McQuay IM-811 Installation Manual

Installation and Maintenance Manual IM-811
AHP Split System Heat Pump
7-1/2 & 10 TON
Group: Unitary
Part Number: IM-811
Date: August 2005
Supersedes: March 2005
IM-811 Page 1
Table of Contents
MODEL NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . 3
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
GENERAL WARNINGS . . . . . . . . . . . . . . . . . . . . . . . . . . 5
PRODUCT DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . 6
DUCKWORK CONSIDERATIONS . . . . . . . . . . . . . . . . . 6
SITE SELECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
TYPICAL INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . 7
RIGGING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
UNIT CORNER WEIGHT . . . . . . . . . . . . . . . . . . . . . . . . . 7
REFRIGERANT TUBING . . . . . . . . . . . . . . . . . . . . . . . . . 7
ELECTRICAL WIRING. . . . . . . . . . . . . . . . . . . . . . . . . . . .9
SYSTEM EVACUATION AND CHARGING . . . . . . . . .11
SYSTEM EVACUATION . . . . . . . . . . . . . . . . . . . . . . . . .12
PRELIMINARY CHARGE ADJUSTMENT . . . . . . . . . .12
FINAL CHARGE ADJUSTMENT . . . . . . . . . . . . . . . . . .13
EXPANSION VALVE INDOOR COILS . . . . . . . . . . . . .14
DEFROST CONTROL (DC) . . . . . . . . . . . . . . . . . . . . . . .14
TROUBLE SHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . .15
TROUBLE SHOOTING - Heating . . . . . . . . . . . . . . . . . .16
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
"McQuay" is a registered trademark of McQuay International.
"Illustrations and information cover the McQuay International products at the time of publication and we reserve the right to make changes in
Page 2 IM-811
© 2004 McQuay International
design and construction at any time without notice."
MODEL NOMENCLATURE
M
A
N
0 1
0
A
odel
HP = Air Cooled Heat Pump
ominal Capacity (tons)
90 = 7-1/2 20 = 10
Table 1: Unit Nameplate Model Number Identifier
Unit Nameplate McQuay Model Number
CPLE090-3C AHP090APEY CPLE090-4C AHP090AQEY CPLE120-3C AHP120APEY CPLE120-4C AHP120AQEY
AHP 090
PEY
Future Use EER
E = 10.1
Voltage/Phase
P = 208-230/3/6 Q = 460/3/60
Vintage
IM-811 Page 3
INTRODUCTION
General Description
These installation instructions cover the outdoor installation of split system heat pumps from 7-½ to 10 tons. See the product catalog applicable to your model for information regarding specifications applicable to your model and accessories.
Receiving Inspection
McQuay products are carefully inspected prior to shipment and the carrier has assumed responsibility for loss or damage upon acceptance of the shipment.
Upon receiving your shipment, check all items carefully against the Bill of Lading. Inspect the unit and/or accessories for shipping damage as soon as they are received. Immedi ately file claims for loss or damage, either shipping or con­cealed, with the shipping company.
Check the unit nameplate to verify the model number and elec­trical characteristics are correct. In the event an incorrect unit is shipped, it must be returned to the supplier and must NOT be installed. The manufacturer disclaims all responsibility for the installation of incorrectly shipped units.
Codes and Regulations
This product is designed and manufactured to permit installa­tion in accordance with National Codes. System design should, where applicable, follow information presented in accepted industry guides such as the ASHRAE Handbooks. It is the installer' s responsibility to install the product in accordance with National Codes and/or prevailing local codes and regula tions. The manufacturer disclaims all responsibility for equip-
ment installed in violation of any code or regulations.
Important Message to the Owner
Read these instructions carefully and keep them near the prod­uct for future reference. Although these instructions are addressed primarily to the installer, useful maintenance infor mation is included. Have the installer acquaint you with the operation of the product and periodic maintenance require ments.
Recognize Safety Symbols, Words, and Labels
The following symbols and labels are used throughout this manual to indicate immediate or potential hazards. It is the owner's and installer's responsibility to read and comply with
-
all safety information and instructions accompanying these symbols. Failure to heed safety information increases the risk of property damage and/or product damage, serious personal injury or death. Improper installation, operation and mainte nance can void the warranty.
DANGER
Immediate hazards which WILL result in property damage, product damage, severe personal injury and/ or death.
WARNING
-
Hazards or unsafe practice CAN result in property damage, product damage, sever personal injury and/or death.
-
-
-
IMPORTANT
The United States Environmental Protection Agency (EPA) regulations cover introduction and disposal of refrigerants in this unit. Failure to follow those regulations can harm the environment and lead to substantial fines. Because regulations can change, a certified technician should perform any work done on this unit. If you have any questions, please contact the local office of the EPA.
