McQuay ICM450 Installation Manual

ICM 450
Programmable Three Phase Voltage
Monitor with 25-Fault Memory
Protects motors from premature failure
Installation, Operation & Application Guide
For more information on our complete range of American-made products – plus wiring diagrams, troubleshooting tips and more, visit us at www.icmcontrols.com
Specication
Input
Line Voltage: Universal, 190-630 VAC
Frequency: 50-60 Hz
Load Side Monitoring: Optional
Control Voltage: 18-240 VAC
Frequency: 50-60 Hz
Output
Type: Relay, SPDT
Voltage Range: 240VAC @ 10A maximum
Frequency: 50-60 Hz
Control Operating Temperature
Operating Temperature: -40ºF to +167ºF (-40ºC to +75ºC)
Storage Temperature: -40ºF to +185ºF (-40ºC to +80ºC)
LCD Operating Temperature
Operating Temperature: -4ºF to +167ºF (-20ºC to +75ºC)
Mechanical
Mounting: Surface mount using (2) #8 screws
Terminations: Screw terminals
Weight: 12 ounces (341 grams)
Dimensions
• 6 1/2” L, 4 1/4” W, 1 3/8” H (16.5 cm. L, 10.8 cm. W, 3.5 cm. H)
Parameters
Phase Unbalance Protection
Voltage Unbalance: 2-20% adjustable
Over/Under Voltage Protection
Under Voltage: 2-25% adjustable
Over Voltage: 2-25% adjustable
Phase Loss Protection
Phase Loss Condition: Equals 25% of nominal for any given phase; system will shut down and a fault will be recorded should this occur
Delay on Break Timer
Control Voltage: 18-240 VAC
Time Delay: 0 to 10 minutes adjustable
Fault Interrogation Delay
Time Delay: 0 to 15 seconds adjustable
• Provides a delay between fault detection and system shutdown - helps to eliminate nuisance trips or unnecessary shutdowns
Caution
Installation of the ICM450 shall be performed by trained technicians only. Adhere to all local and national electric codes.
Disconnect all power to the system before making any connections.
Installation
1. Using (2) #8 screws, mount the ICM450 in a cool, dry, easily accessible
location in the control panel.
2. Connect voltage as shown in Figure 1 (below). Leave existing line and load
side connections intact on the contactor.
3. Load side monitoring is optional (unit may be used to monitor line side
only). Wire the contactor and optional control voltage monitoring as in Figures 2 and 3 (below).
Note: Load/line wire must be rated for 3-phase voltage rating, 20ga
4. Upon application of power, the ICM450 will be on line and will begin to
monitor the system.
“back” side of contactor
minimum.
Figure 1
Incoming 3-phase
voltage from load or
(optional)
LOAD
3
LOAD
2
LOAD
1
LINE
3
LINE
2
LINE
1
Incoming 3-phase voltage from
line or “front” side of contactor
The incoming 3-phase voltage is used to power up the ICM450 as
well (190-600)
• Terminals 1 and 3 are the control signal input terminals
• “Control Mode” is turned ON or OFF in setup
• With “Control Mode” set to “ON,” there must be a voltage present on terminals 1 and 3 for the relay output terminals 4 and 6 to close; this voltage can be supplied from a thermostat, pressure switch, etc.
• When the voltage on these terminals is re-applied, the unit will not re-energize until the delay on break (0-10 minutes) time has elapsed
• Use of terminals 1 and 3 is optional; they will be ignored if the “Control Mode” is set to “OFF”
Figure 3
• Terminals 4 and 6 are “dry,” normally open
6 5 4
13
Contactor Coil
Contactor Voltage (18-240 VAC)
contacts
• Terminals 4 and 6 are closed when power is within specifications
• Terminals 4 and 6 open when there is a fault condition or loss of control signal
Figure 2
6 5 4
* Switch can be
a thermostat, pressure switch, etc.
Control Voltage
(18-240 VAC)
13
Short pins when using 24 VAC control voltage
1
Loading...
+ 5 hidden pages