McQuay IM 777-1, Skyline Maintenance Manual

Installation and Maintenance Manual IM 777-1
Skyline¥ Air Handler
Sizes 003–090
Group: Applied Air
Part Number: IM 777
Date: June 2005
© 2005 McQuay International
McQuay IM 782-1 1
Contents
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Receiving and Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Unit Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Installation Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Service Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Curb Mounting and Unit Leveling . . . . . . . . . . . . . . . . . . . . . . 3
Assembling Sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Access Doors and Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Injected-Foam Insulated Panels . . . . . . . . . . . . . . . . . . . 5
Field Mounting Junction Boxes and Other Components . . . . . 6
Duct Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Dampers and Hoods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Mounting Actuators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Face and Bypass Section Mounting . . . . . . . . . . . . . . . . . . . . 7
Piping Vestibules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Piping and Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Water Cooling Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Direct Expansion Coils . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Steam Coils (see Figure 18 on page 10) . . . . . . . . . . . . . 9
Water Heating Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Drain Pan Traps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Internal Isolation Assembly Adjustment . . . . . . . . . . . . . . . . 12
Electrical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Operation Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Startup Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Fan Wheel Alignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Fan Vibration Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Vibration Causes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Service and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . 20
Periodic Service and Maintenance . . . . . . . . . . . . . . . . . . . . 20
Ball Bearing Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Fan Drive Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
VM and VP Variable Pitch Key Type Sheaves . . . . . . . 21
LVP Variable Speed Sheaves . . . . . . . . . . . . . . . . . . . . 21
MVP Variable Speed Sheaves . . . . . . . . . . . . . . . . . . . . 22
Fan Drive Belt Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
General Rules of Tensioning . . . . . . . . . . . . . . . . . . . . . 24
Tension Measurement Procedure . . . . . . . . . . . . . . . . . 24
Front Load Filter Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Filter Gauges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Maintaining the Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Winterizing Water Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Removing and Replacing Components . . . . . . . . . . . . . . . . . 26
Removing the Fan Section . . . . . . . . . . . . . . . . . . . . . . . 26
Removing and Replacing the Coil . . . . . . . . . . . . . . . . . 27
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Warranty Return Material Procedure . . . . . . . . . . . . . . . . . . . 29
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
McQuay and MicroTech II are registered trademarks of McQuay International.
Copyright © 2005 McQuay International. All rights reserved throughout the world.
Microsoft is a registered trademark of Microsoft Corporation.
Windows is a trademark of Microsoft Corporation.
General Information
The system design and installation must follow accepted industry practice as described in the ASHRAE Handbook, the National Electric Code, and other applicable standards. Install this equipment in accordance with regulations of authorities having jurisdiction and all
applicable codes.
Installation and maintenance must be performed by qualified personnel familiar with applicable codes and regulations and experienced with this type of equipment. Sheet metal parts, self-tapping screws, clips, and such items inherently have sharp edges; the installer should exercise caution.
CAUTION
SHARP EDGES AND COIL SURFACES
are a potential injury hazard. Avoid contact with them.
ATTENTION
Les bords tranchants et les surfaces des bobines sont un
risque de blessure. Ne les touchez pas.
Receiving and Handling
1 Carefully check items against the bills of lading to verify
all crates and cartons have been received. Carefully inspect all units for shipping damage. Report damage immediately to the carrier and file a claim.
2 Skyline air handler units are constructed of galvanized or
painted steel and are inspected thoroughly before leaving the factory. Take care during installation to prevent damage to units.
3 Take special care when handling the blower section. All
fans are dynamically balanced before leaving the factory. Rough handling can cause misalignment or a damaged bearings or shaft. Carefully inspect fans and shaft before unit installation to verify this has not happened.
4 Screws, bolts, etc., for assembling sections are supplied in
a bag attached to each section. All necessary gasketing is applied in the factory for section-to-section mounting. Units require caulk sealant between sections.
Unit Storage
Store unit on a level surface. If air handling units are stored for any period of time, periodically rotate the fan wheel to prevent permanent distortion of drive components. In addition, grease may settle in the lower part of the bearing, which can lead to oxidation on the upper portion of the bearing surface. Keep the fan bearings lubricated.
