McQuay HSS S30 Installation Manual

Group: Fan coil Part Number: # 106332400 Date: August 2000
©2000 McQuay Incorporated
SeasonMaker®Hi-Line Fan-coil Unit Model HSS S30 through S80
IM 255-6
Table of Contents
Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installation and maintenance are to be performed only by qualified personnel who are familiar with and in compliance with state, local and national codes and regulations, and experienced with this type of equipment.
Caution: Sharp edges and coil surfaces are a potential injury hazards. Avoid contact with them.
When the equipment is received, all items must be carefully checked against the bill of lading to be sure all crates and cartons have been received. The units are normally shipped four to a pallet. Visible or concealed damage should be reported immediately to the carrier and a claim filed to him for
damage. The electrical nameplate should be checked to be sure it agrees with the power supply available. DO NOT HANDLE UNITS BY THE RISER PIPING. Riser clamps are used to hold the riser in position. They should not be expected to support the weight of the cabinet.
Inspection
1. Place unit over riser hole in the floor. Adjust location so riser extensions align with risers on unit below.
2. Isolator pads (not provided by McQuay) if used, must be in place before connecting riser.
3. The horizontal stubs protruding into the cabinet from the risers must be centered in the 3” (75mm) slot in the panel before risers are soldered in place. This is important to allow for riser expansion or contraction of ±1” (25mm). Riser normally extends approximately 5” (127mm) above the cabinet when the stub is centered in the slot.
4. The unit has provision for ±1” (25mm) of riser movement due to expansion or contraction. Risers must be anchored to the building structure in such a manner to prevent vertical riser movement in excess of ±1” (25mm).
5. Risers must be anchored to the building as there is no provision on the unit to support the weight of the risers.
6. Care must be taken to prevent dirt and other foreign matter from entering the risers as plugged lines or valves could result.
7. With the unit in the final location, check level to insure proper condensate drainage and operation.
8. Connect supply and return risers by soldering slip couplings. (Reducing couplings not supplied by McQuay). Join drain riser with coupling using PVC solvent cement on both surfaces (or solder if riser is copper).
9. Apply insulation (available from McQuay) to risers between floors and cement joints to avoid condensation problems.
10. To assure compliance with existing building codes, the installing contractor must restore the original fire resistance rating of the structure by sealing the access space around the risers with material having the same fire rating as the structure. This procedure is very important also in assuring that a seal is provided between floors to prevent the passage of warm, humid air which can cause condensation on riser insulation. This is most critical in unpressurized buildings with high infiltration rates.
11. Vent the coils. Vent is accessible from return air opening.
12. Hydrostatically test riser and unit connection joints to assure they are leakproof before unit is furred in.
13. The thermostat box has been installed in the front panel in the position that will allow plasterboard to be attached directly to the unit. If the installation requires that the wall be furred out away from the unit, the box can be adjusted out to 37/8” (98mm) by removing the four screws "A" (see Figure 2), and pulling the box out. Replace screws "A". If a dimension other than the 37/8” or 3/8” (98mm or 10mm) is required, this can be accomplished using the angle bracket as a template and drilling .149" (4mm) diameter screw holes in the box at the desired depth.
14. When the plasterboard or other wall material does not fit flat against the face of the unit, extension sleeves must be furnished by the contractor for both the return and supply air openings.
15. Wire in accordance with local codes or the National Electric Code, whichever is applicable. Provide branch circuit overcurrent protection and disconnect means. The complete system wiring diagram is located on the front cover. Bring electrical wiring through the side of the cabinet into the wiring box located on the right-hand side of the cabinet (see Figures 3 and 5). Two 7/8” (22mm) diameter knockouts for wire entrance are provided.
16. The unit mounted combination thermostat and fan switch has a quick disconnect plug for insertion into a receptacle in the back of the thermostat box to complete the internal wiring. The return air bulb on the thermostat must then be strung through the hole in the back of the thermostat box and down through the hole in the deck support angle and attached to the bulb clip below the fan deck (see Figure
3). Be sure the rubber grommets are in place where the capillary tube passes through the panels.
17. Rotate the fan wheel by hand to make sure the wheel is free.
18. If ducts are being added, be sure the resistance is within the limits of the external static pressures shown in the catalog for the particular unit being installed. The ducts should be designed for velocities in accordance with the methods outlined in the ASHRAE Guidebooks. It is recommended that the airborne noise be controlled with sound attenuating materials and by installing flexible connection between the unit and ductwork. Ductwork should be installed in accordance with NFPA 90A and NFPA 90B.
19. When furring in units, make sure that no screws (other than grille or plaster frame attaching screws) or nails penetrate the unit cabinet. Grille or plaster frame attaching screws should never penetrate the cabinet more than 2” (51mm).
20. The plaster frame should be attached on the opening over the top of the plasterboard. Use the plaster frame as a template to drill pilot holes into the wall or unit for the attaching screws. (See Figure 6).
In order for the grille panel to fit the plaster frame properly, the plaster frame must be mounted with the corners square. When the plaster frame has been mounted to the unit, attach the two retaining clips (supplied with the plaster frame) to the plaster frame adjacent to the lower attaching screws. (See Figure 7).
INSTALLATION
Page 2 / IM 255
Figure 1. Return Air Grille and Plaster Frame HSS/KZZ Sizes S03 Thru S08
Figure 2. Riser Location Plan View
Page 3 / IM 255
Loading...
+ 5 hidden pages