McQuay FCVC, FCVS, FCWC, FCVH Installation Manual

Installation and Maintenance Manual IM 980-1
ThinLine 3G Vertical Fan Coils
Type FCVC, FCVH, FCVS and FCWC Vertical Design
200 to 1200 cfm
IM 980-1
Group: Applied Air Systems Part Number: 910102984 Date: May 2011
Model FCVC
Model FCVS
Table of Contents
IM 980-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Receiving and Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Fresh Air Box Openings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Recommended Maintenance Clearance . . . . . . . . . . . . . . . . . . . . . . . . . 5
Duct Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Uncrating and Inspecting the Unit . . . . . . . . . . . . . . . . . . . . . . . . . .6
Mounting Unit to Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Water Piping Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
General Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Connecting to a Factory-Installed Valve & Piping Package . . . . . . . . . . 8
Field-Installed Valve & Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Shutoff/Balancing Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Condensate Drain Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Steam Piping Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Two-pipe systems with electric heat . . . . . . . . . . . . . . . . . . . . . . .10
External Insulating Requirements . . . . . . . . . . . . . . . . . . . . . . . . .10
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Standard Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Thermostat and Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Initial Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Cleaning & Flushing the Water System . . . . . . . . . . . . . . . . . . . . . . . . . 11
Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Venting Hydronic Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Operation and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Manual 4-Position Fan Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Unit-Mounted, Mechanical Thermostat With 4-Position Fan Switch . . . 13
Digital Thermostats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Low-Voltage (LV) Interface Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Operation and Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Fresh Air Damper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Condensate Overflow Detection Device . . . . . . . . . . . . . . . . . . . . . . . . 16
Leveling Legs Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Cabinet Rear Extension Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Electric Heat Over-Temp Reset Button . . . . . . . . . . . . . . . . . . . . . . . . . 17
Key-lock Access Door Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
General Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Filter Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Condensate Drain Pans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Unit Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Shipping Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Factory-Installed Valve & Piping Packages . . . . . . . . . . . . . . . . .25
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
IM 1121 - Hideaway Unit Discharge Conversion Kit . . . . .35
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
IM 1023 - Fresh Air Damper Kit . . . . . . . . . . . . . . . . . . . . . .37
Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Cold Weather Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
IM 1028 - Fresh Air Damper Motor Kit . . . . . . . . . . . . . . . .39
Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
IM 1024 - Cabinet Rear Extension Kit . . . . . . . . . . . . . . . . .41
Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
IM 1021 - Key-Lock Access Door Kit . . . . . . . . . . . . . . . . .43
IM 1014 - MTA/B 155 Electronic Thermostats . . . . . . . . . .45
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Thermostat Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
Wire Lead Colors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
Application Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
IM 1089 - Field Installation of MT155 Thermostats . . . . . .47
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Two-pipe system (Cooling or Heating) . . . . . . . . . . . . . . . . . . . . . . . . . .47
Four-pipe system (Cooling and Heating) . . . . . . . . . . . . . . . . . . . . . . . .49
IM 1015 - MT 158 and MT 168 Digital Thermostats . . . . . .51
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Thermostat Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Mode Button Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Fan Speed Switch Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Up/ Down Arrow Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Setback Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Pipe Sensor Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Service Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Application Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Power-Up Operating Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . 53
IM 1016-1 - MTB 158 Microprocessor Thermostats . . . . .55
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
Thermostat Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
Mode Button Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
Fan Speed Switch Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
Up/ Down Arrow Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
Setback Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
Pipe Sensor Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
Three Wire Floating Valve Operation . . . . . . . . . . . . . . . . . . . . . . . . . . .56
Outside Air Damper Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
Application Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
Service Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
Power-Up Operating Sequence . . . . . . . . . . . . . . . . . . . . . . . . . .57
IM 1017 - MT 168 0-10Vdc/4020mA Thermostats . . . . . . .59
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
Electrical Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
Application Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
Thermostat Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
Service Menu: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
IM 846 - MT 170 Thermostats . . . . . . . . . . . . . . . . . . . . . . .63
Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
Thermostat Model and Part Number. . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Optional Occupancy Detection Sensors/Kits . . . . . . . . . . . . . . . . . . . . .65
Mounting and Wiring the Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . .65
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67
Thermostat Button Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67
Verifying Thermostat Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67
Thermostat Menu Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68
Fan Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
Fancoil Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70
Setback Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70
Optional Occupancy Detection Equipment Operation . . . . . . . . . .71
SB200-001 Occupancy Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
SD200-001 Occupancy Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73
SD200-002 Occupancy Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74
IM 831 - Thermostat Conversion Kit . . . . . . . . . . . . . . . . . .77
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .77
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .77
Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .77
IM 763 - Automatic Changeover Switch . . . . . . . . . . . . . . . 79
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .79
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .79
Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .79
2 McQuay IM 980-1
General Information
FC V S - 1 02 A
Unit Type FC = Fan Coil FH = Cabinet Unit Heater
Unit Configuration V= Vertical W = Wall Hung (future)
Cabinet Type C = Cabinet (Flat Top) S = Slope Top H = Hideaway
Voltage A = 115/60/1 E = 208-230/60/1 J = 277-265/60/1
Unit Size 02 = 200 CFM 03 = 300 CFM 04 = 400 CFM 06 = 600 CFM 08 = 800 CFM 10 = 1000 CFM 12 = 1200 CFM
Design Series
Multiple Control Options
From 3-speed switch to LV interface board
Remote or unit-mounted
3-speed or staged fan
Multiple Configurations
Flat top
Slope top
Hideaway
Wall mounted
Multiple Coil Options
2, 3 or 4-row main coil
1 or 2-row preheat or 1-row
reheat coil
Hot water or steam
Same or opposite end
connections
Multiple Grille Options
Stamped discharge
louver
Multi-directional grilles
Return grille option
Software Selectable Valve & Piping Packages
Factory-mounted, wired and
tested or factory-assembled and shipped loose for field mount
Normally Closed or Open, On/Off
or modulating valves
Easily Removed Drain Pan & Motor Assembly
For easy maintenance and service
Sloped, polymer drain pan for good IAQ
Optional Secondary Drain Pan (Supplied with Piping Packages)
Noncorrosive
Easily removed
Thinline™ 3G Vertical Fan Coils are intended for use in single zone applications. They are available in sizes from 200 to 1200 cfm. Figure 2 describes the main features of these units and can be refered to for component placement. These units are available in two-pipe configurations with one hydronic coil, with or without electric heat. They are also available in four­pipe configurations with one primary coil and a secondary reheat or preheat coil. A variety of factory-built piping packages are available, either factory or field-installed.
Units are available with a variety of thermostat and fan speed control options, which can be mounted on the unit or shipped loose for mounting in the controlled space. Options include:
Four-position fan switch (Off/Lo/Med/Hi).
Manual thermostat with On/Off valve control.
Digital thermostat with a variety of control options,
including fan control, On/Off or modulating valve control and automatic changeover from heating to cooling on two­pipe systems.
Low-voltage interface board for connecting a unit to
controls provided by others. The controls interface option includes a 24 volt AC transformer and interface terminal strips.
No Controls, with pigtail connections to the unit’s fan motor
wiring harness.
Figure 1: Nomenclature (see Table 1, page 29 for complete model number description)
General Information
Figure 2: Unit Features
McQuay IM 980-1 3
General Information
Receiving and Storage
Upon receipt of the equipment, check carton for visible damage. Make a notation on the shipper’s delivery ticket before signing. If there is any evidence of rough handling, immediately open the cartons to check for concealed damage. If any damage is found, notify the carrier within 48 hours to establish your claim and request their inspection and a report. The Warranty Claims Department should then be contacted.
Do not stand or transport the machines on end. For storing, each carton is marked with “up” arrows.
Temporary storage at the job site must be indoor, completely sheltered from rain, snow, etc. High or low temperatures naturally associated with weather patterns will not harm the units. Excessively high temperatures, 140°F (60°C) and higher, may deteriorate certain plastic materials and cause
permanent damage.
IMPORTANT
This product was carefully packed and thoroughly inspected before leaving the factory. Responsibility for its safe delivery was assumed by the carrier upon acceptance of the shipment. Claims for loss or damage sustained in transit must therefore be made upon the carrier as follows:
VISIBLE LOSS OR DAMAGE Any external evidence of loss or damage must be noted on the
freight bill or carrier’s receipt, and signed by the carrier’s agent. Failure to adequately describe such external evidence of loss or damage may result in the carrier’s refusal to honor a damage claim. The form required to file such a claim will be supplied by the carrier.
CONCEALED LOSS OR DAMAGE Concealed loss or damage means loss or damage which does
not become apparent until the product has been unpacked. The contents may be damaged in transit due to rough handling even though the carton may not show external damages. When the damage is discovered upon unpacking, make a written request for inspection by the carrier’s agent within fifteen (15) days of the delivery date and file a claim with the carrier.
Pre-Installation
Before beginning installation, please read this publication in its entirety. Directions given in this bulletin for right and left sides or coil hand assume a position facing the front of the unit.
1 To prevent damage, do not operate this equipment for
supplementary heating and cooling during the construction period. Doing so will void the warranty.
2 Inspect the carton for any specific tagging numbers
indicated by the factory per a request from the installing contractor. At this time the voltage, phase and capacity should be checked against the plans.