Important Message to the Installer
This equipment is to be installed by an experienced installation company and fully trained personnel. Carefully read all instructions and take into account any special considerations prior to installing the unit. Give this manual to the owner and explain its provisions.
CAUTION
Hazards or unsafe practices which CAN result in property damage, product damage, and/or personal injury.
Replacement Parts
Replacement parts can be obtained by contacting McQuay at 1
-800-37-PARTS. When contacting McQuay for service or replacement parts, refer to the model number and serial num ber of the unit as stamped on the nameplate attached to the unit.
-
Page 4 IM-811
GENERAL WARNINGS
WARNING
Before servicing or installing this equipment, the electrical power to this unit must be in the "OFF" position. More than one disconnect may exist. Failure to disconnect power can cause electrical shock, serious personal injury or death.
WARNING
The unit must have an uninterrupted, unbroken electrical ground. Failure to properly ground can cause severe personal injury or death.
DANGER
Installation and service by trained, qualified technicians only. High pressure and electricity can cause severe personal injury or death. Observe ALL warnings contained in this manual and the labels/tags attached to the equipment.
WARNING
When installing or servicing this equipment wear protective gloves, gear and eyeware. Also observe special safety requirements (hard hats etc.).
CAUTION
To protect the unit when welding close to the painted surfaces, use a quenching cloth to prevent scorching or marring of the equipment finish.
IM-811 Page 5
PRODUCT DESCRIPTION
When matched with the appropriate air handler(s) or evapora­tor coil(s) the AHP090/120 heat pump complies with the mini­mum efficiency equirements found in ASHRAE 90.1-1999. See the product catalog for the indoor model selection recom mendation.
Units operate in the same manner as most heat pumps. How­ever, these products use a TXV in lieu of a flowrater/piston system for refrigerant management.
Units are intended for use with a single stage room thermo­stat. This thermostat is not supplied with this equipment. Only thermostats that use 24-volt control circuitry are to be used.
Table 2: Physical Data
Net Weight (Lbs.) 365 415
Shipping Weight (Lbs.) 390 440
Refrigerant R-22
Compressor Type Scroll
Quantity 1
Oil Charge Initial/Recharge 85/81 110/106
Condenser Fan Type Propeller
Fan Diameter (in) 26
Fan Motor Type Direct Drive PCS
Fan Motor (HP) 1
Fan Motor (RPM) 110 0
Nominal Cond. Airflow (CFM) 6600
Condenser Coil Material Riffled Copper Tubes / Al Fins
Face Area (Ft2)
Refrigerant Connections Sweat Type
Suction Line Connection (in) 1-3/8
Liquid Line Connection (in) 5/8
High Pressure Control (PSIG) 425 Cut-out / Manual Reset
Low Pressure Control (PSIG) 7 Cut-out / 25 Cut-in
Thermal Expansion Valve 1
AHP090 AHP120
30
DUCKWORK CONSIDERATIONS
For proper performance, size the indoor ductwork to accom­modate 375-425 CFM per ton of cooling with a static pressure not to exceed .5" WC. Inadequate ductwork that restricts air flow can result in improper cooling performance and compres­sor failure.
SITE SELECTION
This unit is designed for outdoor installations only.
Air Supply
Units are air-cooled heat pumps. To provide optimum unit performance, the installation site should provide unobstructed airflow. See Figure 1 for minimum clearances from other air­cooled condensers/heat pumps and obstructions such as walls or overhangs.
Figure 1. Recommended Clearances
60"
12"
-
12"
24"
Refrigerant System Requirements
The selected site should be no greater than 50’ below or 70’ above the evaporator section. For optimum performance, use the minimum length of interconnecting tubing. Where possi ble, minimize the amount of bends and turns.
Wiring and Tubing Protection
Electrical wiring and refrigerant tubing is to be protected from damage due to incidental contact, such as being walked upon.
Vibration and Sound Control
Units are engineered to produce the minimum sound and vibration. To minimize sound or vibration issues, securely mount the unit to a surface that is:
•Solid
• Greatest practical mass
•Ridged
• Minimum radiating surface
Where possible, the slab for a ground level unit should not be
­connected to the wall or the building.
Prohibited Locations
Do not locate this unit in the following locations:
• Inside a building
• Directly under a vent termination from a gas appliance
• Within 3 feet of a gas appliance vent
• Where water may rise into the unit
12"
-
Note: Adequate service clearances must also be consid-
ered.
Page 6 IM-811
TYPICAL INSTALLATION
A
Typical locations for the unit are slab mounted and roof mounted. For unit weight data, see the "Product Description" section of this manual.
Slab Mounting
The slab must be capable of supporting the weight of the unit. The slab should be a minimum of 6" wider than the unit in all directions. If required, the slab should be elevated to help avoid water damage due to flooding. Before installing the unit onto a slab, the wooden shipping skid must be removed.
