Operation Manual
MicroTechTM U nit Ventilator Controller
Sequences of Operation
AAF-HermanN elson Classroom Unit Ventilator
Model AEQ, AED, Air Sour ce Heat Pump
Program UV1: Air Source Heat Pump with Electric Heat
OM 101-1
Group: Unit V entilator
Part No.: 106101201
Date: July 1999
Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Software ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Setpoints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Air Source Heat Pump with Electric Heat . . . . . . . . . . . 3
Description of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Occupied or Tenant Override Operating Mode . . . . . . 3
Unoccupied Operating Mode . . . . . . . . . . . . . . . . . . . . 4
Emergency Heat Mode . . . . . . . . . . . . . . . . . . . . . . . . 4
Defrost Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Discharge Air Low Limit Control . . . . . . . . . . . . . . . . . 4
Safeties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Sequence Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Introduction
This manual describes the sequences of operation for MicroTech
controlled AAF-HermanNelson unit ventilators equipped with air
source heat pump (ASHP) heating and cooling, and supplemental
electric heating. Unit ventilators with this heating and cooling
configuration will be AAF-HermanNelson model AED, AEQ.
Regardless of the AAF-HermanNelson model type, the Unit V entilator
Controller (UVC) provided with these units uses program UV1***.
For more information on the MicroTech Unit Ventilator Controller,
refer to Bulletin No. IM613, “MicroTech Unit Ventilator Controller.”
General Information
Software ID
The Unit Ventilator Controller Software must be compatible with the
unit ventilator heating and cooling configuration. The software is identified
by a program code and “software model” number printed on a small
label attached to the controller. Model AE with ASHP heating and cooling
uses program UV1***. The first wild card character defines the UVC
communication type as follows: S = stand-alone, M = master / slave,
and N = network code. The last two wild card characters denote the
software version (numeric) and revision le vel (alphabetical) respectively .
Program UV1*** comprises only one software model: MDL00.
Table 1. UVC Setpoints
Setpoint
Description Abbreviation
Occupied cooling setpoint OCS Hardware setpoint Room Setpoint -Ventilation cooling setpoint VCS Software offset (below OCS) Vent Clg Offset 2oF
Setpoints
Most UVC setpoints are either “hardware” or “software”
adjustable. Hardware adjustable means there is an on-board
potentiometer used for adjustment. Software adjustable means a
PC equipped with Monitor software and proper cable
connection is required to make an adjustment. Default software
adjustable values are shown on the sequence charts. Hardware
adjustable values shown on the charts are for example only.
Several UVC setpoints are defined by offsets relative to other
setpoints. Table 1 summarizes these setpoints and offsets.
Defined By Label
Default
Value
Occupied heating setpoint OHS` Software offset (below OCS) Occ RmT Spt Difl 6oF
Unoccupied heating setpoint UHS Hardware offset (below OHS)
Unoccupied cooling setpoint UCS Hardware offset (above OCS)
Electric heat lockout EHLO Software setpoint OAT EI Ht Lkout 20oF
Compressorized cooling lockout CCLO Not adjustable -- 59oF
Ventilation cooling lockout VCLO Software setpoint OAT Vent Clg Lkout 64oF
Ventilation cooling discharge air low limit VCLL Software setpoint DAT Vent Clg Low 55oF
DX cooling discharge air low limit DXLL Software setpoint DAT DX Clg Low 45oF
Outdoor air lockout OALO Software setpoint OALO Setpoint 35oF
Unocc Offset --
OM 101-1 / Page 2 (Rev. 7/99)
Air Source H eat Pump with Electric Heat
Description of Operation
Definitions
Control T emperature
In order to maintain more stable room temperature control, the
MicroTech Unit Ventilator Controller (UVC) uses the concept of a
“Control Temperature.” The Control Temperature is a weighted v alue
equal to 19/20 room temperature and 1/20 discharge air temperature.
Setpoint Abbreviations
OCS Occupied cooling setpoint
VCS Ventilation cooling setpoint
OHS Occupied heating setpoint
UHS Unoccupied heating setpoint
UCS Unoccupied cooling setpoint
VCLO Ventilation cooling outdoor air lockout setpoint
EHLO Electric heat outdoor air lockout setpoint
VCLL Ventilation cooling discharge air low limit setpoint
DXLL DX cooling discharge air low limit setpoint
OALO Outdoor air lockout setpoint
Software ID
Program: UV1***
Software Model: MDL00
Occupied or Tenant Override Operating Mode
The supply fan will run continually in the occupied or tenant override
operating modes.
When the UVC is first energized it will perform a self-calibration
procedure upon the OA damper actuator . The calibr ation procedure
will take approximately 5 minutes to perform during which time the
supply fan will not operate.
The UVC provides a compressor minimum on time of 2 minutes and
a minimum off time of 3 minutes.
