McQuay GCW 036 Installation Manual

Installation and Maintenance Data
W ater to Water Source Heat Pumps 3 to 35 Tons R-22 and R-407C Refrigerant / 60Hz
GRW - Extended Range Heating and Cooling models GHW - Extended Range Heating only models GCW - Extended Range Cooling only models
IM 816
Group: WSHP Part Number: 667691801
Date: December 2004
©2004 McQuay International IM 816 (12-04)
Table of Contents
Nomenclature ........................................................................ 2
Safety Information ................................................................. 3
Specifications ........................................................................ 4
Pre Installation and Code Requirements.............................. 4
Wiring Diagrams ............................................................... 5-7
60 Hz - 1 Phase, Sizes 036-072 .................................... 5
50/60Hz - 3 Phase, Sizes 036-072................................ 6
60 Hz - 3 Phase, Sizes 120-420 .................................... 7
Installation ............................................................................. 8
Application ..........................................................................8-9
Dimensional Data ......................................................... 10-12
GRW, GHW, GCW, Size 036-072, 60Hz .................... 10
GRW, GHW, GCW, Size 120-180, 60Hz .................... 11
GRW, GHW, GCW, Size 240-420, 60Hz .................... 12
Nomenclature
NOTE: For illustration purposes only . Not all options available with all models.
Please consult your local McQuay Representative for specific availability .
W GRW 1 036 E F T F YY FS S C S R PVM
Product Category
W = WSHP
Product Identifier
GRW = Extended Range
Heating and Cooling Models
GHW = Extended Range
Heating Only Models
GCW = Extended Range
Cooling Only Models
Design Series
1 = 1st Design 2 = 2nd Design 3 = 3rd Design 4 = 4th Design
Nominal Capacity
036 = 36,000 Btuh Nominal Cooling 048 = 48,000 Btuh Nominal Cooling 060 = 60,000 Btuh Nominal Cooling 072 = 72,000 Btuh Nominal Cooling 120 = 120,000 Btuh Nominal Cooling 150 = 150,000 Btuh Nominal Cooling 180 = 180,000 Btuh Nominal Cooling 240 = 240,000 Btuh Nominal Cooling 300 = 300,000 Btuh Nominal Cooling 360 = 360,000 Btuh Nominal Cooling 420 = 420,000 Btuh Nominal Cooling
Water Piping Location
F = Front T = Top L = Left Hand Side R = Right Hand Side
Controls
E = Electromechanical T = Temperature
Control System
Voltage
E = 208-230/60/1 F = 208-230/60/3 K = 460/60/3 L = 575/60/3 N = 380/50/3
Control Box Location
F = Front L = Left Side Control Box R = Right Side Control Box
Start Up................................................................................ 13
Maintenance Procedures .................................................... 13
Circuit Diagrams...........................................................14-16
GHW Circuit Diagram .................................................. 14
GRW Circuit Diagram .................................................. 15
GCW Circuit Diagram .................................................. 16
Replacement Parts List ....................................................... 17
Performance Tables ............................................................ 18
General Service Guide ........................................................ 19
Check, Test & Start Form.................................................... 20
Unit Function Information .................................................... 20
Cabinet Electrical
YYY = None PVM =Phase Monitor
Monitors Voltage and Phase Loss
Refrigerant
R = R-22 C = R-407C
Desuperheater
Y = None D = Lead Compressor
Waste Heat Recovery Water Heater
Source Water to Refrigerant Heat Exchanger Construction
C = Copper Inner Tube -
Steel Outer T ube
S = Cupro-Nickel Inner Tube -
Steel Outer T ube
Y = None
Construction Type
A = Standard S = Severe Indoor Atmosphere
Protection
C = Corrosive Indoor Atmosphere
Protection
Freezestat
YY = None FS = Adjustable for Geothermal and
Boiler/T ower Application
Status Lights
YY = None SL = Three Lights-Compressor-1,
Compressor-2, Compressor fault
The information in this manual supersedes and replaces previous manuals with regard to McQuay products. Illustrations cover the general appearance of McQuay
products at the time of publication and McQuay reserves the right to make changes in design and construction at anytime without notice.
