McQuay Enfinity CRH, Enfinity CRW, Enfinity CCH, Enfinity CCW Installation Manual

®
Installation & Maintenance Data
McQuay® Enfinity™ (R-410A) and Standard (R-22) Horizontal Water Source Heat Pumps
IM 742-4
Group: WSHP
Part Number: 106586605
Date: September 2007
Model Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Transportation & Storage
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-4
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Cleaning & Flushing System . . . . . . . . . . . . . . . . . . . . .
Start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Typical Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . .9-11
©2007 McQuay International
. . . . . . . . . . . . . . . . . . . . . . . . 2
Contents
Unit Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12-14
Thermostat Connections . . . . . . . . . . . . . . . . . . . . .16-17
Options for Mark IV/AC Units. . . . . . . . . . . . . . . . . .18-21
Field Installed Options on MicroTech Units . . . . . . . . . 22
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . 23
6
Troubleshooting WSHP . . . . . . . . . . . . . . . . . . . . . .24-25
Troubleshooting Refrigeration Circuit. . . . . . . . . . . . . . 25
Typical Refrigeration Cycles. . . . . . . . . . . . . . . . . . . . . 26
General Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Model Nomenclature
Note: For illustration purposes only. Not all options available with all models.
Please consult McQuay Sales Representative for specific availability.
W CCH 1 009 M E Y L S
Product Catagory
W = WSHP
Product Identifier CCH = Ceiling Mounted / R-410A / Standard Range CCW = Ceiling Mounted / R-410A / Geothermal CRH = Ceiling Mounted / R-22 / Standard CRW = Ceiling Mounted / R-22 / Geothermal
Design Series
1 = A Design 2 = B Design 3 = C Design 4 = D Design
Nominal Capacity
007 = 7,000 030 = 30,000 009 = 9,000 036 = 36,000 012 = 12,000 042 = 42,000 015 = 15,000 048 = 48,000 019 = 19,000 060 = 60,000 024 = 24,000 070 = 70,000
Controls M = Mark IV K = Micortech 2000 w/LonMark® 3.3 L = Microtech 2000 w/LonTaLk A = BACnet E = Less Board
®
Note: Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes and regulations, and are experienced with this type of equipment. Caution: Sharp edges are a potential injury hazard. Avoid contact with them.
Discharge Air
S = Straight E = End
Return Air
L = Left R = Right
Future
(None)
Voltage
A = 115/60/1 E = 208-230/60/1 F = 208-230/60-/3 J = 277-265/60/1 K = 460/60/3 L = 575/60/3
50 Hz (CCH&CCW Only)
M = 230/50/1 N = 380/50/3
Transportation & Storage
Upon receipt of the equipment, check carton for visible damage. Make a notation on the shipper’s delivery ticket before signing. If there is any evidence of rough handling, immediately open the cartons to check for concealed dam­age. If any damage is found, notify the carrier within 48 hours to establish your claim and request their inspection and a report. The Warranty Claims Department should then be contacted. Do not stand or transport the machines on end. For stor ing, each carton is marked with “up” arrows.
Installation
General
1. To prevent damage, this equipment should not be oper­ated for supplementary heating and cooling during the construction period.
-2. Inspect the carton for any specific tagging numbers indicated by the factory per a request from the installing contractor. At this time the voltage, phase and capacity should be checked against the plans.
3. Check the unit size against the plans to ensure unit installation is in the correct location.
4. After removing the carton, remove the hanger kit from the fan housing.
5. Before installation, check the available ceiling height versus the height of the unit.
6. Note the location and routing of water piping, conden sate drain piping, and electrical wiring. The locations of these items are clearly marked on submittal drawings.
7. The installing contractor will find it beneficial to confer with piping, sheet metal, ceiling and electrical foremen before installing any conditioners.
In the event that elevator transfer makes up-ended posi­tioning unavoidable, absolutely ensure that the machine is in the normal upright position for at least 24 hours before operating. Temporary storage at the job site must be indoors, completely sheltered from rain, snow, etc. High or low tem peratures naturally associated with weather patterns will not harm the conditioners. Excessively high temperatures, 140°F (60°C) and higher, may deteriorate certain plastic
­materials and cause permanent damage.
NOTE: Check the unit name plate for correct voltage with
the plans before installing the equipment. Also, make sure all electrical ground connections are made in accordance with local code.
8. Remove all shipping blocks in the fan wheel.
9. Change the airflow direction from straight discharge to end discharge or vice versa before the unit is installed in the ceiling. Refer to the section in this bulletin for instructions.
10. We recommend that the contractor cover the condi tioners with plastic film to protect the machines during finishing of the building. This is critical while spraying fireproofing material on bar joists, sandblasting, spray painting and plastering. If plastic film is not available,
-
the shipping carton may be modified to cover the units during construction.
-
-
Page 2 / IM 742
Unit Location
B
Coil
Airflow
E
C
D
Comp
Control
Box
Fan
Assembly
A
1. Locate the unit in an area that allows for easy removal of the filter and access panels. Leave a minimum of 18” of clearance around the heat pump for easy removal, and to perform routine maintenance, or troubleshooting. Provide sufficient room to make water, electrical and duct connections.
2. The contractor should make sure that adequate ceil ing panel access exists, including clearance for hanger brackets, duct collars and fittings at water and electrical connections.
3. Allow adequate room below the unit for a condensate trap and do not locate the unit above pipes.
4. Each unit is suspended from the ceiling by four threaded rods. The rods are attached to the unit corners by a hanger bracket through a rubber isolator.
Caution: Do not use rods smaller than shown in Figure 1B. The rods must be securely anchored to the ceiling or to the bar joists.
5. Each unit is furnished with a hanger kit. The kit is shipped unassembled and includes hanger brackets, rubber isolators, washers, bolts and lock washers. Lay out the threaded rods per the dimension in Figures 1A and 1B.
6. When attaching the hanger rods to the unit, a double nut is recommended since vibration could loosen a single nut. The installer is responsible for providing the hex nuts when installing hanger rods.
7. Leave minimum 3" (76 mm) extra threaded rod below the double nuts or minimum 3" (76 mm) clearance between top of unit and ceiling above to facilitate top panel remov­al for servicing.
Filter Access
Each unit is shipped with a filter bracket for side filter remov­al. For bottom removal push the filter up into top bracket to gain clearance of bottom bracket and remove the filter. Also, a sheet metal duct filter retainer can be fabricated when return air duct work is used.
Figure 1A. Hanger bracket detail, sizes 007 thru 070
Figure 1B. Unit sizes 007 thru 070
-
Bolt & Lock Washer
Hanger Bracket Dimensions
Models CCH & CCW
UNIT DIMENSIONS (INCHES) SIZE A B C D E
007 – 009 17.5 34 22 34 20 012 17.5 40 22 40 20 019 – 024 17.5 40 22 40 20 030 – 036 18.5 46 23 46 21
042 – 060 25.5 52 30 52 28
UNIT DIMENSIONS (mm) SIZE A B C D E
007 – 009 445 864 559 864 508 012 445 1016 559 1016 508 019 – 024 445 1016 559 1016 508 030 – 036 470 1168 584 1168 533 042 – 060 648 1321 762 1321 711
Models CRH & CRW
UNIT DIMENSIONS (INCHES) SIZE A B C D E
007 – 012 17.5 34 22 34 20 015 – 024 17.5 42 22 42 20 030 – 042 18.5 46 23 46 21 048 – 070 25.5 52 30 52 28
3/8" Threaded Rod (By Others)
Vibration Isolator
Washer
Hex Nuts (By Others)
UNIT DIMENSIONS (mm) SIZE A B C D E
007 – 012 445 864 559 864 508 015 – 024 445 1067 559 1067 508 030 – 042 470 1168 584 1168 533 048 – 070 648 1321 762 1321 711
IM 742 / Page 3
Air Discharge Conversion
Unit sizes 007 thru 070 can be shipped as straight discharge air or end discharge air arrangement. In the event that the unit needs to be converted from straight discharge to end discharge:
1. Remove top panel.
2. Remove the access panel to the fan motor. Remove the piece of insulation at the bottom on the side of the bottom panel.
3. Remove the fan discharge panel, rotate it 180 degrees, and move it to the other side. In other words, with straight
Ductwork & Attenuation
Discharge ductwork is normally used with these condition­ers. Return air ductwork may also be required. All ductwork should conform to industry standards of good practice as described in the ASHRAE Systems Guide. The discharge duct system will normally consist of a flexible connector at the unit, a transition piece to the full duct size, a short run of duct, an elbow without vanes, and a trunk duct teeing into a branch duct with discharge dif­fusers as shown in Figure 2. The transition piece must not have angles totaling more than 30° or severe loss of air performance can result. Do not connect the full duct size to the unit without using a transition piece down to the size of the discharge collar on the unit. With metal duct material, the sides only of the elbow and entire branch duct should be internally lined with acoustic fibrous insulation for sound attenuation. Glass fiber duct board material is more absorb ing and may permit omission of the canvas connector. The ductwork should be laid out so that there is no line of sight between the conditioner discharge and the distribution diffusers.
air discharge the housing is bottom horizontal and with an end discharge the housing is top horizontal.
