McQuay ACU018ARAY, ACU036APAY, ACU030ARAY, ACU036ARAY, ACU042ARAY Installation And Maintenance Manual

...
Installation and Maintenance Manual IM-800
Group: Unitary
Part Number: IM-800
Date: August 2005
Supersedes: January 2005
ACU Split System Air Conditioners
1-1/2 to 5 ton
IM-800 Page 1
Table of Contents
NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Receiving Inspection . . . . . . . . . . . . . . . . . . . . . . . . . 4
Codes and Regulations . . . . . . . . . . . . . . . . . . . . . . . . 4
Important Message to the Installer . . . . . . . . . . . . . . . 4
Important Message to the Owner . . . . . . . . . . . . . . . . 4
Recognize Safety Symbols, Words, and Labels . . . . 4
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
GENERAL WARNINGS . . . . . . . . . . . . . . . . . . . . . . . 5
CLEARANCES AND ACCESSIBILITY . . . . . . . . . . . 5
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
ELECTRICAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
REFRIGERANT TUBING . . . . . . . . . . . . . . . . . . . . . 6
EVAPORATOR COIL . . . . . . . . . . . . . . . . . . . . . . . . . 6
Field Connection to the Valve and Valve Opening . . . 6
QUICK CONNECT COILS . . . . . . . . . . . . . . . . . . . . . 7
Precharged System Installation . . . . . . . . . . . . . . . . . 7
SYSTEM START UP . . . . . . . . . . . . . . . . . . . . . . . . . 7
Processing Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
CHARGE CHECKS . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Capillary Tube/Fixed Orifice System. . . . . . . . . . . . . . 8
Superheat Determination . . . . . . . . . . . . . . . . . . . . . . 8
Expansion Valve System . . . . . . . . . . . . . . . . . . . . . . 8
WIRING DIAGRAM - SINGLE PHASE . . . . . . . . . . . 9
WIRING DIAGRAM - THREE PHASE . . . . . . . . . . . 10
"McQuay" is a registered trademark of McQuay International.
"Illustrations and information cover the McQuay International products at the time of publication and we reserve the right to make changes in
Page 2 IM-800
© 2004 McQuay International
design and construction at any time without notice."
MODEL NOMENCLATURE
Model
ACU = Air Cooled Cooling Unit
Nominal Capacity (tons)
18 = 1-1/2 24 = 2 36 = 3 42 = 3-1/2 48 = 4 49 = 4 60 = 5 61 = 5 62 = 5
* 10 SEER Size 036, 049 and 060 only. **10 SEER Size 060 only.
Table 1: Unit Nameplate Model Number Identifier
Unit Nameplate McQuay Model Number
CKL18-1L ACU018ARAY CKL24-1L ACU024ARAY CKL30-1L ACU030ARAY CKL36-1L ACU036ARAY CKL36-3L ACU036APAY CKL42-1L ACU042ARAY CKL49-1L ACU049ARAY CKL49-3L ACU049APAY CKL60-1L ACU060ARAY CKL60-3L ACU060APAY CKL60-4L ACU060AQAY CKL62-1L ACU062ARAY CLJ18-1C ACU018ARBY CLJ24-1C ACU024ARBY CLJ30-1C ACU030ARBY CLJ36-1C ACU036ARBY CLJ42-1C ACU042ARBY CLJ48-1C ACU048ARBY CLJ60-1C ACU060ARBY CLT24-1B ACU024ARCY CLT30-1B ACU030ARCY CLT36-1B ACU036ARCY CLT42-1B ACU042ARCY CLT48-1B ACU048ARCY
CLT60-1B ACU060ARCY CLQ24-1B ACU024ARDY CLQ30-1B ACU030ARDY CLQ36-1B ACU036ARDY CLQ42-1B ACU042ARDY CLQ48-1B ACU048ARDY CLQ60-1B ACU060ARDY
ACU 018
A
RAY
Future Use
SEER
A = 10 B = 12 C = 13 D = 14
Voltage/Phase
P = 208-230/3/60* Q = 460/3/60** R = 208-230/1/60
Vintage
IM-800 Page 3
INTRODUCTION
General Description
These installation instructions cover the outdoor installation of cooling only split systems from ½ to 5 tons. See the product catalog applicable to your model for information regarding specifications applicable to your model and accessories.