Page 2 of 20 / IM 816 (12-04) Water to Water Source Heat Pumps
Safety Information
Safe Operation Rules
Installation and maintenance are to be performed only by qualified personnel who are familiar with and in compliance with state, local and national codes and regulations, and experi­enced with this type of equipment.
Please take a few minutes to read the instructions before you install the heat pump. This will help you obtain the full value from this unit. It will also help you avoid needless costs that result from incorrect installation and are not covered in the war­ranty.
Follow these instructions carefully. Failure to do so could cause a malfunction of the heat pump, resulting in injury, death and/or property damage.
Tubing and compressor contain high pressure refrigerant and they must not be exposed to high temperature or be punctured.
!
WARNING
To prevent electrical shock, disconnect electric power to system at main fuse or circuit breaker box until installation is complete.
!
CAUTION
Danger Label
White lettering on a black background except the word DANGER which is white with a red background.
Electric Shock Hazard. Turn Off All Power
Before Servicing.
Warning Label
White lettering on a black background except the word WARNING which is white with an orange background.
Fire Hazard.
Sharp edges and coil surfaces are injury hazards. Avoid contact with them.
SAFETY AND SIGNAL WORDS
The signal words DANGER, WARNING and CAUTION are used to identify levels of hazard seriousness. The signal word DANGER is only used on product labels to signify an immedi­ate hazard. The signal words WARNING and CAUTION will be used on product labels and throughout this manual and other manuals that may apply to the product.
DANGER
Immediate hazards which WILL result in severe personal injury or death.
WARNING
Hazards or unsafe practices which COULD result in severe personal injury or death.
CAUTION
Hazards or unsafe practices which COULD result in minor personal injury or product or property damage.
Use copper wire only . Failure to observe
could result in property damage, bodily injury or death
Caution Label
White lettering on a black background except the word CAUTION which is white with a yellow background.
Cuts and Abrasion Hazard.
Wear gloves and handle with care.
Failure to observe could result in bodily injury .
!
WARNING
This unit contains chlorodifluoromethane (HCFC-22), a substance that harms public health and environment by destroying ozone in the upper atmosphere. DO NOT VENT HCFC-22 to the atmosphere. The U.S. Clean Air Act requires the recovery of any residual refrigerant.
Water to Water Source Heat Pumps Page 3 of 20 / IM 816 (12-04)
SPECIFICATIONS
Voltage Model Size 036 048 060 072 120 150 180 240 300 360 420
Compressor
208/230-1-60
208/230-3-60
380/415-3-60
460-3-60
575-3-60
Ampacity (1) 20.2 23.3 30.4 37.7 N/A N/A N/A N/A N/A N/A N/A Max. Fuse Size (2) 35 40 50 60 N/A N/A N/A N/A N/A N/A N/A
Compressor Ampacity (1) 12.9 14.8 17.9 25.9 30 42 42 51 68 96 119
Max. Fuse Size (2) 20 25 30 45 40 60 60 70 90 125 150
Compressor Ampacity (1) N/A N/A N/A N/A 15 21 21 25 36 40 54
Max. Fuse Size (2) N/A N/A N/A N/A 20 25 25 35 50 50 70
Compressor Ampacity (1) 6.5 7.4 9 12.5 15 21 21 25 36 40 54
Max. Fuse Size (2) 15 15 15 20 20 25 25 35 50 50 70
Compressor Ampacity (1) 5.4 6 7.2 9.4 12 16 17 19 28 31 48
Max. Fuse Size (2) 15 15 15 15 15 20 20 25 35 40 60
N/A = Not Applicable
RLA 16.1 18.6 24.3 30.1 N/A N/A N/A N/A N/A N/A N/A LRA 88 104 131 144 N/A N/A N/A N/A N/A N/A N/A
RLA 10.3 11.8 14.3 20.7 12.9 18.6 18.6 22.5 30.2 42.4 52.6 LRA 77 88 91 128 91 128 156 164 225 245 425
RLA N/A N/A N/A N/A 6.5 9 9 10.9 15.6 17.7 23.8 LRA N/A N/A N/A N/A 48 65.5 75 100 114 125 187
RLA 5.2 5.9 7.2 10 6.5 9 9 10.9 15.6 17.7 23.8 LRA 39 44 46 63 46 63 75 100 114 125 187
RLA 4.3 4.8 5.7 7. 4 5.2 6.7 7.4 8.4 12.2 13.6 21.1 LRA 31 34 37 49 37 49 54 78 80 100 148
NOTES: (1) MINIMUM CIRCUIT AMPACITY
(2) MAXIMUM TIME DELAY FUSE OR HACR CIRCUIT BREAKER
As a result of continuing product improvement, all specifications and ratings are subject to change without notice.