3 Check the packing list and unit identification/tagging
numbers against the plans to verify that the unit is being
installed in the correct location. The unit data plate is attached to the deck plate on the front of the fan coil (see
Figure 3). Remove the front panel on cabinet units to
access it. The panel contains specific information on standard components as listed in Figure 1, page 3 and in
Table 1, page 29.
Figure 3: Data Plate Location
Before installation, check the available dimensions
4
where the unit is to be installed against the dimensions of the unit.
5 Note the location and routing of water piping,
condensate drain piping, and electrical wiring. The locations of these items are clearly marked on submittal drawings.
6 An installing contractor may find it beneficial to confer
with piping, sheet metal, and electrical foremen before installing any unit.
Note: Check the unit data plate for correct voltage with the
plans before installing the equipment. Also, make sure all electrical ground connections are made in accordance with local code.
7
The unit is not designed to be free-standing. Install it against a wall or other flat surface that meets fire and electrical codes requirements for heating and cooling devices.
8 After installation, cover the unit with the shipping carton
or other appropriate material for protection during finishing of the building. This is critical while spraying fireproofing material on bar joists, sandblasting, spray painting and plastering. Damage to the unit due to a failure to protect it during finishing of the building is not covered by the warranty.
Fresh Air Box Openings
ThinLine 3G Vertical Fan Coils can be installed with an optional fresh air box that is designed to let in outside air while preventing water (such as rain) from getting into the unit itself. If used, prior to unit installation, confirm that the exterior wall opening and the wall box are ready and installed in accordance with the job plans.
4 McQuay IM 980-1
General Information
0.5 in
13 mm
0.5 in
13 mm
10 in
254 mm
Recommended Maintenance Clearance
Cabinet units have removable front and side panels for easy access to components for service and maintenance. The fan assembly and main drain pan are easily removable from the front for cleaning. See Accessing/removing the main drain pan
and motor assembly‚ page 19 for more information. Figure 4 shows recommended maintenance clearances: 0.5
inches (13 mm) on either side and 10 inches (254 mm) in front. Units are referred to as either right-hand or left-hand depending upon the piping connection. Hand is designated by facing the front of the unit (airflow discharges from the front or top). Unless it is a special-order unit, the control panel is always on the end opposite the cooling coil pipe connections.
Figure 4: Recommended maintenance clearance
Duct Connections
1 Discharge ductwork should run in a straight line,
unchanged in size or direction, for a minimum distance of three fan diameters from the unit (approximately 20 inches).
2 Avoid making sharp turns when making duct turns and
transitions. Use proportional splits, turning vanes, and air scoops when necessary.
3 When possible, construct and orient supply ductwork
turns in the same direction as the fan rotation.
Safety
Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing operations. Have a fire extinguisher available. Follow all warnings and cautions in these instructions and attached to the unit. Consult applicable local building codes and National Electrical Codes (NEC) for special requirements.
Recognize safety information. When you see a safety symbol on the unit or in these instructions, be alert to the potential for personal injury. Understand the meanings of the words DANGER, WARNING, and CAUTION. DANGER identifies the most serious hazards that will result in death or severe personal injury; WARNING means the hazards can result in death or severe personal injury; CAUTION identifies unsafe practices that can result in personal injury or product and property damage. Improper installation, adjustment, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may result in personal injury or property damage. This product must be installed only by personnel with the training, experience, skills, and applicable licensing that makes him/her “a qualified professional HVACR installer.”
Air ducts, when used with hideaway units, should be installed in accordance with local and national codes, including National Fire Protection Association standards for the Installation of Air Conditioning and Ventilating Systems and the National Fire Protection Association standards for the Installation of Air Conditioning and Ventilation Systems other than Residence Type.
A one-inch duct collar is provided on units with a ducted return and/or discharge to attach ductwork. McQuay recommends using galvanized sheet metal ductwork. Slide the sheetmetal duct over the duct collar flange of the unit, seal the joint and fasten with sheetmetal screws.
Note: Do not run screws through the removable front panel on
hideaway units.
Ductwork Recommendations
Follow the general recommendations listed below when installing the ductwork for the unit.
McQuay IM 980-1 5
DANGER
Disconnect all electrical power before servicing unit. Electrical shock will cause severe injury or death.
WARNING
Hazardous Voltage!
Use copper conductors only. Unit terminals are not designed to accept other types of conductors. Failure to do so may cause damage to the equipment.
WARNING
Personal injury hazard. Wear protective gloves to avoid possible cuts and abrasions from exposed edges. Avoid contact with sharp edges.
CAUTION
Cleaning agents may cause serious damage to internal components, such as aluminum coils and electronic controls, etc. Do not operate fan coil while building maintenance cleaning agents are in use..
Installation
Installation
Uncrating and Inspecting the Unit
1 Carefully remove the packaging, remaining alert to any
signs of shipping damage. Be careful not to discard components that may be included with the packaging.
2 If the unit is damaged, file a claim with the carrier.
Notify the local McQuay representative immediately.
3 You may want to retain some or all of the packaging to
provide jobsite unit location information and temporary protection for the fan coil after installation. Be sure to dispose of plastic packaging and protective cardboard properly, in accordance with local recycling rules and guidelines.
WARNING
Plastic packaging is a suffocation hazard, dispose of properly. Keep away from children.
4 Touch up painted panels if necessary. If panels need
paint, sanding is not necessary. However, clean the surface of any oil, grease, or dirt residue so the paint will adhere. Purchase factory approved touch up paint from your McQuay representative or McQuay Factory Service.
Mounting Unit to Wall
WARNING
Installation and maintenance are to be performed by qualified personnel who are familiar with local codes and Regulations, and experienced with this type of equipment..
CAUTION
Personal injury hazard. Wear protective gloves to avoid possible cuts and abrasions from exposed edges. Avoid contact with sharp edges.
1 Consult job blueprints for unit location. 2 Clean area where unit is to be installed, removing all
construction dirt and debris. Remove an y mouldings at the floor or wall.
3 Remove the unit from the shipping carton and plastic
covering. Save the carton and plastic to use as a protective cover after the installation is complete.
4 On cabinet units, remove the screws shown in Figure 5
that secure the right and left cabinet corner panels to the subbase. For ease of installation, you may also remove the center panel. Lift the panels up and out.
Note: Set the unit panels aside where they will not be
damaged. Take care not to bend the mounting tabs on the bottom of the panels.
Figure 5: Cabinet Side Panel Removal
5
STOP! If an outside air damper kit is to be installed, install it now. See Fresh Air Damper‚ page 16 and the IM included with the damper for more information.
6 Position the chassis/subbase against the wall where the
unit is to be installed. Make sure that the area under the unit is free of combustible materials such as carpet. For cabinet units, the wall must act to close off the back of the unit.
7 For hideaway units, if you are using McQuay’s
decorative wallplate, use blocks or other suitable material to raise the unit off the floor a minimum of 1.5 inches (38 mm).
8 Make sure electrical and piping connections are in the
proper location within the end compartments. The control box is in the end compartment opposite the main coil piping connections. Power to the unit is hooked up through the junction box/disconnect box located under the control box. See Figure 30, page 21 through
Figure 33, page 24 for location information.
9 Use a level to check that the unit is level both front to
back and side to side (see Figure 6). Adjust the unit as needed using the optional leveling legs or shims.
CAUTION
It is critical that the unit is level to avoid condensate accumulation in the drain pan. This is especially important when using a stainless steel drain pan which does not have a sloped bottom.
10 The chassis has a series of slots on the back flange to
mount the assembly to the wall. Transfer a mark with a marker or pencil to the wall at the mounting hole locations.
11 Insert fasteners through the mounting holes in the chassis
and secure the unit to the wall. Do not over-tighten fasteners. It is the installing contractor’s responsibility to
6 McQuay IM 980-1
Installation
Make sure unit is level front-to-back and side-to-side.
Use a quenching cloth when soldering or brazing to avoid overheating the piping components and creating valve damage or eratic operation.
select the correct fasteners for each unit to meet local codes. At location(s) where no stud is present, secure with a Toggle bolt or equivalent.
Note: Use a minimum of two fasteners on each side to
secure the unit (field supplied).
12
On cabinet units, reinstall the side/quarter panels in reverse order as performed in step 4.
13 If you raised the unit off the floor in step 7, remove the
block or other material supporting the bottom of the unit. Make sure the unit is securely fastened to and supported by the wall mounts.
14 Cut out one side and the bottom of the shipping carton,
leaving the top and three sides to place over the unit for protection during construction.
Figure 6: Unit Mounting
Water Piping Connections
General Guidelines
1 Piping can be steel, copper or PVC, but must comply
with local codes.
2 Proper ventilation is required for soldering. When
soldering, use a quenching cloth to protect fan coil components from overheating damage—melting
insulation, also damage to valves, wiring, electronics, sensors, etc. See Figure 7. When McQuay provides valve
McQuay IM 980-1 7
packages with unions, o-rings are included. When soldering near unions, remove the o-rings before heating.
Figure 7: Protect Components From Overheating
3
If sealant compound is not provided for flexible hose fittings, apply Teflon tape to the connections to help prevent leaks.