4. Remove the three bolts holding the fan motor on and rotate it so that the motor oilers are in the up position.
5. Install insulation base panel below new access panel location.
6. Reinstall the top panel.
7. Reinstall the piece of insulation and the access panel.
Return air ducts can be brought in through a low side wall filter-grille and then up through the stud pieces to a ceiling plenum or through air ceiling filter-grilles. The ceiling filter-grille must not be placed directly under the conditioner. Return air ductwork can be connected to the standard filter rack. See Figure 3 (side filter removal shown). The filter rack can be installed for bottom filter removal or side filter removal by locating the brackets. For side filter removal the brackets should be located on the bottom, left side, and top. For bottom filter removal the brackets should be mounted on the left side top and right side with the spring clips support­ing the filter. Do not use sheet metal screws directly into the unit cabi net for connection of supply or return air ductwork, espe­cially return air ductwork which can hit the drain pan or the air coil.
-
-
Figure 2. Suggested duct layout
Both Sides Internally Lined With Acoustic Fibrous Glass Insulation
Transformation
Piece
Discharge Collar
On Heat Pump
Suggested Duct Layout For
Multiple Diffuser Application
Heat Pump
Canvas Collar
Square Elbow
2x2 Ft. Diffuser (Example Only)
Trunk Duct
Branch Duct Internally Lined With Acoustic Fibrous Insulation
Ventilation Air
Ventilation may require outside air. The temperature of the ventilation air must be controlled so that mixture of outside air and return air entering the conditioner does not exceed conditioner application limits. It is also typical to close off the ventilation air system during unoccupied periods (night setback).
Figure 3. Filter rack/return air duct collar
Standard 1" (25mm)
Optional 2" (51 mm) Rack also available.
The ventilation air system is generally a separate building subsystem with distribution ductwork. Simple introduction of the outside air into each return air plenum chamber reason­ably close to the conditioner air inlet is recommended. Do not duct outside air directly to the conditioner inlet. Provide sufficient distance for thorough mixing of outside and return air. See Operating Limits on page 8.
Page 4 / IM 742
Electrical Data
1. Verify the compatibility between the voltage and phase of the available power and that shown on the unit serial plate. Line and low voltage wiring must comply with local codes or the National Electrical Code, whichever applies.
7
2. Apply correct line voltage to the unit. A and/or a 11⁄8" (29 mm) knockout is supplied on the side of the unit. A disconnect switch near the unit is required by code. Power to the unit must be sized correctly and have dual element (Class RK5) fuses or an HACR circuit
All 208-230 volt single-phase and three-phase units are factory wired for 208 volt operation. For 230 phase opera tion, the line voltage tap on the 24 volt transformer must be
All fan motors are multi-speed, PSC type with integral mounting brackets and thermal overload protection. The motor is isolated from the fan housing for minimum vibration transmission. Fan motors on 019 thru 070 have a terminal strip on the motor body for simple motor speed change without going back to the control box. To change fan motor speed to high on size 015 through 048, interchange the red wire with the black wire. For low speed, sizes 012, 024, 030, 036, 042, 060 and 070, interchange the black wire with the red wire. To change the 460 volt motor from high to low
Figure 4. CCH, CCW, CRH & CRW Sizes 007 thru 070 (Factory wired)
8" (22mm) hole
General
230 Volt Operation
Fan Assembly
breaker for branch circuit overcurrent protection. See the nameplate for correct ratings.
3. Three phase 50 cycle units, 380/50/3, require a neutral wire for 230/50/1 power to the fan circuit.
4. Connect the thermostat/subbase wiring with the power “off ” to the unit.
Field supplied relays installed on the input terminals W1, W2, Y1,
5.
Y2 or G may introduce electrical noise. Never install relay coils in series with the inputs.
changed. Disconnect and cap the red lead wire and inter­change it with the orange lead wire on the primary of the 24
­volt transformer.
speed, interchange Black and Red wires, then add jumper between Black and Blue wires. All the fan/motor assemblies have a removable orifice ring on the housing to accommo­date motor and fan wheel removal without disconnecting the ductwork. The fan housing protrudes through the cabinet allowing adequate material for connection of flexible duct. Each model unit is shipped from the factory for maximum performance and minimum sound requirements. Fan sound levels and performance can be affected by external static pressure.
Figure 4a. CCH, CCW, CRH & CRW Sizes 042 thru 070 (Factory wired, 460 volt motor only)
1. All units should be connected to supply and return pip­ing in a two-pipe reverse return configuration. A reverse return system is inherently self-balancing and requires only trim balancing where multiple quantities of units with different flow and pressure drop characteristics exist in the same loop. Check for proper water balance by measuring differential temperature reading across the water connections. To insure proper water flow, the differential flow should be 10°F to 14°F (5°C to 8°C) for units in cooling mode.
A direct return system may also work acceptably, but
proper water flow balancing is more difficult to achieve and maintain.
2. The piping can be steel, copper or PVC.
3. Supply and return runouts usually join the unit via short lengths of high pressure flexible hose which are sound attenuators for both unit operating noise and hydraulic pumping noise. One end of the hose should have a swivel fitting to facilitate removal for service. Hard pip
Note: For low speed applications a jumper must be installed between the motor's Black and Blue terminal.
Piping
4. Some flexible hose threaded fittings are supplied with
5. Supply and return shutoff valves are required at each
6. No unit should be connected to the supply and return
-
ing can also be brought directly to the unit. This option is not recommended since no vibration or noise attenu­ation can be accomplished. The hard piping must have unions to facilitate unit removal. See Figure 5 for typical piping setup.
sealant compound. If not, apply Teflon tape to assure a tight seal.
conditioner. The return valve is used for balancing and should have a “memory stop” so that it can always be closed off but can only be reopened to the proper posi­tion for the flow required.
piping until the water system has been cleaned and flushed completely. After the cleaning and flushing has taken place, the initial connection should have all valves wide open in preparation for water system flushing.
IM 742 / Page 5
7. Condensate piping can be steel, copper or PVC. Each unit includes a condensate connection.
8. The condensate disposal piping must be trapped. The piping must be pitched away from the unit not less than
1
4" per foot. The unit has a 3/4 inch female pipe fitting
on each water source heat pump to accommodate the condense drain connection. Factory supplied conden sate hose assemblies have a pipe thread fitting to facili­tate connection of a flexible vinyl or steel braided hose. A complete copper or PVC condense system can be
used. Union fittings in the copper or PVC lines should be applied to facilitate removal.
9. Do not locate any point in the drain system above the drain connection of any unit.
10. Automatic flow controlled devices must not be installed
-
prior to system cleaning and flushing.
11. A high point of the piping system must be vented.
12. Check local code for the need for dielectric fittings.
Figure 5. (Sizes 007 through 070 shown)
Electrical Access Panel
Hanger Kits (4)
Flex Hoses
Return
Riser
Condensate
Riser
Ball
Supply
Riser
Note: Do not overtorque fittings. The maximum torque without damage to fittings is 30 foot pounds. If a torque wrench is not available, use as a rule of thumb, finger-tight plus one quarter turn.
Valves
Supply Air
Figure 6. Condensate disposal trapping detail
11⁄2"
11⁄2"
(38 mm)
(38 mm)
Optional Field Installed Vent
1
4" Per Foot
(21 mm Per Meter)
Cleaning & Flushing System
1. Prior to first operation of any conditioner, the water circulating system must be cleaned and flushed of all construction dirt and debris.
If the conditioners are equipped with water shutoff
valves, either electric or pressure operated, the supply and return runouts must be connected together at each conditioner location. This will prevent the introduction of dirt into the unit. See Figure 7.
Figure 7. Supply & return runouts connected together
Return Runout
Supply Runout
Mains
Flexible Hose
Runouts Initially Connected Together
2. Fill the system at the city water makeup connection with all air vents open. After filling, close all air vents.
The contractor should start main circulator with the
pressure reducing valve open. Check vents in sequence to bleed off any trapped air, ensuring circulation through all components of the system.
Power to the heat rejector unit should be off, and the
supplementary heat control set at 80°F (27°C).
