McQuay IM-701 Installation Manual

Installation and Maintenance IM-701
DesignFlow
TM
Precision Outdoor Air Measurement System
Group:
Part Number:
Date:
Applied Systems
April 2001
© 2001 McQuay International
General
DesignFlow™ airflow measurement stations are located inside the louvered outdoor air intake doors between the intake louver and outside air dampers. Essentially, they con­sist of a vane that is repositioned by airflow, the amount of rotation indicating the amount of airflow. They have been precision calibrated at the factory and no further calibration is required. However, a leveling adjustment is required. The DesignFlow unit must be accurately leveled so that when operating it will be orientated the same as when it was cali­brated.
The rotational position of the DesignFlow unit vane is trans­lated into CFM by the microprocessor in the MicroTech II control system. The position of the vane is determined by two things - the force of the airflow impacting the vane and the gravitational effect on the vane. Gravity is the only factor at the lower CFM end of the range. On a correctly leveled unit, this gravitational effect will be the same as when the unit was calibrated in the factory.
Both the right-hand and left-hand DesignFlow stations must be accurately leveled. To accurately level a station, a precise mechanical force is applied against the vane. That force should cause the vane to move to a specific position if the DesignFlow unit is correctly leveled. If the vane does not move to the correct position with the force applied, the DesignFlow unit is not properly leveled and gravity is caus­ing the difference.
The DesignFlow unit is mounted such that it pivots at the top. A lock nut, a slotted hole, and a threaded adjuster allow posi­tioning the bottom of the assembly so it can be correctly lev­eled. When the lock nut is loosened, the threaded adjuster allows precise, controlled movements.
3. Remove the covers from the access opening in the bottom blade of the outdoor air intake louvers (See Figure 1). The leveling procedure must be accomplished with the louvered door in the closed position. These openings provide access for leveling.
Figure 1
ACCESS OPENING
COVER
4. The leveling procedure is performed with the fans off and the outdoor air dampers closed. If there is a wind, the out­door air louvers should be covered with poly film, cardboard, etc. to prevent adverse readings due to wind.
5. Tape the fulcrum Alignment Plate to the vane (See Figure
2). Locate the Alignment Plate so the bottom edge of its notches are flush with the bottom edge of the vane, one side of one notch is even with the bend near the outer edge of the vane, and the plate is flat against the outer surface of the vane.
Figure 2
DesignFlow Airflow Measurement Station Startup:
Note: Before starting the station startup procedure, locate the leveling components kit that can be found in the main unit con­trol box.
Note: Before starting the station startup procedures, varify that power has been supplied to the unit’s MicroTech II con­trol system. The DesignFlow startup procedure cannot be completed without use of the MicroTech II controls.
VANE
DUCT TAPE THIS EDGE FLUSH WITH BEND ON VANE
THESE EDGES FLUSH WITH BOTTOM OF VANE
ALIGNMENT PLATE
FULCRUM DUCT TAPE
1. The swinging vanes on the measurement stations have been locked in place for shipment. The stations are accessi­ble when the louvered outdoor air intake doors are opened. Remove the two shipping screws from each vane. One screw is located one inch from the top of the vane. The other is one inch from the bottom of the vane. Both are about eight inches in from the outer edge of the vane.
2. Examine the station for shipping damage. Manually rotate the vane and verify that it does not rub against anything. Close and latch the louvered intake door.
2 IM-701
6. Install the fulcrum that is used in the leveling procedure (See Figure 2). The fulcrum will be held in place with duct tape. Wipe the bottom of the louver door where the fulcrum will be located so the tape will stick. Pre-apply the duct tape to the top surface of the bottom flat of the fulcrum, having it extend about one inch beyond the edges on three sides. Once the fulcrum is positioned, these extensions can be pressed
Loading...
+ 2 hidden pages