4 Ensure proper insulation of supply and return piping.
Proper insulation prevents loss of fan coil capacity, overheating of end compartments, and/or moisture dripping.
5 The piping to and from the unit must be protected from
outside air and freeze conditions. It must be suitably insulated for condensation and for heat loss or gain. Penetrations entering the unit end compartments must be fitted/sealed for unit integrity.
6 Exterior condensate may be an issue if field piping does
not have a control valve. Review the supply and return header locations in the Dimensions drawing beginning on page 21. If using a field-assembled piping package, allow sufficient room to install the secondary drain pan. Piping for chilled water should not extend over the edges of the secondary condensate drain pan.
7 Supply and return shutoff valves are recommended at
each unit. The return valve is used for balancing and should have a “memory stop” so that it can always be closed off, but can only be re-opened to the proper position for the flow required.
8 Primary coils are factory-equipped with vents for venting
the system, but secondary coils (preheat or reheat) are not. If the unit is not equipped with a factory-built piping packages, then a vent must be added. See step 1, page 8.
9 Be sure to install control valves on the correct fan coil.
Indiscriminate mixing of valves in the field can result in valves improperly sized for the desired flow rate, which can result in poor operation and coil freezeups.
10 Install control valves so there is at least 2" (51mm)
minimum clearance to remove the actuator from the valve body.
Installation
Secondary Coil Air Vent
11 Do not connect a unit to the supply and return piping
until the water system has been cleaned and flushed completely. After this is done, the initial connection should have all valves wide open in preparation for water system flushing.
12 Condensate piping can be steel, copper, or PVC. A
means of disconnection must be furnished to facilitate fan section removal.
13 No point of the drain system may be above the drain pan
of any unit.
14 Automatic flow control devices must not be installed
prior to system cleaning and flushing.
15 Check local code for any requirement for electrical
fittings.
Connecting to a Factory-Installed Valve & Piping Package
To view connection locations for factory-i nstalled valve & piping packages, see Figure 34, page 25. Before instal ling supply and return lines to a factory piping package, review the following items.
All piping connections are 5/8" O.D.S. (1/2" nominal)
female copper connections.
Supply and return piping should not interfere with the
secondary drain pan or condensate line.
The installer must provide adequate piping system filtration
and water treatment.
McQuay Deluxe and Enhanced piping packages include a
strainer which prevents debris from entering the coil. Clean the strainer regularly.
The fan coil ships with brackets to adequately support the
piping package during shipment. Remove these brackets before connecting water piping to the unit.
Set end valves to the fully open position to prevent damage
to the valve seat during brazing.
Remove the secondary drain pan, if in place, to prevent
exposure to dripping solder or excessive temperatures.
Solder water piping connections to supply and return end
connections. Avoid overheating factory soldered joints to prevent the possibility of leakage.
Insulate fan coil piping to secondary drain pan connections
and any piping that is not above the secondary drain pan.
Field-Installed Valve & Piping
Review General Guidelines‚ page 7 before beginning. Then carry out the following steps to install valves and piping.
1 For units equipped with a secondary coil make sure that
an air vent is included in the return line piping (see
Figure 8). Primary coils are factory-equipped with vents
for venting the system, but secondary coils (preheat or reheat) are not.
IMPORTANT
Venting is required on the return piping for secondary preheat or reheat coils. It is included on factory-built piping packages, but must be added by the installing contractor for field-installed piping. See Figure 8.
Figure 8: Secondary Coil Air Vent
2 Remove the secondary drain pan, if in place, to prevent
exposure to dripping solder or excessive temperatures.
Note: Factory-installed valve and piping packages include
the secondary drain pan, which ships with the unit. For other arrangements, the secondary drain pan must be ordered separately.
3
Push the main drain pan condensate hose back inside the end plate to prevent it from getting burned when making sweat connections. Be sure to pull the hoses back through and route to the secondary drain pan when the end panel has cooled.
4 Slide ½" copper tubing or connection couplings (installer
provided) onto the coil connections. Solder the joint using a good-quality, lead-free solder to provide a watertight connection.
WARNING
Avoid overheating when soldering field connections to the coil to prevent leakage, overheating of the copper tubes, and melting of valves, factory-soldered joints or component gasketing. A quenching cloth is recommended. See Figure 7.
5 After connections are complete, insulate all piping to the
coil connections as necessary to prevent condensate from dripping outside of the secondary drain pan.
6 Install the optiona l seco nd ary drain pan.
Shutoff/Balancing Valve
Each fan coil should be at least be equipped with shutoff valves on both the supply and return lines for easy serviceability and removal if it becomes necessary. We suggest using our combination shutoff/balancing valves between the
8 McQuay IM 980-1
Installation
7/8-inch OD copper pipe
Changeover switch
Changeover sensor
main supply line and the fan coil unit. These can be furnished as part of a factory-installed valve & piping package or they can be installed in the field. The balancing valve installed on the return line is used to adjust the water flow to provide the best performance.
Condensate Drain Connection
1 Connect a copper or plastic pipe to the 7/8 inch copper
pipe on the secondary drain pan. This should be a mechanical connection that allows easy removal of the secondary drain pan when servicing the piping end pocket.
2 Slide the pipe over the drain pan nipple and tighten the
collar on the pipe with a hose clamp (installer supplied). A drain line pitch of one inch per ten feet of drain line run must be maintained to provide adequate condensate drainage.
3 The drain line should be supported to prevent undue
stress on the secondary drain pan. Make sure the drain line is free of kinks and obstructions and the secondary drain pan is level.
4 The installer is responsible for adequately insulating
field piping. See External Insulating Requirements‚ page
10 for more information.
Figure 9: Condensate Drain Connection
Automatic Changeover Sensor
Two-pipe changeover units require an automatic changeover switch or pipe sensor that determines heating or cooling mode based on the supply water temperature. A switch is provided with a unit-mounted analog thermostat on a two-pipe system. A sensor is provided with any digital control on a two-pipe system. On units with a factory-installed valve & piping package, the factory straps the changeover switch or sensor to the piping supply water pipe. See Figure 10.
For a two-pipe system with intermediate electric heat, a second set is required including a changeover switch or sensor.
Figure 10: Changeover switch & sensor attachment
If the unit does not have a factory-installed valve & piping package, the changeover switch or sensor can be ordered for field installation. The installer should attach the sensor or auto­changeover switch parallel to and in direct contact with the supply water pipe.
Note: The installer is responsible to ensure the changeover
sensor is installed in a location that can sense active water temperature. Otherwise, the unit may fail to sense the correct operating mode and disable temperature control.
When using field-supplied three-way valves, install the changeover sensor upstream of the valve on the supply water pipe. When using field-supplied two-way control valves, install the changeover sensor in a location that will detect active water temperature. The unit must always be able to sense the correct system water temperature, regardless of the control valve position.
Note: The maximum length of the automatic changeover wire
cannot exceed ten feet from the control panel to the sensor. If the wire extends beyond the unit chassis, use shielded conductors to eliminate radio frequency interference (RFI).
Steam Piping Connections
CAUTION!
Coil Damage! In all steam coil installations, the condensate return connections must be at the low point of the coil to ensure condensate flows freely from the coil at all times. Failure to do so may cause physical coil damage from water hammer, unequal thermal stresses,freeze-up and/or corrosion.
McQuay IM 980-1 9
Make piping connections to the steam coil per job requirements. (McQuay does not supply steam piping connections.) Install a 1/2", 15-degree swing check vacuum breaker in the unused condensate return trapping as close as possible to the coil.The following procedures are recommended:
Installation
Low-voltage conductors brought in here
Electric heat power conductors brought in here
Unit power conductors brought in here
1 Vent the vacuum breaker line to atmosphere or connect it
into the return main at the discharge side of the steam trap.
2 Pitch all steam supply and return mains down a
minimum of one inch per ten feet in the direction of flow.
3 Do not drain the steam mains or takeoff through the
coils. Drain the mains ahead of the coils through a steam trap to the return line.
4 Overhead returns require one psig of pressure at the
steam trap discharge for each two-feet elevation to ensure continuous condensate removal.
5 Proper steam trap selection and installation is necessary
for satisfactory coil performance and service life. For installation, use the following steps:
a Position the steam trap discharge at least 12 inches
below the condensate return connection. This provides sufficient hydrostatic head pressure to overcome trap losses and ensure complete condensate removal.
b McQuay recommends using flat and thermostatic
traps because of gravity drain and continuous discharge operation.
c Use float and thermostatic traps with atmospheric-
pressure gravity condensate return, with automatic controls or where the possibility of low pressure supply steam exists.
d Always install strainers as close as possible to the trap
inlet side.
Electrical Connections
Installation and maintenance must be performed only by qualified personnel who are familiar with local codes and regulations, and are experienced with this type of equipment.
DANGER
Hazardous Voltage!
The installer must determine and follow all applicable codes and regulations. This equipment presents hazards of electricity, rotating parts, sharp edges, heat and weight. Failure to read and follow instructions can result in property damage, severe personal injury or death.
Standard Electrical Connection
Field electrical power connections are made in the electrical junction box, which is mounted to the control box on the side of the chassis opposite the primary coil piping connections. See Figure 11. If the unit is equipped with an optional disconnect switch, it is located in this junction box.