While circulating water, the contractor should check
and repair any leaks in the piping. Drains at the lowest point(s) in the system should be opened for initial flush and blowdown, making sure city water fill valves are set to make up water at the same rate. Check the pressure gauge at pump suction and manually adjust the makeup to hold the same positive steady pressure both before and after opening the drain valves. Flush should continue for at least two hours, or longer if required, to see clear, clean drain water.
3. Shut off supplemental heater and circulator pump and open all drains and vents to completely drain down the system. Short circuited supply and return runouts should now be connected to the conditioner supply and return connections. Do not use sealers at the swivel flare con nections of hoses.
4. Trisodium phosphate was formerly recommended as a cleaning agent during flushing. However, many states and localities ban the introduction of phosphates into their sewage systems. The current recommendation is to simply flush longer with warm 80°F (27°C) water.
-
Page 6 / IM 742
5. Refill the system with clean water. Test the water using litmus paper for acidity, and treat as required to leave the water slightly alkaline (pH 7.5 to 8.5). The specified per centage of antifreeze may also be added at this time. Use commercial grade antifreeze designed for HVAC systems only. Do not use automotive grade antifreeze.
Once the system has been filled with clean water
and antifreeze (if used), precautions should be taken to protect the system from dirty water conditions. Dirty water will result in system wide degradation of perfor­mance and solids may clog valves, strainers, flow regu­lators, etc. Additionally, the heat exchanger may become clogged which reduces compressor service life or causes premature failure.
Start-up
1. Open all valves to full open position and turn on power
to the conditioner.-
2. Set thermostat for “Fan Only” operation by selecting
“Off” at the system switch and “On” at the fan switch. If “Auto” fan operation is selected, the fan will cycle with the compressor. Check for proper air delivery.
3. For those units that have two-speed motors, reconnect
for low speed operation if necessary.
4. Set thermostat to “Cool.” If the thermostat is an automat
ic changeover type, simply set the cooling temperature to the coolest position. On manual changeover types additionally select “Cool” at the system switch.
Again, many conditioners have time delays which
protect the compressor(s) against short cycling. After a few minutes of operation, check the discharge grilles for cool air delivery. Measure the temperature differ ence between entering and leaving water. It should be approximately 11⁄2 times greater than the heating mode temperature difference. For example, if the cooling temperature difference is 15°F (8°C), the heating tem­perature difference should have been 10°F (5°C).
Without automatic flow control valves, target a cooling
temperature difference of 10°F to 14°F (5°C to 8°C). Adjust the combination shutoff/balancing valve in the return line to a water flow rate which will result in the
10˚F to 14°F (5°C to 8°C) difference.
5. Set thermostat to “Heat.” If the thermostat is the auto
matic changeover type, set system switch to the “Auto” position and depress the heat setting to the warmest selection. Some conditioners have built-in time delays which prevent the compressor from immediately start­ing. With most control schemes, the fan will start imme diately. After a few minutes of compressor operation, check for warm air delivery at discharge grille. If this is
6. Set the loop water controller heat add setpoint to 70°F
-
-
-
-
-
(21°C) and the heat rejection setpoint to 85°F (29°C). Supply power to all motors and start the circulating pumps. After full flow has been established through all components including the heat rejector (regardless of season) and air vented and loop temperatures stabilized, each of the conditioners will be ready for check, test and start-up, air balancing, and water balancing.
a “cold building” start-up, leave unit running until return air to the unit is at least 65°F (18°C).
Measure the temperature difference between enter
ing and leaving air and entering and leaving water. With entering water of 60°F to 80°F (16°C to 27°C), leaving water should be 6°F to 12°F (3.3°C to 6.6°C) cooler, and the air temperature rise through the machine should not exceed 35°F (19°C). If the air tempera ture exceeds 35°F (19°C), then the water flow rate is inadequate.
6. Check the elevation and cleanliness of the condensate line. If the air is too dry for sufficient dehumidification, slowly pour enough water into the condensate pan to ensure proper drainage.
7. If the conditioner does not operate, check the following points:
a. Is supply voltage to the machine compatible? b. Is thermostat type appropriate? c. Is thermostat wiring correct?
8. If the conditioner operates but stops after a brief period:
a. Is there proper airflow? Check for dirty filter, incor
rect fan rotation (3-phase fan motors only), or incor­rect ductwork.
b. Is there proper water flow rate within temperature
limits? Check water balancing; backflush unit if dirt­clogged.
9. Check for vibrating refrigerant piping, fan wheels, etc.
10. Do not lubricate the fan motor during the first year of operation as it is prelubricated at the factory.
Field supplied relays installed on the input terminals W1, W2,
11.
Y1, Y2 or G may introduce electrical noise. Never install relay coils in series with the inputs.
-
-
-
IM 742 / Page 7
Operating Limits
Environment
This equipment is designed for indoor installation only. Sheltered locations such as attics, garages, etc., gener ally will not provide sufficient protection against extremes in
Air limits Water limits
Cooling Heating Cooling Heating
Min. Ambient Air 50˚F/10˚C 50˚F/10˚C 40˚F/5˚C 40˚F/5˚C Normal Ambient Air 80˚F/27˚C 70˚F/21˚C 80˚F/27˚C 70˚F/21˚C Max. Ambient Air 100˚F/38˚C 85˚F/29˚C 100˚F/38˚C 85˚F/29˚C Min. Ent. Air ➀➁ 50˚F/10˚C 50˚F/10˚C 50˚F/10˚C 40˚F/5˚C Normal Ent. Air, 80/67˚F 70˚F 80/67˚F 70˚F
dw/wb 27/19˚C 21˚C 27/19˚C 21˚C Max. Ent. Air 100/83˚F 80˚F 100/83˚F 80˚C
db/wb ➀➁ 38/28˚C 27˚C 38/28˚C 27˚C
Standard Range Units
Geothermal Range
Units
Additional Information For Initial Start-up Only
temperature and/or humidity, and equipment performance,
-
reliability, and service life may be adversely affected.
Geothermal Range
Cooling Heating Cooling Heating Min. Ent. Water ➀➁ 55°F/13°C 55°F/13°C 30°F/-1°C 20°F/-6°C
Normal Ent. Water 85°F/29˚C 70˚F/21°C 77°F/25˚C 40˚F/5°C
Max. Ent. Water ➀➁ 110°F/43˚C 90°F/32°C 110°F/43˚C 90°F/32°C
➀ At ARI flow rate.Maximum and minimum values may not be combined. If one
value is at maximum or minimum, the other two conditions may not exceed the normal condition for standard units. Extended range units may combine any two maximum or minimum con­ditions, but not more than two, with all other conditions being normal conditions.
Standard Range Units
Units
Standard Range units CCH & CRH
Units are designed to start-up in an ambient of 50°F (10°C), with entering air at 50°F (10°C), with entering water at 70°F (21°C), with both air and water flow rates used in the ISO 13256-1 rating test, for initial start-up in winter. Note: This is not a normal or continuous operating condi­tion. It is assumed that such a start-up is for the purpose of bringing the building space up to occupancy temperature.
Geothermal Range units CCW & CRW
Geothermal heat pump units are designed to start-up in an ambient of 40°F (5°C), with entering air at 40°F (5°C), with entering water at 25°F (-4°C), with both air and water at flow rates used in the ISO 13256-1 rating test, for initial start-up in winter. Note: This is not a normal or continuous operating condi­tion. It is assumed that such a start-up is for the purpose of bringing the building space up to occupancy temperature.
Operating voltages
115/60/1 . . . . . . . . . . . . . . . . 104 volts min.; 127 volts max.
208-230/60/1 . . . . . . . . . . . . 197 volts min.; 253 volts max.
265/60/1 . . . . . . . . . . . . . . . . 238 volts min.; 292 volts max.
230/50/1 . . . . . . . . . . . . . . . . 197 volts min.; 253 volts max.
460/60/3 . . . . . . . . . . . . . . . . 414 volts min.; 506 volts max.
380/50/3 . . . . . . . . . . . . . . . . 342 volts min.; 418 volts max.
575/60/3 . . . . . . . . . . . . . . . . 515 volts min.; 632 volts max.
Note: Voltages listed are to show voltage range. However, units operating with overvoltage and undervoltage for extended periods of time will experience premature com­ponent failure. Three phase system unbalance should not exceed 2%.
