McQuay IM 782-2 Installation Manual

Installation and Maintenance IM 782-2
Group: Destiny Air Handler
Destiny™ Air Handler
Sizes 002 to 030
Part Number: IM 782
Date: March 2007
© 2007 McQuay International
Contents
Smoke Control and Management Systems. . . . . . . . . . . . . . . . . . . 3
Receiving and Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Storing the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Installation Guidelines . . . . . . . . . . . . . . . . . . . . . . . 5
Attaching the Mixing Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Service Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Unit Leveling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Panels and Doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Panel Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Fan Section Doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Mounting Actuators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Reversing the Coil Handing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Reversing the Drive Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Hanging the Unit from a Ceiling . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Piping and Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Water Cooling Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Direct Expansion Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Steam Coils. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Water Heating Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Drain Pan Traps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Internal Isolation Assembly Adjustment . . . . . . . . . . . . . . . . . . . . 14
Before Operating the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Spring Mount Adjustments—Twin Fan Units . . . . . . . . . . . . 14
Electric Heat Section (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Open Coil Duct Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Single Point Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Quality Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Electric Heat KW Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Heater Amps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Electric Heat Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Overcurrent Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Thermal (Over temperature) Protection. . . . . . . . . . . . . . . . . 18
Fan Interlock Method: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Airflow Switch: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Electric Heat Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Field Power Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Supply Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Electrical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Operation Guidelines . . . . . . . . . . . . . . . . . . . . . . 20
Startup Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Before starting the unit: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
After first 48 hours of operation: . . . . . . . . . . . . . . . . . . . . . . 21
Operating Limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Fan Vibration Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Vibration Causes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Service and Maintenance . . . . . . . . . . . . . . . . . . . 22
Periodic Service and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . 22
Ball Bearing Lubrication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Fan Drive Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
VM and VP Variable Pitch Key Type Sheaves . . . . . . . . . . . 23
LVP Variable Speed Sheaves . . . . . . . . . . . . . . . . . . . . . . . . 23
MVP Variable Speed Sheaves . . . . . . . . . . . . . . . . . . . . . . . 25
Fan Drive Belt Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
General Rules of Tensioning . . . . . . . . . . . . . . . . . . . . . . . . . 26
Tension Measurement Procedure . . . . . . . . . . . . . . . . . . . . . 26
Coil Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Component Removal and Replacement . . . . . . . . . . . . . . . . . . . . 28
Panel Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Fan Section Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Coil Removal and Replacement . . . . . . . . . . . . . . . . . . . . . . 28
Warranty. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Warranty Return Material Procedure . . . . . . . . . . . . . . . . . . . 29
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

General Information

WARNING
Improper installation or maintenance can cause
equipment damage or personal injury.
Installation and maintenance must be performed by qualified personnel familiar with applicable codes and regulations, and experienced with this type of equipment.
AVERTISSEMENT
Une installation ou un entretien inadéquats peut endommager l’équipement ou entraîner des blessures personnelles. L’installation et l’entretien doivent être
exécutés par un personnel qualifié, familier avec les codes et règlements applicables et possédant de l’expérience avec ce type d’équipement.
CAUTION
SHARP EDGES AND COIL SURFACES
can cause personal injury. Avoid contact with them.
ATTENTION
Les bords tranchants et les surfaces des bobines sont un risque de blessure. Ne les touchez pas.
CAUTION
Destiny units are not designed to be weather resistant;
DO NOT install outdoors.
ATTENTION
Les Unités Destiny ne sont pas à l’épreuve des intempéries;
NE PAS les installer à l’extérieur.

Smoke Control and Management Systems

The system design and installation must follow accepted industry practice, such as described in the ASHRAE Handbook, the National Electric Code, and other applicable standards. The installation of this equipment must be in accordance with regulations of authorities having jurisdiction and all applicable codes. It is the responsibility of the installer
to determine and follow the applicable codes
WARNING
Improper smoke or fume air handling can result in severe personal injury or death.
A registered professional engineer must design and approve the air conditioner and air handler application to make sure smoke and fume control meet local fire codes and NFPA requirements for the specific building application. Due to the wide variation in building design and ambient operating conditions into which our products can be applied, we do not represent or warrant that our products will be fit and sufficient for smoke and fume control and management purposes. The owner and building designer must consult a registered professional engineer to satisfy themselves in this regard.
AVERTISSEMENT
Un traitement inadéquat de l’air contenant de la fumée peut entraîner des blessures personnelles ou même la mort.
Un ingénieur professionnel doit faire la conception et approuver l’unité de traitement d’air et son application pour s’assurer que le contrôle de la fumée rencontre les codes d’incendies locaux et les normes NFPA pour l’application spécifique du bâtiment. Dû à la grande diversité de conceptions des édifices ainsi que des conditions d’opération ambiantes dans lesquelles nos produits peuvent être appliqués, nous n’avançons ni ne garan-tissons que nos produits seront adéquats et efficaces quant au contrôle de la fumée. Le propriétaire et le concepteur du bâtiment doivent consulter un ingénieur professionnel à cet égard
McQuay IM 782-2 3
General Information

