Note: Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes and
regulations, and are experienced with this type of equipment. Caution: Sharp edges are a potential injury hazard. Avoid contact
with them.
Transportation and Storage
Upon receipt of the equipment, check carton for visible
damage. Make a notation on the shipper’s delivery ticket
before signing. If there is any evidence of rough handling, the
cartons should be opened at once to check for concealed
damage. If any damage is found, notify the carrier within 48
hours to establish your claim and request their inspection
and a report. The Warranty Claims Department should then
be contacted.
Do not stand or transport the machines on end. For
storing, each carton is marked with “up” arrows.
In the event that elevator transfer makes upended posi-
tioning unavoidable, absolutely insure that the machine is in
the normal upright position for at least 24 hours before
operating.
Temporary storage at the jobsite must be indoors, completely shielded from rain, snow, etc. High or low temperatures naturally associated with weather patterns will not
harm the conditioners. Excessively high temperatures of
o
140
F (60oC) may deteriorate certain plastic materials and
cause permanent damage. In addition, the solid-state circuit
boards may experience operational problems.
Installation
General
1. To prevent damage, this equipment should not be operated for supplementary heating and cooling during the
construction period.
2. Inspect the carton for any specific tagging numbers as
requested by the installing contractor. At this time the
voltage, phase and capacity should be checked against
the plans.
3. Check the unit size against the plans to be sure that the
unit will be installed in the correct location.
4. Before installation, check the available closet dimensions
versus the dimensions of the unit.
5. Pay attention to the location and routing of water piping,
and electrical wiring. The locations of these items are
clearly marked on submittal drawings.
6. The installing contractor will find it beneficial to confer
with piping, sheet metal, ceiling and electrical foremen
together before installing any conditioners.
7. Remove shipping block from under the fan wheel.
8. We recommend that the contractor cover the conditioners with plastic film to protect the machines during finishing of the building. This is important if spraying fireproofing material on bar joists, sandblasting, spray painting
and plastering operations have not been completed. If
plastic film is not available, the shipping carton may be
modified to cover the units during construction.
9. On extra-quiet construction units with spring mounted
compressors, remove the shipping block under the compressor.
Page 2 / IM 407
Unit location
1. Locate the unit in an area that allows for easy removal of
the filter and access panels, and has enough space for
service personnel to perform maintenance or repair. Provide sufficient room to make water, electrical and duct
connections.
2. The contractor should make sure that access has been
provided including clearance for duct collars and fittings
at water and electrical connections.
3. Allow adequate room around the unit for a condensate
trap.
4. The unit can be installed “free standing” in an equipment
room; however, closet installations are more common for
small vertical type units. Generally, the unit is located in
the corner of a closet with the nonducted return air facing
90o to the door and the major access panels facing the
door as in Figure 1A. Alternatively, the unit can have a
ducted return air with the opening facing the door and the
major access panels facing 90
Figure 1A. Typical closet installation with louver door return
o
to the door as in Figure 1B.
5. It is recommended that the unit be located on top of a
vibration absorbing material such as rubber or carpet to
reduce any vibration. See Figure 5.
6. If optional field installed controls are required (boilerless
system), space must be provided for the enclosure to
mount around the corner from the electrical entrances. Do
not locate the side of the unit too close to a wall. See
Figures 1A and 1B.
Minimum distance requirement from return air duct
collar to wall, for non-ducted units.
ModelDistance
007 – 012 .......................... 4 inches
015 – 019 .......................... 5 inches
024 – 030 .......................... 6 inches
036 – 042 .......................... 7 inches
048 – 060 .......................... 8 inches
Filter access
Each unit is shipped with a filter bracket for side filter removal.
Heat Pump
With Left-Hand
Return Air Arrangement
Return
Air
Opt. Controls
Elec. Entrance
Main Access Panel
Condensate
Water Supply
Water Return
Louvered Door
RisersReturn Air Thru
Figure 1B. Typical closet installation with ducted return
Heat Pump
Return
Duct &
Grille
With Left-Hand
Return Air Arrangement
Air
Opt. Controls
Elec. Entrance
Main Access PanelMain Access Panel
Heat Pump
With Right-Hand
Return Air Arrangement
Opt. Controls
Elec. Entrance
Main Access Panel
Condensate
Water Supply
Water Return
Return Air Thru
Louvered Door
Heat Pump
With Right-Hand
Return Air Arrangement
Opt. Controls
Elec. Entrance
NOTE: Minimum distance
Return
requirement for non-ducted
Air
units. (see chart above)
Return
Air
Duct &
Grille
Condensate
Water Supply
Water Return
Condensate
Water Supply
Water Return
Risers
IM 407 / Page 3
Ductwork and attenuation
Discharge ductwork is normally used with these conditioners. Return air ductwork may also be required, but will require
field installation of a return air duct collar/2" (51mm) filter rack
kit.