Units with an electric heat option that has the same voltage as the unit can bring the power conductors into this same junction box. Units with electric heat that has a different voltage should bring the electric heat into one of the knockouts on the control box. See Figure 11.
Low voltage wires should be brought into the conduit located next to the field electrical power junction box. See Figure 11.
Figure 11: Electrical Power Connections
Two-pipe systems with electric heat
The electric heating coil is designed to be the total source of heat for the unit. If used for auxiliary intermediate season heating, additional control is required. A second switch or pipe sensor is required. Contact your McQuay representative for more information.
To protect the electric heat elements, an automatic and manual electric heat switch disengages the electric heat to prevent overheating. For information on resetting the manual switch, see Electric Heat Over-Temp Reset Button‚ page 17.
External Insulating Requirements
Insulate and vapor-seal surfaces that are colder than the surrounding air dew point to prevent unplanned condensation. McQuay recommends field-insulation in the following areas to prevent potential condensate problems:
Supply and return water piping connections
Condensate drain lines and connections
Fresh air intake duct connections
Discharge duct connections
Wall boxes
If electrical wiring or conduit comes through the floor, all wires or conduit should be sealed at this point. It will prevent any condensation or water leakage that may occur due to lack of preventive maintenance.
Note: Wiring coming through the wall should be sealed to stop cold air
infiltration through the wall cavity, which could affect unit thermostat operation. Wiring coming through the floor should be sealed to prevent condensation or water leakage from reaching live wires.
10 McQuay IM 980-1
Installation
Cabinet unit: Wiring diagram inside cabinet corner panel
Hideaway unit: Wiring diagram on front panel
Return Runout
Supply Runout
Mains
Flexible Hose
Install a strain relief and pass the wires through the strain relief into the junction box. Make the connections and reinstall the junction box cover.
Electrical Data
The wiring diagram for the unit is attached to the inside of the corner panel on cabinet units. It is attached to the front cover of the unit on hideaway units. See Figure 11. Be sure the available power is the same voltage and phase as that shown on the unit serial plate. See Figure 3, page 4 for the location of the serial plate.
Figure 12: Wiring Diagram Locations
Note: Voltages listed are to show voltage range. However,
units operating with overvoltage and undervoltage for extended periods of time will experience premature component failure.
Thermostat and Controls
DANGER
READ THE INSTRUCTIONS INCLUDED WITH THE THERMOSTAT/CONTROL CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE IT.
Failure to observe safety information and comply with instructions could result in PERSONAL INJURY, DEATH AND/ OR PROPERTY DAMAGE.
To avoid electrical shock or damage to equipment, disconnect power before installing or servicing. Use only wiring with insulation rated for full thermostat operating voltage. Use copper wire only. Insulate or wirenut all un-used leads. Any wiring, including the remote probe,may carry the full operating voltage of the thermostat.
To avoid potential fire and/ or explosion do not use in potentially flammable or explosive atmospheres.
Retain the installation instructions for future reference. You must review your application and national and local codes to ensure that your installation will be functional and safe.
After wiring and installation are complete, energize the system and check the operation. Adjust the thermostat as necessary to complete at least one cycle. Be sure the thermostat and all other equipment are functioning correctly.
Line and voltage wiring must be done in accordance with local codes or the National Electrical Code, whichever is applicable.
Apply correct line voltage to the unit. Power to the unit must be sized correctly. Branch circuit overcurrent protection must be provided per local codes. See the nameplate for correct ratings.
All 208-230V single-phase units are factory wired for 230 volt operation. For 208 V operation the L1 wire connection to the unit transformer (found in the main control box) must be changed. The L1 wire must be disconnected from the 230 V (orange) wire and connected to the 208 V (red) wire. The 230 V wire must then be capped off with a wire nut or male terminal as appropriate. Please refer to the unit wiring diagram.
Operating Voltages
Operating voltages are as follows (+/– 10%).
115/60/1
208-230/60/1
265-277/60/1
McQuay IM 980-1 11
Initial Startup
Cleaning & Flushing the Water System
1 Prior to first operation of any unit, clean and flush the
water circulating system of all construction dirt and debris.
2 If units are equipped with water shutoff valves, either
electric or pressure operated, connect the supply and return runouts together at each unit location. This will prevent the introduction of dirt into the unit. See
Figure 13.
Figure 13: Connections for flushing system piping
Installation
Primary coil
air vent
Reheat coil air vent on
factory-installed package
3 Fill the system at the city water makeup connection with
all air vents open. After filling, close all air vents.
4 Start the main circulator with the pressure reducing valve
open.
5 Check vents in sequence to bleed off any trapped air,
ensuring circulation through all components of the system.
6 While circulating water , check and repair any leaks in the
unit and surrounding piping.
CAUTION
Units must be checked for water leaks upon initial water system startup. Water leaks may be a result of mishandling or damage during shipping. Failure by the installing contractor to check for leaks upon start-up of the water system could result in property damage
7 Drains at the lowest point(s) in the system should be
opened for initial flush and blow-down, making sure city water fill valves are set to make up water at the same rate.
8 Check the pressure gauge at pump suction and manually
adjust the makeup to hold the same positive steady pressure both before and after opening the drain valves.
9 Flush should continue for at least two hours or longer
until the drain water is clean and clear.
10 Shut off the circulator pump and open all drains and
vents to completely drain down the system.
11 Short-circuited supply and return run outs should now be
connected to the unit supply and return connections. Do not use sealers at the swivel flare connections of hoses.
12 Refill the system with clean water. 13 Test the water using litmus paper for acidity, and treat as
required to leave the water slightly alkaline (pH 7.5 to
8.5).
14 Antifreeze may also be added at this time. Use
commercial grade antifreeze designed for HVAC systems only. Do not use automotive grade antifreeze. Antifreeze will have an effect on the performance of the unit.
15 Once the system has been filled with clean water and
antifreeze (if used), precautions should be taken to protect the system from dirty water conditions.
It is McQuay’s policy not to make recommendations on water treatment. It is the responsibility of the user to check that the water supply to the units is free of contaminants or corrosive agents, chemicals or minerals. The general contractor or owner should contact a local water treatment company regarding water treatment. A fouled water system will lead to premature component failure.
IMPORTANT
Operating Limits
This equipment is designed for indoor installation only. Sheltered locations such as attics, garages, etc., generally will not provide sufficient protection against extremes in temperature and/or humidity , and equipment performance, reliability , and service life may be adversely affected.
Venting Hydronic Coils
Hydronic coils require a vent, either manual or automatic, to release air from the unit. Primary coils on all Thinline fan coils come standard with a coil air vent. It is located on the piping side of the unit, above the coil connections. See Figure 14.
Secondary coils on ThinLine units are not equipped with an air vent, but one is included on all factory-supplied valve and piping packages. It is located on the pipe closest to the outlet coil connection. See Figure 14.
Perform the following steps to vent both primary and secondary coils after installing the unit.
1 Pressurize the building piping system with water and
vent any trapped air at system vents.
2 For units with manual air vents, back the set screw out to
expel air from the unit and then re-tighten the set screw.
3 Automotic air vents should require no adjustment for the
coil to vent. However, if the coil does not vent immediately, unscrew the outer portion of the fitting to expel air from the port. If debris has become trapped in the vent, completely remove the outer portion of the fitting and clean.
Figure 14: Coil Air Vents
12 McQuay IM 980-1
Operation and Maintenance
Operation and Maintenance
Controls
A wide variety of control options are available for ThinLine 3G Vertical Fan Coils, both unit-mounted and remote­mounted. This section provides a brief overview of these options and their operation. For more complete information, contact your McQuay representative.
Manual 4-Position Fan Switch
This four-position fan switch (Off, High, Med, Low) option, shown at the right, is available remote-mounted. It operates on low-voltage or line-voltage power and can be provided with a factory-mounted low­voltage interface board, which contains three-24 volt relays with line voltage contactors and terminal connections. The transformer is factory-installed and wired.
Sequence of operation
Off: Fan is turned off. The motorized fresh-air damper, when
supplied, is closed (see Fresh Air Damper‚ page 16).
High, Medium, Low: Fan runs continuously at the selected
speed. The two-position, motorized fresh-air damper, when supplied, is opened.
Unit-Mounted, Mechanical Thermostat With 4-Position Fan Switch
The unit-mounted option, shown at the right, combines the four-position fan switch with a mechanical thermostat. For two­pipe systems with a factory installed valve package, it can be provided with a manual switch (shown in picture to the right) to change from heating to cooling. Alternatively, the changeover can be automatic.
Changeover Switch: With a manual switch, the user selects
whether heating or cooling is desired. With automatic changeover, a pipe sensor works with the thermostat to operate the heating or cooling valve.
Heating: Opens the valve when the temperature is below the setpoint.
Cool: Opens the valve when the temperature is above the setpoint.
Digital Thermostats
McQuay offers a broad range of unit-mounted and remote, wall-mounted digital thermostats with the capabililty to control On-Off, 3-wire and proportional modulating valves, and Normally Closed or Normally Open actuator valves. For more information, refer to the McQuay publication ED 18513-1 and ED 18527.
