assembly. d. Refrigerant absorbed in compressor oil after extended shutdown. e. Equipment improperly installed. f. Damper solenoid hums.
g. Loose terminal box cover on side of compressor. h. Loose electrical components. i. Copper tubing vibrating. j. Harmonics.
k. Loose sheet metal parts.
a. No steam or hot water being applied. b. No Power.
c. Faulty push-button switch. d. Loose connection at push-button switch. e. Thermostat set too high. f. Thermostat faulty. g. No power output on transformer secondary. h. In-operative valve.
1) Steam valve normally closed.
2) Hot water valve normally closed.
d. Refertooriginalloadcalculations;recalculateheatload.
e. Close them. f. * Ship cooling chassis prepaid to nearest McQuay authorized warranty station.
g. * Ship cooling chassis prepaid to nearest McQuay authorized war
ranty station.
a. Adjust. b. Replace.
a. Removeobstructionstowaterow.
b. Adjust or replace. c. Check for correct voltage. Oil motor if necessary. d. Adjust.
a. Correct as in #1. b. Open heat valve or turn on heating system. c. Replace. d. Tighten.
e. Adjust–rotatecontrolknobto“Warmer”.
a. Adjust fan position on motor shaft to reposition fan motor bracket assembly. b. Lubricate with SAE #19 oil or replace motor. c. Align blower assembly and tighten nuts. d. Noise will disappear after equipment runs awhile. e. Make necessary adjustments to components. f. Check for proper adjustment. Apply silicone oil or grease to gap between solenoid and armature. g. Tighten. h. Fasten securely. I. Adjust by bending or applying tape. j. Occasionally equipment will have noisy operation for no apparent
reason. Inspect ion has revealed no loose components that might be the source of the noise. Due to the action of the compressor, it is possible to have internal noise develop if the refrigerant tubing has become bent even slightly. To distinguish this condition from the simple rattle producing vibration caused by loose screws, nuts, and other components, grasp the refrigerant tubing at various points throughout the system until a point is found where the noise is eliminated or reduced. Bend the copper tubing very gently until the noise disappears.
k. Tighten.
a. Contact building management. b. Check power supply line fuses, circuit breakers. Blow fuses would
indicate circuit overloading, a short circuit, or a grounded condition in
the circuit. c. Replace. d. Replace wire or tighten.
e. Adjust–rotateknobto“Warm”.
f. Replace. g. Replace. h.
 1)Temporarilylockvalveopen;replace.
2) Replace.
-
IM 1068 / Page 29 of 32
Approximate Shipping Weights
Cooling Chassis
Size 007 ........................................................................ 137 lbs.
Size 009 ........................................................................ 137 lbs.
Size 012 ........................................................................ 143 lbs.
Size 019 ........................................................................ 228 lbs.
Hydronic Heat Section With Control
Size 007 .......................................................................... 65 lbs.
Size 009 .......................................................................... 65 lbs.
Size 012 .......................................................................... 65 lbs.
Size 019 .......................................................................... 77 lbs.
Electric Heat Section With Control
Size 007 .......................................................................... 60 lbs.
Size 009 .......................................................................... 60 lbs.
Size 012 .......................................................................... 60 lbs.
Size 019 .......................................................................... 70 lbs.
Wall Box With Rear Extension of:
Sizes 007–012 2½'' ...................................................... 45 lbs.
3½" ...................................................... 46 lbs.
Size 019 2½'' ...................................................... 57 lbs.
3½" ...................................................... 59 lbs.
Room Cabinet
Sizes 007–012 7¼" ...................................................... 44 lbs.
8¼'' ...................................................... 48 lbs.
Size 019 8½'' ...................................................... 60 lbs.
Louver
007–012............................................................................ 6 lbs.
Size 019 ............................................................................ 9 lbs.
IM 1068 / Page 30 of 32
IM 1068 / Page 31 of 32
Warranty
All McQuay equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local McQuay Representative for warranty details. Refer to Form 933-43285Y. To find your local McQuay Representative, go to www.mcquay.com.
This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.mcquay.com.
Products Manufactured in an ISO Certified Facility.
© 2010 McQuay International • www.mcquay.com • (800) 432-1342 Catalog 1068 (3/10)
Loading...