McQuay HSS Installation Manual

Installation & Maintenance Data IM 283-8
Group: Fan Coil Part Number: 106332300 Date: August 2000
Additional Installation Instruction for
Type HSS HiLine SeasonMaker Twin Units
Refer to Installation and Maintenance Bulletins 254 and 255 for additional information.
Twin opposite hand units share a common riser system; i.e., supply, return, and drain riser. This is commonly called a “master/slave” arrangement. The master unit is shipped with the risers attached. These special risers have stub-outs which must be field connected to the slave units. In addition to the instructions in bulletins IM 254 (KZZ units) or IM 255 (HSS units), the following procedures must be followed for all twin unit installations.
1. The slave unit has no risers and no stub-outs. Knock­out holes are provided for internal piping connections.
2. HSS-S10 and -S12 units will not match up with the smaller units sizes S03, S04, S06 and S08 due to differences in riser stub-out locations.
3. Master units are offered in two-pipe or four-pipe systems with either right-hand or left-hand. Slave units are offered to accomodate internal connections to any of these riser systems or locations.
4. The riser location (right or left) is determined by facing the return air grille panel. The risers are located on either the right or left of the unit. This defines the riser location. See Figure 1.
5. The riser block-off plates are located in the base of the slave unit. Block-offs must be installed on slave before putting unit into position. See Figure 8.
6. Install the master unit per IM 254 or IM 255.
7. Recommended wall opening sizes for the slave unit stub-outs are shown in Figure 6.
8. The openings must provide enough space to allow
easy installation of the unit. During installation, the unit is tilted at an angle to set into place. Unless the opening in the wall is large enough, there will be interference and the unit cannot be set into position.
9. Openings must be large enough to accommodate riser stubs with foam insulation. An allowance must be made for insulation thickness, fitting connections, and hand valves on the stub-outs.
10. The opening in the wall must provide space for vertical movement of riser stubs as a result of riser expansion and contraction.
5
11. The slave unit piping terminates with
8" sweat connec­tion. The piping is also supported inside the cabinet to prevent any damage to them during shipment. This
support bracket must be removed to allow expan­sion or contraction in the piping after unit is installed.
12. On the slave units, the ball valves will not be attached to the unit. The ball valves (quantity 2 on two-pipe, 4 on four-pipe), if ordered from McQuay, will be shipped in a separate box. The ball valves are not factory mounted to the slave unit piping because there would be insufficient room between ball valve and cabinet to make field connections to the unit. The correct installation proce­dure as outlined in subsequent paragraphs is to first mount the ball valves to the riser stub-outs and then set the slave unit in place with the ball valves protruding through the slave unit riser knockouts. The connections can then be made between ball valves and unit piping within the HiLine slave unit.
Figure 1. HiLine Twin Unit Arrangements
Right-Hand
Master
Left-Hand
Slave
Left-Hand
Master
Wall
Right-Hand
Slave
Note: Arrows refer to return air panel position
©2000 McQuay Incorporated
Figure 2. Return Air Grille and Plaster Frame HSS/KZZ Sizes S03 Thru S08
Figure 3. Riser Location Plan View
Page 2 / IM 283
Figure 4. Return Air Grille and Plaster Frame HSS/KZZ Sizes S10 & S12
Figure 5. Riser & Discharge Locations (Plan View)
IM 283 / Page 3
Loading...
+ 5 hidden pages