All ductwork should conform to industry standards of
good practice as described in ASHRAE Systems Guide.
The discharge duct system will normally consist of a
flexible connector at the unit, a noninsulated transition piece
to the full duct size, a short run of duct, an elbow without
vanes, and a trunk duct teeing into a branch circuit with
discharge diffusers as shown in Figure 2. The transition piece
must not have an angle greater than 30
performance can result. Do not connect the full duct size to
the unit without using a transition piece down to the size of
the discharge collar on the unit. With metal duct material, the
sides only of the elbow and entire branch duct should be
internally lined with acoustic insulation for sound attenuation. Glass fiber duct board material is more absorbing and
may permit omission of the flexible connector.
The ductwork should be laid out so that there is no line of
sight between the conditioner discharge and the distribution
diffusers.
Return air ducts can be brought in through a wall grille and
then to the unit. The return duct system will normally consist
of a flexible connector at the unit and a trunk duct to the
return air grille. With metal duct material, the return air duct
should be internally lined with acoustic insulation for sound
attenuation. Glass fiber duct board material is more absorbing and may permit omission of the flexible connector.
Return air ductwork to the unit requires the optional return
air duct collar/2" (51mm) filter rack kit. See Figure 3. The kit
can be installed for face side or bottom filter removal. The
flexible connector can then be attached to the 1" (25mm)
duct collar.
Do not use sheet metal screws directly into the unit
cabinet for connection of supply or return air ductwork,
especially return air ductwork which can puncture the drain
pan or the air coil.
o
or severe loss of air
Figure 2.
Trunk Duct
Square Elbow
(Both Sides
Internally Lined
With Acoustic
Insulation)
Branch Duct
(Internally
Lined)
Duct
Transition
Canvas
Collar
Discharge Collar
(on Heat Pump)
Heat Pump
2 ft. x 2 ft
Diffuser
Ventilation air
Outside air may be required for ventilation. The temperature
of the ventilation air must be controlled so that mixture of
outside air and return air entering the conditioner does not
exceed application limits. It is also general practice to close
off the ventilation air system during unoccupied periods
(night setback).
The ventilation air system is generally a separate building
subsystem with distribution ductwork. Simple introduction
of the outside air into each return air plenum chamber
reasonably close to the conditioner air inlet is not only
adequate, but recommended. Do not duct outside air directly
to the conditioner inlet. Provide sufficient distance for thorough mixing of outside and return air. See “Operating limits”
on page 7.
Figure 3.
Sizes 007 thru 042Sizes 048 & 060
Page 4 / IM 407
Electrical Data
General
1. Be sure the available power is the same voltage and phase
as that shown on the unit serial plate. Line and low voltage
wiring must be done in accordance with local codes or the
National Electrical Code, whichever is applicable.
2. Apply correct line voltage to the unit. A 7⁄8" (22mm) or 11⁄8"
(29mm) hole is supplied on the side of the unit. A disconnect switch near the unit is required by code. Power to the
unit must be sized correctly and have time delay (dual
element) fuses or an HACR circuit breaker for branch
circuit overcurrent protection. See the nameplate for
correct ratings.
230 Volt operation and 50 cycle units
All 208-230 volt single and three-phase units are factory
wired for 208 volt operation. For 230 volt operation, the line
voltage tap on the 24 volt transformer must be changed.
Figure 4A.Figure 4B.
Disconnect and cap the red lead wire and interchange it with
the orange lead wire on the primary of the 24 volt transformer. Three-phase 50 cycle units require a neutral wire for
230/50/1 power.
Fan speed change
All units have two-speed fan motors and are shipped for
high speed operation. On unit sizes 007, 009 and 012, the
change from high speed to low speed is done by removing
the black wire from the fan relay and connecting the red wire
to the fan relay (Figure 4A). On units sizes 015 through 060,
each fan motor is supplied with a 5-pin terminal block
mounted on the fan motor. To change from high speed to
low speed, move the wire from the black #3 location to the
red #4 location on unit sizes 015 through 042 or to the red
#5 location on units sizes 048 and 060. On 575 volt units,
add a jumper between black #3 and blue #4 for low speed
operation. See Figure 4B.