PRE-INSTALLATION AND CODE REQUIREMENTS
After removing the unit from the carton, immediately remove
the panels and inspect for any damage that might have occurred
!
WARNING
during shipment. Report concealed damage immediately to the transportation company and request inspection.
The electric power source must be the same voltage and phase as shown on the serial plate. Line and low voltage wiring must be done in accordance with local codes or the national electric code.
This unit contains chlorodifluoromethane (HCFC-22), a substance that harms public health and environment by destroying ozone in the upper atmosphere. DO NOT VENT HCFC-22 to the atmosphere. The U.S. Clean Air Act requires the recovery of any residual refrigerant.
Make a survey of the final location for the unit before setting it in place. The unit should be centrally located with respect to the distribution system. Install the unit within a heated area. Exposure to inclement weather conditions may cause freeze damage that is not covered by the warranty.
Page 4 of 20 / IM 816 (12-04) Water to Water Source Heat Pumps
WIRING DIAGRAM 208/230-60-1 PHASE, UNIT SIZES 036, 048, 060 AND 072
Water to Water Source Heat Pumps Page 5 of 20 / IM 816 (12-04)
WIRING DIAGRAM 3 PHASE, UNIT SIZES 036, 048, 060 AND 072
Page 6 of 20 / IM 816 (12-04) Water to Water Source Heat Pumps
WIRING DIAGRAM 3 PHASE, UNIT SIZES 120, 150, 180, 240, 300, 360 AND 420
Water to Water Source Heat Pumps Page 7 of 20 / IM 816 (12-04)
INSTALLATION
Mounting the Unit
The unit should be mounted level on a vibration absorbing pad slightly larger than the base to provide isolation between the unit and the floor. It is not necessary to anchor the unit to the floor.
Unit Operating Shipping
Size Weight Weight
036 250 lbs 259 lbs 048 300 lbs 297 lbs 060 305 lbs 302 lbs 072 370 lbs 392 lbs 120 700 lbs 660 lbs 150 770 lbs 735 lbs 180 950 lbs 900 lbs 240 1,140 lbs 1,040 lbs 300 1,230 lbs 1,130 lbs 360 1,540 lbs 1,420 lbs 420 1,750 lbs 1,620 lbs
The electrical connections are accessible from the front. The compressor can be accessed from either side. A minimum of 24" clearance in front and sides of the unit should be provided to allow sufficient room to make water and electrical connec­tions. If the unit is located in a confined space such as a closet, provisions must be made for unit servicing. Unit sizes 036 thru 072 may be stacked vertically (2 high) in tight mechanical rooms.
Piping the Unit
Both source and load connections must be at least as large as the unit connection on the unit. The unit may be furnished with either copper or optional cupronickel coil on either source or load coaxial heat exchanger. Cupronickel should always be used when chlorinated water or ground water which is high in min­eral content is the load or source load fluid. Never use flexible hoses that are smaller (inside diameter) than that of the water connection on the unit. Make sure hoses and pipes are suitable for system water pressure and sized for proper flow rate.
The supply and the discharge pipes should be insulated to prevent condensation damage caused by low water temperature in the pipes.
If water hammer should occur during start-up or shut down, slow closing diaphragm type solenoid valves should be used. Placing the solenoid valve on the outlet side of the system helps relieve this situation. Due to high pressure drop or poor throt­tling characteristics, globe and gate valves should not be used, all flow valves should be ball type.