Roof Mounting
Give careful consideration to the load carrying capability of the roof. If possible, locate the unit where walls or partitions can offer additional support. If doubt exists regarding the integrity of the roof or its supporting structure, consult a struc tural engineer.
RIGGING
WARNING
All panels must be in position and secured before lifting this equipment. Dislodged panels cause equipment damage, severe personal injury or death.
UNIT CORNER WEIGHT
Use Figure 3 and Table 3 for determining the unit corner weight. The unit net weight and shipping weight is provided in the “Product Description” section of this manual.
Figure 3. Unit Corner Weight
35.5"
D
C
35.5"
B
-
Table 3: Unit Corner Weight
Corner AHP090 AHP120
A 95 Lbs. 110 Lbs.
B 95 Lbs. 110 Lbs.
C 80 Lbs. 85 Lbs.
D 95 Lbs. 110 Lbs.
REFRIGERANT TUBING
41.5"
Figure 2. Rigging Unit for Lifting
When lifting the unit, use spreader bars (field supplied) to help avoid damage from lifting cables/straps. Use protective mate rial, such as plywood, behind the cables/straps to help avoid damage to the cabinet louvers.
Arrange the straps to form a central suspension point (see Fig­ure 2). When raising and setting the unit, observe all safety rules. When the unit is in position, the wooden shipping skid and all lifting materials must be removed.
CAUTION
Wrap service valves with a wet rag or similar approved thermal heat trap around the valve to avoid damage due to overheating.
WARNING
To avoid severe personal injury, wear protective clothing and eye protection when making any welded connection.
Preparing the Tubing
All cut ends are to be round, burr free and cleaned. Failure to follow this practice can result in refrigerant leaks.
Post Brazing
Quench all welded joints with water or a wet rag.
Piping Size
Using a carefully estimated length of refrigerant tubing (dis­tance between condenser and evaporator), use Table 4 to deter­mine the tubing diameter:
Table 4: Tubing Diameter For Refrigerant Tubing Length
-
Model
AHP090 5/8 1-1/8 5/8 1-3/8 5/8 1-3/8 5/8 1-3/8
AHP120 5/8 1-1/8 5/8 1-5/8 5/8 1-5/8 5/8 1-5/8
L = Liquid Line S = Suction Line * = Full Rating Line Size
0"-24’ *25’-49’ 50’-74’ 75’-99’
L S L S L S L S
Outside Diameter Line Size (in)
IM-811 Page 7
Suction Line Insulation
All suction lines must be insulated with a recognized tubing insulation that is a minimum of 3/8" thick.
Solder
Solder should consist of a minimum of 2% silver.
Hangers and Isolation
All refrigerant lines must be isolated from the structure and supported with hangers. See Figure 4 for details.
Figure 4. Hangers and Isolation
Inverted Suction Line Loop
When the condenser is located at the same level or above the evaporator section, an inverted loop must be employed on the suction line. This practice will prevent liquid refrigerant from migrating into the compressor during shutdown (see Figure 5).
Figure 5. Inverted Suction Line Loop
8'
50' MAX
LIQUID LINE
CONDENSING UNIT
INVERTED LOOP
EVAPORATOR BLOWER
SUCTION LINE
Condenser Above the Evaporator
When the condenser is located 4’ or greater above the evapora­tor section, a suction line oil trap is to be used at the base of the riser. An additional oil trap is to be added for each 20’ of verti cal riser. See the Figure 7.
Figure 7. Suction Line Oil Trap
CONDENSING UNIT
ADDITIONAL SUCTION LINE OIL
70' MAX
LIQUID LINE SUCTION LINE OIL TRAPS WHEN INDOOR UNIT IS 4 FEET OR MORE BELOW OUTDOOR UNIT
TRAP FOR EACH 20' RISE OF PIPE
EVAPORATOR BLOWER
Filter Drier and Sight Glass
A liquid line filter drier is factory installed. A sight glass/ moisture indicator is provided with the unit. This is to be field installed on the liquid line as close as practical to the service valve.
Holding Charge
Units are factory shipped with a 2-pound R-22 holding charge. When welding, introduce an inert gas (e.g. nitrogen) through the tubing to help prevent the formation of copper oxide inside the tubing.
TXV
For improved refrigerant management, the evaporator coil is to be equipped with a thermal expansion valve (TXV).
Liquid Line Solenoid
Add a field supplied liquid line solenoid to the liquid line as close as possible to the evaporator coil. The solenoid must be wired to close when the compressor stops to prevent refriger ant migration in the “OFF” cycle.
-
-
Evacuation and Charging
See the “Evacuation and Charging” section of this manual for
Oil Return
instructions.