Receiving Inspection
McQuay products are carefully inspected prior to shipment and the carrier has assumed responsibility for loss or damage upon acceptance of the shipment.
Upon receiving your shipment, check all items carefully against the Bill of Lading. Inspect the unit and/or accessories for shipping damage as soon as they are received. Immedi­ately file claims for loss or damage, either shipping or con­cealed, with the shipping company.
Check the unit nameplate to verify the model number and elec­trical characteristics are correct. In the event an incorrect unit is shipped, it must be returned to the supplier and must NOT be installed. The manufacturer disclaims all responsibility for the installation of incorrectly shipped units.
Codes and Regulations
This product is designed and manufactured to permit installa­tion in accordance with National Codes. System design should, where applicable, follow information presented in accepted industry guides such as the ASHRAE Handbooks. It is the installer' s responsibility to install the product in accor­dance with National Codes and/or prevailing local codes and regulations. The manufacturer disclaims all responsibility for equipment installed in violation of any code or regulations.
Important Message to the Owner
Read these instructions carefully and keep them near the prod­uct for future reference. Although these instructions are addressed primarily to the installer, useful maintenance infor­mation is included. Have the installer acquaint you with the operation of the product and periodic maintenance require­ments.
Recognize Safety Symbols, Words, and Labels
The following symbols and labels are used throughout this manual to indicate immediate or potential hazards. It is the owner's and installer's responsibility to read and comply with all safety information and instructions accompanying these symbols. Failure to heed safety information increases the risk of property damage and/or product damage, serious personal injury or death. Improper installation, operation and mainte­nance can void the warranty.
DANGER
Immediate hazards which WILL result in property damage, product damage, severe personal injury and/ or death.
WARNING
Hazards or unsafe practice CAN result in property damage, product damage, sever personal injury and/or death.
IMPORTANT
The United States Environmental Protection Agency (EPA) regulations cover introduction and disposal of refrigerants in this unit. Failure to follow those regulations can harm the environment and lead to substantial fines. Because regulations can change over time, a certified technician should perform any work done on this unit. If you have any questions, please contact the local office of the EPA.
Important Message to the Installer
This equipment is to be installed by an experienced installation company and fully trained personnel. Carefully read all instructions and take into account any special considerations prior to installing the unit. Give this manual to the owner and explain its provisions.
CAUTION
Hazards or unsafe practices which CAN result in property damage, product damage, and/or personal injury.
Replacement Parts
Replacement parts can be obtained by contacting McQuay at 1
-800-37-PARTS. When contacting McQuay for service or replacement parts, refer to the model number and serial num­ber of the unit as stamped on the nameplate attached to the unit.
Page 4 IM-800
GENERAL WARNINGS
WARNING
Before servicing or installing, the electrical power must be in OFF. More than one disconnect may exist. Failure to disconnect all power can cause electrical shock, serious personal injury or death.
WARNING
The unit must have an uninterrupted, unbroken electrical ground. Failure to properly ground can cause severe personal injury or death.
Figure 1. Clearances and Accessibility
Service Access
18" Min.
10" Min.
WARNING
Installation and service by trained, qualified technicians only. High pressure and electricity can cause severe personal injury or death. Observe ALL warnings contained in this manual and the labels/tags attached to the equipment.
WARNING
When installing or servicing, wear protective gloves, gear and eyeware. Also observe special safety requirements (hard hats etc.).
CCAUTION
To protect the unit when welding close to the painted surfaces, use a quenching cloth to prevent scorching or marring the equipment finish.
CCAUTION
Read these instructions before performing this installation or servicing this unit. All installations must be in accordance with all national, state, or local building codes.
Service Access
18" Min.
Figure 2. Clearances and Accessibility
10" Min.
10"
10"
CLEARANCES AND ACCESSIBILITY
The condensing unit is designed to be located outside the building with unobstructed condenser air inlet and discharge. Additionally, the unit must be situated to permit access for ser­vice and installation. Condenser air enters from three sides. Air discharges upward from the top of the unit. Refrigerant tube electrical connections are made on the right side of the unit as you face the compressor compartment. The best and most common application is for the unit to be located 10” from the back wall with the connection side facing the wall. Refer to Figures 1 and 2. This “close to the wall” application mini­mizes exposed tubing and wiring and reduces the space for children to run around the unit. This will help to avoid possi­ble damage to the tubes or wiring and/or personal injury.