MT155 Thermostat
For more details refer to page 47. The MT155 series thermostat provides on-off control for low-voltage or line-voltage valves and fan motors. This thermostat is designed as a remote-mount with connection to the LV interface board mounted on the fan coil unit. Options include manual or automatic changeover and three-speed fan control for continuous or cycling fan operation. The thermostat may be mounted on units already at the job site. Each unit should be equipped with an LV Interface Board, if not, a Controls Mounting Kit PN9101120 80 needs to be ordered. For field installation instructions of the MT155 on a unit, refer to page 45.
Figure 15: MT155 Thermostats
Sequence of operation
Fan Switch
Off: Fan is turned off. The two-position, motorized fresh-air damper, when supplied, is closed (see Fresh Air
Damper‚ page 16).
High, Medium, Low: Fan runs conti nuously at the selected speed. The two-position, motorized fresh-air damper, when supplied, is opened.
Thermostat
• Cycles the valve(s) open or clo sed on deman d based on occupant-desired level.
McQuay IM 980-1 13
Three standard control options are available:
On-Off fan cycle operation only: The thermostat cycles the
fan from the manually selected fan speed (high, medium or low) to off.
Continuous fan and On-Off valve cycle operation: The
thermostat cycles the valves on and off. The fan runs continuously at the manually selected fan speed.
Operation and Maintenance
On-Off fan and On-Off valve cycle operation: The
thermostat cycles the fan from the manually selected fan speed to off and it cycles the valves on and off.
When the system switch is in the OFF position, the fan coil system including the fan is shut off.
TA155: A HEAT-OFF-COOL system switch manually selects heating or cooling mode. In the HEAT position, only the heat output cycles with demand. In the COOL position, only the cool output cycles with demand. In the OFF position, heating and cooling outputs are off. Units with a two position system switch or without a system switch must use a load transfer switch when both heating and cooling outputs are used. This prevents control failure and equipment damage caused by direct cycling between loads.
TB155: An ON-OFF system switch enables auto-changeover of heating and cooling modes. In the ON position the thermostat activates heating or cooling outputs dependant upon the relationship between set point and ambient temperature. Heat on to cool on dead band is 4°F. In the OFF position, heating and cooling outputs are off. Units without a system switch cycle between heating and cooling with a 4°F dead band.
FAN: Some units have a switch for manual selection of fan speed. On these units fan operation is either internally wired for fan continuous operation or is dependant upon connection to the fan supply input . When internally wired for fan continuous operation, the fan will be off when the system switch is off. When dependant upon external connections the fan may not be off with the system switch in the off position. The fan supply input is switched to fan speed outputs (HI­MED-LO).
Heating and cooling outputs for the MT158 are individually configurable for three-wire floating control valves or On/Off valves in the Normally Open or Normally Closed modes.
Heating and cooling outputs for the MT168 provide 0-10 Vdc or 4-20 mA for proportional modulating valve control. The integrated, three-speed fan control switch is line voltage to allow direct connection to the fan motors. Manual or automatic changeover is provided with remote setback capability from a time clock or facility management system. Features include a Fahrenheit or Celsius digital display and a built-in purge cycle which assists the controller to determine if the system is supplying hot water or cooling.
Two standard control options are available:
Continuous fan and modulating (or On-Off) valve
operation: The fan runs continuously at the manually
selected fan speed (high, medium or low). The controller modulates the valves or, on the MT158, dip-switches can be set to cycle the valves on and off.
On-Off fan cycle operation and modulating (or On-Off)
valve operation: The controller cycles the fan from the
manually selected fan speed to off. The controller modulates the valves or, on the MT158, dip-switches can be set to cycle the valves on and off.
T170 Thermostat with Digital Display
Two thermostats are offered for remote installation only: TA170 for three-speed fan control and TB170 for staged fan operation. Both thermostats are used for On-Off control of low- or line-voltage valves with auto changeover. Detailed installation instructions and modes of operation can be found in page 63.
MT158 and MT168 Thermostat-Controllers with Digital Display
For more details refer to page 51, 55 or 59. Series MT158 and MT168 microprocessor-based thermostat-controllers combine a proportional integral control algorithm with adaptive logic. They may be unit-mounted or remote-wall mounted.
Figure 16: MT158 and MT168 Thermostats
Figure 17: T170 Thermostat with Digital Display
14 McQuay IM 980-1
Operation and Maintenance
Low Voltage Fan motor control
Low-voltage valve actuators
Room air or return air temperature sensor Pipe temperature sensor Condensate overflow sensor
Remote thermostat 24 VAC power
Low-Voltage (LV) Interface Board
The low-voltage interface board is used with any remote (wall mounted) McQuay thermostat or control. It can also be used in conjunction with a controller of a building automation system (BAS) control where low voltage is needed to operate the fan coil. It is located in the control box for the unit (see Figure 11,
page 10).
The LV interface board includes:
Three 24-volt relays with line-voltage contactors to operate
the fan motor speeds.
Terminal connections for interfacing to:
• An optiona l rem ote-mounted thermostat.
• Low-voltage actuators for heating and cooling valves.
• A return air sensor.
• A pipe temperature sensor for changeover from heating to cooling on two-pipe systems.
A factory-wired and installed transformer.
Figure 18: LV Interface Board 24 VAC connections
See Figure 18 for a list of connecting points to the board. For additional wiring information, see the typical wiring diagram
Figure 37, page 28 or the unit’s wiring diagram, which is
attached to the corner panel on cabinet units and to the chassis front cover on hideaway units. (see Figure 12, page 11).
For instructions on field-mount MT155 thermostats on units supplied with LV Interface boards (a typical arrangement for a 5-day Quick Ship Program), refer to page 45.
McQuay IM 980-1 15
Operation and Maintenance
To open damper, reach under the unit and pull the damper handle toward you
To adjust damper tension, loosen or tighten nuts on each end of damper axis.
Accessories
Fresh Air Damper
The fresh air damper kit provides up to 25% outside air to the unit heater. It consists of an intake with damper blade and insect screen. The damper may be manually controlled through the return air opening or with an optional field-installed damper motor. For detailed installation information, refer to
page 37.
Operation
To open the damper, reach under the unit and pull the damper handle toward you. To close, push the damper away from you. See Figure 19.
Figure 19: Opening and Closing the Damper
Fresh Air Damper Motor Kit (Low Voltage)
This damper motor kit is for field installation with the fresh air damper kit. The damper kit must be ordered separately. For detailed installation instructions, refer to page 39, which is supplied with the damper motor kit. Under most control schemes, the damper motor is set up to open the damper automatically whenever the unit fan is in operation.
Figure 21: Damper Motor Kit Installed in Unit
Condensate Overflow Detection Device
The condensate overflow detection device is a factory-installed option on fan coils. This device has a condensate overflow floater with dry contacts and is connected to the LV interface board. See Figure 22.
If the damper is difficult to open or moves too freely, you can adjust the tension by tightening or loosening the nuts on its pivot axis. See Figure 20.
Figure 20: Adjusting Damper Tension
Cold Weather Operation
Unit heaters may experience erratic operation during cold ambient conditions with the outside air damper in the open position.
If you suspect it is not working properly, check to be sure that the float is installed straight up with the proper elevation. See
Accessing/removing the main drain pan and motor assembly‚ page 19 for instructions on removing the main drain pan to
access the device. The condensate overflow switch needs to be wired to the
proper controller (T170 for example) to shut off the fan if water is present in the drain pan.
Figure 22: Condensate Overflow Switch Installation
16 McQuay IM 980-1
Operation and Maintenance
To adjust height, loosen the locking nut with a 9/16” wrench. Then, turn the leveling leg bolt head clockwise to raise the unit, or counterclockwise to lower it.
Cabinet Rear Extension
Vertical Fan Coil Unit
Push the red reset button
Leveling Legs Option
Field or factory-installed kits are available with 0” to 1" adjustment for positive leveling of floor-mounted units.
Height Adjustment
To adjust the height of a leveling leg:
1 Loosen the locking nut on the leveling leg bolt with a
9/16-inch wrench.
2 Turn the leveling leg bolt clockwise to lower the unit or
counterclockwise to raise it.
3 When you are finished adjusting the height, hold the
leveling leg bolt in place and draw the locking nut up tight against the mounting bracket.
Figure 23: Leveling Legs Adjustment
Electric Heat Over-Temp Reset Button
The elecric heat options comes with two over-temperature switches. The first resets automatically when the over­temperature condition no longer exists. The second, backup switch must be reset manually.
Note: The need to reset the manual switch may indicate that
there are improperly functioning system components. If the switch trips again, contact McQuay Factory Service for help in diagnosing the cause.
T o reset the manual switch, carry out the following steps:
1 Disconnect all power to the unit. Verify the power has
been disconnected.
DANGER
Personal Injury Hazard.
Power supply can cause electrical shock. Always disconnect power to unit before servicing.
2 Remove the main drain pan and motor assembly from
the unit (see Accessing/removing the main drain pan and
motor assembly‚ page 19).