Page 8 / IM 742
Typical Wiring Diagrams
Fan
Motor
070 - Blk 060 - Blk 048 - Red 042 - Blk 036 - Blk 030 - Blk
Compr
Motor
CC - Compressor Contactor HTR - Crankcase Heater (Optional) CAP - Motor Capacitor
Condensate
Sensor
Common
Fan
L1
Compressor
Reversing Valve Solenoid (24 VAC)
0
W
2
G
W1Y
1
F E
L
U A
P
V
R C
Mark IV
PC
Board
Hi Pressure
Lo Pressure
Lo Temp
Ground
L1 L2
CC
Heater
Figure 8. Typical Mark IV/AC wiring diagram
COMPONENT LAYOUT
COMPRESSOR CONTACTOR FAN CONTACTOR TRANSFORMER PC BOARD AUXILIARY RELAY CIRCUIT BREAKER
Notes:
1. Unit is factory wired for 208V operation. If 230V power supply is used, transformer must be rewired by disconnecting the power lead from the red transformer primary wire and connecting the power lead to the orange transformer primary wire. Place an insulation cap on the red transformer primary wire.
2. All temperature and pressure switches are normally closed.
3. Component layout shown below is typical. Some components may not be used on this model or voltage.
4. Mark IV/AC controller board contains a static sensitive microprocessor. Proper grounding of field service personnel should be observed or dam­age to controller may result.
5. Terminal block on Mark IV/AC board provides 24 VAC at terminals R and C. All other outputs are 24 VDC.
6. Field supplied relays installed on the input terminals (W1, W2, Y1 or G) may inter-
fere with proper unit operation. Never install relay coils in series with inputs.
7. For more information pertaining to the Mark IV/AC controller, refer to OM120.
IM 742 / Page 9
Figure 9. Typical MicroTech 2000 WSHP unit controller single circuit wiring diagram
Notes:
1. Unit is factory wired for 208V operation. If 230V power supply is used, transformer must be rewired by disconnecting the power lead from the red transformer primary wire and connecting the power lead to the orange transformer primary wire. Place an insulation cap on the red transformer primary wire.
Page 10 / IM 742
2. All temperature and pressure switches are normally closed.
3. Wires 71 and 72 used only on units with no factory installed options.
Figure 10. Typical BACnet® WSHP unit controller
BACnet
Controller
Notes:
1. Unit is factory wired for 208V operation. If 230V power supply is used, transformer must be rewired by disconnecting the power lead from the red transformer primary wire and connecting the power lead to the orange transformer primary wire. Place an insulation cap on the red transformer primary wire.
2. All temperature and pressure switches are normally closed.
IM 742 / Page 11
Unit Operation
Chassis Ground
Unit
1
Unit
2
Unit
3
To
Additional
Units
Time
Clock
Two types of units are available: Mark IV/AC control units or units equipped with the new MicroTech 2000 Water Source Heat Pump Controller.
Mark IV/AC Control Units
The Mark IV/AC circuit board is an optional control sys­tem with built-in features such as random start, compressor time delay, night setback, load shed, shutdown, condensate overflow protection, defrost cycle, brownout, and LED/fault outputs. Figure 11 shows the LED and fault output sequenc es. The unit has been designed for operation with a 24 volt mercury bulb type wall thermostat or a microelectronic wall thermostat selected by the manufacturer. Do not operate the unit with any other type of wall thermostat. Each unit has a printed circuit board control system. The low voltage output from the low voltage terminal strip can be either AC voltage or DC voltage to the wall thermostat. This is dependent on what terminals you use. R is A/C voltage output and F is D/C voltage output to the wall stat. The 24 volt low voltage terminal strip is set up so R-G or F-G energizes the fan, R-Y1 or F-Y1 energizes the com­pressor for cooling operation, R-W1 or F-W1 energizes the compressor and reversing valve for heating operation. The reversing valve is energized in the heating mode. The circuit board has a fan interlock circuit to energize the fan when­ever the compressor’s on if the thermostat logic fails to do so. Remember the output to the wall stat can be AC current or DC current. Terminal (R) on the wall stat can be con nected to terminal (R) on the PC board for AC voltage or to terminal (F) on the PC board for DC voltage.
AC current DC current
R to G = fan only F to G = fan only R to Y1 = cooling F to Y1 = cooling R to W1 = heat F to W1 = heat
The Mark IV/AC control board has a lockout circuit to stop compressor operation if any one of its safety switches opens (high pressure switch and low pressure switch on units CCH & CCW 019 thru 060, R-410A), (CRH & CRW 024 thru 070, R-22). If the low temperature switch opens, the unit will go into the cooling mode for 60 seconds to defrost any slush in the water-to-refrigerant heat exchanger. After 60 seconds the compressor is locked out. If the condensate sensor detects a filled drain pan, the compressor operation will be suspended only in the cooling mode. The unit is reset by opening and closing the disconnect switch on the main power supply to the unit in the event the unit compressor operation has been suspended due to low temperature (freezestat) switch, (high pressure switch, or low pressure switch on units CCH & CCW 019 thru 060, R-410A), (CRH & CRW 024 thru 070, R-22). The unit does not have to be reset on a condensate overflow detection. The Mark IV/AC control circuit fault output sends a signal to an LED on a wall thermostat. Figure 11 shows for which functions the fault output is “on” (sending a signal to the LED).
Figure 11.
LEDs
Normal Mode Off On Off Off High Pressure Fault Off Off Flash On Low Temperature Fault* Flash Off Off On Condensate Overflow On Dim Off On Brownout Off Flash Off On On Load Shed Off Off On Off Off Unoccupied Mode On On Off Off Unit Shutdown Off Flash Off On
Indication
Yellow Green Red
Fault
Output
The Remote Reset feature provides the means to remotely reset automatic lockouts generated by high-pres­sure and/or low-temperature (in heating) faults. When the Mark IV board is in automatic lockout due to one of these
­faults, and the cause of the fault condition has been allevi-
ated, energizing the O-terminal for 10 seconds or more will force the Mark IV board to clear the lockout. A unit power cycle can also be used to clear an automatic lockout if the conditions causing the fault have been alleviated. The Fault Retry feature helps to minimize nuisance trips of automatic lockouts caused by high-pressure and/or low­temperature (in heating) faults. This feature clears faults the first two times they occur within a 24-hour period and trig­gers an automatic lockout on the 3rd fault. The retry count is reset to zero every 24 hours. The Mark IV/AC control circuit has built-in night setback operation. A “grounded’ signal to the “U” terminal on the low voltage terminal strip puts the unit into the unoccupied mode for night setback operation. Fan operation terminates and unit control reverts to the night setback terminal on the thermostat, W2; day heating and cooling operation is locked out. R-W2 energizes the compressor and reversing valve for
­heating operation. Night setback operation can be overrid
den for two hours by toggling the fan switch (intermittently closing the R to O terminals) on the Deluxe Auto Changeover thermostat. Day thermostat setpoints then control the heat ing and cooling operation. The Mark IV/AC control system also accommodates load shed and shutdown operation on receipt of a “grounded” signal to the “L” and “E” terminals, respectively, on the low voltage terminal strip.
Figure 12.
To activate the unoccupied mode for units on the same clock schedule, a single wire can be “daisy chained” between units and simply grounded through the time clock contacts. The same system can also be done to activate the load shed and unit shutdown modes by running additional wires between units to ground.
The P and C terminals of the Mark IV/AC board are used for pump restart. These terminals pass a voltage signal whenever the unit compressor is turned on. This signal is detected by a pump restart relay board providing a N.O. or N.C. set of contacts for heat pump loop circulation pump control. When used with the Loop Water Controller, the relay operation accommodates turning off circulation pumps dur­ing unoccupied periods with a safety override dependent, at minimum, on WSHP’s need. The P and C terminals may be “daisy chained” between 200 units. See page 21. Field supplied relays installed on the input terminals W1, W2, Y1, Y2 or G may introduce electrical noise. Never install relay coils in series with the inputs.
-
-
Page 12 / IM 742
MicroTech™ 2000 WSHP Unit Controller
Each McQuay Enfinity R-410A and standard R-22 horizontal water source heat pump can be equipped with a MicroTech 2000 water source heat pump unit controller. The controller is microprocessor-based and is designed to communicate over a LonWorks® (LonTalk® or LonMark® 3.3) communica­tions network. The unit controller is factory programmed and tested with all the logic required to monitor and control the unit. The controller sets the unit mode of operation, monitors water and air temperatures, and can communicate fault conditions to a LonWorks communications network.
The MicroTech 2000 unit controllers include unit-mounted return air, discharge air and leaving water temperature sen­sors. Options include a tenant setpoint adjustment knob and tenant override button, and the capability of substituting the return air sensor with a wall-mounted room sensor.
MicroTech 2000™ WSHP unit controller
An amber, on-board status LED aids in diagnostics by indicating the water source heat pump operating mode and alarm conditions. If there are no current alarm conditions, the LED will indicate the unit operating mode as shown in the table below. If there are one or more alarm conditions
present, the LED will flash to indicate an alarm condition.
