McQuay Enfinity CRH, Enfinity CRW, Enfinity CCH, Enfinity CCW Installation Manual

®
Installation & Maintenance Data
McQuay® Enfinity™ (R-410A) and Standard (R-22) Horizontal Water Source Heat Pumps
IM 742-4
Group: WSHP
Part Number: 106586605
Date: September 2007
Model Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Transportation & Storage
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-4
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Cleaning & Flushing System . . . . . . . . . . . . . . . . . . . . .
Start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Typical Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . .9-11
©2007 McQuay International
. . . . . . . . . . . . . . . . . . . . . . . . 2
Contents
Unit Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12-14
Thermostat Connections . . . . . . . . . . . . . . . . . . . . .16-17
Options for Mark IV/AC Units. . . . . . . . . . . . . . . . . .18-21
Field Installed Options on MicroTech Units . . . . . . . . . 22
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . 23
6
Troubleshooting WSHP . . . . . . . . . . . . . . . . . . . . . .24-25
Troubleshooting Refrigeration Circuit. . . . . . . . . . . . . . 25
Typical Refrigeration Cycles. . . . . . . . . . . . . . . . . . . . . 26
General Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Model Nomenclature
Note: For illustration purposes only. Not all options available with all models.
Please consult McQuay Sales Representative for specific availability.
W CCH 1 009 M E Y L S
Product Catagory
W = WSHP
Product Identifier CCH = Ceiling Mounted / R-410A / Standard Range CCW = Ceiling Mounted / R-410A / Geothermal CRH = Ceiling Mounted / R-22 / Standard CRW = Ceiling Mounted / R-22 / Geothermal
Design Series
1 = A Design 2 = B Design 3 = C Design 4 = D Design
Nominal Capacity
007 = 7,000 030 = 30,000 009 = 9,000 036 = 36,000 012 = 12,000 042 = 42,000 015 = 15,000 048 = 48,000 019 = 19,000 060 = 60,000 024 = 24,000 070 = 70,000
Controls M = Mark IV K = Micortech 2000 w/LonMark® 3.3 L = Microtech 2000 w/LonTaLk A = BACnet E = Less Board
®
Note: Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes and regulations, and are experienced with this type of equipment. Caution: Sharp edges are a potential injury hazard. Avoid contact with them.
Discharge Air
S = Straight E = End
Return Air
L = Left R = Right
Future
(None)
Voltage
A = 115/60/1 E = 208-230/60/1 F = 208-230/60-/3 J = 277-265/60/1 K = 460/60/3 L = 575/60/3
50 Hz (CCH&CCW Only)
M = 230/50/1 N = 380/50/3
Transportation & Storage
Upon receipt of the equipment, check carton for visible damage. Make a notation on the shipper’s delivery ticket before signing. If there is any evidence of rough handling, immediately open the cartons to check for concealed dam­age. If any damage is found, notify the carrier within 48 hours to establish your claim and request their inspection and a report. The Warranty Claims Department should then be contacted. Do not stand or transport the machines on end. For stor ing, each carton is marked with “up” arrows.
Installation
General
1. To prevent damage, this equipment should not be oper­ated for supplementary heating and cooling during the construction period.
-2. Inspect the carton for any specific tagging numbers indicated by the factory per a request from the installing contractor. At this time the voltage, phase and capacity should be checked against the plans.
3. Check the unit size against the plans to ensure unit installation is in the correct location.
4. After removing the carton, remove the hanger kit from the fan housing.
5. Before installation, check the available ceiling height versus the height of the unit.
6. Note the location and routing of water piping, conden sate drain piping, and electrical wiring. The locations of these items are clearly marked on submittal drawings.
7. The installing contractor will find it beneficial to confer with piping, sheet metal, ceiling and electrical foremen before installing any conditioners.