IM-800 Page 5
Close to the wall application provides free, unobstructed air to the other two sides. In more confined application spaces, such as corners, provide a minimum 10” clearance on all air inlet sides. Allow 18” minimum for service access to the compres­sor compartment and controls.
The top of the unit should be completely unobstructed. If units are to be located under an overhang, there should be a mini­mum of 36” clearance and provisions made to deflect the warm discharge air out from the overhang.
LOCATION
If unit is to be located under an overhang, there should be a minimum of 36” clearance and provisions made to deflect the water discharge air out from the overhang. If the outdoor unit is mounted above the air handler, the maximum lift should not exceed 70’ (suction line). If the air handler is mounted above condensing unit, the lift should not exceed 50’ (liquid line.). Refer to Figure 3 and Table 2 for maximum refrigerant line lenghts.
Figure 3. Maximum Refrigerant Line Lengths
70' MAX
CONDENSING UNIT
LIQUID LINE
CONDENSING UNIT
CONDENSING UNIT
LIQUID LINE SUCTION LINE OIL TRAPS WHEN INDOOR UNIT IS 4 FEET OR MORE BELOW OUTDOOR UNIT
INVERTED LOOP
PITCH SUCTION LINE TOWARD OUTDOOR UNIT 1/2" FOR EVERY 10' OF LINE
LIQUID LINE
EVAPORATOR BLOWER
SUCTION LINE
EVAPORATOR BLOWER
ADDITIONAL SUCTION LINE OIL TRAP FOR EACH 20' RISE OF PIPE
EVAPORATOR BLOWER
8'
50' MAX
ELECTRICAL
Electrical installation will consist of power supply wiring to the condensing unit, as well as control wiring between thermo­stat, indoor unit and the condensing unit as shown on wiring diagram. All wiring must be in accordance with National Electrical Code and/or local codes that may apply.
The condensing unit rating plate lists pertinent electrical data necessary for the selection of proper size electrical service and over-current protection. The installer should make the owner familiar with the location of the over-current protection, the proper size for this application, and the proper procedure for disconnecting power service to the unit.
The condensing unit control wiring requires a 24 Volt mini­mum 25 VA service from the indoor transformer as shown on the wiring diagram.
REFRIGERANT TUBING
Use only refrigerant grade (dehydrated and sealed) copper tub­ing of the size indicated in Table 1 to interconnect the condens­ing unit with the indoor evaporator. Take extreme care to keep the refrigerant tubing clean and dry prior to and during instal­lation.
Do not remove plugs from ends of tubing until connection is ready to be made. Suction line insulation is necessary to pre­vent condensation from forming on and dropping from suc­tion line. Generally 3/8" wall thickness of Armflex or equivalent is satisfactory. In severe applications (hot, high humidity areas) greater thickness may be required. Apply suc­tion line insulation by sliding it on the sealed tubing before cutting and making connections.
Table 2: Maximum Refrigerant Line Lengths
REFRIGERANT LINE LENGTH (Ft)
Cond
Unit
Ton s
1 1/2 5/8 1/4 3/4 3/8 3/4 3/8
2 5/8 1/4 3/4* 3/8 3/4 3/8
2 1/2 3/4 3/8 3/4** 3/8 7/8 3/8
3 3/4 3/8 3/4** 3/8 7/8 3/8
3 1/2 3/4 3/8 7/8** 3/8 1 1/8 3/8
4 7/8 3/8 1 1/8 3/8 1 1/8 3/8
5 7/8 3/8 1 1/8 3/8 1 1/8 3/8
0-24 25-49 50-74***
Line Diameter (In. OD)
Suct Liq Suct Liq Suct Liq
* 7/8" required for full ratings
** 1 1/8" required for full ratings The condensing unit must be mounted on a solid, level founda­tion (i.e. pre-formed concrete slab or other suitable base). For rooftop application, verify that the building construction can support the weight and that proper consideration is given to the weather-tight integrity of the roof. The condensing unit con­tains moving components and can vibrate. Therefore, sound is also a consideration in rooftop application. Since this unit dis­charges warm condenser air from the top with cooler air being drawn in three sides, plantings can be made in relatively close proximity to the unit. However, debris on the fan coil surface reduces product efficiency. Avoid lawn mower discharge toward the unit.