MicroTech 2000 heat pumps are designed to be linked with a centralized building automation system through a LonWorks communications network for centralized schedul­ing and management of multiple heat pumps. Wall-mounted room sensors are available to control the heating and cool­ing operation of each MicroTech 2000 Water Source Heat Pump Unit Controller. Available room sensors include: room sensor with LED status and tenant override button, room sensor with LED status, timed-override button, and bi-metal thermostat, room sensor with LED status, timed-override button, and setpoint adjustment, and room sensor with LED status, timed-override button, setpoint adjustment and bi­metal thermostat.
MicroTech 2000 Unit Controller LED Indication
Status LED State Mode On Continually Occupied, Occupied Load
Shed
On 1⁄2 sec., Off 5 1⁄2 sec. Unoccupied On 5 1⁄2 sec., Off 1⁄2 sec. Tenant Override, Override
Load Shed Flashing Alarm Condition
Each unit controller orchestrates the following unit operations:
Enable heating and cooling to maintain setpoint based on
a room sensor.
Enable fan and compressor operation.
Monitor all safety controls.
Monitor discharge air temperature.
Monitor leaving water temperature.
Relay status of all vital unit functions.
Support optional control outputs.
MicroTech 2000™ WSHP unit control box
IM 742 / Page 13
BACnet® WSHP Unit Controller
McQuay Enfinity horizontal water source heat pumps are available with a factory mounted and tested Alerton BACnet unit controller as a special. The unit controller is factory programmed and tested with all the logic required to control the unit, and is designed to communicate over a BACnet MS/TP communications network to an Alerton BACtalk building automation system (BAS). Each individual controller must be programmed with a unique mac address. Each controller must be physically addressed at the board using dip switches. The controller operates the compressor, fan, and reversing valve as required to maintain the space temperature within the current setpoints. Data regarding equipment status, water and air temperatures, and fault conditions can be monitored by an Alerton BACtalk BAS. Setpoints and other system preferences must be changed remotely using an Alerton BACtalk workstation or Alerton service tool software.
The controller makes operational data and commands available on the Alerton BACtalk network using BACnet objects and properties. Each heat pump controller connects to the BACtalk network using a BACnet MS/TP LAN, which is a simple twisted-pair communications connection that operates at up to 76.8 Kbps. DIP switches on the control ler enable the MS/TP MAC address to be set in the range 0-127. A status LED on the unit indicates communication activity on the MS/TP LAN.
BACnet® WSHP unit controller
Each BACnet-compliant unit includes discharge air and leaving water temperature sensors, as well as all safety sensors, signals, and switches. Wall-mounted room sen sors are available from Alerton to control heating and cool­ing operation. Available sensors include tamper-resistant stainless steel wall sensors with optional push-button for status override; wall-mounted sensors with tenant setpoint adjustment lever and timed-override button; wall-mounted sensors with LED status, timed-override button, tenant set­point adjustment buttons, password-protected field service access to operational data, and optional humidity sensor; and wall-mounted sensors with LCD and programmable operation.
Each BACnet-compliant controller has the following operat­ing features:
Start-up – The unit will not operate until all the inputs and
safety controls are checked for normal conditions.
Fan operation – Fan operation can be customized in
software to run continuously during occupied mode, or to cycle ON or OFF appropriately on a call for heating and cooling.
Cooling mode – On a call for cooling, the compressor
and fan start immediately. Compressor run-time is cal
­culated as a percent of full cycle time (17 minutes) using proportional-integral control to maximize efficiency.
Heating mode – On a call for heating, the compressor
and fan start immediately, and compressor run-time is calculated as a percent of full cycle time (17 min­utes) using proportional-integral control to maximize efficiency.
Short Cycle Protection and Random Start – A start
delay of 180 seconds plus the compressor’s MAC address in seconds prevents short-cycling and simul­taneous start-up. A minimum 2-minute on time and 5-minute off time for the compressor further ensures short-cycle protection.
-
Occupied Mode – A simple software control signal
from the building automation system or a wall-mounted unit puts the unit into occupied mode. The unit controls compressor and fan operation to maintain occupied setpoints. High and low limits for occupied setpoints are software configurable.
Unoccupied Mode – A simple software control signal
from the building automation system or a wall-mounted unit puts the unit into unoccupied mode for night set­back operation. The unit controls compressor and fan operation to maintain unoccupied heating and cooling setpoints, which are also software configurable.
After-hours Override Mode – A simple software control
signal from the building automation system or a wall­mounted unit can initiate after-hours heating or cooling in half-hour increments. Maximum override time is soft
­ware configurable up to 9.5 hours. This feature can also be disabled in software.
Reversing valve delay – When the compressor turns
off after heating mode, the reversing valve remains energized for 60 seconds before it returns to the normal cooling position to eliminate swishing. The reversing valve energizes 10 seconds before the compressor.
Load Shed – Load shedding can be orchestrated by the
building automation system using the occupied/unoccu-
-
pied command in software.
Brownout Protection – An onboard sensor measures
input voltage and suspends compressor and fan opera­tion if the supply voltage drops below 82% of the normal line voltage for a minimum of 10 seconds, creating an alarm available in software. The alarm automatically resets when the supply voltage returns to above 90% of normal.
Page 14 / IM 742
BACnet® WSHP Unit Controller
Condensate Overflow Protection – A liquid sensor at
the top of the drain pan senses a high water level. Upon sensing water, cooling operation is suspended, while heating operation is allowed. The controller creates an alarm available in software. The alarm automatically resets when the water level returns to normal.
Safety Control – The unit monitors refrigerant pressure
and generates separate high-pressure and low-pres­sure alarms available in software. While either alarm is active, compressor operation is suspended. In a refriger ant low-temperature condition, an alarm occurs and the unit operates in cooling mode for 60 seconds to defrost the heat exchanger, after which compressor operation is suspended. These alarms can be reset in software or by cycling power to the controller.
Attained Temperature and Water Temperature Alarms
– Attained temperature, water temperature alarms with software-adjustable setpoints are available in software. The controller samples supply air and records attained temperatures for heating and cooling. If after two hours of operation, the attained temperature does not meet the software-configurable setpoint for heating or cooling as appropriate, a software alarm occurs. The alarm auto matically resets when the attained temperature is within
temperature is within setpoints. The controller also
monitors leaving water temperature. If the leaving water temperature is outside software-configurable setpoints, compressor operation is suspended and high or low water temperature alarms occur. The alarm automatically resets when the water temperature returns to within 6 deg. F of the setpoint.
Unit Self-test Mode – While the unit is in occupied
mode, a self-test can be initiated via software. Upon
-
initiation of the test, compressor operation is suspended for a minimum of five minutes, cooling attained tem­peratures are cleared, and attained temperature alarms are cleared. The unit then switches to full heat for four minutes and then records the attained supply air tem­perature. Compressor operation is then suspended for five minutes. The unit then switches to full cooling for four minutes and the attained supply air temperature is recorded. Attained temperature alarms are set if the attained temperatures failed to reach alarm setpoints during heating or cooling.
-
IM 742 / Page 15
WSHP Mark IV/AC Board Low Voltage Terminal Strip (Circuit 1)
O W
2 G
W1 Y1 F E L U A P V R C
W1 Y1 W2 Y2 G
Thermostat Terminals
-
C
+
R
Thermostat Connection Diagrams
WSHP Mark IV/AC Board Low Voltage Terminal Strip (Circuit 1)
O
W1 Y1 F E L U A P V R C
W1 Y1 W2 Y2 G O
Thermostat Terminals
Override (Optional)
-C +R
W2 G
S1
S2
S1
S2
Cut R12 from circuit board
Remote Senso
r
Thermostat
Wire 1
Wire 2
Mark IV/AC Units – Unit Sizes 007-070
7-Day Programmable Electronic Thermostat (P/N 107095901)
Non-Programmable Electronic Thermostat (P/N 668054201)
Includes Thermostat and Wall Plate.
Refer to the installation, operation & application guide (LIA217) for thermostat 107095901 installa­tion details
Includes Thermostat and Wall Plate.
Optional Remote Sensor (P/N 667720401)
1. Remove cover from remote sensor housing.
2. Select an appropriate location for mounting the remote sensor.
3. Mount remote sensor unit using hardware provided.
4. Install two strand shielded wire between remote sensor
and thermostat. Shielded wire must be used.
Do not run remote sensor wire in conduit with other wires.
• Wire 1 should run between the S1 terminal on the ther
mostat and the S1 terminal on the remote sensor
• Wire 2 should run between the S2 terminal on the ther-
mostat and the S2 terminal on the remote sensor
• Connect the shielding of the wire to the S2 terminal on
the thermostat
5. Disable the main sensor (R12) on the thermostat by cutting it from the circuit board.
Page 16 / IM 742
Notes: When remote reset of a lockout condition is required at the wall thermostat, it will be necessary to utiilize a conductor between terminal "O" on the wall thermostat to termi­nal "O" on the Mark IV control board (non­programmable stat only).