To facilitate oil return to the compressor a horizontal suction line should be pitched (1/2" per 10’) toward the condensing unit (see Figure 6).
Figure 6. Suction Line Pitch
CONDENSING UNIT
Page 8 IM-811
PITCH SUCTION LINE TOWARD OUTDOOR UNIT 1/2" FOR EVERY 10' OF LINE
LIQUID LINE
EVAPORATOR BLOWER
ELECTRICAL WIRING.
WARNING
Before servicing or installing this equipment, the electrical power to this unit must be in the “OFF” position. More than one disconnect may exist. Failure to observe this warning can result in an electrical shock that can cause personal injury or death.
WARNING
The unit must have an uninterrupted, unbroken electrical ground. Failure to properly ground can result in severe personal injury or death.
CAUTION
To avoid risk of fire or equipment damage, use only copper conductors.
Inspection of the Building Electrical Service
This unit is designed for 3-phase operation. DO NOT OPER­ATE ON A SINGLE PHASE POWER SUPPLY. Measure the power supply to the unit. The supply voltage must be in agreement with the unit nameplate power requirements and within the range shown in Table 5.
Table 5: Minumum/Maximum Supply Voltage Range
Model Vol tag e
AHP090 208/230 187 253
AHP090 460 414 506
AHP120 208/230 187 253
AHP120 460 414 506
Voltage Balance
The supply voltage shall be unbalance (phase to phase) within 2%. To calculate the percentage of voltage unbalance use the following formula:
Percentage Voltage = 100 x Unbalance
Max. Voltage Devation From Avg.Voltage Avg. Voltage
Example
Avg. Voltage =(220 + 216 + 213) / 3
Max. Deviation from Avg. =220 - 216 = 4 % Voltage Unbalance = 100 x 4 / 216
Minimum Supply
Voltage
L1 - L2 = 220V
L2 - L3 = 216V L1 - L3 = 213V
=649 / 3 =216
= 400 / 216 = 1.8%
Maximum Supply
Voltage
Determine Wire Size
The selection of the appropriate supply wire size is important to the operation of the equipment. When selecting the wire size, the following are important elements of the decision:
• The wire size is sufficient to carry the Minimum Circuit Ampac­ity (MCA). The unit MCA can be found on the equipment name­plate and the following table.
Table 6: Minimum Circuit Ampacity
• The wire is appropriately sized to allow for no more than a 2%
• Refer to the latest edition of the National Electric Code or, in
Table 7: Maximum Allowable length in Feet to Limit Voltage drop to 2%*
*Based on NEC 1996
Example
Model Vol tag e MCA
AHP090 208/230 37.8
AHP090 460 18.8
AHP120 208/230 43.3
AHP120 460 22.2
voltage drop from the building breaker/fuse panel to the unit.
Canada, the Canadian Electric Code when determining the cor­rect wire size. The following table shows the current carrying
o
capabilities for copper conductors rated at 75
C with a 2% volt-
age drop.
Wire Size
(AWG)
14 75 50 37 NR NR NR NR NR
12 118 79 59 47 NR NR NR NR
10 188 125 95 75 63 54 NR NR
8 301 201 150 120 100 86 75 68
6 471 314 235 188 157 134 118 11 0
10 15 20 25 30 35 40 45
Min. Circuit Ampacity (MCA)
A 208/230 volt AHP120 is to be installed. The distance from the building breaker box to the unit is 75’. Calculate the minimum wire size assuming no more than 2% voltage drop.
MCA = 43.3 (from nameplate and table).
Applying previous table wire sizes less than #8 AWG can­not be used for circuits which have a rating of 45A. The #8 wire is not suitable because the maximum length for a 45A circuit is 68’. Solution, a #6 AWG wire is suitable up to 110’. Note: It is the contractors responsibility to follow the NEC (USA) or CEC (Canada) when sizing the service wire for this unit.
IM-811 Page 9
Service Disconnect Box
A service disconnect box is required as per NEC.
Fuse – HACR Breakers
Protection is to be provided by either fuses or HACR type breakers. Refer to the unit nameplate and the following table for the maximum overcurrent protection permitted.
Table 8: Maximum Overcurrent Protection
Model Vol tag e *Max. Fuse
AHP090 208/230 60
AHP090 460 30
AHP120 208/230 60
AHP120 460 35
* Fuse or HACR Breaker of same value.
Line Voltage Wiring
Run all line voltage wiring through conduit from the service disconnect box to the unit. Refer to the NEC (in Canada CEC) for the correct size conduit based on the wire size. The conduit must enter the control box through the hole provided in the bottom. Note: hole is sized for ¾” conduit. If permitted by code, flexible conduit is preferred to minimize vibration trans mission from the unit to the building.