!
CAUTION
Domestic Hot Water Heat Recovery
The unit may have an optional factory installed waste heat recovery feature. The heat recovery device is factory piped to the refrigerant circuit of the unit. The plumbing to the water tank and the power to the recovery pump are to be completed in the field as required.
Care should be exercised in plumbing water lines to and from the water heater. Note: It is important that both water lines be insulated. For run less than 50 feet one way, use 1/2" O.D. water lines on models sizes 036 thru 072. A run over 50 feet should be avoided. On models 120 thru 420 specific system data must be matched to industry standard pipe sizing charts.
T o make a connection to Hot Water Heat Recovery:
1. Turn off power or gas valves to the water heater.
2. Turn off water supply to the water heater.
3. Open hot water faucet and drain tank.
4. Connect tubing to “Heat Recovery Water Out” on the unit
and extend this line to the hot water heater. Attach to hot water heater with fittings.
5. Connect tubing to “Heat Recovery Water In” on the unit
and extend this line to the water heater. Attach to cold wa­ter supply. Place pump in this line.
6. Set water heater thermostat as follows:
Electric, Double element - Upper 125°F , Lower minimum Gas, Oil or Single element - 125°F
7. Wire according to single phase diagram (page 5) and three
phase diagram (pages 6 and 7).
8. The piping and wiring are now complete. Turn on water
supply to water heater. With an open hot water faucet, al­low tank to fill. Bleed air from water lines. Check for water leaks. Do not restore power to water heater until after you have verified that the heat recovery unit is working and you have hot water circulating back to the water heater. Restore power to the water heater.
9. On start up of the unit, make the following operation checks: — Pump runs only when the compressor is on. Pump is turned
on by thermostat on compressor discharge line. — All air is purged from water lines. — Verify water circulation to and from water heater .
APPLICATIONS
Cooling Tower/ Boiler Application Closed Loop
Cooling T ower and Boiler Loop System temperature is usu­ally maintained between 55°F and 90°F. In the cooling mode, heat is rejected from the unit into the source water loop. To reject excess heat from the water loop, the use of a closed cir­cuit evaporative cooler or an open type cooling tower with a secondary heat exchanger between the tower and the water loop is recommended. When utilizing open cooling towers chemical water treatment is mandatory so that the water is free from cor­rosive minerals. It is imperative that all air be removed from the source closed loop side of the heat exchanger to protect against fouling.
Improper water flow in the system due to piping, valving or improper pump operating will void the warranty.
Water piping exposed to outside may freeze.
Page 8 of 20 / IM 816 (12-04) Water to Water Source Heat Pumps
!
CAUTION
In the heating mode, heat is absorbed from the source water loop. A boiler can be utilized to maintain the loop at the desired temperature. In milder climates a “flooded tower” concept is often used. This concept involves adding makeup water to the cooling tower sump to maintain the desired loop temperature.
When making water connections to unit sizes 036 thru 072, a T eflon taped thread sealant is recommended to minimize foul­ing of the pipes. Sweat connections are used for unit sizes 120 thru 420. The water lines should be routed so as not to interfere with access to the unit. The use of short lengths on high pressure hose with a swivel type fitting may simplify the connections and prevent vibration transmission to the building.
Before final connection to the unit, the supply and return hose kits must be connected together and the system flushed to remove dirt, piping chips and foreign material. Ball valves should be installed in the supply and return lines for unit isolation and unit water flow rate balancing. The return valve can be adjusted to obtain the proper flow rate whenever the unit heats or cools.
Pressure/temperature ports recommended both supply and return lines adjacent to the unit for system flow balancing. Flow can be accurately set by measuring the refrigerant-to-water heat exchangers water side pressure drop.