Nomenclature
OAH 003 G D A C
Model
OAH = Outdoor air handler OAC = Outdoor component
Nominal Unit Size (nominal square foot of coil)
003, 004, 006, 008, 010, 012, 014, 017, 021, 025, 030, 035, 045, 055, 065, 080, 085, 090
Vintage of McQuay Air Handling Unit
Unit Cross Section
C = Standard unit cross section M = Custom size cross section
Motor Location
A = Motor along side of fan housing D = Motor downstream of belt drive plenum fan F = Motor on inline fan
G = Motor downstream of direct drive plenum fan
T = Motor behind twin housed fans
Unit Type/Coil Position
B = Blow-thru cooling coil location D = Draw-thru cooling coil location H = Heating only V = Vent only
McQuay IM 777-1 1
Installation Guidelines
Service Clearances
In addition to providing adequate space around the unit for piping coils and drains, access to at least one side of the unit is always required to allow for regular service and routine maintenance, which includes filter replacement, drain pan inspection and cleaning, fan bearing lubrication, and belt adjustment. Provide sufficient space—at least equal to the length of the coil—on the side of the unit for coil removal. See Figure 1 for servicing space requirements.
Maintain at least 54" of clearance in front of electrical power devices. Electrical power devices that are mounted on the side of the unit typically are up to 12" deep. See Figure 2.
Figure 1: Servicing space requirements
4 . 0 0 " b a s e r a i l e x t e n s i o n
W i d t h
3 0 . 0 0 "
4 . 0 0 "
W i d t h o f c o i l s e c t i o n
W i d t h o f
f a n s e c t i o n
Figure 2: Service clearance for electrical power devices
1 2 "
5 4 "
Rigging
Skyline air assembled, or in modules of assembled sections.
be rigged as it ships from the factory. Do not rig units after assembly.
and the corners of each shipping section. unit cabinetry, use spreader bars. Position spreader bars to prevent cables from rubbing the frame or panels. Before hoisting into position, test lift for stability and balance. Avoid twisting or uneven lifting of the unit.
handlers ship as separate sections, completely
The unit must
Units are
provided with a factory-installed base
rail
can be lifted using the 2" diameter lifting holes located in
To prevent damage to the
3 0 . 0 0
"
H e i g h t
Figure 3: Unit and section rigging
2 McQuay IM 777-1
Installation Guidelines
S t a
Curb Mounting and Unit Leveling
Do not place a Skyline unit over an open curb unless it is equipped with a curb-ready base. Installation instructions for mounting units on a roof curb are provided in IM 770. For a copy, contact your local McQuay representative or visit www.mcquay.com. Make provisions under the unit to divert any moisture from entering the building below.
For units without roof curb mounting, place the equipment on a flat and level surface. Where surface irregularities exist, shim the base of the unit at one or more points along the length of the rails to prevent distortion or sagging. Uneven or distorted sections cause misfit or binding of the doors and panels and improper draining of drain pans. See Figure 4.
Figure 4: Leveling the unit
h i m s e c t i o n s u n t i l
h e y a r e s t r a i g h t
n d l e v e l
S h i m t o p r e v e n t d i s t o r t i o n i f w i d t h i s o v e r 1 0 8 "
Assembling Sections
If the unit is shipped in more than one shipping section, rig each section into position separately. provided with a connection splice joint attached on the leaving air side of the shipping
section that seals against the frame channel on the entering-air side of the adjoining splice joint is insulated and provides an air-tight seal between two sections once they are assembled together. joint to seat into the mating gasket to provide an air seal.
was
splice joint
bent during shipping or rigging, restore it to its
original position. See Figure 7
To assemble shipping sections:
1 Caulk all assembly joints of the unit—Before joining the
sections, apply at least 1/4 inch diameter bead of sealant to the mating faces of the cabinet. Use the splice joint as a guide for applying the sealant. See Figure 5.
Shipping sections are
section. The
Align the splice
If the
.
Figure 5: Apply sealant to mating faces
1 / 4 " d i a m e t e r b e a d c e n t e r e d i n f a c e o f c l e a r a n c e
U s e S p l i c e J o i n t a s a g u i d e
2
Pull sections together to fasten. Use straps and a ratchet to help pull the sections together securely. Apply sealant to any gaps that may admit moisture.
3 Fasten base rails together first using the 3/8"-16 × 5" bolts
located in the splice kit provided with the unit. See Figure 7.
a To fasten two shipping sections together, 4 bolts are
needed (2 on each side of the unit). The bolts are run from one base rail into the other and fastened with a nut. Complete each section bottom and top before attaching additional sections.
b If desired, shipping sections for non curb-ready units
can be fastened together internally. To fasten internally, run field-provided #10 sheet metal screws or drill screws (4" long, maximum) through the interior frame channel of one unit into the splice joint of the neighboring section.
c Handle units with curb-ready bases and vestibules so the
lifting bracket can be removed after the unit is placed on the curbing.
– Remove the lifting bracket that projects inward over
the curbing. Save the self tapping screws.