Refer to the installation, operation & appli­cation guide (LIA204-4) for thermostat 668054201 installation details
-
MicroTech Wall Sensor – Wiring Diagram
MicroTech Controller
J2
6 7 8 9 10 11 12
62 63 64 65 66 67 68
1 2 3 4 5 6 7
Terminal Board #1
Red
Grn
Wht
Blk
Stranded Wire (Blk, Wht, Grn, Red)
Wall Sensor
Locate the sensor on a wall where exposure to unrestrict­ed air circulation represents the average temperature of the space. A common mistake is to mount the sensor too close to the supply air diffuser in a room. This causes short cycling of the air conditioning unit and large room tempera­ture swings.
Note: All sensors have black (common), white (thermistor), and red (LED) wires. With the tenant override and /or set point adjustment option, a green wire is provided. The optional thermometer does not affect wiring.
Refer to IM 529 for detailed installation instructions.
Sensor Tenant Override Setpoint Bi-Metal No. of Conductors Part No. Switch Adjustment Pot Thermometer Required
107230301 Yes No No 4 + Shield 107230401 Yes No Yes 4 + Shield 107230501 Yes Yes No 4 + Shield 107230601 Yes Yes Yes 4 + Shield
IM 742 / Page 17
WSHP Mark IV/AC Board Low Voltage Terminal Strip
O W
2 G
W1 Y1 F E L U A P V R C
1
2
3
Auxiliary Relay
Orange
Yellow
White
WSHP Mark IV/AC Board Low Voltage Terminal Strip
O W
2 G
W1 Y1 F E L U A P V R C
1
2
3
Auxiliary Relay
Orange
Yellow
White
Auxiliary Relay (P/N 106059701)
WSHP Mark IV/AC Board Low Voltage Terminal Strip
O W2 G W1 Y1 F E L U A P V R C
1
2
3
Auxiliary Relay
Orange
Yellow
White
O W2 G W1 Y1 F E L U A P V R C
WSHP Mark IV/AC Board Low Voltage Terminal Strip
O W2 G W1 Y1 F E L U A P V R C
O W2 G W1 Y1 F E L U A P V R C
R
Y
G
W
R
Y
G
W
R
Y
G
W
G W Y R C
G W1 Y1 R Rc C
Thermostat Terminals
Multiple Unit
Control Panel
TB3
TB2
TB1
TB4
WSHP Mark IV/AC Board Low Voltage Terminal Strip
WSHP Mark IV/AC Board Low Voltage Terminal Strip
Operation: In this example the auxiliary relay contacts can be used to indicate a fault condi­tion. With the auxiliary relay connected as shown, the nor­mally open contacts will close during a fault condition.
Options on Mark IV/AC Units
The auxiliary relay is designed to interface external equip­ment with the Mark IV/AC board. The auxiliary relay has been provided with the components necessary to protect from electrical damage that may occur to the Mark IV/AC board when using standard off-the-self relays. The auxiliary relay can be used to provide fault signals, unit operation signals, or to provide a means for remote equipment to control the Mark IV/AC board. The orange, yellow, and white connections are short flying leads pre-attached to the board. The diagrams shown are some connection examples.
Operation: In this example the auxiliary relay contacts can be used to signal WSHP fan oper­ation to another device. In this example when the thermostat energizes the “G” terminal the auxiliary relay normallyopen contacts wil close.
Multiple Unit Control (up to 3 units) (P/N 056794201)
This multiple unit control board is an accessory used when you need to control up to 3-units from a single thermostat. The board is typically mounted in the unit control box clos­est to the thermostat. A maximum of 2 boards may be used together if up to 6-units must be connected and controlled from a single thermostat.
This version of the board uses VAC relays and should not be used in combination with any other accessories or equip-
Operation: In this example the auxiliary relay is used to interface other control devices to the Mark IV/AC board. Using the Orange (-) and White (+) wires, and 24vac or 24vdc, another device could be used to start and stop the WSHP heating sequence.
ment that require VDC connections to the “G”, “W1”, or “Y1” terminals (i.e. Boilerless System Kit).
The multiple unit control board provides the components necessary to protect the Mark IV/AC board from electrical damage that may occur when using standard off-the-shelf relays.
Do not use the unoccupied (U-terminal) feature with the multiple unit control board.
Page 18 / IM 742
Multiple Unit Control (up to 2 units) (P/N 106059801)
WSHP Mark IV/AC Board Low Voltage Terminal Stri
p
O W 2 G W1 Y1 F E L U A P V R C
R
Y
G
W
L
G W1 Y1 R Rc C
Thermostat Terminals
Multiple Unit Control Panel
O W 2 G W1 Y1 F E L U A P V R C
G W Y C L
WSHP Mark IV/AC Board Low Voltage Terminal Strip
WSHP Mark IV/AC Board Low Voltage Terminal Strip
O W2 G W1 Y1 F E L U A P V R C
1
2
3
Auxiliary Relay
Orange
Yello w
White
6 3 1
Time Clock (by others)
Daisy-chain to additional Mark IV/AC board “U” terminals
BL
GN
6 3 1
Black to 6
White to 1
Plug
Pins,
Female
Conduit
Anti-Short Bushing
Connector
Valve
36" (915 mm)
Lead Length
This multiple unit control board is an accessory used when you need to control up to 2-units from a single thermostat. The board is typically mounted in the unit control box closest to the thermostat. The are short flying leads pre-attached to the board. A maximum of 3 boards may be used together if up to 4-units must be connected and controlled from a single thermostat.
This version of the board uses VDC relays and should not be used in combination with any other accessories
G”, “W”, “Y”, “C”, and “L” connections
or equipment that require VAC connections to the “G”, “W1”, or “Y1” terminals (i.e. Boilerless System Kit). Do not use the unoccupied (U-terminal) feature with the multiple unit control board.
The multiple unit control board provides the components necessary to protect the Mark IV/AC board from electrical damage that may occur when using standard off-the-shelf relays.
Motorized Valve & Relay for Unit Sizes 007 thru 070
Wired as shown below the motorized valve will open on a call for compressor operation. Valves for unit sizes 007 to 019 are 1⁄2" power-open spring-return while unit sizes 024 to 070 are 3⁄4" power-open spring return. Other thermostat combinations may be used. Valve and auxiliary relay are purchased separately.
Note: The wiring shown below can only be used when the “P” terminal is not being used as a pump restart signal to other equip­ment. If the “P” terminal must be used as a pump restart signal to other equipment, then wire the auxiliary relay’s yellow wire to “Y1”, white wire to “W1”, and orange wire to “C”, then the valve will open on a call for occupied heating or cooling from the thermostat.
P/N 060977401 - 1/2" Motorized Valve Kit P/N 060977301 - 3/4" Motorized Valve Kit P/N 859004354 - Valve Relay Kit
IM 742 / Page 19
Boilerless System Kit (BSK) – P/N 062522204 for sizes 007 - 070
RD
1
2
3
Auxiliary Relay
Orange
Yellow
White
1 2 3 4 5
RD
BR
WH
OR
OR
WH
WH
YE
GR GR
BK
WH
RD
OR
Normal
Override
Pot 1
Boilerless
System
Board
43 Ohm
4-pin
Plug
Water
Temperature
Sensor
Signal to remote duct heater control circuit
F L W1 V
Mark IV Board Terminals
9.66
(245 mm)
(007 – 042)
14.50
(368 mm)
(048 – 060)
6.5 (165 mm) (007 – 042)
4.12 (105 mm) (048 – 060)
1.75
(44.5 mm)
The BSK option for use with the Mark IV/AC control board provides the capability to control a remote duct heater. The duct heater must be provided with a low voltage control cir­cuit that only requires a set of dry contacts for operation. The contacts shown on the Boilerless System board (ter­minals 1, 2, and 3) are used to control the remote duct heater, the N.O. contacts will close on a call for duct heater heat. POT1 provides a means to manually adjust the water temperature setpoint (adjustment range is 43oF to 60oF). The Normal/Override switch provides a means to manually force electric heat to always be used in place of heat pump heat when in the override position (default position is normal
- heat pump heat).
When the water temperature drops below the value of POT1, then the duct heater will be used instead of heat pump heat on a call for heat from the low voltage thermostat (not included).