Well Water Application Open Loop
W ater pressure must be maintained in the heat exchanger by placing water control valves at the outlet of the unit. A bladder type expansion tank may be used to maintain pressure on the system. Pressure/temperature ports should be used to set flow rates by checking pressure drop across the heat exchanger. A void using low voltage (24 volt) solenoids, using them may overload the unit transformer or interfere with the lockout impedance cir­cuit. Line voltage solenoids across the load side of compressor contactor are recommended. Normally residential systems re­quire about 2-gpm of flow rate per ton of cooling capacity is needed in open loop systems.
Discharge water from a heat pump is not contaminated in any manner and can be disposed of in various ways depending on local building codes.
Disposal methods may be by recharge well, storm sewer, drain field, adjacent stream or pond. Most local codes forbid the use of sanitary sewer for disposal. Consult the local building and zoning department to determine compliance in your area.
Earth Coupled Application Closed Loop
Earth coupled closed loop systems should follow the same International Ground Source Heat Pump Association guidelines used for closed loop heat pump applications. Once piping is completed between the loop pump kit and the earth loop, final purging and charging of the loop is required. A flush/purge as­sembly capable of obtaining a velocity of 2 fps throughout the entire system is required. Usually a pump of at least 1.5 hp will be adequate to purge air and dirt particles from the loop itself for most residential systems. Commercial systems must be sized carefully using pump manufacturer pump curves and system specific data. Flush the system adequately to remove as much air as possible then pressurize the loop to a static pressure of 20 to 30 psi. This is normally adequate for proper system opera­tion. Check for proper flow through the unit by checking pres­sure drop across the heat exchanger and comparing it to the performance tables shown on page 15 and 16. In order to achieve proper cooling capacity in a earth coupled close loop applica­tion, a rate of 3 gpm per ton is required. Antifreeze solutions are required when low evaporating conditions are anticipated. Al­ways use pressure/temperature ports to provide proper fluid flow rates.
Typical Load Side Applications
There are many load side applications for which the fluid to fluid liquid chiller heat pumps can be used. The most popular used would include: Hydronic baseboard heating, hydronic in­slab floor heating, forced air fan coil heating or cooling, ice and snow removal, heating potable water, heating swimming pools and spas, and process fluid heating and cooling. When specify­ing load side heat transfer surface it is important to consider the heat pump output capacities and fluid flow rates. Insufficient load side heat transfer surface may cause unstable heat pump operating. Pressure/temperature ports should always be used to determine load side flow rates. Avoid contact of dissimilar met­als in the load side piping system.
The units can provide heating or cooling for pools and spas without the use of a secondary heat exchanger. This application would however require a cupronickel load side heat exchanger. Automatic chemical feeders must never be installed upstream of the heat pump. An external bypass should be installed to avoid over flowing the heat exchanger which could cause erosion. Proper pool PH levels and chemical balances must be main­tained to avoid possible heat exchanger damage.
Water to Water Source Heat Pumps Page 9 of 20 / IM 816 (12-04)
Dimensional Data – GRW, GHW, GCW 036, 048, 060 and 072
60Hz Unit
Cabinet Dimensions Water Connection Sizes
Unit Width Depth Height Unit Load Domestic Size A B C Size Source Hot Water
036 28-1/8 28-1/8 19 036 3/4" FPT ½" FPT 048 28-1/8 28-1/8 21 048 1" FPT ½" FPT 060 28-1/8 28-1/8 21 060 1" FPT ½" FPT
072 35-1/8 28-1/8 21 072 1" FPT ½" FPT
Piping Connection Location Dimensions
Unit Size D E F G H J
036 1-3/4 6-3/8 3-7/8 2 11-7/8 17-1/8 048 2-3/4 7-1/2 3-7/8 2 13-3/4 19 060 2-1/4 7-1/2 3-7/8 2 13-3/4 19 072 2-11/16 10-5/8 9-5/16 2 11-1/2 19
Page 10 of 20 / IM 816 (12-04) Water to Water Source Heat Pumps
Dimensional Data – GRW, GHW, GCW 120, 150 and 180
60Hz Unit
DIM ENSION / MODEL 120 - 150 180
CONNECTION LOC.