In the event that elevator transfer makes up-ended posi­tioning unavoidable, absolutely ensure that the machine is in the normal upright position for at least 24 hours before operating. Temporary storage at the job site must be indoors, completely sheltered from rain, snow, etc. High or low tem peratures naturally associated with weather patterns will not harm the conditioners. Excessively high temperatures, 140°F (60°C) and higher, may deteriorate certain plastic
­materials and cause permanent damage.
NOTE: Check the unit name plate for correct voltage with
the plans before installing the equipment. Also, make sure all electrical ground connections are made in accordance with local code.
8. Remove all shipping blocks in the fan wheel.
9. Change the airflow direction from straight discharge to end discharge or vice versa before the unit is installed in the ceiling. Refer to the section in this bulletin for instructions.
10. We recommend that the contractor cover the condi tioners with plastic film to protect the machines during finishing of the building. This is critical while spraying fireproofing material on bar joists, sandblasting, spray painting and plastering. If plastic film is not available,
-
the shipping carton may be modified to cover the units during construction.
-
-
Page 2 / IM 742
Unit Location
B
Coil
Airflow
E
C
D
Comp
Control
Box
Fan
Assembly
A
1. Locate the unit in an area that allows for easy removal of the filter and access panels. Leave a minimum of 18” of clearance around the heat pump for easy removal, and to perform routine maintenance, or troubleshooting. Provide sufficient room to make water, electrical and duct connections.
2. The contractor should make sure that adequate ceil ing panel access exists, including clearance for hanger brackets, duct collars and fittings at water and electrical connections.
3. Allow adequate room below the unit for a condensate trap and do not locate the unit above pipes.
4. Each unit is suspended from the ceiling by four threaded rods. The rods are attached to the unit corners by a hanger bracket through a rubber isolator.
Caution: Do not use rods smaller than shown in Figure 1B. The rods must be securely anchored to the ceiling or to the bar joists.
5. Each unit is furnished with a hanger kit. The kit is shipped unassembled and includes hanger brackets, rubber isolators, washers, bolts and lock washers. Lay out the threaded rods per the dimension in Figures 1A and 1B.
6. When attaching the hanger rods to the unit, a double nut is recommended since vibration could loosen a single nut. The installer is responsible for providing the hex nuts when installing hanger rods.
7. Leave minimum 3" (76 mm) extra threaded rod below the double nuts or minimum 3" (76 mm) clearance between top of unit and ceiling above to facilitate top panel remov­al for servicing.
Filter Access
Each unit is shipped with a filter bracket for side filter remov­al. For bottom removal push the filter up into top bracket to gain clearance of bottom bracket and remove the filter. Also, a sheet metal duct filter retainer can be fabricated when return air duct work is used.
Figure 1A. Hanger bracket detail, sizes 007 thru 070
Figure 1B. Unit sizes 007 thru 070
-
Bolt & Lock Washer
Hanger Bracket Dimensions
Models CCH & CCW
UNIT DIMENSIONS (INCHES) SIZE A B C D E
007 – 009 17.5 34 22 34 20 012 17.5 40 22 40 20 019 – 024 17.5 40 22 40 20 030 – 036 18.5 46 23 46 21
042 – 060 25.5 52 30 52 28
UNIT DIMENSIONS (mm) SIZE A B C D E
007 – 009 445 864 559 864 508 012 445 1016 559 1016 508 019 – 024 445 1016 559 1016 508 030 – 036 470 1168 584 1168 533 042 – 060 648 1321 762 1321 711
Models CRH & CRW
UNIT DIMENSIONS (INCHES) SIZE A B C D E
007 – 012 17.5 34 22 34 20 015 – 024 17.5 42 22 42 20 030 – 042 18.5 46 23 46 21 048 – 070 25.5 52 30 52 28
3/8" Threaded Rod (By Others)
Vibration Isolator
Washer
Hex Nuts (By Others)
UNIT DIMENSIONS (mm) SIZE A B C D E
007 – 012 445 864 559 864 508 015 – 024 445 1067 559 1067 508 030 – 042 470 1168 584 1168 533 048 – 070 648 1321 762 1321 711
IM 742 / Page 3
Air Discharge Conversion
Unit sizes 007 thru 070 can be shipped as straight discharge air or end discharge air arrangement. In the event that the unit needs to be converted from straight discharge to end discharge:
1. Remove top panel.
2. Remove the access panel to the fan motor. Remove the piece of insulation at the bottom on the side of the bottom panel.