Connect the line voltage wires to the L1, L2, and L3 terminals of the definite purpose contactor (located in the unit control box). Refer to the wiring diagram attached to the unit when making these connections. The unit wiring diagram is also included at the end of this manual.
The unit must be grounded. The electrical ground circuit must consist of an appropriately sized electrical wire connecting to the ground lug in the unit control box and wire to the building electrical service panel. Other methods of grounding are per mitted if performed in accordance with the National Electric Code (NEC)/American National Standards Institute (ANSI)/ National Fire Protection Association (NFPA) 70 and local/state codes. In Canada, electrical grounding is to be in accordance with the Canadian Electric Code CSA C22.1.
Low Voltage Connections
Units require a 5-conductor low voltage circuit from the room thermostat. The wires are to be no smaller than 18 AWG. The field connection for this circuit is to be made in the unit control box using wire nuts or other solderless connectors. See Figures 8 and 9 for a typical low voltage hook-up.
Figure 8. Single Stage Low Voltage Hook-up
THERMOSTAT
G
Y
OC
CONDENSING
UNIT
AHP090/120
YELLOW
ORANGE
RED
-
WHITE
BLUE
W2
R
Figure 9. Two Stage Low Voltage Hook-up
THERMOSTAT
Y
CONDENSING
UNIT
AHP090/120
OC
W1
W2
GR
-
YELLOW
ORANGE
RED
WHITE
BLUE
AIR
HANDLER
SAH090/120
GREEN
RED
BROWN
WHITE
BLUE
AIR
HANDLER
SAH090/120
GREEN
RED
BROWN
WHITE
BLUE
Page 10 IM-811
Control Box Components
See Figure 10 for the location of the electrical components.
Figure 10. Electrical Component Locations
SYSTEM EVACUATION AND CHARGING
WARNING
To avoid possible explosion, injury or death, refrigerants must be handled by trained, experienced qualified technicians only.
WARNING
Refrigerants are heavier than air. They can “push out” the oxygen in your lungs or in any enclosed space. To avoid suffocation or death.
• Never sniff refrigerant.
• Never purge refrigerant.
WARNING
If an indoor refrigerant leak is suspected, thoroughly ventilate the area and repair leak before beginning work.
WARNING
Liquid refrigerant can be very cold. To avoid possible frostbite or blindness, avoid contact and wear protective gloves and eyeware. If liquid refrigerant contacts your skin or eyes, seek medical help immediately.
Always follow EPA regulations. Never burn refrigerant as poisonous gas can be produced.
WARNING
To avoid possible explosion, use refrigerant cylinders properly:
• If you must heat a cylinder for faster charging, partly immerse it in warm water. Never apply flame or steam to the cylinder.
• Store cylinders in a cool, dry place. Never use a cyl­inder as a platform or a roller.
• Never add anything other than R-22 to an R-22 cyl­inder.
• Never fill a cylinder more than 80% full of liquid refrigerant.
• When removing refrigerant from a system, use only returnable (not disposable) service cylinders. Check the cylinder for its pressure rating and hydrostatic test date. Check the cylinder for any damage that may lead to a leak or explosion. If in doubt, do not use the cylinder.
Leak Test
WARNING
To avoid the risk of fire or explosion, never use oxygen, high pressure or flammable gas for leak testing of a refrigeration system.
1. Verify that both hand valves on the gauge manifold are closed relative to the center port (i.e., turned in all the way). Attach this gauge manifold to the service valves on
the unit.
WARNING
To avoid possible explosion, the line from the nitrogen cylinder must include a pressure regulator and a pressure relief valve. The pressure relief valve must be set to open at no more than 150 psig.
2. Connect a cylinder of dry nitrogen to the center port on the gauge manifold.
3. Open the hand valve a minimal amount on the line com­ing from the nitrogen cylinder.
4. Open the high pressure valve on the gauge manifold. Pressurize the refrigerant lines and the indoor coil to 150
psig (1034 kPA).
WARNING
To avoid possible explosion or equipment damage, do not exceed 150 psig when pressure testing.
After you reach 150 psig, close the valve on the nitrogen cylin­der. Disconnect it from the gauge manifold. If you plan to use an electronic leak detector, add a trace of R-22 to the system (if permitted by current EPA regulations).
5. Apply a soap solution on all connections and joints. If you see bubbles, you have a leak. Mark these locations.
6. Use the gauge manifold to carefully release the nitrogen from the system. If leaks are found, repair them. After repair, repeat the above pressure test. If no leaks exist, proceed to system evacuation.
IM-811 Page 11
SYSTEM EVACUATION
1. Connect the vacuum pump, high vacuum manifold set with high vacuum hoses, thermocouple vacuum gauge and charging cylinder as shown in Figure 10. Begin with all valves fully closed.
2. If service fill valves are used for evacuation, use a core
remover to lift the valve core. It provides greater effi ciency.