A,G B,H
C,F
D,E
NOTE: ALL DIMENSIONS ARE IN INCHES AND ALL PIPE SIZES ARE IN FPT
LOAD OUT LOAD OUT
LOA D IN LOA D IN
SO URCE IN S OURCE O UT
SO URCE OUT S O URCE IN
Water to Water Source Heat Pumps Page 11 of 20 / IM 816 (12-04)
DIM. 120 - 150 180
A B C D
E
F G H
PIPE SIZE
27 23 5/8 19 3/4 18 3/8 12 5/8 14 5/8
4 5/8 9 3/8 38 5/8 21 3/4 24 3/8 21 3/4 38 5/8 21 3/4 24 3/8 18 3/4
1 1/2 2
Dimensional Data – GRW, GHW, GCW 240, 300, 360 and 420
60Hz Unit
240 & 360 300 & 420 A B C D E F
G
H
CONNECTION SI ZE
NOTE: ALL DIMENSIONS ARE IN INCHES AND ALL PIPE SIZES ARE IN FPT
Page 12 of 20 / IM 816 (12-04) Water to Water Source Heat Pumps
25 7/8 26 1/4 20 1/2 20 7/8 10 3/8 10 1/4
54 7/8
30 29 1/2
27 1/8 26 3/4
30 29 1/2
27 1/8 26 3/4
22
CONNECTION L O CAT IO N
A,G
B,H C,F D,E
240 - 420
LOAD OUT
LOA D IN
SO URCE OUT
SOURCE IN
START UP
Check the following before powering the unit.
Avoid starting any electrical equipment for the first time alone, always have another person a safe distance from the unit that can turn off the main power in the event of an accident.
High voltage supply matches the nameplate rating.
Field wire size, breakers and fuses are the correct size.
Low voltage control circuit is correct.
Water piping is complete and correct.
Closed loop system is flushed and purged.
Isolation valves are open.
Loop pumps are correctly wired.
Access panels are in place and secured.
Thermostat is in “off” position.
Electric Shock Hazard. Turn Off All Power
Before Servicing.
MAINTENANCE PROCEDURES
Proper maintenance is important to provide the most effi­cient operation and longest life for your equipment. The fol­lowing points are to serve as a general guide. Always consult with your maintenance contractor with regard to the specific requirements of your own installation.
Paint Finish
The electrodeposition paint finish may be polished if de­sired. Spray paint is available in case of accidental scratching or chipping.
The following should be checked only by a competent con­tractor.
Contactor Points
Check contactor points twice a year to see that they are not burned or pitted as a result of low voltage, lightning strikes, or other electrical difficulties.
Water System
The water circulating pump should be checked and cleaned, so that it is operating normally . Clogged coils lead to high head pressures and inefficient operation. If coil is limed, a cleaning treatment may be necessary . W ater coils should be checked yearly for liming or clogging.
Check, Test and Start
1. Set thermostat to highest position.
2. Set thermostat switch to “cool”. Compressor should not operate. The source water pump should energize.
3. Slowly lower the thermostat setting until the compressor is energized. Regulate the water flow utilizing the P/T plugs and compare to the performance tables on page 18.
4. Check the cooling refrigerant pressures against valves with the tables .
5. Turn thermostat switch to the “off” position. The unit will stop running and the reversing valve should de-energize.
6. Leave unit “off” for approximately five minutes to allow pressure to equalize.
7. Adjust thermostat to lowest setting.
8. Set thermostat switch to “heat” position.
9. Slowly adjust thermostat to higher temperature until com­pressor energizes.
10. Compare the heating refrigerant pressure with valves with the tables .
11. Check for vibrations, noise, water leaks, etc.
12. Adjust thermostat to correct mode and set to maintain de­sired temperature.
13. Instruct the equipment owner/operator of correct thermo­stat and system operation.
14. Be certain to complete and forward the warranty papers to McQuay .
Improper Unit Functioning
If unit is not performing properly, several readings of tem­perature, pressure and electrical characteristics need to be taken. The normal required troubleshooting information is listed on the Check, Test and Start Form on page 20.