3. Remove the fan discharge panel, rotate it 180 degrees, and move it to the other side. In other words, with straight
Ductwork & Attenuation
Discharge ductwork is normally used with these condition­ers. Return air ductwork may also be required. All ductwork should conform to industry standards of good practice as described in the ASHRAE Systems Guide. The discharge duct system will normally consist of a flexible connector at the unit, a transition piece to the full duct size, a short run of duct, an elbow without vanes, and a trunk duct teeing into a branch duct with discharge dif­fusers as shown in Figure 2. The transition piece must not have angles totaling more than 30° or severe loss of air performance can result. Do not connect the full duct size to the unit without using a transition piece down to the size of the discharge collar on the unit. With metal duct material, the sides only of the elbow and entire branch duct should be internally lined with acoustic fibrous insulation for sound attenuation. Glass fiber duct board material is more absorb ing and may permit omission of the canvas connector. The ductwork should be laid out so that there is no line of sight between the conditioner discharge and the distribution diffusers.
air discharge the housing is bottom horizontal and with an end discharge the housing is top horizontal.
4. Remove the three bolts holding the fan motor on and rotate it so that the motor oilers are in the up position.
5. Install insulation base panel below new access panel location.
6. Reinstall the top panel.
7. Reinstall the piece of insulation and the access panel.
Return air ducts can be brought in through a low side wall filter-grille and then up through the stud pieces to a ceiling plenum or through air ceiling filter-grilles. The ceiling filter-grille must not be placed directly under the conditioner. Return air ductwork can be connected to the standard filter rack. See Figure 3 (side filter removal shown). The filter rack can be installed for bottom filter removal or side filter removal by locating the brackets. For side filter removal the brackets should be located on the bottom, left side, and top. For bottom filter removal the brackets should be mounted on the left side top and right side with the spring clips support­ing the filter. Do not use sheet metal screws directly into the unit cabi net for connection of supply or return air ductwork, espe­cially return air ductwork which can hit the drain pan or the air coil.
-
-
Figure 2. Suggested duct layout
Both Sides Internally Lined With Acoustic Fibrous Glass Insulation
Transformation
Piece
Discharge Collar
On Heat Pump
Suggested Duct Layout For
Multiple Diffuser Application
Heat Pump
Canvas Collar
Square Elbow
2x2 Ft. Diffuser (Example Only)
Trunk Duct
Branch Duct Internally Lined With Acoustic Fibrous Insulation
Ventilation Air
Ventilation may require outside air. The temperature of the ventilation air must be controlled so that mixture of outside air and return air entering the conditioner does not exceed conditioner application limits. It is also typical to close off the ventilation air system during unoccupied periods (night setback).
Figure 3. Filter rack/return air duct collar
Standard 1" (25mm)
Optional 2" (51 mm) Rack also available.
The ventilation air system is generally a separate building subsystem with distribution ductwork. Simple introduction of the outside air into each return air plenum chamber reason­ably close to the conditioner air inlet is recommended. Do not duct outside air directly to the conditioner inlet. Provide sufficient distance for thorough mixing of outside and return air. See Operating Limits on page 8.
Page 4 / IM 742
Electrical Data
1. Verify the compatibility between the voltage and phase of the available power and that shown on the unit serial plate. Line and low voltage wiring must comply with local codes or the National Electrical Code, whichever applies.