COMMON (WHITE)
FAN
MOTOR
BROWN (CAPACITOR)
BLACK (HIGH SPEED)
RED (LOW SPEED)
Piping
1. All units are recommended to be connected to supply
and return piping in a two-pipe reverse return configuration. A reverse return system is inherently self-balancing
and requires only trim balancing where multiple quantities of units with different flow and pressure drop characteristics are connected to the same loop. A simple
way to check for proper water balance is to take a
differential temperature reading across the water connections. To insure proper water flow, the differential
should be 10
A direct return system may also be made to work acceptably, but proper water flow balancing is more difficult to achieve and maintain.
2. The piping can be steel, copper or PVC.
3. Supply and return runouts are usually connected to the
unit by short lengths of high pressure flexible hose which
are sound attenuators for both unit operating noise and
hydraulic pumping noise. One end of the hose should
have a swivel fitting to facilitate removal for service. Hard
piping can also be brought directly to the unit although
it is not recommended since no vibration or noise attenuation can be accomplished. The hard piping must
have unions to facilitate unit removal. See Figure 5 for
typical piping setup.
4. Supply and return shutoff valves are required at each
conditioner. The return valve is used for balancing and
should have a “memory stop” so that it can always be
closed off but can only be reopened to the proper
o
F (5oC) to 14oF (8oC).
COMMON
CAPACITOR
HIGH SPEED
LOW SPEED
LOW SPEED
FAN
MOTOR
YELLOW 1
BROWN 2
BLACK 3
*RED 4
*RED 5
*On unit sizes 048 and 060, terminal 4 is colorcoded blue and terminal 5 is color-coded red.
JUMPER
position for the flow required.
5. No unit should be connected to the supply and return
piping until the water system has been cleaned and
flushed completely. After the cleaning and flushing has
taken place, the initial connection should have all valves
wide open in preparation for water system flushing.
6. Condensate piping can be steel, copper or PVC. Each
unit is supplied with a
7
⁄8" (22mm) ODM copper stub.
7. The condensate disposal piping must have a trap and
the piping must be pitched away from the unit not less
1
⁄4" inch per foot (21mm per meter). Generally, the
than
condensate trap is made of copper and soldered on the
unit. See Figure 6. A piece of vinyl hose from the trap to
the drain line is used for simple removal. A complete
copper or PVC condensate system can also be used.
Union fittings in the copper lines should be applied to
facilitate removal. Factory supplied condensate hose
assemblies have a
7
⁄8" (22mm) sweat to FPT fitting to
facilitate connection of a flexible vinyl, rubber or steel
braided hose.
8. No point in the drain system may be above the drain
connection of any unit.
9. Automatic flow controlled devices must not be installed
prior to system cleaning and flushing.
10. A high point of the piping system must be vented.
11. Check local code for the need for dielectric fittings.
IM 407 / Page 5
Figure 5.Figure 6.
Balancing
Blower
Motor
Access
Flexible Hose
With Brass
Pipe Fitting
Electrical &
Compressor
Access
Isolator Pad
Note: Condensate drain connection must be minimum of 1" (25mm)
below connection to heat pump.
Note: Do not overtorque fittings. The maximum torque without damage to fittings is 30 foot pounds. If a torque wrench is not available, use as a rule of thumb,
finger-tight plus one quarter turn. Use two wrenches to tighten the union, one to hold the line and one for simultaneous tightening of the nut.
Valve With
Close-off
Supply
Return
Condensate
1
1
(38mm)
⁄2"
Electrical Access Panel
1
⁄2"
1
(38mm)
Optional Cleanout
1
⁄4'' Per Foot
(21mm Per Meter)
Cleaning and Flushing System
1. Prior to first operation of any conditioner, the water circulating system must be cleaned and flushed of all construction dirt and debris.
If the conditioners are equipped with water shutoff
valves, either electric or pressure operated, the supply
and return runouts must be connected together at each
conditioner location. This will prevent the introduction of
dirt into the unit. Additionally, pressure operated valves
only open when the compressor is operating.
Figure 7.
Return Runout
Supply Runout
Mains
Rubber Hose
Runouts Initially
Connected Together
2. The system should be filled at the city water makeup connection with all air vents open. After filling, vents should be
closed.
The contractor should start main circulator with pressure reducing valve makeup open. Vents should be
checked in sequence to bleed off any trapped air to
assure circulation through all components of the system.
Power to the heat rejector unit should be off, and the
supplementary heat control set at 80
o
F (27oC).