3 Access and push in the red reset button. See Figure 25.
Figure 25: Electric Heat Over-Temp Reset Button Location
Cabinet Rear Extension Kit
The field-installed cabinet rear extension option may be utilized to place the fan coil farther out from the wall than the standard unit allows. Refer to page 41 for more details.
Figure 24: Cabinet Rear Extension Kit
McQuay IM 980-1 17
Reinstall the drain pan and motor assembly.
4 5 Reconnect the power.
Operation and Maintenance
Push filter backward and tilt down front edge to remove
Main Drain Pan
Secondary Drain Pan
Remove screws and slide forward to access pan
Key-lock Access Door Kit
The key-lock access door kit (see Figure 26) can be installed on ThinLine 3G cabinet units to prevent access to unit controls. For detailed installation information, refer to page 43.
Figure 26: Key-Lock Access Door Kit
General Maintenance
Normal maintenance on all units is generally limited to filter changes and cleaning the condensate drain pans. Units are provided with permanently lubricated motors and require no oiling even though oil caps may be provided.
Record performance measurements of volts, amps, and water temperature differences (both heating and cooling). A comparison of logged data with start-up and other annual data is useful as an indicator of general equipment condition.
Filter Changes
4 Remove the filter from under the unit.
To install a new filter:
1 Slide the filter under the unit and tilt its rear 0edge
upward and into the pocket at the rear of the filter housing.
2 Push the front edge of the filter backward until it clears
the front lip on the filter housing, then push it up and into place.
Figure 27: Filter Removal
Condensate Drain Pans
The main and secondary condensate drain pans should be checked annually and cleaned and flushed as required. See
Figure 28.
Figure 28: Drain Pan Locations
Filter changes are required at regular intervals. The time period between changes will depend upon the project requirements. Some applications, such as motels, produce a lot of lint from carpeting and linen changes, and will require more frequent filter changes. Check filters at 60-day intervals for the first year until experience is acquired. If light cannot be seen through the filter when held up to sunlight or a bright light, it should be changed. A more critical standard may be desirable.
Filters can be removed without removing any panels. See
Figure 27. However, if the unit is equipped with a return air
grille, this must first be removed to access the filter. To remove the filter:
1 Slide your hands under the front opening on the bottom
of the unit and feel for the filter above.
2 Slide your fingers along the bottom of the filter until they
reach the rear paperboard edge.
3 Push the paperboard edge backward about a half-inch
until the front edge of the filter drops down.
18 McQuay IM 980-1
Accessing the secondary drain pan
To access the secondary drain pan, remove the corner panel from the side of the unit where the main piping connections are made (this is opposite the side where the control access panel is located on units with unit-mounted controls. See
Figure 5, page 6 for a description of how to remove it.
Operation and Maintenance
Accessing/removing the main drain pan and motor assembly
The main drain pan is housed in the top of the unit’s fan deck. Both the fan deck and the main condensate drain pan are easily removed for access and cleaning as follows.
1 Disconnect electrical power to the unit. 2 Remove the two screws that attach the center panel of
the unit to the base ( see Figure 5, page 6).
3 Lift the center panel upward and off the unit. 4 Pull the main condensate drain line out of the side of the
chassis where it flows into the secondary drain pan.
5 Disconnect the fan motor wiring harness by removing
the plug where it attaches to the connector on the side of the chassis. See Figure 29.
Note: Push the tabs inward on the sides of the plug to free
it from the connector base.
Figure 29: Motor Connector Location
6
Remove the screws that attach the fan deck to the unit chassis. See Figure 28
7 Firmly grasp the fan deck, then slide it towards you and
out of the unit.
8 The main condensate drain pan sits atop the fan deck and
is now easily accessed for cleaning.
9 To reinstall, follow these steps in reverse order.
McQuay IM 980-1 19
Physical Data
Physical Data
Unit Data
Table 1: Unit Data
02 03 04 06 08 10 12
Primary Coil Data
Face Area, ft2 (cm2) Fins/inch (cm) 12 [4.7] 12 [4.7] 12 [4.7] 12 [4.7] 12 [4.7] 12 [4.7] 12 [4.7]
Coil Connection 1/2" Nominal copper female (5/8" OD) Coil Dimensions 2-Row
L x D x H, in (cm) 3-Row L x D x H, in (cm) 4-Row L x D x H, in (cm) Coil Volume, Gal (Liters)
2-Row 0.15 (0.6) 0.19 (0.7) 0.24 (0.9) 0.32 (1.2) 0.37 (1.4) 0.46 (1.7) 0.55 (2.1) 3-Row 0.20 (0.7) 0.26 (1.0) 0.32 (1.2) 0.45 (1.7) 0.52 (2.0) 0.64 (2.4) 0.77 (2.9) 4-Row 0.26 (1.0) 0.34 (1.3) 0.43 (1.6) 0.61 (2.3) 0.70 (2.6) 0.87 (3.3) 1.05 (4.0)
Reheat Coil Data: 1-Row, Hot Water or Steam
Face Area, ft2 (cm2) Fins/inch (cm) 12 [4.7] 12 [4.7] 12 [4.7] 12 [4.7] 12 [4.7] 12 [4.7] 12 [4.7]
Coil Connection 1/2" Nominal copper female (5/8" OD) L x D x H, in (cm) 11.8 x 0.9 x 6
Volume, Gal (Liters) 0.04 (0.1) 0.05 (0.2) 0.07 (0.3) 0.10 (0.4) 0.11 (0.4) 0.14 (0.5) 0.17 (0.7)
Preheat Coil Data, 2-Row, Hot Water or Steam
Hot Water or Steam
Face Area, ft2 (cm2) Fins/inch (cm) 12 [4.7] 12 [4.7] 12 [4.7] 12 [4.7] 12 [4.7] 12 [4.7] 12 [4.7]
Coil Connection 1/2" Nominal copper female (5/8" OD) L x D x H, in. (cm) 11.8 x 1.7 x 6
Volume, Gal (Liters) 0.08 (0.3) 0.10 (0.4) 0.13 (0.5) 0.19 (0.7) 0.22 (0.8) 0.29 (1.1) 0.35 (1.3)
Fan/Motor Data
Fan Quantity 1 1 2 2 3 4 4 Size, Dia” x W” (cm) 6.26 x 6.3
Motor Quantity 1 1 1 1 2 2 2
Filter Data
Part Number 668332901 668332902 668332903 668332907 668332905 668332906 668332904 1” (25.4 cm) Media TA only TA only TA only TA only TA only TA only TA only Quantity 1 1 1 1 2 2 2 L x D x H, in. (cm) 16 x 8.75 x 1
0.74 (685) 1.08 (1004) 1.43 (1323) 2.11 (1962) 2.46 (2281) 3.14 (2917) 3.83 (3559)
11.8 x 1.7 x 9
(30.0x4.4x22.9)
11.8 x 2.6 x 9 (30x6.6x22.9)
11.8 x 3.5 x 9
(30.0x8.8x22.9)
0.49 (456) 0.72 (669) 0.95 (882) 1.41 (1308) 1.64 (1521) 2.09 (1944) 2.55 (2372)
(30.0x2.2x15.2)
0.49 (456) 0.72 (669) 0.95 (882) 1.41 (1308) 1.64 (1521) 2.09 (1944) 2.55 (2372)
(30.0x4.4x15.2)
(15.9 x 16)
(40.6 x 22 x 2.5)
17.3 x 1.7 x 9
(43.9x4.4x22.9)
17.3 x 2.6 x 9
(43.9x6.6x22.9)
17.3 x 3.5 x 9
(43.9x8.8x22.9)
17.3 x 0.9 x 6
(43.9x2.2x15.2)
17.3 x1.7 x 6
(43.9x4.4x15.2)
7.95 x 6.3 (20 x 16)
21.5 x 8.75 x 1
(54.6 x 22 x 2.5)
22.8 x 1.7 x 9
(57.9x4.4x22.9)
22.8 x 2.6 x 9
(57.9x6.6x22.9)
22.8 x 3.5 x 9
(57.9x8.8x22.9)
22.8 x 0.9 x 6
(57.9x2.2x15.2)
22.8 x 1.7 x 6
(57.9x4.4x15.2)
6.26 x 6.3
(15.9 x 16)
27 x 8.75 x 1
68.5 x 22 x 2.5
33.8 x 1.7 x 9
(85.9x4.4x22.9)
33.8 x 2.6 x 9
(85.9x6.6x22.9)
33.8 x 3.5 x 9
(85.9x8.8x22.9)
33.8 x 0.9 x 6
(85.9x2.2x15.2)
33.8 x 1.7 x 6
(85.9x4.4x15.2)
7.95 x 6.3 (20 x 16)
38 x 8.75 x 1
(96.5 x 22 x 2.5)
39.3x 1.7 x 9
(99.8x4.4x22.9)
39.3 x 2.6 x 9
(99.8x6.6x22.9)
39.3 x 3.5 x 9
(99.8x8.8x22.9)
39.3 x 0.9 x 6
(99.8x2.2x15.2)
39.3 x 1.7 x 6
(99.8x4.4x15.2)
6.26 x 6.3
(15.9 x 16)
21.7 x 8.75 x 1
(56.1 x 22 x 2.5)
50.2 x 1.7 x 9
(127.6x4.4x22.9)
50.2 x 2.6 x 9
(127.6x6.6x22.9)
50.2 x 3.5 x 9
(127.6x8.8x22.9)
50.2 x 0.9 x 6
(127.6x2.2x15.2)
50.2 x 1.7 x 6
(127.6x4.4x15.2)
6.26 x 6.3
(15.9 x 16)
27.2 x 8.75 x 1
(69.0 x 22 x 2.5)
61.3 x 1.7 x 9
(155.7x4.4x22.9)
61.3 x 2.6 x 9
(155.7x6.6x22.9)
61.3 x 3.5 x 9
(155.7x8.8x22.9)
61.3 x 0.9 x 6
(155.7x2.2x15.2)
61.3 x 1.7 x 6
(155.7x4.4x15.2)
7.95 x 6.3 (20 x 16)
32.7 x 8.75 x 1
(83.1 x 22 x 2.5)
Shipping Weights
Table 2: Approximate Shipping Weights - lbs (kg)*
Unit Type
FCVC,FCVS 84 (38) 95 (43) 108 (49) 131 (60) 152 (69) 177 (80) 202 (92) FCVH 55 (25) 63 (29) 74 (34) 91 (41) 110 (50) 129 (59) 149 (68)
Note: *Approximate shipping weights do not include valve packages, hot water coils, electric heaters or other options.