7
2. Apply correct line voltage to the unit. A and/or a 11⁄8" (29 mm) knockout is supplied on the side of the unit. A disconnect switch near the unit is required by code. Power to the unit must be sized correctly and have dual element (Class RK5) fuses or an HACR circuit
All 208-230 volt single-phase and three-phase units are factory wired for 208 volt operation. For 230 phase opera tion, the line voltage tap on the 24 volt transformer must be
All fan motors are multi-speed, PSC type with integral mounting brackets and thermal overload protection. The motor is isolated from the fan housing for minimum vibration transmission. Fan motors on 019 thru 070 have a terminal strip on the motor body for simple motor speed change without going back to the control box. To change fan motor speed to high on size 015 through 048, interchange the red wire with the black wire. For low speed, sizes 012, 024, 030, 036, 042, 060 and 070, interchange the black wire with the red wire. To change the 460 volt motor from high to low
Figure 4. CCH, CCW, CRH & CRW Sizes 007 thru 070 (Factory wired)
8" (22mm) hole
General
230 Volt Operation
Fan Assembly
breaker for branch circuit overcurrent protection. See the nameplate for correct ratings.
3. Three phase 50 cycle units, 380/50/3, require a neutral wire for 230/50/1 power to the fan circuit.
4. Connect the thermostat/subbase wiring with the power “off ” to the unit.
Field supplied relays installed on the input terminals W1, W2, Y1,
5.
Y2 or G may introduce electrical noise. Never install relay coils in series with the inputs.
changed. Disconnect and cap the red lead wire and inter­change it with the orange lead wire on the primary of the 24
­volt transformer.
speed, interchange Black and Red wires, then add jumper between Black and Blue wires. All the fan/motor assemblies have a removable orifice ring on the housing to accommo­date motor and fan wheel removal without disconnecting the ductwork. The fan housing protrudes through the cabinet allowing adequate material for connection of flexible duct. Each model unit is shipped from the factory for maximum performance and minimum sound requirements. Fan sound levels and performance can be affected by external static pressure.
Figure 4a. CCH, CCW, CRH & CRW Sizes 042 thru 070 (Factory wired, 460 volt motor only)
1. All units should be connected to supply and return pip­ing in a two-pipe reverse return configuration. A reverse return system is inherently self-balancing and requires only trim balancing where multiple quantities of units with different flow and pressure drop characteristics exist in the same loop. Check for proper water balance by measuring differential temperature reading across the water connections. To insure proper water flow, the differential flow should be 10°F to 14°F (5°C to 8°C) for units in cooling mode.
A direct return system may also work acceptably, but
proper water flow balancing is more difficult to achieve and maintain.
2. The piping can be steel, copper or PVC.
3. Supply and return runouts usually join the unit via short lengths of high pressure flexible hose which are sound attenuators for both unit operating noise and hydraulic pumping noise. One end of the hose should have a swivel fitting to facilitate removal for service. Hard pip
Note: For low speed applications a jumper must be installed between the motor's Black and Blue terminal.
Piping
4. Some flexible hose threaded fittings are supplied with
5. Supply and return shutoff valves are required at each
6. No unit should be connected to the supply and return
-
ing can also be brought directly to the unit. This option is not recommended since no vibration or noise attenu­ation can be accomplished. The hard piping must have unions to facilitate unit removal. See Figure 5 for typical piping setup.
sealant compound. If not, apply Teflon tape to assure a tight seal.
conditioner. The return valve is used for balancing and should have a “memory stop” so that it can always be closed off but can only be reopened to the proper posi­tion for the flow required.
piping until the water system has been cleaned and flushed completely. After the cleaning and flushing has taken place, the initial connection should have all valves wide open in preparation for water system flushing.
IM 742 / Page 5
7. Condensate piping can be steel, copper or PVC. Each unit includes a condensate connection.
8. The condensate disposal piping must be trapped. The piping must be pitched away from the unit not less than
1
4" per foot. The unit has a 3/4 inch female pipe fitting
on each water source heat pump to accommodate the condense drain connection. Factory supplied conden sate hose assemblies have a pipe thread fitting to facili­tate connection of a flexible vinyl or steel braided hose. A complete copper or PVC condense system can be
used. Union fittings in the copper or PVC lines should be applied to facilitate removal.