3. Confirm proper pump and gauge operation. Open the
shutoff valve that leads to the high vacuum gauge mani fold. Start the pump. When the compound gauge (low side) reading drops approximately 29 inches of vacuum, open the valve to the thermocouple vacuum gauge and evacuate until the gauge reads 250 microns or less.
4. Close the valve to the thermocouple vacuum gauge. This
avoids potential gauge damage from “pegging the meter”.
5. Open the high and low side valves on the gauge manifold.
Keeping the valve on the charging cylinder closed, open the valve on the gauge manifold that leads to the cylinder.
6. Evacuate the system to about 29 inches Hg as measured by
the compound (low side) gauge.
7. Open the valve to the thermocouple vacuum gauge. Evacu-
ate until the gauge reads 250 microns or less.
8. Close the valve to the vacuum pump. Wait five minutes,
then check the pressure on the thermocouple vacuum gauge:
• If the pressure is not more than 1500 microns, the system is leak-free and properly evacuated. Proceed to Step 9.
• If the pressure rises, but holds at about 5000 microns, mois­ture and non-condensibles are still present. Open the valve to the vacuum pump, and go back to Step 7.
• If the pressure rises above 5000 microns, a leak is present. Go back to “Leak Testing” section above
9. Close the valve to the thermocouple vacuum gauge. Close the valve to the vacuum pump. Shut off the pump.
Figure 11. System Evacuation Components
THERMOCOUPLE VACUUM GAUGE
DIAL-A-CHARGE
TO
RELATED
GAUGE
PORTS OF
COND. UNIT
LARGE DIAMETER
BRAIDED VACUUM
A. LOW SIDE VA LVE B. HIGH SIDE VALVE C. VACUUM PUMP D. THERMOCOUPLE GAUGE E. MANIFOLD GAUGE F. CHARGING CYLINDER
HIGH VACUUM
MANIFOLD
HOSES
CHARGING CYLINDER
LOW SIDE
GAUGE
HIGH VACUUM PUMP
A
HIGH SIDE
GAUGE
D
B
C
E
F
-
-
PRELIMINARY CHARGE ADJUSTMENT
CAUTION
See the wiring diagram or outdoor unit specification sheet to determine if this unit has a crankcase heater. If it does, you must connect electrical power to the unit for four hours before operating the compressor. Failure to do so can result in compressor damage.
CAUTION
During all installation and service work, follow all regulations of the Environmental Protection Agency. (This system uses R-22 - an HCFC [Hydrogenated Chlorofluorocarbon]). Violation of EPA regulations can result in environmental damage, fines or other penalties.
Use a male hex head wrench (5/16" for liquid) to carefully open the liquid valve stem on the unit. Use a service wrench or crescent wrench to open the suction ball valve. The valve is fully open with a 90-degree turn (i.e. the stem is inline with the valve flow direction).
The outdoor unit is factory charged with 2 lb. R-22.
CAUTION
Use only refrigerant that is certified to meet ARI Standard 700. Used refrigerant can cause compressor damage and will void the warranty. Most portable machines cannot clean used refrigerant well enough to meet this ARI Standard.
CAUTION
When adding additional refrigerant to a system, add only refrigerant vapor (not liquid) through the suction valve (low side) on the outdoor unit. Any other practice can cause compressor damage.
FINAL CHARGE ADJUSTMENT
CAUTION
Never operate the compressor with the suction valve closed to “test the compressor pumping efficiency”. In some cases, this can cause serious compressor damage.
For 25’ of line set, the 7-1/2-ton charge is approximately 17 lb. For 25’ of line set, the 10-ton charge is approximately 20 lb.
Do not start with these amounts.
For installations greater than 25’ of line set, the indoor unit air­flow, condensing unit location and number of tubing fittings will have an impact on final unit charge amount. Start with half of the 25’ line set charge and proceed.
Turn the electrical power on, and let the system run. Wait for the refrigerant pressures to stabilize.
Page 12 IM-811
EXPANSION VALVE INDOOR COILS
NOTE: EXPANSION VALVE BULB must be in place on
suction line and insulated.
Outdoor Temperature Over 60°F. When the outdoor tem­perature is above 60°F, charge the system with the room ther­mostat set in the “Cooling” mode and the fan operating in the “Auto” position.
Outdoor Temperature Less Than 60°F. If the outdoor temperature is less than 60°F, charge the unit with the room thermostat set in the “Heat” mode and the fan set in the “Auto” position.
System Charging – Cooling Mode
The following describes adjusting the refrigerant charge with the ambient temperature in excess of 60°F and the room ther mostat adjusted as indicated above.