20 McQuay IM 980-1
S02S03S04S06S08S10S12
Unit Size
Unit Dimensions
PREHEAT OPTION NOITPO TAEHERNOITPO TAEH CIRTCELE
PRIMARY
PREHEAT
EE
DD
GG
AA
CC
BB
HH
FF
A
B
F
FRONT VIEW
K
8.9
227
6.1
154
8.8
[224]
8.8
[224]
BACK VIEW
ELECTRICAL CONTROL BOX
OPTIONAL DISCONNECT SWITCH
DRAIN PAN 7/8" OD CONNECTION
ELECTRIC HEAT PANEL BOX
1.3
33.8
C
3.6
90.3
E
TOP VIEW
DISCHARGE GRILL
ELECTRICAL CONTROL ACCESS DOOR
ELECTRIC HEAT
PRIMARY
EE
AA
BB
DD
CC
GG
1.0
24.7
PRIMARY
REHEAT
DD
GG
BB
EE
HH
FF
CC
AA
4.6
[117]
9.3
[236]
3.4 [86]
15.7
[399]
17.6
[447]
J
FRESH AIR DAMPER OPENING
2.4 [61
]
Figure 30: Dimensions: Flat Top Fan Coils
Physical Data
Dimension
inch mm inch mm inch mm inch mm inch mm inch mm inch mm
Unit Width A 35.0 889 40.5 1029 46.0 1168 57.0 1448 62.5 1588 73.5 1867 84.5 2146 Unit Height B 25.0 635 25.0 635 25.0 635 25.0 635 25.0 635 25.0 635 25.0 635 Unit Depth C 10.0 254 10.0 254 10.0 254 10.0 254 10.0 254 10.0 254 10.0 254 Discharge Grille - Width E 16.3 414 21.8 554 27.3 693 38.3 973 43.8 1113 54.8 1392 65.8 1671 Return Air Opening - Width F 16.2 411 21.7 551 27.2 691 38.2 970 43.7 1110 54.7 1389 65.7 1669
AA 15.1 384 15.1 384 15.1 384 15.1 384 15.1 384 15.1 384 15.1 384 CC 3.0 76 3.0 76 3.0 76 3.0 76 3.0 76 3.0 76 3.0 76 DD 21 533 21 533 21 533 21 533 21 533 21 533 21 533 EE 1.1 28 1.1 28 1.1 28 1.1 28 1.1 28 1.1 28 1.1 28
BB 16.7 424 16.7 424 16.7 424 16.7 424 16.7 424 16.7 424 16.7 424 GG 7.8 198 7.8 198 7.8 198 7.8 198 7.8 198 7.8 198 7.8 198 CC 18.7 475 18.7 475 18.7 475 18.7 475 18.7 475 18.7 475 18.7 475 HH 1.2 30 1.2 30 1.2 30 1.2 30 1.2 30 1.2 30 1.2 30
AA 15 381 15 381 15 381 15 381 15 381 15 381 15 381
FF 4.7 119 4.7 119 4.7 119 4.7 119 4.7 119 4.7 119 4.7 119 CC 23.2 589 23.2 589 23.2 589 23.2 589 23.2 589 23.2 589 23.2 589 HH 4.2 107 4.2 107 4.2 107 4.2 107 4.2 107 4.2 107 4.2 107
AA 20.3 516 20.3 516 20.3 516 20.3 516 20.3 516 20.3 516 20.3 516
FF 8.3 211 8.3 211 8.3 211 8.3 211 8.3 211 8.3 211 8.3 211
Electric Heat Connection
Primary Coil - Water Return
Primary Coil - Water Supply
Preheat Coil - Water Return
Preheat Coil - Water Supply
Reheat Coil - Water Return
Reheat Coil - Water Supply
McQuay IM 980-1 21
S02 S03 S04 S06 S08 S10 S12
Physical Data
A
B
F
FRONT VIEW
6.1
154
8.9
227
5
[127]
15.7
[399]
17.6
[447]
BACK VIEW
ELECTRICAL CONTROL BOX
OPTIONAL DISCONNECT SWITCH
DRAIN PAN 7/8" OD
3.7
95.1
C
1.9
47.4
E
TOP VIEW
ELECTRIC HEAT OPTION
PREHEAT OPTION
REHEAT OPTION
DISCHARGE GRILL
ELECTRIC CONTROL ACCESS DOOR
AA
DD
CC
HH
FF
EE
GG
BB
4.6
[117]
9.3
[236]
3.4 [86]
.9
23.1
REHEAT
PRIMARY
DD
EE
GG
CC
AA
HH
FF
BB
PREHEAT
PRIMARY
DD
EE
GG
AA
CC
BB
PRIMARY
ELECTRIC HEAT
8.8
[224]
8.8
[224]
J
FRESH AIR DAMPER OPENING
2.4 [61
]
Figure 31: Dimensions: Slope Top Fan Coils
Dimension
S02 S03 S04 S06 S08 S10 S12
inch mm inch mm inch mm inch mm inch mm inch mm inch mm
Unit Width A 35.0 889 40.5 1029 46.0 1168 57.0 1448 62.5 1588 73.5 1867 84.5 2146 Unit Height B 27.6 701 27.6 701 27.6 701 27.6 701 27.6 701 27.6 701 27.6 701 Unit Depth C 10.0 254 10.0 254 10.0 254 10.0 254 10.0 254 10.0 254 10.0 254 Discharge Grille - Width E 16.3 414 21.8 554 27.3 693 38.3 973 43.8 1113 54.8 1392 65.8 1671 Return Air Opening - Width F 16.2 411 21.7 551 27.2 691 38.2 970 43.7 1110 54.7 1389 65.7 1669
AA 15.1 384 15.1 384 15.1 384 15.1 384 15.1 384 15.1 384 15.1 384 CC 3.0 76 3.0 76 3.0 76 3.0 76 3.0 76 3.0 76 3.0 76 DD 21 533 21 533 21 533 21 533 21 533 21 533 21 533 EE 1.1 28 1.1 28 1.1 28 1.1 28 1.1 28 1.1 28 1.1 28
BB 16.7 424 16.7 424 16.7 424 16.7 424 16.7 424 16.7 424 16.7 424 GG 7.8 198 7.8 198 7.8 198 7.8 198 7.8 198 7.8 198 7.8 198 CC 18.7 475 18.7 475 18.7 475 18.7 475 18.7 475 18.7 475 18.7 475 HH 1.2 30 1.2 30 1.2 30 1.2 30 1.2 30 1.2 30 1.2 30
AA 15 381 15 381 15 381 15 381 15 381 15 381 15 381
FF 4.7 119 4.7 119 4.7 119 4.7 119 4.7 119 4.7 119 4.7 119 CC 23.2 589 23.2 589 23.2 589 23.2 589 23.2 589 23.2 589 23.2 589 HH 4.2 107 4.2 107 4.2 107 4.2 107 4.2 107 4.2 107 4.2 107
AA 20.3 516 20.3 516 20.3 516 20.3 516 20.3 516 20.3 516 20.3 516
FF 8.3 211 8.3 211 8.3 211 8.3 211 8.3 211 8.3 211 8.3 211
Electric Heat Connection
Primary Coil - Water Return
Primary Coil - Water Supply
Preheat Coil - Water Return
Preheat Coil - Water Supply
Reheat Coil - Water Return
Reheat Coil - Water Supply
22 McQuay IM 980-1
Figure 32: Dimensions: Hideaway, Front-Discharge Fan Coils
ELECTRIC HEAT
DRAIN PAN 7/8 OD CONNECTION
BB
D
D
E
E
GG
B
A
A
C
C
HH
F
F
PRIMARY
REHEAT
5
127
4.6
1
17
9.3
2
36
ELECTRIC HEAT OPTION
PREHEAT OPTION REHEAT OPTION
E
5.4
138.2
F
1.0
26.6
H
G
F
RON
T VIEW
FRONT DISCHARGE
E
LECTRIC
CONTROL BOX
OPTIONAL DISCONNECT SWITCH
8.9
227
6.1
154
BACK VIEW
E
LECTRIC HEAT
PANEL BO
X
A
C
TOP VIEW
PRIMARY
B
FF
HH
AA
BB
CC
DD
EE
GG
PRIMARY
PREHEAT
0.6 [15.9]
0.6 [15.9]
H
G
J
FRESH AIR DAMPER OPENING
2.4 [61
]
Physical Data
Dimension
Unit Width A 18.8 475 24.3 617 29.8 757 40.8 1036 46.3 1176 57.3 1455 68.3 1735 Unit Height B 24.0 610 24.0 610 24.0 610 24.0 610 24.0 610 24.0 610 24.0 610 Unit Depth C 9.6 243 9.6 243 9.6 243 9.6 243 9.6 243 9.6 243 9.6 243 Discharge Grille - Width E 16.3 414 21.8 554 27.3 693 38.3 973 43.8 1113 54.8 1392 65.8 1671 Return Air Opening - Width F 16.2 411 21.7 551 27.2 691 38.2 970 43.7 1110 54.7 1389 65.7 1669 Control Box to Floor G 17.6 447 17.6 447 17.6 447 17.6 447 17.6 447 17.6 447 17.6 447 Disconnect Switch to Floor H 15.7 399 15.7 399 15.7 399 15.7 399 15.7 399 15.7 399 15.7 399