9. Do not locate any point in the drain system above the drain connection of any unit.
10. Automatic flow controlled devices must not be installed
-
prior to system cleaning and flushing.
11. A high point of the piping system must be vented.
12. Check local code for the need for dielectric fittings.
Figure 5. (Sizes 007 through 070 shown)
Electrical Access Panel
Hanger Kits (4)
Flex Hoses
Return
Riser
Condensate
Riser
Ball
Supply
Riser
Note: Do not overtorque fittings. The maximum torque without damage to fittings is 30 foot pounds. If a torque wrench is not available, use as a rule of thumb, finger-tight plus one quarter turn.
Valves
Supply Air
Figure 6. Condensate disposal trapping detail
11⁄2"
11⁄2"
(38 mm)
(38 mm)
Optional Field Installed Vent
1
4" Per Foot
(21 mm Per Meter)
Cleaning & Flushing System
1. Prior to first operation of any conditioner, the water circulating system must be cleaned and flushed of all construction dirt and debris.
If the conditioners are equipped with water shutoff
valves, either electric or pressure operated, the supply and return runouts must be connected together at each conditioner location. This will prevent the introduction of dirt into the unit. See Figure 7.
Figure 7. Supply & return runouts connected together
Return Runout
Supply Runout
Mains
Flexible Hose
Runouts Initially Connected Together
2. Fill the system at the city water makeup connection with all air vents open. After filling, close all air vents.
The contractor should start main circulator with the
pressure reducing valve open. Check vents in sequence to bleed off any trapped air, ensuring circulation through all components of the system.
Power to the heat rejector unit should be off, and the
supplementary heat control set at 80°F (27°C).
While circulating water, the contractor should check
and repair any leaks in the piping. Drains at the lowest point(s) in the system should be opened for initial flush and blowdown, making sure city water fill valves are set to make up water at the same rate. Check the pressure gauge at pump suction and manually adjust the makeup to hold the same positive steady pressure both before and after opening the drain valves. Flush should continue for at least two hours, or longer if required, to see clear, clean drain water.
3. Shut off supplemental heater and circulator pump and open all drains and vents to completely drain down the system. Short circuited supply and return runouts should now be connected to the conditioner supply and return connections. Do not use sealers at the swivel flare con nections of hoses.
4. Trisodium phosphate was formerly recommended as a cleaning agent during flushing. However, many states and localities ban the introduction of phosphates into their sewage systems. The current recommendation is to simply flush longer with warm 80°F (27°C) water.
-
Page 6 / IM 742
5. Refill the system with clean water. Test the water using litmus paper for acidity, and treat as required to leave the water slightly alkaline (pH 7.5 to 8.5). The specified per centage of antifreeze may also be added at this time. Use commercial grade antifreeze designed for HVAC systems only. Do not use automotive grade antifreeze.
Once the system has been filled with clean water
and antifreeze (if used), precautions should be taken to protect the system from dirty water conditions. Dirty water will result in system wide degradation of perfor­mance and solids may clog valves, strainers, flow regu­lators, etc. Additionally, the heat exchanger may become clogged which reduces compressor service life or causes premature failure.
Start-up
1. Open all valves to full open position and turn on power
to the conditioner.-
2. Set thermostat for “Fan Only” operation by selecting
“Off” at the system switch and “On” at the fan switch. If “Auto” fan operation is selected, the fan will cycle with the compressor. Check for proper air delivery.
3. For those units that have two-speed motors, reconnect
for low speed operation if necessary.
4. Set thermostat to “Cool.” If the thermostat is an automat
ic changeover type, simply set the cooling temperature to the coolest position. On manual changeover types additionally select “Cool” at the system switch.
Again, many conditioners have time delays which
protect the compressor(s) against short cycling. After a few minutes of operation, check the discharge grilles for cool air delivery. Measure the temperature differ ence between entering and leaving water. It should be approximately 11⁄2 times greater than the heating mode temperature difference. For example, if the cooling temperature difference is 15°F (8°C), the heating tem­perature difference should have been 10°F (5°C).