EVAPORATOR COIL
Suction and liquid lines are under pressure. Point lines away from persons and obects that can be damaged. Use extreme care when removing caps. Use fittings on the liquid line to remove pressure.
Do not remove caps until installation is complete and final connections are to be made.
Field Connection to the Valve and Valve Opening
1. Cut tubing square. Make sure it is round and free of burrs at the connecting ends. Clean the tubing to prevent con­taminants from entering the system.
2. Wrap a wet rag around the copper valve stub before braz-
ing.
3. Braze or silver solder the joint.
4. After brazing, quench with a wet rag to cool the joint.
Evacuate and charge the connecting lines as outlined in this manual.
5. Remove the valve top cap. It is important to keep the cap
in a clean area to provide proper sealing once replaced.
6. Using a standard L shaped Allen wrench, break open the
valve body. To expedite opening the valve body after it is broken, use a ratchet wrench with a short Allen stub. Please note that it is normal to see oil on the valve stem body once the cap is removed.
7. Replace the valve cap and tighten with a wrench, making
sure that the the cap is sealed.
Page 6 IM-800
QUICK CONNECT COILS
Precharged System Installation
Installation procedure will differ when condensing units are provided for use with precharged refrigerant coils and lines. Condensing units are provided with #6 and #11 male quick connects instead of liquid and suction valves attached to cabi­net to contain the R-22 charge that is sufficient for matching evaporator coils and 15’ of interconnecting lines.
Coils are provided with #6 and #11 male quick connects. Line sets are required with #6 and #11 female quick connects on both ends. Access ports are required in the fittings of both liq­uid and suction lines at condenser end. Both coil and line sets include R-22 holding charge only.
1. Connect lines to evaporator coil before connecting to the condensing unit, locating access ports adjacent to condens­ing unit.
a. Form tubing so it properly aligns with the coil connec-
tions.
b. Remove plugs and caps from connections.
c. Check to verify mating surfaces are clean.
d. Lubricate rubber seal with clean refrigerant oil and
thread couplings together by hand to verify they are not cross threaded.
e. Tighten connections using backup wrench on stationary
fitting until coupling bottoms; then tighten 1/6 turn to complete knife edge seal.
SYSTEM START UP
Processing Checks
Condensing units are supplied with R-22 charge sufficient for typical matching evaporator and approximately 15’ of inter­connecting tubing. Condensing unit liquid and suction valves are closed to contain the charge within the unit.
The recommended procedure for processing and charge adjust­ment is as follows:
1. Connect vacuum pump to both base valve service ports.
2. Evacuate tubing and evaporator through liquid and suction base valve ports, to 500 microns or less for a minimum of 30 minutes. Close valve to pump and wait 15 minutes. Vacuum should not rise above 800 microns. If unable to obtain 500 micorns, or vacuum rises above 800 microns over a 15 minute period, discontinue evacuation, pressurize and check for leaks. Repair any leaks found and repeat step 2.
3. Close valve to vacuum pump and stop pump. Break vac­uum by opening liquid and suction base valves. Fully open base valves and remove pump lines. Connect service gauges to verify lines are purged.
4. Set thermostat system switch to “COOL” and temperature to highest setting. Close all disconnects.
5. Set thermostat to call for cooling. Check for operation of indoor and outdoor fans. Allow for at least 10 minutes.
6. Check charge and adjust if necessary. Refer to appropriate “Check Charge” section.
2. Connect lines to condensing unit in the same manner as to evaporator coil. Observe same precautions.
3. After making all connections and opening valves, check all piping for leaks.
IM-800 Page 7
CHARGE CHECKS
Capillary Tube/Fixed Orifice System
1. Fully open both base valves.
2. Connect service gauge manifold to base-valve service ports to purge lines. Run system at least 10 minutes to allow pressure to stabilize.
3. Temporarily install thermometer on suction (large) line near condensing unit. Provide good contact between the thermometer and line. Wrap thermometer with insulating material to provide an accurate reading.
4. Refer to Table 3 for proper system superheat. Add charge to lower superheat. Remove charge to raise superheat.
5. Remove gauge lines carefully.
CWARNING
Escaping liquid refrigerant can cause burns. Wear protective gloves, gear and eyewear.