Electric Heat Connection
Primary Coil - Water Return
Primary Coil - Water Supply
Preheat Coil - Water Return
Preheat Coil - Water Supply
Reheat Coil - Water Return
Reheat Coil - Water Supply
S02 S03 S04 S06 S08 S10 S12
inch mm inch mm inch mm inch mm inch mm inch mm inch mm
AA 15.1 384 15.1 384 15.1 384 15.1 384 15.1 384 15.1 384 15.1 384 CC 3.0 76 3.0 76 3.0 76 3.0 76 3.0 76 3.0 76 3.0 76 DD 21 533 21 533 21 533 21 533 21 533 21 533 21 533
EE 1.1 28 1.1 28 1.1 28 1.1 28 1.1 28 1.1 28 1.1 28
BB 16.7 424 16.7 424 16.7 424 16.7 424 16.7 424 16.7 424 16.7 424 GG 7.8 198 7.8 198 7.8 198 7.8 198 7.8 198 7.8 198 7.8 198 CC 18.7 475 18.7 475 18.7 475 18.7 475 18.7 475 18.7 475 18.7 475 HH 1.2 30 1.2 30 1.2 30 1.2 30 1.2 30 1.2 30 1.2 30
AA 15 381 15 381 15 381 15 381 15 381 15 381 15 381
FF 4.7 119 4.7 119 4.7 119 4.7 119 4.7 119 4.7 119 4.7 119 CC 23.2 589 23.2 589 23.2 589 23.2 589 23.2 589 23.2 589 23.2 589 HH 4.2 107 4.2 107 4.2 107 4.2 107 4.2 107 4.2 107 4.2 107
AA 20.3 516 20.3 516 20.3 516 20.3 516 20.3 516 20.3 516 20.3 516
FF 8.3 211 8.3 211 8.3 211 8.3 211 8.3 211 8.3 211 8.3 211
McQuay IM 980-1 23
Physical Data
1.3
32.9
1.3
32.9
ELECTRIC HEAT
5
127
4.6
117
9.3
236
F
H
G
FRONT VIEW
ELECTRIC
CONTROL BOX
OPTIONAL DISCONNECT SWITCH
T
T
8.9
227
6.1
154
BACK VIEW
A
E
3.5
89.6
4.8
120.7
TOP V
IEW
TOP DISCHARGE
PRIMARY
DRAIN PAN 7/8 OD CONNECTION
REHEAT
BB
DD
EE
GG
AA
CC
HH
FF
B
1.3
32.9
PRIMARY
PREHEAT
FF
HH
AA
BB
CC
DD
EE
GG
B
PRIMARY
BB
DD
EE
GG
B
AA
CC
ELECTRIC HEAT OPTION
PREHEAT OPTION REHEAT OPTION
J
FRESH AIR DAMPER OPENING
2.4 [61
]
Figure 33: Dimensions: Hideaway, Top-Discharge Fan Coils
Dimension
S02 S03 S04 S06 S08 S10 S12
inch mm inch mm inch mm inch mm inch mm inch mm inch mm
Unit Width A 18.8 475 24.3 617 29.8 757 40.8 1036 46.3 1176 57.3 1455 68.3 1735 Unit Height B 24.0 610 24.0 610 24.0 610 24.0 610 24.0 610 24.0 610 24.0 610 Unit Depth C 9.6 243 9.6 243 9.6 243 9.6 243 9.6 243 9.6 243 9.6 243 Discharge Grille - Width E 16.3 414 21.8 554 27.3 693 38.3 973 43.8 1113 54.8 1392 65.8 1671 Return Air Opening - Width F 16.2 411 21.7 551 27.2 691 38.2 970 43.7 1110 54.7 1389 65.7 1669 Control Box to Floor G 17.6 447 17.6 447 17.6 447 17.6 447 17.6 447 17.6 447 17.6 447 Disconnect Switch to Floor H 15.7 399 15.7 399 15.7 399 15.7 399 15.7 399 15.7 399 15.7 399
AA 15.1 384 15.1 384 15.1 384 15.1 384 15.1 384 15.1 384 15.1 384 CC 3.0 76 3.0 76 3.0 76 3.0 76 3.0 76 3.0 76 3.0 76 DD 21 533 21 533 21 533 21 533 21 533 21 533 21 533
EE 1.1 28 1.1 28 1.1 28 1.1 28 1.1 28 1.1 28 1.1 28
BB 16.7 424 16.7 424 16.7 424 16.7 424 16.7 424 16.7 424 16.7 424 GG 7.8 198 7.8 198 7.8 198 7.8 198 7.8 198 7.8 198 7.8 198 CC 18.7 475 18.7 475 18.7 475 18.7 475 18.7 475 18.7 475 18.7 475 HH 1.2 30 1.2 30 1.2 30 1.2 30 1.2 30 1.2 30 1.2 30
AA 15 381 15 381 15 381 15 381 15 381 15 381 15 381
FF 4.7 119 4.7 119 4.7 119 4.7 119 4.7 119 4.7 119 4.7 119 CC 23.2 589 23.2 589 23.2 589 23.2 589 23.2 589 23.2 589 23.2 589 HH 4.2 107 4.2 107 4.2 107 4.2 107 4.2 107 4.2 107 4.2 107
AA 20.3 516 20.3 516 20.3 516 20.3 516 20.3 516 20.3 516 20.3 516
FF 8.3 211 8.3 211 8.3 211 8.3 211 8.3 211 8.3 211 8.3 211
Electric Heat Connection
Primary Coil - Water Return
Primary Coil - Water Supply
Preheat Coil - Water Return
Preheat Coil - Water Supply
Reheat Coil - Water Return
Reheat Coil - Water Supply
24 McQuay IM 980-1
Factory-Installed Valve & Piping Packages
Front View
4-Pipe, Right Hand with Same-Side Secondary Coil
4.2”
[107 mm]
6.9” [175 mm]
End View
Primary Coil Piping (preheat piping hidden)
4.9” [125 mm]
6.4”
[163 mm]
1.3” [33 mm]
2” [51 mm]
Supply Return
End View
Preheat Coil Piping (primary piping hidden)
4.8” [122 mm]
1.3” [33 mm]
3.5”
[90 mm]
Supply Return
End View:
Reheat Coil Piping (primary piping hidden)
3.7” [94 mm]
1.3” [33 mm]
4.7” [120 mm]
3.4” [86 mm]
Supply Return
4.2” [107 mm]
1.7” [43 mm]
2.8”
[71 mm]
3.4” [86 mm]
1.4” [36 mm]
4.9” [124 mm]
5.5”
[140 mm]
End View:
Preheat Coil Piping
Return Supply
End View:
Primary Coil Piping
Front View: 4-Pipe, Right Hand with Opposite-End Preheat
ypg
4.9” [125 mm]
2”
[51 mm]
6.7”
[170 mm]
1.2” [32 mm]
Return Supply
Front View
2-Pipe, Right Hand
4.2”
[107 mm]
End View
2-Pipe, Right Hand
4.9” [125 mm]
6.4”
[163 mm]
1.3” [33 mm]
2” [51 mm]
Supply Return
4-Pipe Arrangement with Same-End Connections
4-Pipe Arrangement with Opposite-End Connections
2-Pipe Arrangement
Deluxe package cofiguration shown
Note: All valve packages, regardless of
components included, have the same hookup locations. RIght-hand connections are shown here. Left-hand connection distances are the same. Distances to connections from chassis are from unit mounting holes. Dimensions may vary slightly from given values.
See catalog CAT 722-1 for detailed descriptions of piping packages.
Figure 34: Hook Up Locations: Factory-installed Valve & Piping Packages
Physical Data
McQuay IM 980-1 25
Loading...
+ 57 hidden pages