Without automatic flow control valves, target a cooling
temperature difference of 10°F to 14°F (5°C to 8°C). Adjust the combination shutoff/balancing valve in the return line to a water flow rate which will result in the
10˚F to 14°F (5°C to 8°C) difference.
5. Set thermostat to “Heat.” If the thermostat is the auto
matic changeover type, set system switch to the “Auto” position and depress the heat setting to the warmest selection. Some conditioners have built-in time delays which prevent the compressor from immediately start­ing. With most control schemes, the fan will start imme diately. After a few minutes of compressor operation, check for warm air delivery at discharge grille. If this is
6. Set the loop water controller heat add setpoint to 70°F
-
-
-
-
-
(21°C) and the heat rejection setpoint to 85°F (29°C). Supply power to all motors and start the circulating pumps. After full flow has been established through all components including the heat rejector (regardless of season) and air vented and loop temperatures stabilized, each of the conditioners will be ready for check, test and start-up, air balancing, and water balancing.
a “cold building” start-up, leave unit running until return air to the unit is at least 65°F (18°C).
Measure the temperature difference between enter
ing and leaving air and entering and leaving water. With entering water of 60°F to 80°F (16°C to 27°C), leaving water should be 6°F to 12°F (3.3°C to 6.6°C) cooler, and the air temperature rise through the machine should not exceed 35°F (19°C). If the air tempera ture exceeds 35°F (19°C), then the water flow rate is inadequate.
6. Check the elevation and cleanliness of the condensate line. If the air is too dry for sufficient dehumidification, slowly pour enough water into the condensate pan to ensure proper drainage.
7. If the conditioner does not operate, check the following points:
a. Is supply voltage to the machine compatible? b. Is thermostat type appropriate? c. Is thermostat wiring correct?
8. If the conditioner operates but stops after a brief period:
a. Is there proper airflow? Check for dirty filter, incor
rect fan rotation (3-phase fan motors only), or incor­rect ductwork.
b. Is there proper water flow rate within temperature
limits? Check water balancing; backflush unit if dirt­clogged.
9. Check for vibrating refrigerant piping, fan wheels, etc.
10. Do not lubricate the fan motor during the first year of operation as it is prelubricated at the factory.
Field supplied relays installed on the input terminals W1, W2,
11.
Y1, Y2 or G may introduce electrical noise. Never install relay coils in series with the inputs.
-
-
-
IM 742 / Page 7
Operating Limits
Environment
This equipment is designed for indoor installation only. Sheltered locations such as attics, garages, etc., gener ally will not provide sufficient protection against extremes in
Air limits Water limits
Cooling Heating Cooling Heating
Min. Ambient Air 50˚F/10˚C 50˚F/10˚C 40˚F/5˚C 40˚F/5˚C Normal Ambient Air 80˚F/27˚C 70˚F/21˚C 80˚F/27˚C 70˚F/21˚C Max. Ambient Air 100˚F/38˚C 85˚F/29˚C 100˚F/38˚C 85˚F/29˚C Min. Ent. Air ➀➁ 50˚F/10˚C 50˚F/10˚C 50˚F/10˚C 40˚F/5˚C Normal Ent. Air, 80/67˚F 70˚F 80/67˚F 70˚F
dw/wb 27/19˚C 21˚C 27/19˚C 21˚C Max. Ent. Air 100/83˚F 80˚F 100/83˚F 80˚C
db/wb ➀➁ 38/28˚C 27˚C 38/28˚C 27˚C
Standard Range Units
Geothermal Range
Units
Additional Information For Initial Start-up Only
temperature and/or humidity, and equipment performance,
-
reliability, and service life may be adversely affected.