If enabled, an outdoor air lockout setpoint has been pro vided to force
the OA damper to close when the OA temperature goes below the
OALO setpoint (software adjustable). This feature is typically used
only on valve control hydronic heat and or hydronic cool units. This
feature is disabled by default in UV Model 00.
If provided, the optional ventilation lock out feature can ov erride UVC
temperature control and keep the OA damper closed as required.
If provided, the optional exhaust fan output will energize when the
OA damper opens and de-energize when the OA damper closes.
If provided, the optional auxiliary heat output will operate a normally
open device. The auxiliary output will energize (close the device)
when the Control Temperature is abov e the OHS. The auxiliary output
will de-energize (open the device) when the Control T emperature is
o
3
F below the OHS.
The same UVC output is used for both the auxiliary heat output
feature and the exhaust f an output f eature . Therefore , both f eatures
cannot be used together.
Note: When switching from unoccupied-to-occupied mode the OA
damper will remain closed for the first 5-minutes of occupied operation.
Morning Start
If the space is cool and heating is required, the unit will operate as
described in “Heating Operation” belo w. The outdoor air (OA) damper
will remain closed until the Control Temperature rises to within 3
of the OHS setpoint. Then it will be opened to minimum position.
If the space is warm and cooling is required, the unit will operate as
described in “Cooling Operation” below. If the outdoor air is not
suitable for free cooling, the OA damper will remain closed until the
Control Temperature falls to within 3
o
F of the OCS setpoint. Then it
will be opened to minimum position.
o
Cooling Operation
Certified Drawing
When the Control Temperature is greater than the OHS setpoint and
less than the VCS setpoint, the O A damper will be held at its minimum
position setpoint (hardware adjustable). As the Control Temperature
rises and cooling becomes necessary, the UVC will decide whether
the outdoor air is suitable for free cooling by comparing the outdoor
air temperature (dry bulb) to the VCLO setpoint.
If the OA temperature is less than or equal to the VCLO setpoint,
the economizer will modulate as required to maintain the VCS
setpoint (default = 2
o
F less than OCS). The Control T emper ature will
rise if the outdoor air is too warm to satisfy the cooling load. If the
OA damper is more than 85% open, mechanical cooling will be
energized when the Control Temperature rises to the OCS setpoint.
If the OA temperature is warmer than the VCLO setpoint, mechanical
cooling will be energized when the Control Temperature rises to the
OCS setpoint. The OA damper will be held to the minimum position
setpoint, except when the OA temperature is warmer than the VCLO
setpoint and the Control Temperature is 3
o
F or more above the OCS.
In this unlikely situation, the OA damper will be closed.
Once the compressor is energized, the start-to-stop (minimum on)
timer will override normal temperature control maintaining compressor
operation for the minimum on time. The compressor will be deenergized when the Control Temperature f alls below the OCS setpoint.
Note: Regardless of the economizer state, its operation is subject
to discharge air low limit control.
Note: During normal (non-alarm) operation, the compressor will be
disabled if any of the following conditions exist:
• OA temperature less than the CCLO setpoint
• Discharge air temperature less than the DXLL setpoint
• Stop-to-start (minimum off) timer has not expired
• Emergency heat mode active
Heating Operation
When the Control Temperature is greater than the OHS setpoint
and less than the VCS setpoint, the OA damper will be held at its
minimum position setpoint.
If the Control Temperature f alls to 1
o
F greater than the OHS setpoint,
the reversing valve will be energized in preparation for mechanical
(heat pump) heating.
The compressor will be energized when the Control Temperature
falls to 1
o
F below the OHS setpoint. Once the compressor is
energized, the start-to-stop (minimum on) timer will override normal
temperature control maintaining compressor operation for the
minimum on time. The compressor will be de-energized when the
Control Temperature rises above the OHS setpoint.
Normally, supplemental electric heat is enabled when the OA
temperature drops below the EHLO setpoint. It can also be enabled
by the emergency heat, defrost cycle, or “v ent cooling” discharge air
low limit functions. If the electric heat is enabled and the Control
Temperature drops to 2
o
F below the OHS setpoint, the two or three
(optional) stages of electric heat will be energized as required. A
“stage-up” interstage dela y timer (default = 30 seconds) must expire
before each subsequent stage is energized. When the Control
Temperature rises to 1
o
F below the OHS setpoint, the electric heat
stages will be de-energized using a “stage-down” interstage delay
timer (default = 30 seconds).
F
The OA damper will maintain its minimum position when the Control
Temperature is within 3
o
F of the OHS. If the Control Temperature
falls to 3oF or more below the OHS, the OA damper will be closed.
When heating is no longer required and the Control Temperature
rises to 2
energized. Note that in addition to the 1
o
F above the OHS setpoint, the re v ersing valve will be de-
o
F offset between the
compressor and reversing v alve de-energization points, a time dela y
OM 101-1 / Page 3 (Rev. 7/99)