Table 3: System Superheat
AMBIENT CONDENSER INLET
TEMPERATURE (
o
F DB)
100
95
90
85
80
75 5 10172529
70 5 14202832
65 13 19 26 32 35
60 17 25 30 33 37
RETURN AIR TEMPERATURE (
65 70 75 80 85
579
71218
5101720
5122126
Superheat Determination
1. Read suction pressure. Using Table 4, determine saturated
suction temperature.
2. Read suction line temperature.
3. Use the following formula to determine superheat:
Superheat = Suction Line Temp. - Saturated Suction Temp.
Table 4: Saturated Suction Pressure (R-22)
SUCTION PRESSURE PSIG
50 26
53 28
55 30
58 32
61 34
63 36
66 38
69 40
72 42
75 44
78 46
81 48
SATURATED SUCTION
TEMPERATURE
o
F DB)
55
o
F
Expansion Valve System
1. Fully open both base valves.
2. Connect service gauge manifold to base-valve service parts making sure lines are purged. Run system at least 10 min­utes to allow pressure to stabalize.
3. Temporarily install the thermometer to liquid (small) line near condensing unit. Provide good contact between ther­mometer and line. Wrap thermometer with insulating material to provide an accurate reading.
4. Referring to Table 5, adjust charge to obtain a temperature 12-15°F below the saturated liquid temperature.
Example:
If the Liquid Pressure is 260 psig then the Saturated Tempera­ture will be 120°F. Adjust the Saturated Temperature by sub­tracting 12-15°F. This will give you a Liquid Line Temperature of 105° - 108°F.
Table 5: Saturated LIquid Temperature
LIQUID PRESSURE PSIG
200 102
210 105
220 108
230 111
240 114
250 117
260 120
270 123
280 126
290 128
300 131
SATURATED TEMPERATURE
o
F
SPECIAL NOTE: For systems with more than 15’ of inter­connecting tubing, please refer to Table 6 for line charge allowance per foot of tubing.
Table 6: Line Charge Allowance (R-22 - oz./ft.)
LINE O.D. (IN) LIQUID LINE SUCTION LINE
1/4 0.22
3/8 0.58
1/2 1.14
5/8 1.86 0.04
3/4 0.06
7/8 0.08
1 1/8 0.15
1 3/8 0.22
NOTE: Systems with over 50’ separation between condens­ing unit and evaporator may require oil charge adjustment (Table 7).
Table 7: Oil Charge Adjustment
UNIT MODEL
(TONS)
1 - 1 1/2 0.25
2 - 5 0.5
*Use either Texaco WF-32 (formerly cappella B) or Suniso 3G-S oil.
ADDITIONAL OIL CHARGE PER EACH ADDI-
TIONAL 10’ OF LINE (OZ)*
Page 8 IM-800
WIRING DIAGRAM - SINGLE PHASE
FAN MOTOR
COMPRESSOR
SC
Y
R
R
BK
BK
CRANKCASE HEATER IF USED
WIRING C ODE
HIGH VOLTAGE
LOW VOLTAGE
WIRE NUT
OPTIONAL START ASSIST
PU
BK
BK
OUTDOOR CONTROL BOX
BR
FACTORY
WIRING
C
R
F
HERM
Y
COMPRESSOR/FAN
CAPACITOR
START ASSIST
Y (START ASSIST IF USED)
PU
FIELD
WIRING
PU
R
Y
R
Y
WIRING FOR
FACTORY OPTIONS
BR
NOTES:
REPLACEMENT WIRE MUST BE SAME GAGE AND INSULATION THICKNESS, 105° C APPLIANCE W IRING MATERIAL.
BK
PU
BK
BK
ALT. DOUBLE
POLE CONTACTOR
T1
T2
C
L2 O N T
L2
BK
PU
R
R
T2
T1
L2
L1
CONNECT TO APPROP. CONTROL CIRCUIT HAVING MIN. 40 VA 24 VOLT
N.E.C. CLASS 2 TRANSFORMER OR FOR CERTIFIED C.S.A. INSTALLATION. USE C.S.A. CERTIFIED ENERGY LIMITED CLASS 2 TRANSFORMER.