Geothermal Range
Cooling Heating Cooling Heating Min. Ent. Water ➀➁ 55°F/13°C 55°F/13°C 30°F/-1°C 20°F/-6°C
Normal Ent. Water 85°F/29˚C 70˚F/21°C 77°F/25˚C 40˚F/5°C
Max. Ent. Water ➀➁ 110°F/43˚C 90°F/32°C 110°F/43˚C 90°F/32°C
➀ At ARI flow rate.Maximum and minimum values may not be combined. If one
value is at maximum or minimum, the other two conditions may not exceed the normal condition for standard units. Extended range units may combine any two maximum or minimum con­ditions, but not more than two, with all other conditions being normal conditions.
Standard Range Units
Units
Standard Range units CCH & CRH
Units are designed to start-up in an ambient of 50°F (10°C), with entering air at 50°F (10°C), with entering water at 70°F (21°C), with both air and water flow rates used in the ISO 13256-1 rating test, for initial start-up in winter. Note: This is not a normal or continuous operating condi­tion. It is assumed that such a start-up is for the purpose of bringing the building space up to occupancy temperature.
Geothermal Range units CCW & CRW
Geothermal heat pump units are designed to start-up in an ambient of 40°F (5°C), with entering air at 40°F (5°C), with entering water at 25°F (-4°C), with both air and water at flow rates used in the ISO 13256-1 rating test, for initial start-up in winter. Note: This is not a normal or continuous operating condi­tion. It is assumed that such a start-up is for the purpose of bringing the building space up to occupancy temperature.
Operating voltages
115/60/1 . . . . . . . . . . . . . . . . 104 volts min.; 127 volts max.
208-230/60/1 . . . . . . . . . . . . 197 volts min.; 253 volts max.
265/60/1 . . . . . . . . . . . . . . . . 238 volts min.; 292 volts max.
230/50/1 . . . . . . . . . . . . . . . . 197 volts min.; 253 volts max.
460/60/3 . . . . . . . . . . . . . . . . 414 volts min.; 506 volts max.
380/50/3 . . . . . . . . . . . . . . . . 342 volts min.; 418 volts max.
575/60/3 . . . . . . . . . . . . . . . . 515 volts min.; 632 volts max.
Note: Voltages listed are to show voltage range. However, units operating with overvoltage and undervoltage for extended periods of time will experience premature com­ponent failure. Three phase system unbalance should not exceed 2%.
Page 8 / IM 742
Typical Wiring Diagrams
Fan
Motor
070 - Blk 060 - Blk 048 - Red 042 - Blk 036 - Blk 030 - Blk
Compr
Motor
CC - Compressor Contactor HTR - Crankcase Heater (Optional) CAP - Motor Capacitor
Condensate
Sensor
Common
Fan
L1
Compressor
Reversing Valve Solenoid (24 VAC)
0
W
2
G
W1Y
1
F E
L
U A
P
V
R C
Mark IV
PC
Board
Hi Pressure
Lo Pressure
Lo Temp
Ground
L1 L2
CC
Heater
Figure 8. Typical Mark IV/AC wiring diagram
COMPONENT LAYOUT
COMPRESSOR CONTACTOR FAN CONTACTOR TRANSFORMER PC BOARD AUXILIARY RELAY CIRCUIT BREAKER
Notes:
1. Unit is factory wired for 208V operation. If 230V power supply is used, transformer must be rewired by disconnecting the power lead from the red transformer primary wire and connecting the power lead to the orange transformer primary wire. Place an insulation cap on the red transformer primary wire.
2. All temperature and pressure switches are normally closed.
3. Component layout shown below is typical. Some components may not be used on this model or voltage.
4. Mark IV/AC controller board contains a static sensitive microprocessor. Proper grounding of field service personnel should be observed or dam­age to controller may result.
5. Terminal block on Mark IV/AC board provides 24 VAC at terminals R and C. All other outputs are 24 VDC.
6. Field supplied relays installed on the input terminals (W1, W2, Y1 or G) may inter-
fere with proper unit operation. Never install relay coils in series with inputs.
7. For more information pertaining to the Mark IV/AC controller, refer to OM120.
IM 742 / Page 9
Loading...
+ 19 hidden pages