Receiving and Handling

1 Carefully check items against the bills of lading to verify
all crates and cartons were received. Carefully inspect all units for damage when received. Report visible and concealed damage immediately to the carrier and a file a claim for damage.
2 Destiny air handler units are thoroughly inspected before
leaving the factory. Install units carefully to prevent damage.
3 Leave enough space around the unit for proper
maintenance, filter removal, lubrication, belt adjustment, and removal of coils, if necessary.
4 Use flexible connections on the inlet and outlet duct
connections of the unit.
5 For 002 - 010 sized ceiling hung units, spring isolation of
the cabinet is recommended.
6 All fans are dynamically balanced before leaving the
factory. Carefully inspect fans for rough handling that can cause misalignment or a damaged shaft.
7 Adequately pitch and trap drain line from drain pan
connection.

Storing the Unit

Store unit on a level surface. If air handling units are to be stored for any period of time, it is important to rotate the fan wheel (quarterly, as a minimum) to prevent permanent distortion of drive components. Keep the fan bearings lubricated. Grease may settle in the lower part of the bearing, which may lead to oxidation on the upper portion of the bearing surface.
Store units indoors in a clean, dry environment on a level surface. Moisture, debris, and minerals can cause permanent damage to the cabinet and components. Do not allow coverings to trap moisture on the galvanized surface.
4 McQuay IM 782-2

Installation Guidelines

Attaching the Mixing Box

Mixing boxes ship with Destiny units as a field-installed option. Attach the mixing box to the intake end of the air handler using cleats included with the mixing box section.
Figure 1: Mixing Box Installation
Cleat locations
Install the cleats into the interior mounting frames, with the hardware included as shown in Figure 1.
Cleat installation
Cleat locations (sizes 015 and above)
McQuay IM 782-2 5
Installation Guidelines

Service Clearances

Leave adequate space around the unit for piping, coils, and drains. Always have access to at least one side of the unit for regular service and maintenance. See Figure 2 for servicing space requirements. Routine maintenance examples include filter replacement, drain pan inspection and cleaning, fan bearing lubrication, and belt adjustment. Provide sufficient space on the drive side of the fan and the connection side of the coil for shaft and coil removal, if necessary (refer to the “Coil Data” section in Catalog 580 for information about coil sizes). Both the fan drive and coil can be field modified to right or left hand to accommodate clearance restrictions. See “Reversing the Coil Handing” on page 9 and “Reversing the Drive Package” on page 11.
Figure 2: Servicing Space Requirements
Vertical unit
Width
Height
For routine maintenance, remove panels on either side of the unit. See “Panel Removal” on page 8. Optional service doors are available for the fan and filter sections. Allow sufficient space for service door(s) to swing completely open, or to meet the clearance requirement of the section it accesses, whichever is greater. Service doors are not interchangeable with access panels on the opposite side of the unit. Determine clearances before specifying doors.
Have at least 54" of clearance in front of electrical power devices (starters, VFDs, disconnect switches, and combination devices). Electrical power devices that are mounted on the side of the unit typically are 12" deep (see Figure 3).
Figure 3: Service Clearance for Electrical Power Devices
54"
Horizontal unit
Width of
fan section
Top view
coil section
Width of
12"
Width
30.00”
Height
Width
6 McQuay IM 782-2
Installation Guidelines

Rigging

Rig units using straps or a sling. Fasten strapping under the skid that ships with the section. If a field-installed mixing box is attached, adjust to balance the unit properly.
To avoid damage to the unit cabinetry, use spreader bars. Position spreader bars to keep cables from rubbing the frame, connections, or panels. Before hoisting into position, test lift for stability and balance. Avoid twisting or uneven lifting of the unit.
Figure 4: Rigged Unit on Skids
Horizontal unit

Unit Leveling

Place the equipment on a flat and level surface (or verify that
unit is level when hanging from the ceiling). Where the surface
irregularities allow the equipment to distort, shim the base of
the unit to a straight line. Distorted units can cause misfit or
binding of the doors and panels and improper draining of drain
pans.
Figure 5: Leveling the Unit
Horizontal unit
Vertical unit
Vertical unit
McQuay IM 782-2 7
Installation Guidelines