The BSK field installed kits include the sheet metal enclosure with cover, wire harness, boilerless system board, auxiliary relay, and water temperature sensor. When used, one BSK is required for each unit. To use the BSK kit you attach the sheet metal enclosure to the unit as shown, route the 4-wire harness through knockouts and connect to the Mark IV/AC board, mount and connect and insulate the water tempera­ture sensor on the water supply line, and then connect the duct heater control contacts to the duct heater control cir­cuit. If night setback (U-terminal) is used, the duct heater will respond to the occupied W1 thermostat signal. The load shed input (L-terminal) cannot be used for other control func­tions when being used with the BSK. The BSK is a DC voltage device, when the BSK is used the thermostat must be wired for VDC operation.
Page 20 / IM 742
When the water temperature drops below the value of POT1, then the duct heater will be used instead of heat pump heat on a call for heat from the low voltage thermostat (not included).
Pump Restart Relay Kit P/N 061419001
WSHP Mark IV/AC Board Low Voltage Terminal Strip
Pump
Restart
Relay
7
6
5
4
3
2
1
O W2 G W1 Y1 F E L U A P V R C
Loop Water Controller Terminals
Daisy chain to other Mar
k
IV/AC board “P” and “C” terminals
64
58
65
WSHP Mark IV/AC Board Low Voltage Terminal Strip (Circuit 1)
Pump
Restart
Relay
7
6
5
4
3
2
1
O W2 G W1 Y1 F E L U A P V R C
Power by others
Daisy chain to other Mar
k
IV/AC board “P” and “C” terminals
Used as an option with the Mark IV/AC board, the pump restart relay kit provides a means to alert the loop water controller that water flow is required by a WSHP so that the system pump can be started. This option is typically used in installations where the pump may be shut off when there is no need for water flow (i.e. temperature OK, etc.). Typically only one pump restart relay kit is required per installation as up to 200 Mark IV/AC boards can be “daisy-chained” together.
The Mark IV/AC “P” terminal is used to determine WSHP compressor operation. Wired as shown below, when com pressor operation is required, the Mark IV/AC “P” terminal
will change state causing a contact closure between terminal 58 and 64 signaling the loop water control (LWC) panel to restart the loop pump if Off.
The pump restart relay kit is typically mounted within one WSHP or within the LWC panel, whichever is more conve­nient, diagrams are provided below for each location. To install the relay, remove the cover on the double-faced tape provided on the relay and attach the relay either to the inside of the LWC panel (adjacent to circuit breaker CB1 and termi­nal block TB3) or in the WSHP control box (in a convenient
-
location), then wire as shown below.
Wiring Pump Restart Relay when Installed within the LWC Panel
Wiring Pump Restart Relay when Installed within a WSHP Control Box
IM 742 / Page 21
Field Installed Options on MicroTech 2000 Units
1 2 3 4 5 6 7
E L U P C
4 3 2 1
(by others)
24VAC
4 3 2 1
(by others)
24VAC
4 3 2 1
(by others)
24VAC
MicroTech 2000 units can provide up to 4-outputs, that can be configured for any of the following output control signals:
1) Scheduled Output
When using a Network Master Panel (NMP) these out
puts can be assigned to one of 32 available schedules. The output will energize when the assigned schedule is occupied and de-energize when in unoccupied. These outputs could be used to control lights, etc.
2) Auxiliary Heat (Skin Heat)
When using a Loop Water Controller (LWC) the MicroTech
2000 receives loop water temperature information from the LWC and will use the Auxiliary Heat output for heat­ing when loop water temperature is inappropriate for heat pump heating. These outputs provide a signal that can be used to control a remote electric heater. The output will energize on a call for electric heat and de-energize when not required.
3) Fresh Air Damper
These outputs provide a signal that can be used to control
a remote fresh air damper. The output will energize when the unit fan is energized and de-energize when the unit fan is de-energized.
1st Control Signal Output
(Located externally on the WSHP chassis)
Terminal Boards
4) Motorized Water Valve These outputs provide control for a motorized water valve
that can be used to stop or divert flow away from the
-
WSHP when compressor operation is not needed. The output will be energized when compressor operation is required.
If more than one of the above control signals is required on a single WSHP, the MicroTech 2000 Auxiliary Module Kit (1077311001) must be used and these additional output con­trol signals will be connected to the Auxiliary board. 1-circuit units can provide up to 4-outputs.
If the Auxiliary board is added in the field to provide addition­al outputs it will need to be mounted within the WSHP control box so that J1 on the Auxiliary board can be connected to J6 on the MicroTech 2000 board without exceeding a maximum wire length of 10".
Also, each output is by default configured to “none” and must be field set to one of the four signal types listed above using the Monitor software, cable, and a PC communicating to the unit through an MCG panel.
2nd Control Signal Output
Terminals Located on
Microtech 2000 Auxiliary Board
J6
IMPORTANT: To use onboard 24VAC, change the jumper PF1 on the MicroTech 2000 controller from factory default pins 1 and 2 to pins 2 and 3.
3rd Control Signal Output
Terminals Located on
Microtech 2000 Auxiliary Board
J7
Use contacts as needed for option
24VAC
Pilot Duty Relay
(by others)
24VAC
Pilot Duty Relay
(by others)
Pilot Duty Relay
Use contacts as needed for option
4th Control Signal Output
Terminals Located on
Microtech 2000 Auxiliary Board
J10
Pilot Duty Relay
(by others)
Use contacts as needed for option
24VAC
(by others)
24VAC
Page 22 / IM 742
Read Outputs
Check Timers
Hi
Pres. Sw ?
Brown Out ?
Low Temp SW?
Lo Shed ?
N S B ?
Cond. Overflw?
R - W 1 ?
R -Y 1 ?
Stop Comp.
Flash Red LED
Stop Fan
Flash Green LED
Stop Comp.
Htg Mode?
Stop Comp.
Fla sh Yel low LE D
Stop Comp.
Turn On Red LED
R - W 2 ?
Start Comp.
Cooling Mode
Stop Comp.
Reversing Valve On
Time Delay
Start Comp.
Start Comp.
No
No
No
Ye s
No
No
No
No
No
No
No
No
Turn on Yellow LED
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Mark IV/AC Sequence of Operation
14-Position Terminal Strip
Pin Designation Description
1 C Transformer ground (Ovac)
2 R Transformer supply (24vac) 3 V -DC power connection 4 P Pump request output 5 A Alarm fault output 6 U Unoccupied input 7 L Load shed input 8 E Remote shutdown input 9 F +DC power connection 10 Y1 Occupied cooling mode input 11 W1 Occupied heating mode input 12 G Fan only input 13 W2 Unoccupied heating mode input 14 O` Tenant override input
LED Status and Fault Output Status
Board Status LED’s Fault Output
Mode Yellow Green Red Terminal A
Occupied Off On Off Energized
Unoccupied On On Of Energized
Load Shed Off Off On Energized
Condensate Overflow On Dim Off De-Energized
High/Low Pressure Fault Off Off Flash De-Energized
Low Temperature Fault* Flash Off Off De-Energized
Brownout Off Flash Off De-Energized
Emergency Shutdown Off Flash Off De-Energized
*in heating mode only
Note: The fault output is energized when no faults exist. The fault ouput is
de-energized during faults and when unit power is off.
General Use and Information
The Mark IV/AC control board is provided with three drive terminals, R(24vac), F(24vdc), and C(Ovac) that can be used by the end user to drive the thermostat inputs (G, Y1, W1, and W2) and control inputs (U, L, E, and O). Any combination of a single board drive terminal (R, F, or C) may be used to operate the Mark IV/AC boards control or thermostat inputs. However, only one drive terminal (R, F, or C) can be connected to any individual input terminal or damage will occur. Some of the control inputs are used within the Water Source Heat Pump and not accessible to the end user. For example, HP, LT, and COF are not available for use by the end user.
Typically the Mark IV/AC board’s R(24vac) terminal is used to drive the board’s thermostat inputs and control inputs by connecting it to the R terminal of an industry standard thermostat. The control outputs of the standard thermostat are then con nected to the Mark IV/AC board thermostat inputs and control inputs as needed. Any remaining board input(s) may be operated by additional thermostat outputs or remote relays (dry contacts only).
All Mark IV/AC board inputs must be operated by dry contacts powered by the con­trol board’s power terminals. No solid state devices (Triacs) may be used to operate Mark IV/AC board inputs. No outside power source may be used to operate Mark IV/AC board inputs.
Using Drive Using Drive Using Drive
Terminal R (24vac) Terminal F (24vdc) Terminal C (ground)
De-engergized Energized D-energized Energized De-energized Energized
Place the Meters
Red (+) Lead on
Input to be
checked
U, L, E, Y1, W1, 10 to 22 to G. W2. P 14vac 26vac 33vdc 14vac 26vac
Place the Meters Place the Meters Place the Meters on Black (-) Lead Black (-) Lead Black (-) Lead
on C on V on R
Ovdc
30 to 10 to 22 to
-
IM 742 / Page 23
Troubleshooting Water Source Heat Pump
Low Voltage, check power supply voltage
Fuse may be blown, circuit breaker is open
Wires may be loose or broken.