Water to Water Source Heat Pumps Page 13 of 20 / IM 816 (12-04)
GHW CIRCUIT DIAGRAM
GHW Load Coil = Heater-Condenser
Source Coil = Evaporator
Page 14 of 20 / IM 816 (12-04) Water to Water Source Heat Pumps
GRW CIRCUIT DIAGRAM
GRW Reverse Cycle
No Domestic Hot Water
GRW Reverse Cycle
With Domestic Hot Water H.R. Coil
Water to Water Source Heat Pumps Page 15 of 20 / IM 816 (12-04)
GCW CIRCUIT DIAGRAM
GCW Load Coil = Chiller-Evaporator Source Coil = Condenser
No Domestic Hot Water
GCW Load Coil = Chiller-Evaporator Source Coil = Condenser
With Domestic Hot Water H.R. Coil
Page 16 of 20 / IM 816 (12-04) Water to Water Source Heat Pumps
REPLACEMENT PARTS LIST
# Description 036 048 060 072 120 150 180 240 300 360 420 1 Expansion Valve* 564-376 564-397 564-450 546-436
Contactor
2
(Compressor)
3 Reversing Valve 564-411 564-286 564-286 564-289
Microprocessor
4
Board Capacitor
5
(Compressor) High Pressure
6
Switch (HP) Low Pressure
7
Switch (LP1) Fluid/Refrigerant
8
Coil S/W Copper Fluid/Refrigerant
8
Coil S/W CU-NI
9 Transformer 846-073 846-073 846-073 846-073
Low pressure
10
switch (LP2)
11 Compressor 800-486 800-487 800-465 800-441
Reversing Valve
12
Coil Refrigerant
13
Charge R-22 lb.
*Where same valve is used in two or more units superheat settings may differ. Consult factory for valve with correct setting.
841-077 841-077 841-077 841-077
843-253 843-253 843-253 843-253
856-115 856-116 856-117 856-079
844-079 844-079 844-079 844-079
844-041 844-041 844-041 844-041
512-193 512-194 512-194 512-263
512-200 512-201 512-201 512-259
844-062 844-062 844-062 844-062
874-083 874-083 874-083 874-083
2.8 4.4 4.4 6.25
Water to Water Source Heat Pumps Page 17 of 20 / IM 816 (12-04)
PERFORMANCE TABLES
COOLING MODE OPERATING PRESSURES (PSIG) GRW & GCW MODELS
Entering Source Temperature °F
Leaving Load °F 50 70 90
SUCT DISCH SUCT DISCH SUCT DISCH
45 51 – 61 128 – 153 53 – 63 165–190 55–65 222–247 50 55 – 65 130 – 155 57 – 67 170–195 61–71 227–252 55 61 – 71 133 – 158 63 – 73 177–202 67–77 233–258
HEATING MODE OPERATING PRESSURES (PSIG) GRW & GHW MODELS
Entering Entering Suction Discharge
Load°F Source°F Pressure Pressure
30 33 – 48 169 – 194
80
100
120
50 47 – 62 182 – 207 70 66 – 81 200 – 225 90 80 – 95 226 – 251 30 35 – 50 233 – 258 50 50 – 65 247 – 272 70 69 – 84 262 – 287 90 85–100 278 – 303 30 35 – 50 312 – 337 50 52 – 67 320 – 345 70 71 – 86 330 – 355 90 90 - 105 347 - 372
INTERNAL PRESSURE DROP CHART
Unit Load FT. Source FT. GPM Size Pres. Drop Pres. Drop source/load
036 16.8 16.8 9.0 048 12.3 12.3 12.0 060 14.5 14.5 13.5 072 25.0 25.0 17.0 120 13.3 13.3 24.0 150 17.3 17.3 30.0 180 16.7 16.7 36.0 240 14.8 14.8 45.0 300 24.3 24.3 60.0 360 15.7 15.7 75.0 420 23.4 23.4 90.0
Page 18 of 20 / IM 816 (12-04) Water to Water Source Heat Pumps
GENERAL SERVICE GUIDE
All models employ an electromechanical control system for maximum reliability.