COLOR CODE
BK R Y BL PU LTBL BR G
L1
OUTDOOR POWER SUPPLY - (SEE UNIT RATING PLATE) USE COPPER CONDUCTORS ONLY
USE L1 FOR NEUTRAL OR GROUNDED SUPPLY IF USED
EQUIPMENT GROUND
BLACK RED YELLOW BLUE PURPLE LIGHT BLUE
BROWN GREEN
A C T O
T2
R
THERMOSTAT
R
R
OUTDOOR POWER SUPPLY
COMPRESSOR MOTOR
START ASSIST
(IF USED)
THERMOSTAT FAN SWITCH
THERMOSTAT
COOL
ANTICIPATOR
BULB
THERMOSTAT ADJ. HEAT ANTICIPATOR
R
S
ON
AUTO
COOL
HEAT
CRANKCASE HEATER
(IF USED)
C
COMPRESSOR
INTERNAL OVERLOAD
G
FAN RELAY
Y
THERMOSTAT SYSTEM SWITCH
W
LOW VOLTAGE TRANSFORMER
FAN MOTOR
CAPACITOR
OFF
24V
CONTACTOR
COIL
COIL
COIL
L1
C O N T A C T O
T1
R
C
INDOOR POWER SUPPLY
IM-800 Page 9
WIRING DIAGRAM - THREE PHASE
HP
Y
BR
V
BK BK
R
Y
T3
L3
Y
BK
R
S
C
COMP
V
FC
POWER SUPPLY
MAIN
AUX
CM
IO
BR
V
BR
BK
R
(SEE RATING PLATE)
USE COPPER CONDUCTORS ONLY
R
BL
V
T1BLT2
L1CL2
BK
BK
BK
BK
CH
V
Y
CONNECT TO APPROP. CONTROL CIRCUIT HAVING N.E.C. CLASS 2 CERTIFIED C.S.A CERTIFIED ENERGY
TRANSFORMER.
COPPER CONDUCTORS ONLY
R
MIN. 40 VA. 24 VOLT
TRAMSFORMER OR FOR
INSTALLATION. USE C.S.A.
LIMITED CLASS 2
EQUIPMENT GROUND USE
COLOR CODE
BK
BLACK
R
RED
Y
YELLOW
BL
BLUE
V
VIOLET
LTBL
LIGHT BLUE
BR
BROWN
G
GREEN
O
ORANGE
W
WHITE
USE N.E.C. CLASS 2 WIRE
C
L3
T3
R
THERMOSTAT BULB
R
OUTDOOR POWER SUPPLY
L2
C
T2
2
3
COMP
THERMOSTAT FAN SWITCH
THERMOSTAT
COOL
ANTIC IPATOR
THERMOSTAT
ADJ. H EAT
ANTIC IPATOR
CH
1 CAP
ON
G
AUTO
Y
COOL
OFF
HEAT
24V
THERMOSTAT SYSTEM SWITCH
COIL
W
LOW VOLTAGE TRANSFORMER
MOTOR
CONTACTOR
COIL
FAN RELAY
COIL
L1
L1
C
C
T1
T1
P H
C
HIGH VOLTAGE LOW VOLTAGE WIRE NUT LINE SPLICE
WIRING CODE
FACTORY WIRING
FIELD WIRING
COMPONENT CODE
OUTDOOR FAN MOTOR
CM
COMPRESSOR
COMP
CONTACTOR
C
DEFROST CONTROL
DC
LOW VOLTAGE DEFROST RELAY
LDVR
CRANKCASE HEATER
CH
INTERNAL OVERLOAD
IO
LOW PRESSURE CONTROL
LP
HIGH PRESSURE CONTROL
HP
OUTDOOR THERMOSTAT (OPTIONAL)
OT
FAN CAPACITOR
FC
DEFROST THERMOSTAT
DFT
REVERSING VALVE COIL
RVC
HIGH VOLTAGE DEFROST RELAY
HVDR
CONTROLS SHOWN WITH UTILITIES IN 'ON'POSITION IN 'OFF' POSITION.
AND THERMOSTAT
INDOOR POWER SUPPLY
NOTES:
1) TO INDOOR UNIT LOW VOLTAGE TERMINAL BLOCK & INDOOR THERMOSTAT.
2) SEE INDOOR UNIT & OUTDOOR UNIT INSTALLATION INSTRUCTIONS FOR CONNECTION OF OPTIONAL OUTDOOR THERMOSTAT.
Page 10 IM-800
IM-800 Page 11
This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.mcquay.com.
www.mcquay.com • 800-432-1342
Loading...