Replace or retighten wires
Unit Control, check thermostat for correct wiring or bad thermostat
Neither Fan, nor Compressor Runs
Unit
Compressor runs in short cycle
Fan operates, Compressor does not
Compressor attempts to start but does not
Insufficient cooling or heating
Check compressor wiring for defective wiring or loose connection
Check thermostat for improper location
Check for defective compressor internal windings with ohm meter
Check for bad compressor capacitor
Check for lock rotor amp draw
Check for proper air flow. Filter could be dirty
Check blower assembly for dirt or bad fan motor capacity
Check for low refrigerant charge
Check amp draw on blower assembly
Check capacitor
Check wiring - loose or broken and check for bad connection
Hi pressure lockout ­A. Cool mode, check water flow B. Heating mode, check air flow C. Check reversing valve for proper valve position
Check compressor overload make sure it is closed
Check compressor to ground, or for internal short to ground.
Compressor winding may be open. Check continuity with ohm meter
Check wiring - loose or broken and check for bad connection
Check relays and contacts, also capacitor and wiring
Check high pressure switch and low temperature switch to see if unit is cycling on the safety
Check to see if the reversing valve is not hung up and is operating correctly
Check condensate overflow switch in cool mode of operation
DANGER
To avoid electrical shock, personal injury or death, be sure that field wiring complies with local and national fire, safety, and electrical codes, and voltage to the system is within the limits shown in the job-specific drawings and unit electrical data plate(s). Power supply to unit must be disconnected when making field connections. To avoid electrical shock, personal injury or death, be sure to rigorously adhere to field wiring procedures regarding proper lockout and tagout of components.
Page 24 / IM 742
The in and outs of Enfinity™ R-410A
Troubleshooting
Refrigerant 410A is a non-ozone depleting blend of two refrigerants HFC-125 and HFC-32 in a fifty percent mix­ture. Refrigerant 410A exhibits higher operating pressure and refrigeration capacity than R-22. R-410A refrigerant is intended for use in new air conditioning application that has traditionally been serviced by HCFC-22 or R-22. Due to higher capacity and pressure of R-410A, it is not recom­mended as a retrofit to existing R-22 systems.
Although R-410A is non-flammable at ambient tem­perature and atmosphere pressure, it can become com­bustible under pressure when mixed with air. (NOTE: R-410A should not be mixed with air under pressure for leak testing. Pressure mixtures of dry nitrogen and R-410A
can be used for leak testing.)
Lubrication
R410A should be used only with polyolester (POE) oil. The HFC refrigerant components in R-410A will not be compat­ible with mineral oil or alkylbenzene lubricants. R-410A sys­tems will be charged with the OEM recommended lubricant, ready for use with R-410A.
Charging
Due to the zeotropic nature of R-410A, it should be charged as a liquid. In situations where vapor is normally charged into a system, a valve should be installed in the charging line to flash the liquid to vapor while charging.
Warning
It is very important to make certain that the recycle or recov­ery equipment used is designed for R-410A. The pressure of R-410A refrigerant is approximately 60 percent greater than that of R-22. Pressure gauges require a range up to 800 PSIG high side and 250 PSIG low side. Recovery cyl inders require a 400 PSIG rating – do not put R-410A in a 300 PSIG rated cylinder.
(NOTE: because a water source heat pump operates under a wide range of water and air temperatures, the values printed below are to be taken as suggested pressure and temperatures.) All McQuay water source heat pumps are designed for commercial use. The units are designed for the cooling mode of operation and fail safe to cooling. The revising valve is energized for the heating mode of operation.
Superheat Head Pressure Water Delta T
8 to 14 degrees 335-355 PSIG 10° to 12°
All information above is based on ISO standard 13256-1 and are tested at these conditions.
-
Troubleshooting Refrigeration Circuit
Air Water Safety
Symptom
Pressure Pressure Amp Draw Heat Differential Differential Out
Charge
Undercharge System Low Low Low High Low Low Low Low Pressure (Possible Leak)
Overcharge System Pressure
Low Air Flow Heating
Low Air Flow Cooling Low Low Low
Low Water Flow Heating Low Low
Low Water Flow Cooling High High High High Low Low High High Pressure
High Air Flow Heating Low Low Low Low High Low Low Low Temp
High Air Flow Cooling Low High Normal High Low Low Normal High Pressure
High Water Flow Heating Normal Low Normal High Normal Normal Low High Pressure
High Water Flow Cooling Low Low Low Low High Normal Low Low Temp
Head Suction Compressor Super
High High High Normal High Normal High
High High High
Low Normal
Low Normal
High
Low
Normal
Normal
Subcooling
High High Low Low Temp
High Low High Low Temp
Temp (loops) Temp Lock
Normal Low
Low High Low High Pressure
TXV Restricted High Low High High Low Low
Normal Low
IM 742 / Page 25
Typical Refrigeration Cycles
Cooling Mode – (Single Circuit Only Shown)
Return Air
Thermal
Expansion Valve
Co-Axial Heat
Exchanger
Coil – Air to Refrigerant
Heat Exchanger
Blower
Reversing Valve
Conditioned Air – (Cooling)
Water In
Water Out
Sensing Bulb and Capillary Tube
Compressor
Cooling Refrigeration Cycle
When the wall thermostat is calling for COOLING, the reversing valve directs the flow of the refrigerant, a hot gas, leaving the compressor to the water-to-refrigerant heat exchanger. Here the heat is removed by the water and the hot gas condenses to become a liquid. The liquid then flows through a thermal expansion metering system to the air-to-refrigerant heat exchanger coil. The liquid then evaporates becoming a gas, at the same time absorbing heat and cooling the air passing over the surfaces of the coil. The refrigerant then flows as a low pressure gas through the reversing valve and back to the suction side of the compressor to complete the cycle.
Heating Mode – (Single Circuit Only Shown)
Return Air
Thermal
Expansion Valve
Co-Axial Heat
Exchanger
Coil – Air to Refrigerant
Heat Exchanger
Blower
Conditioned Air – (Heating)
Heating Refrigeration Cycle
When the wall thermostat is calling for HEATING, the reversing valve directs the flow of the refrigerant, a hot gas, leaving the compressor to the air-to-refrigerant heat exchanger coil. Here the heat is removed by the air passing over the surfaces of the coil and the hot gas condenses to become a liquid. The liquid then flows through a capillary thermal expansion metering system to the water-to-refrigerant heat exchanger. The liquid then evaporates becoming a gas, at the same time absorbing heat and cooling the water. The refrigerant then flows as a low pressure gas through the reversing valve and back to the suction side of the compressor to complete the cycle.
Page 26 / IM 742
Reversing Valve
Water In
Water Out
Sensing Bulb and Capillary Tube
Compressor
General Maintenance
1. Normal maintenance on all conditioners is generally lim­ited to filter changes. Motors used with WSHP unit size 007 through 070 are provided with permanently lubricated motors and require no oiling even though oil caps may be provided.
2. Filter changes are required at regular intervals. The time period between changes will depend upon the project requirements. Some applications such as motels pro duce a lot of lint from carpeting and linen changes, and will require more frequent filter changes. It is suggested that the filter be checked at 60-day intervals for the first year until experience is acquired. If light cannot be seen through the filter when held up to sunlight or a bright light, it should be changed. A more critical standard may be desirable.
3. The condensate drain pan should be checked annually and cleaned and flushed as required.
4. Recording of performance measurements of volts, amps, and water temperature differences (both heating and cooling) is recommended. A comparison of logged data with start-up and other annual data is useful as an indica-
-
tor of general equipment condition.
5. Periodic lockouts almost always are caused by air or water problems. The lockout (shutdown) of the condi tioner is a normal protective result. Check for dirt in the water system, water flow rates, water temperatures, airflow rates (may be dirty filter), and air temperatures. If the lockout occurs in the morning following a return from night setback, entering air below machine limits may be the cause.
-
IM 742 / Page 27
®
McQuay Training and Development
Now that you have made an investment in modern, efficient McQuay equipment, its care should be a high priority. For training information on all McQuay HVAC products, please visit us at www. mcquay.com and click on training, or call 540-248-9646 and ask for the Training Department.
Warranty
All McQuay equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local McQuay Representative for warranty details. Refer to Form 933-43285Y. To find your local McQuay Representative, go to www.mcquay.com.
This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.mcquay.com.
Products Manufactured in an ISO Certified Facility.
©2007 McQuay International • 800.432.1342 • www.mcquay.com IM 742 (Rev. 9-07)
Loading...