Symptom Possible Trouble Method of Finding
1. Noisy Operation. a. Chattering contactor noise. a. Check contactor points, check for adequate control
voltage from transformer, and check control circuit for shorts or breaks, check thermostat.
2. Compressor will a. Lock Out Relay Open. a. Turn thermostat off, then on.
not start.
b. Loose electrical connections. b. Check all connections at contactor and compressor
terminal box for loose or burned connection on terminal.
c. Refrigerant charge lost, low pressure c . Check for R-22 pressure.
cutout open.
d. No control voltage to the compressor d. Check for 24 volts across contactor coil.
contactor. If no voltage, check for thermostat circuit trouble
or for compressor safety controls open.
e. Contactor pulled in, but compressor still e. Check compressor overload circuit, contactor points, etc.
won’t start.
3. Compressor starts but a. Run capacitor could be bad. a. Check capacitor.
hums and trips out on overload. b. Voltage may be low. b. Check it.
c. Seized bearings on compressor. c . Replace compressor.
4. Compressor starts but a. Low liquid flow (heating cycle). a. Check liquid flow.
cuts out on low pressure control. b. Low refrigerant charge. b. Remove refrigerant, repair leak and recharge.
c. Restriction in liquid refrigerant line. c. Check pressures and look for frosting across
the restriction.
d. Low airflow (cooling cycle). d. Check and correct.
e. Low pressure cutout may have incorrect e. Check low pressure cutout for correct pressure.
pressure function.
5. Compressor starts a. Condenser coils limed or restricted. a . Check it. (Open systems)
but cuts out on high pressure control. b. Malfunctioning high pressure control. b. Check that the control is cutting out at the correct
pressure.
c. Reduced or lack of liquid flow. c. Check liquid.
d. Reduced evaporator air flow d. Check air flow.
(heating cycle).
6. Compressor runs on a . Reversing valve may be defective. a. See that it has shifted.
heating cycle, but does not heat. b. Thermostat may be defective. b. Check wiring diagram.
Water to Water Source Heat Pumps Page 19 of 20 / IM 816 (12-04)
CHECK, TEST AND START FORM
General Information
Customer Name ____________________________________ Dealer Name _____________________________________ Address___________________________________________ Address__________________________________________
_________________________________________________ ________________________________________________ _________________________________________________ ________________________________________________
Phone # __________________________________________ Phone # _________________________________________
Product Information
Unit Model # ____________________________________________________________ Unit Serial # ____________________________________________________________
Source Coil Application Ground Source Open Well Other _________________
Load Coil Application Fan Coil Unit Radiant Htg/Clg Coils Baseboard Radiation
Other ____________________________________________
Voltage ____________ Amperage _______________ Phase _______________ Transformer Volts ________________
UNIT FUNCTION
HEATING (GRW & GHW) ENTERING LEAVING DIFF (TD) Load Liquid Temperature, °F
From fan coil unit, radiant coils, baseboard radiation, etc. ________________ _________________ ________________
Source Liquid Temperature, °F
From well, geothermal closed loop, plate heat exchanger, etc. ________________ _________________ ________________
COOLING (GRW & GCW)
Load Liquid Temperature, °F To fan coil unit, radiant coils, baseboard radiation, etc. _________________ ________________ ________________
Source Liquid Temperature, °F
From well, geothermal closed loop, plate heat exchanger, etc. _________________ ________________ ________________
Load Fluid Pressure FT. HD or PSIG
[Note 1 PSIG = 2.31 FT. HD] _________________ _______________ _________________
Source Fluid Pressure _________________ _______________ _________________
Load GPM ___________________ Source GPM _________________
Source Fluid Water Anti-freeze HA or HR = 500 x TD x GPM For Anti-Freeze solution = 485 x TD x GPM
Calculation __________ x __________ x __________ = ________________
(Load) 500 or 485 TD GPM HA or HR
Check product performance tables on page 18 to determine if calculation is within 10% of table value.
4900 Technology Park Boulevard • Auburn, New York 13021-9030 • 1.800.432.1342 • USA Page 20 of 20 / IM 816 (12-04)
©2004 McQuay International
Loading...