Panels and Doors

DANGER
Hazardous moving parts, high static pressure, and/or high voltage. Can cause severe injury or death.
Disconnect and lock ALL electric power off before entering or servicing unit. Unit may employ multiple power supplies and/or remote disconnects. Secure drive sheaves to prevent motors and fan from free wheeling. When leaving the unit, use screw or door handle locking mechanism provided to secure access panel closed and prevent unintentional entry.
DANGER
Pieces mobiles dangereuses, haute pression statique et/ ou de hautes tensions. Risques de blessures graves, voire mortelles.
Débranchez et verrouillez toutes les alimentation électriques avant de pénétrer ou d’intervenir sur cet appareil. Cet appareil peut étre alimenté par plusieurs sources etlou par l’intermédiaire de plusieurs disjoncteurs éloignés. Attachez les disques d’entrainement afin d’éviter que les moteurs et le ventilateur ne tournent librement. A Ia sortie de l’appareil, fermer le panneau d’accès avec Ia vis ou avec le mécanisme de verrouillage de Ia poignée de porte qui sont founis pour éviter toute entrée inopinée.

Fan Section Doors

1 Use a flat head screwdriver and rotate the screw 1/4 turn as
shown in Figure 7.
2 Rotate door handle 1/4 turn and open the door.
Figure 7: Fan Section Doors

Panel Removal

Destiny air handlers have pocket pull handles in alternate sections that allow side panels to be easily removed and handled. To gain access through a side panel, remove the fasteners along the sides of the panel and lift the panel off using the pocket pull handle. If the panel you are accessing does not have a pocket pull handle, remove an adjoining panel with a pocket pull handle and push the panel out from inside the unit.
Figure 6: Panel Removal

Mounting Actuators

The installing contractor is responsible for the mounting of all field-installed actuators. An actuator mounting plate is provided on the shaft side of the damper frame to accommodate many actuators. However, due to the number of options, size variations, and arrangements available, some actuators may require alternate field provided mounting hardware. Provide proper support for the actuator to avoid excessive stress in the cabinet, linkage, or damper shafts.
8 McQuay IM 782-2
Installation Guidelines

Reversing the Coil Handing

Coil connections can be switched to the opposite side of the unit by rotating the coil(s) 180 degrees side to side and reworking the coil section panel on the opposite side of the air handler.
Note – Direct expansion (DX) coils require 180 degree rotation
on the top to bottom to locate distributor tubes at the leaving face of the coil.
CAUTION
Sharp edges and coil surfaces can cause personal injury. Avoid contact with them.
ATTENTION
Les bords tranchants et les surfaces des bobines sont un risque de blessure. Ne les touchez pas.
To reverse the coil connections, follow the steps below, referring to Figure 8 on page 10.
1 Remove exterior panels from both sides of the coil section.
Remove screws that secure the top of the leaving coil face to the upper track on the inside top of the unit.
2 Lift drain pan condensate connection above the unit frame
flange and slide drain pan, coil(s) and baffles out of unit.
3 Remove screws and remove coil blockoffs. 4 Remove screws holding coil to drain pan and remove coil.
5 Rotate the coil 180° and reposition coil blockoffs to the
entering air side of the coil.
6 Drill holes if required and fasten the blockoffs to the
entering side of the coil.
7 If unit has both heating and cooling coils, position and bolt
heating coil and cooling coil casings together in same arrangement in the direction of airflow as unit was shipped from factory. Reheat coils must remain in reheat position; do not place in preheat position. Fasten the first coil in the air stream to the entering side of the drain pan using the same holes provided for the coil before it was rotated.
8 Mark locations and drill holes to align with holes in upper
track.
9 Slide the coil, blockoffs and drain pan assembly back into
unit the same way it was removed. Check the installation for an airtight fit. Re-install screws that secure the top of the leaving coil face to the upper track on the inside top of the unit.
Depending on whether the air handler was purchased from
stock or if it was manufactured for the specific job, the panel
on the opposite side may or may not have predrilled
connection holes.
10 If connection holes need to be drilled, determine the proper
diameter in order to use the existing grommets.
11 Mark connection locations on panel and drill new holes to
accommodate connections and grommets.
12 Plug and seal unused connection holes on opposite side
panel with new solid grommet or other suitable material.
McQuay IM 782-2 9
Loading...
+ 21 hidden pages