– When the adjacent section is placed in position, use
self tapping screw to secure the bases together.
McQuay IM 777-1 3
Installation Guidelines
Figure 6: Remove vestibule lifting bracket
R e m o v a b l e L i f t i n g B r a c k e t
Figure 7: Fasten bottom of section
Figure 8: Internal fastening
A
S p l i c e C o l l a r m u s t b e a l i g n e d t o s e a l t o g a s k e t .
4
Check that the sealant is compressed between the mating channels when the unit sections are joined. Touch up any places where gaps are noted.
5 After sections are seated tightly together, slip the splice cap
over the top panel flanges. Bend the ends of the splice cap down to secure in place.
6 Assemble the small splice plate at the top rail to secure the
sections together at the top. Use 5/16" bolts. See Figure 9.
3 / 8 x 1 " B o l t a n d N u t
Figure 9: Splice cap and splice plate
S l i d e S p l i c e C a p o n a n d b e n d e n d s d o w n
5 / 1 6 - 1 8 B o l t
5 / 1 6 - 1 8 N u t
S p l i c e P l a t e
4 McQuay IM 777-1
Installation Guidelines
Access Doors and Panels
For routine maintenance, access normally is obtained through access doors or by removing side panels. Removing all flat head fasteners along the sides of a panel allow it to be removed.
Fan and filter sections are always provided with a service door on one side of the unit. If requested on order, doors can be provided on both sides of the unit. Optional service doors are available for most section types and are provided based on customer request.
Note – Opening fan section doors requires using a 1/2" socket
wrench, which satisfies ANSI standards and other codes that require the “use of tools” to access compartments containing moving parts or electrical wiring. See Figure 10.
1 Remove padlock if one is present.
CAUTION
SHARP EDGES AND COIL SURFACES
are a potential injury hazard. Avoid contact with them.
ATTENTION
Les bords tranchants et les surfaces des bobines sont un
risque de blessure. Ne les touchez pas.
CAUTION
DO NOT attempt to rotate the cup.
Damage to the unit will occur.
ATTENTION
NE PAS tenter de faire tourner la cuvette (cup).
Ceci va dendomagger l’unité.
2 Insert 1/2" socket into cup and rotate 1/4 turn clockwise as
shown in Figure 10. If the cup and handle are on the left side of the door, rotate 1/4 turn counterclockwise.
3 Rotate the door handle 1/4 turn clockwise and then 1/4 turn
counterclockwise to release any internal pressure or vacuum and open the door. If the cup and handle are on the left side of the door, rotate the door handle 1/4 turn counterclockwise and then 1/4 turn clockwise.
4 To prevent air leakage, tighten the door panels by adjusting
the jam nuts.
Figure 10: Opening fan section door
Do Not Rotate Cup
Jam Nuts
View from inside doo r
OPEN
Injected-Foam Insulated Panels
Skyline air handlers now are furnished with double-wall, injected-foam insulated panels. Foam panels are stronger, more rigid, and lighter than panels with fiberglass insulation. The insulation R-value is improved to 13. However, foam insulation can burn when exposed to flame or other ignition sources and release toxic fumes. Take care in cutting and sealing all field-cut openings in these panels.
Panel cutting procedure
1 Determine the number and location of holes required for
electrical conduit, piping, and control wiring as follows:
Check that adequate space is available inside the unit for
conduit or pipe routing.
Do not locate holes in a panel that provides access to key
maintenance components such as filters and fan assemblies.
Do not locate where the conduit or piping blocks airflow
or obstructs hinged access doors.
2 Once a proper location is determined, drill a small pilot
hole completely through the panel. Then use a sharp hole saw or a saber saw and cut from each side of the panel.
McQuay IM 777-1 5
Installation Guidelines
3
Seal the double-wall panel on each side with an industrial/ commercial grade silicone sealant or duct seal compound. It is extremely important to seal each panel hole or penetration securely so it is airtight and watertight and
there is NO EXPOSED FOAM INSULATION.
WARNING
Flame and smoke can cause equipment damage, severe personal injury, or death.
Before operating unit, seal all piping and wiring holes on both inner and outer panels with an industrial grade silicone sealant or duct seal compound. Do not use a cutting torch or expose panel to fire. Panel damage can occur.
WARNING
La fumée et les flammes peuvent endommager le matériel et causesr des blessures graves ou la mort.
Avant d’utiliser le dispositif, obturer tous les trous de passage de tubulures et de fils ménagés dans les panneaux intérieurs et extérieurs au moyen d’une pâte à base de silicone ou d’un mastic d’étanchéite â conduits de qualité industrielle. Ne pas se servir d’un chalumeau coupeur ni exposer les pannequx à une flamme nue pour ne pas risquer de les endommager.