While circulating water, the contractor should check
and repair any leaks in the piping. Drains at the lowest
point(s) in the system should be opened for initial flush
and blow-down, making sure city water fill valves are set
to make up water at the same rate. Check the pressure
gauge at pump suction and manually adjust the makeup
to hold the same positive steady pressure both before and
after opening the drain valves. Flush should continue for
at least two hours, or longer if required, to see clear, clean
drain water.
3. Supplemental heater and circulator pump should be shut
off. All drains and vents should be opened to completely
drain down the system. Short circuited supply and return
runouts should now be connected to the conditioner
supply and return connections. Teflon tape is recommended over pipe dope for pipe thread connections. Use
no sealers at the swivel flare connections of hoses.
4. Trisodium phosphate was formerly recommended as a
cleaning agent during flushing. However, many states
and localities ban the introduction of phosphates into
their sewage systems. The current recommendation is to
simply flush longer with warm 80
o
F (27oC) water.
5. Refill the system with clean water. Test the litmus paper
for acidity, and treat as required to leave the water slightly
alkaline (pH 7.5 to 8.5). The specified percentage of
antifreeze may also be added at this time. Use commercial grade antifreeze designed for HVAC systems only. Do
not use automotive grade antifreeze.
6. Set the system control and alarm panel heat add setpoint
o
to 70
F (21oC) and the heat rejection setpoint to 85oF
o
C). Supply power to all motors and start the circulating
(29
pumps. After full flow has been established through all
components including the heat rejector (regardless of
season) and air vented and loop temperatures stabilized,
each of the conditioners will be ready for check, test and
start-up and for air and water balancing.
Start-up
1. Open all valves to full open position and turn on power
to the conditioners.
2. Set thermostat for “Fan Only” operation by selecting
“Off” at the system switch and “On” at the fan switch. If
“Auto” fan operation were selected, the fan would cycle
with the compressor. Check for proper air delivery.
Page 6 / IM 407
3. All units have two-speed motors. Reconnect for low
speed operation if necessary.
4. Set thermostat to “Cool.” If the thermostat is an automatic changeover type, simply set the cooling temperature to the coolest position. On manual changeover
types additionally select “Cool” at the system switch.
Again, many conditioners have time delays which
protect the compressor against short cycling. After a
few minutes of operation, check the discharge grilles for
cool air delivery. Measure the temperature difference
between entering and leaving water. It should be approximately 1
temperature difference. For example, if the cooling temperature difference is 15
ture difference should have been 12
Without automatic flow control valves, a cooling
temperature difference of 10
1
⁄2 times greater than the heating mode
o
F (8oC), the heating tempera-
o
F (5oC).
o
F to 14oF (5oC to 8oC) is
about right. Adjust the combination shutoff/balancing
valve in the return line to a water flow rate which will
result in the 10
o
F to 14oF (5oC to 8oC) difference.
5. Set thermostat to “Heat.” If thermostat is the automatic
changeover type, set system switch to the “Auto” position and depress the heat setting to the warmest selection. Some conditioners have built-in time delays which
prevent the compressor from immediately starting. With
most control schemes, the fan will start immediately.
After a few minutes of compressor operation, check for
warm air delivery at discharge grille. If this is a “cold
building” start-up, leave unit running until return air to
the unit is at least 65
o
F (18oC).
Measure the temperature difference between entering and leaving air and entering and leaving water. With
entering water of 60
water should be 6
o
F to 80oF (16oC to 27oC), leaving
o
F to 12oF (3.3oC to 6.7oC) cooler, and
the air temperature rise through the machine should not
exceed 35oF (19oC). If the air temperature exceeds 35oF
o
(19
C), the airflow rate is probably inadequate.
If the water temperature difference is less than 6
o
(3.3
C), the water flow rate is excessive. If the water
temperature difference exceeds 12
o
F (6.7oC), then the
o
water flow rate is inadequate.
6. Check the elevation and cleanliness of the condensate
line. If the air is too dry for sufficient dehumidification,
slowly pour enough water into the condensate pan to
ensure proper drainage.
7. If the conditioner does not operate, the following points
should be checked:
a. Is proper voltage being supplied to the machine?
b. Is the proper type of thermostat being used?
c. Is the wiring to the thermostat correct?
8. If the conditioner operates but stops after a brief period,
check for:
a. Is there proper airflow? Check for dirty filter, incorrect
fan rotation (3-phase fan motors only), or incorrect
ductwork.
b. Is there proper water flow rate within temperature
limits? Check water balancing; backflush unit if dirt
clogged.
9. Check the unit for vibrating refrigerant piping, fan wheels,
etc.
10. Do not lubricate the fan motor during the first year of
operation as it is prelubricated at the factory.
F
Operating Limits
Environment
This equipment is designed for indoor installation only.