At stabilized cooling conditions and with an outdoor tempera­ture of 60°F or higher, the system should have from 9°F to 13°F subcooling. For a proper subcooling reading, measure the refrigerant pressure and temperature at the outdoor unit liquid line service valve. If you have less than 9°F subcooling, add charge. If you have more than 13°F subcooling, remove charge.
While reaching the proper subcooling level, it is important to know the discharge line temperature. This temperature should be at least 80°F over ambient or the unit is flooding back to the compressor. If flooding (i.e. low discharge line temperature) occurs, adjust the valve stem on the expansion valve inward (clockwise viewing the end of the expansion valve). This will increase the super heat.
After achieving the proper subcooling and a sufficient dis­charge temperature, make small adjustments to the expansion valve stem to reach 8°F to 10°F of superheat. Adjusting the valve stem in (or clockwise) increases superheat. Adjusting the valve stem out (or counter clockwise) decreases superheat. If the system is performing properly, re-install the service port caps and the valve bonnets. With the valve opened, the valve bonnet is the primary seal against refrigerant leaks. Apply two drops of clean oil to the cap threads, allowing the oil to run down to the inner cap seal surface. Close the caps finger-tight. Then tighten the cap an additional two to three hex flats.
System Charging – Heating Mode
The following method can be employed as a method to check the system charge in the heating mode by measuring the hot gas discharge at the compressor.
1. Allow the system to operate for at least 20 minutes.
2. Attach and insulate an electronic thermometer to the hot gas discharge line mid way between the compressor and the reversing valve. Note: The thermometer must be well insulated to prevent ambient influences.
3. Adjust the charge to maintain a clear sight glass.
4. Allow the compressor to operate for about 10 additional minutes and measure the hot gas discharge temperature.
5. Using an additional electronic thermometer, measure the ambient.
6. Adjust the charge until the hot gas temperature equals 105° F + ambient (+ or – 5°F). Remove charge to increase the temperature.
Note: When adjusting the charge, allow the compressor to
operate for about 10 minutes before taking readings.
Note: Subsequent opening and replacing of the cap will
require only 1/2 to 1 hex flat. See the table below for the torque required for an effective seal on the valve bonnet (1/6 turn past finger tight).
Table 9: Cap Torqure
After closing the valve bonnet, perform a final refrigerant leak
-
Tubing Size Torque (Foot-Pounds)
5/8 14
1 3/8 16
test on the valves and sweat connections. Return the room thermostat to the desired settings.
DEFROST CONTROL (DC)
Units use a time/temperature method for defrost. A thermal sensor is attached to the condenser coil to determine the out door coil temperature. The coil temperature sensor is electri­cally “Normally Open” and is wired to the electronic defrost control that is located in the control box.
Both coil temperature and compressor run time determine defrosting of the outdoor coil. Adjustments to the defrost tim ing selection can be changed from the 60 minute factory set­ting to either 30 or 90 minutes by moving the jumper on the defrost control. To initiate a defrost, the following statements must be true:
• The defrost sensor must be closed.
• The compressor run time must equal the timing selection on the
defrost board.
Note: The compressor run time is accumulative during
multiple “heating” cycles. The timer will reset to zero only when the defrost sensor returns to an open condition. If the room thermostat is operating in the “EM HT” mode, no accumulation of compressor time is recorded.
During defrost, the following actions occur:
1. The reversing valve is energized and the heat pump oper­ates in the cooling mode.
2. The air handler auxiliary heat (if equipped) is activated.
3. The condenser fan motor is shut-off.
If the defrost cycle has not terminated after ten (10) minutes, the control will override the defrost sensor and revert to a heat ing mode.
The defrost control has test pins which can be useful when troubleshooting in the heating mode. These test pins accelerate the compressor run time counter. The suggested method for accessing this feature is:
A. Run unit in heat mode.
B. Check unit for proper charge.
Note: Bands of frost indicate low refrigerant charge.
C. Shut off power to unit.
-
-
-
IM-811 Page 13
D. Disconnect outdoor fan by removing the purple lead from
the Condenser Fan Defrost Relay.
E. Restart unit and allow frost to accumulate.
F. After a few minutes the defrost thermostat should close. To
verify the position of the thermostat check for 24V between “DFT” and “C” on the defrost board. Should the defrost thermostat fail to close after a heavy build-up of frost and the thermostat is less than 28°F, the thermostat is to be replaced.
G. After the thermostat has closed, short across the test pins
with a screwdriver blade until the reversing valve shifts. This could take up to 21 seconds depending upon the posi tion of the timing setting on the defrost board. Immediately remove the short upon the action of the reversing valve. Note: If this short is not removed immediately, the defrost activity will last only 2.3 seconds.
H. After defrost has terminated (up to 10 minutes) check the
defrost thermostat for 24V between “DFT” and “C”. This reading should be 0 V (open sensor).