Figure 11: Cutting and sealing injected-foam insulated panels
Seal completely with silicone
Cut hole from both sides of panel
sealant or duct seal compound
inner panels. To maintain panel integrity, seal both ends with an industrial/commercial grade silicone sealant or duct seal compound.
The unit frame channel is another excellent location for securing heavier components; self-tapping screws are not acceptable. Ensure that the location permits the full operation of all access doors and panels and does not interfere with other vital components.
Duct Connections
Use flexible connectors on the outlet and inlet duct connections of all units. Do not position down flow fans over air ducts that are routed down into the building. Use a discharge plenum when bottom connections are necessary. See Figure 12
Figure 12: Discharge plenum
D i s c h a r g e
P l e n u m
If the unit has a top mixing box or economizer damper or a top duct connection, field fabricate and install flashing to divert moisture from the connection. The flashing must lap over the standing seams of the top panels. The flashing also must lap over the side edges of the unit. See Figure 13.
Figure 13: Flashing over top panels and sides of units
.
F l a s h i n g
U n i t t o p p a n e l
F l a s h i n g
Prop 65—Substances in fuel or from fuel combustion can cause personal injury or death, and are known to the State of California to cause cancer, birth defects or other reproductive harm.
F l a s h i n g
D u c t
F l a s h i n g
D u c t
Field Mounting Junction Boxes and Other Components
For field mounting 4" × 4" or smaller junction boxes to the standard panel exterior, use a minimum quantity of 4, 3/16" diameter pop rivets. Do NOT use self-tapping drill screws.
They will not tighten nor secure properly and panel damage can occur.
If larger, heavier components require mounting on unit panels, use through-bolts with flat washers through both outer and
6 McQuay IM 777-1
Installation Guidelines
Dampers and Hoods
Side dampers may be provided in the mixing box and economizer sections of units. When dampers are provided, a removable panel is located above the weather hood to provide access to the damper drive shaft. Other access may be available depending on the specific construction of the unit. See Figure 14.
Figure 14: Filler panel over the weather hood
Remove screws and panel to access damper control shaft.
Hood
When units are ordered with exhaust hoods and intake hoods adjacent to each other, install a field-supplied barrier to prevent recirculation of exhaust air into the intake openings. See Figure 15.
Figure 15: Field-installed barrier between hoods
Mounting Actuators
The installing contractor is responsible for the mounting of all field-installed actuators. No provisions are made for the location of these actuators due to the number of options and arrangements available and the variety of specific applications. Typically, actuators are mounted inside the cabinet. Provide proper support for the actuator to avoid excessive stress in the cabinet, linkage, or damper shafts.
Note – Damper blades are at full flow when open to 70 degrees.
Do not open blades further than 70 degrees.
Fresh air and return air dampers can be linked together and driven from the same actuator if the dampers are the same size. If the dampers are different sizes, they must be driven by separate actuators and controlled appropriately. Exhaust dampers are always driven by a separate actuator.
A typical rotary electric actuator can handle up to 40 sq. ft. of damper. For pneumatic actuators, allow 5 in-lb per square foot
of damper area.
CAUTION
Maximum damper rotation is 70°.
Maximum shaft torque is 205 inches/pound.
Greater rotation or torque can cause equipment damage.
ATTENTION
La rotation maximale des colets est de 70°. Le couple (torque) maximum de l’arbre est de 205po/lb. Une plus grande rotation (ou torque) peut endommager
l’équipement.
E x h a u s t
I n t a k e
B a r r i e r
Face and Bypass Section Mounting
Internal and external face and bypass sections are mounted together using the instructions for horizontal components and do not require additional instruction. Skyline air handlers are provided with a bypass duct that is integral to the unit construction and requires no field assembly.
Face and bypass dampers may or may not be linked together. When dampers are placed before a single bank of coils, they always are linked together and require a single actuator. When dampers bypass a stacked or staggered coil, the dampers are not linked and require multiple actuators.
Face and bypass dampers have a torque requirement of 10 in-lbs per square foot of damper face area.
McQuay IM 777-1 7
Installation Guidelines
Piping Vestibules
For units that include a piping vestibule, cut the openings for routing the field piping as required in the field. Carefully seal passages cut through the panels to prevent air leakage. A single metal thickness pan is provided in the bottom of the curb-mounted vestibule. The pan can be removed if necessary. If holes are cut into the pan for a piping passage, seal the holes to prevent moisture leakage. See Figure 16.