Sheltered locations such as attics, garages, etc., generally
will not provide sufficient protection against extremes in
temperature and/or humidity, and equipment performance,
reliability, and service life may be adversely affected.
Power supply
A voltage variation of ±10% of nameplate utilization voltage
is acceptable. Three-phase system unbalance shall not exceed 2%.
Note: Voltages listed are to show voltage range. However,
units operating with overvoltage and undervoltage for extended periods of time will experience premature component
failure.
Additional information
1. Standard units — Units are designed to start and operate
in an ambient of 40
with entering water at 70
at the flow rates used in the ARI Standard 320-86 rating
test, for initial start-up in winter.
Note: This is not a normal or continuous operating con-
dition. It is assumed that such a start-up is for the purpose
of bringing the building space up to occupancy temperature.
o
F (5oC), with entering air at 40oF (5oC),
o
F (21oC), with both air and water
2. Extended range units— Extended range heat pump
conditioners are designed to start and operate in an
ambient of 40
entering water at 40
o
F (5oC), with entering air at 40oF (5oC), with
o
F (5oC), with both air and water at the
flow rates used in the ARI Standard 320-86 rating test, for
initial start-up in winter.
Note: This is not a normal or continuous operating con-
dition. It is assumed that such a start-up is for the purpose
of bringing the building space up to occupancy temperature.
Air and water limits
STANDARDEXTENDED
UNITSRANGE UNITS
CoolingHeatingCoolingHeating
Min. Amb. Air50oF/10oC50oF/10oC40oF/5oC40oF/5oC
Normal Amb. Air80oF/27oC70oF/21oC80oF/27oC70oF/21oC
Max. Amb. Air100oF/38oC85oF/29oC 100oF/38oC85oF/29oC
Min. Ent. Air ➀ ➁50oF/10oC50oF/10oC50oF/10oC40oF/5oC
Normal Ent. Air,80/67
db/wb27/19oC21oC27/19oC21oC
Max. Ent. Air,100/83
db/wb ➀ ➁38/28oC27oC38/28oC27oC
o
F70oF80/67oF70oF
o
F80oF100/83oF80oF
Water enthalpy
Min. Ent. Water
➀ ➁
Normal Ent. Water 85oF/29oC70oF/21oC85oF/29oC70oF/21oC
Max. Ent. Air,
➀ ➁
➀ At ARI flow rate
➁ Maximum and minimum values may not be combined. If one value is at
maximum or minimum, the other two conditions may not exceed the
normal condition for standard units. Extended range units may combine
any two maximum or minimum conditions, but not more than two, with all
other conditions being normal conditions.
CoolingHeatingCoolingHeating
o
F/13oC55oF/13oC40oF/5oC40oF/5oC
55
o
F/43oC90oF/32oC 110oF/43oC90oF/32oC
110
IM 407 / Page 7
60 Cycle Wiring Diagrams — Mark IV/AC Units
Figure 8. Unit sizes 007 through 012 (208-230, 265 volts, single-phase) 060686404 Rev. A
Notes:
1. Mark IV/AC controller board contains a static sensitive microprocessor. Proper grounding of field service personnel is required or
damage to controller may result.
2. Unit is factory wired for 230V operation. If 230V power supply is
used, transformer must be rewired by disconnecting the power
from the red transformer primary wire and connecting the power
lead to the orange transformer primary wire. Place an insulation
cap on the red transformer primary wire.
3. Terminal block on Mark IV/AC board provides 24 VAC at terminals R and C. All other terminals are 24 VDC output.
4. All temperature and pressure switches are normally closed.
5. Field supplied relays attached to the 24 volt terminals R, W, Y or
G may introduce electrical noise. Never install relays in series
with the inputs.
Figure 9. Unit size 015 (208-230, 265 volts, single-phase) 060856804 Rev. A
Notes:
1. Mark IV/AC controller board contains a static sensitive microprocessor. Proper grounding of field service personnel is required or
damage to controller may result.
2. Unit is factory wired for 230V operation. If 230V power supply is
used, transformer must be rewired by disconnecting the power
from the red transformer primary wire and connecting the power
lead to the orange transformer primary wire. Place an insulation
cap on the red transformer primary wire.
3. Terminal block on Mark IV/AC board provides 24 VAC at terminals R and C. All other terminals are 24 VDC output.
4. All temperature and pressure switches are normally closed.
5. Field supplied relays attached to the 24 volt terminals R, W, Y or
G may introduce electrical noise. Never install relays in series
with the inputs.
Page 8 / IM 407
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.