I. Shut off power to the unit.
J. Replace outdoor fan motor wire removed in Step D.
Figure 12. Shunt Section Jumper
TROUBLE SHOOTING
WARNING
Troubleshooting can present hazards of electricity, rotating parts, sharp edges and weight. troubleshooting must be done by trained, experienced technicians only. Improper troubleshooting can result in equipment damage, severe personal injury or death.
IMPORTANT: Qualified installer/servicer only
When troubleshooting, the first step should always be to check for clean coils, clean filter(s) and proper airflow. Indoor air flow should be 375 to 425 CFM per ton of cooling based on
­the size of the outdoor unit. The most common way of estab
lishing indoor airflow is heating temperature rise. Indoor air­flow will then be (Heating output of equipment) / (1.1 x temp. rise). In other cases, measurement of external static pressure is helpful. For details, see the Installation Instructions for your indoor equipment.
CAUTION
3-Phase Scroll Compressor
The AHP090/120 condenser is equipped with a 3­phase scroll compressor. Improper phase can damage equipment.
-
-
SHUNT
SELECTION
JUMPER
If the unit sounds noisy and/or the suction and liquid pressures are almost equal, the compressor is operating in the reverse rotation. Reverse the two (2) incoming power supply leads.
Page 14 IM-811
Table 10: Trouble Shooting Analysis - Cooling
COMPLANT PROBABLE CAUSE REMEDY
1. High Head Pressure
2. Low Head Pressure
3. Low Suction Pressure
4. High Suction Pressure
5. Compressor will not start.
1. Excessive charge of refrigerant in system.
2. Inadequate supply of air across the condenser coil.
3. Non-condensate gases in the system.
1. System low on refrigerant.
2. Compressor valves broken.
1. Liquid line valve closed.
2. Restricted liquid line.
3. The bulb of the thermal expansion valve has lost its charge.
4. System low on refrigerant.
5. Dirty filters.
6. Coil frosted up.
7. Flash gas in the liquid line.
8. Quantity of air through evaporator not adequate.
1. Expansion valve stuck open.
2. Expansion valve bulb not in contact with suction line.
3. Suction and/or discharge valve leaking or broken.
1. Disconnect switch open.
2. Blow fuse or fuse at disconnect switch.
3. Thermostat set too high.
4. Selector switch in "Off" position.
5. Contactor and/or relay coils burned out.
6. Loose or open electrical connection in either the con­trol or power circuit.
1. Purge or pump-down excessive charge.
2. Make certain that coil is not fouled in any way, or that air is not re-circulating.
3. Purge these gases from the system. Recharge system, if necessary.
1. Charge system until sight glass is clear of bubbles.
2. Replace compressor.
1. Open the liquid line valve.
2. Replace filter-dryer.
3. Detach the bulb from the suction line and hold in one hand. If no liquid refriger­ant goes through the valve, replace the valve.
4. Test the unit for leaks. Add refrigerant until sight glass is free from bubbles, after repairing leak.
5. Clean or replace filter.
6. Defrost and clean coil. Clean or replace filters.
7. Excessive liquid line drop. Check liquid line size.
8. Increase the blower speed.
1. Correct valve action or replace the valve.
2. Fasten bulb securely to suction line.
3. Replace compressor.
1. Close the disconnect switch.
2. Check the cause of failure and replace the fuse.
3. Adjust to lower temperature.
4. Turn selector switch knob to "Cool" position.
5. Replace contactor and/or relay.
6. Inspect and secure all electrical connections.
TROUBLE SHOOTING - Heating
Common Causes of Unsatisfactory Operation of Heat Pumps on the Heating Cycle include:
Dirty Filters
Dirty filters or inadequate airflow through the indoor coil. Failure to keep clean filters and adequate airflow (375-425 CFM/ton) will cause excessive discharge pressures that may cause the high-pressure switch to function.
Low Return Air Temperatures
Return ductwork temperatures that are less than 60°F will cause low discharge pressure, low suction pressure and exces sive defrost cycling.
Undercharging
An undercharged system will cause low discharge pressure, low suction pressure and an accumulation of frost on the lower section of the outdoor coil.
Poor Termination of Defrost
The defrost sensor must make good contact with the outside coil return bend or a non-termination of defrost may occur.
Reversing Valve
A reversing valve may not function correctly for the following reasons:
1. Solenoid does not energize when voltage is present
Replace the reversing valve.
2. No voltage to the solenoid
Check the wiring.
3. The valve will not shift
-
a.Undercharged
Check for leaks
b.Valve body damage
Replace the reversing valve
c.Valve sticking
Replace the reversing valve
IM-811 Page 15
WIRING DIAGRAM
Page 16 IM-811
IM-811 Page 17
This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.mcquay.com.
www.mcquay.com • 800-432-1342
Loading...