Figure 16: Seal holes for piping—curb mounted units
Seal holes cut for piping
For units with standard base rails, the vestibule is open to the coil section; therefore, seal all holes to prevent air leakage.
Figure 17: Seal holes for piping—standard base rail units
Seal holes cut for piping
Piping and Coils
When designing and installing piping:
Follow applicable piping design, sizing, and installation information in ASHRAE handbooks.
Observe all local codes and industry standards.
Do not apply undue stress at the connection to coil headers; always use a backup pipe wrench.
Support pipework independently of the coils.
Water Cooling Coils
Note – Use glycol in water coils for outdoor air handlers. Power
failures and other mechanical issues can expose coils to freezing temperatures.
Water supply, water return, drain, and vent connections extend through the end panel of the coil section. All connections are labeled on the end panel.
Water supply and water return connections are typically male NPT iron pipe.
When installing couplings, do not apply undue stress to the connection extending through unit panel. Use a backup
pipe wrench to avoid breaking the weld between coil connection and header.
Follow recommendations of the control manufacturer
regarding types, sizing, and installation of controls.
Direct Expansion Coils
The coil distributor and suction connection extend through the end panel of the coil section.
Check nozzle in distributor for proper tonnage.
When a thermostatic expansion valve is supplied with the
unit, it is located outside the unit and connected directly to the distributor (except on units with piping vestibules). Do not apply heat to the body of the expansion valve.
The thermostatic expansion valve must be the external equalizer tube type. Connect the 1/4-inch diameter external equalizer tube provided on the coil to the connection on the expansion valve.
Use care when piping the system, making sure all joints are tight and all lines are dry and free of foreign material. For typical refrigerant piping, see condensing unit product manual.
8 McQuay IM 777-1
Installation Guidelines
Steam Coils (see Figure 18 on page 10)
Piping
Steam supply and steam return connections typically are male NPT iron pipe and are labeled on the end panel of coil section. Connections extend through the coil section end panel.
When installing couplings, do not apply undue stress to the connection extending through unit panel. Use a backup
pipe wrench to avoid breaking the weld between coil connection and header.
Support piping independently of coils and provide adequate
piping flexibility. Stresses resulting from expansion of closely coupled piping can cause serious damage.
Do not reduce pipe size at the coil return connection. Carry return connection size through the dirt pocket, making the reduction at the branch leading to the trap.
Coils
Pitch all steam coils in units toward the return connection.
Do not drip supply mains through the coil.
Do not attempt to lift condensate when using modulating or
on/off control.
Install vacuum breakers on all applications to prevent retaining condensate in the coil. Generally, connect the vacuum breaker between the coil inlet and the return main. The vacuum breaker should be open to the atmosphere and the trap design should allow venting of large quantities of air.
Traps
Note – Do not place steam traps outdoors.
Size traps in accordance with the manufacturers’ recommendations. Make sure the required pressure differential is always available. Do not undersize.
Use float and thermostatic or bucket traps for low pressure steam. On high pressure steam, use bucket traps. Use thermostatic traps only for air venting.
Use bucket traps for on/off control only.
Locate traps at least 12 inches below the coil return connection.
Multiple coil installation
– Individually trap each coil or group of coils that is
controlled individually trapped.
– Coils in series—use separate traps for each coil, or a bank
of coils.
– Coils in parallel—a single trap can be used, but an
individual trap for each coil is preferred.
– Do not attempt to lift condensate when using modulating
or on/off control.
With coils arranged for series airflow, use a separate control on each bank or coil in the direction of airflow.
Valves
Do not use modulating steam valves on high pressure systems.
Properly size modulating valves. Do not undersize.
Freezing conditions (entering air temperatures below 35°F).
– McQuay strongly recommends 5JA, 8JA, 5RA and 8RA
coils.
– Supply 5 psi steam to coils at all times.
Do not use modulating valves. Provide control by face and bypass dampers.
– Consider using two or three coils in series with two
position steam control valves on the coil or coils that handle 35°F or colder air. Use a modulating valve on the downstream coil to provide the desired degree of control.
– Thoroughly mix fresh air and return air before it enters the
coil. Also, to obtain true air mixture temperatures, properly locate temperature control elements.
– As additional protection against freeze-up, install the trap
sufficiently below the coil to provide an adequate hydrostatic head to remove condensate during an interruption in the steam pressure. Estimate three feet for each 1 psi of trap differential required.
– On startup, admit steam to coil ten minutes before
admitting outdoor air.
– Close fresh air dampers if steam supply pressure falls
below the minimum specified.
McQuay IM 777-1 9
Loading...
+ 25 hidden pages