McQuay 5EJ User Manual

Catalog
McQuay® Water Cooling & Evaporator Coils
Types HI-F5 & E-F5
411-7
SelectTOOLSTM for Contractor Coils
McQuay offers a wide variety of standard fin spacings, row and circuiting combinations. For optimum coil selection, McQuay's SelectTOOLS gram makes it easy to select the most economical standard or special application coil to meet your job requirements.
Contact your local McQuay representative for a coil selection that meets the most exacting specification.
TM
for Contractor Coils selection pro-
Contents
SelectTOOLSTM..........................................................3
ARI certification................ ... ... .... ... ... ... .... ...................3
Nomenclature.............................................................5
Standard availability chart.......... ... ... ..........................5
Circuiting arrangements.............................................6
Design features..........................................................7
Coil selection..............................................................8
Application recommendations, water cooling coils.....8
HI-F5 & E-F5 water cooling coils .............................10
General formulas ............................................. .... ... .10
HI-F5 water coil capacity data ...........................11, 12
HI-F5 coils air pressure drop....................................13
ARI Certification
McQuay® water cooling and evap­orator coils are certified in accor­dance with the forced circulation air cooling and air heating coil cer­tification program, which is based on ARI Standard 410.
Note: Special application coils may be outside the scope of ARI Standard 410.
E-F5 water coil capacity data........................... 14, 15
E-F5 coils air pressure drop................................... 16
Water pressure drop, HI-F5 & E-F5....................... 17
Dimensional data - water coils .... ... ... ... ... .... ... ... 18-20
HI-F5 & E-F5 evaporator coils............................... 21
Capacity reduction applications............................. 21
Evaporator capacity data................................. 22, 23
Distributor and suction connection size .......... 24, 25
Dimensional data - evaporator coils ........... ... ... ..... 26
Conversion of air volume to standard air....... ... ... .. 31
Total heat (enthalpy).............................................. 32
Engineering guide specifications........................... 33
“McQuay" and "HI-F" are registered trademarks of McQuay International, Minneapolis, MN.
The McQuay HI-F fin surface is covered by U.S. Patent No. 3,645,330.
Copyright ©2006 McQuay International. All rights reserved throughout the world.
Bulletin illustrations cover the general appearance of McQuay International products at time of publication
and we reserve the right to make changes in design and construction at any time without notice.
McQuay Catalog 411-7 3
A pioneer in corrugated fin de velopment
HI-F Means High Efficiency
A principal factor governing fin heat transfer efficiency is the boundary layer film of air adhering to any fin surface. This boundary layer insulates the fin, severely reducing the rate of heat exchange. The advanced rippled-corrugated HI-F design creates a state of continuous turbulence which effectively reduces the boundary layer formation. The exclusive rippled edge instantly deflects the incoming air to create initial turbulence. A succession of corrugations across the fin depth, in conjunc­tion with the staggered tubes, increases the turbulating effect and eliminates the "dead spots" behind the tubes. In this manner, the HI-F design establishes a high standard in heat transfer efficiency yielding sharply increased performance. The rippled fin edge also strengthens the fin edge and pro­vides a pleasing overall appearance.
E-F Means Energy Efficient
The term "energy efficient," which is used to describe how well a system utilizes energy, has become a common expres­sion in the HVAC industry. With costs of energy rising, the need for cutting operating expenses is apparent. Lowering the air pressure drop across the face of the coil will reduce the fan brake horsepower requirement and fan motor electrical demand. The need to cut operating energy expenses is met by the E-F fin surface. The smoother fin design of the E-F surface results in lower operating costs over the life of the equipment.
Nomencla ture
COIL TYPE
Water: 5M, 5W Evaporator: 5E
CIRCUITING Water:
H = 1/2 Serpentine L = 3/4 Serpentine S = 1 Serpentine M = 1-1/2 Serpentine D = 2 Serpentine
Evaporator:
N=Normal F = Face Control R = Row Control J = Interlaced K = Interlaced Face Control
Staggered Tube Design For High Performance
The more moving air in contact with the tubes in the coil, the more performance obtained from the total available surface. The staggered tube design exposes the tubes to more mov­ing air than the in-line design. The geometry of the staggered tube design also allows the rows to be spaced closer together. This results in a more compact coil providing higher capacities.
5W S - 10 06 C - 18 x 45
FINNED LENGTH (INCHES) FIN HEIGHT (INCHES) FIN DESIGN
C = HI-F5 B = E-F5
ROWS DEEP ( 02, 03, 04, 05, 06, 08, 10, 12) FINS PER INCH
(06, 07, 08, 09, 10, 11, 12, 13, 14)
4 McQuay Catalog 411-7
Standard Availability Chart
COIL TYPE CHILLED WATER EVAPORATOR
COIL MODEL 5MH 5MS 5WH 5WL 5WS 5WM 5WD 5EN 5EF 5ER 5EJ 5EK
SERPENTINE CIRCUIT 1/2 1 1/2 3/4 1 1-1/2 2 Normal Face Row Interlaced
ROWS 2
CONNECTION LOCATION Same End Except 5WS 3,5 Row, 5WD 6,10 Row Same End
FIN HEIGHT 3" INCREMENT 12-54 12-54 15-54
FINNED LENGTH 12-141 12-141
FIN TYPE
ALUMINUM
FINS
COPPER
SPACING
(FPI)
DIAMETER 5/8 5/8
FACE C/C 1.5 1.5
TUBING
COPPER
HEADERS STANDARD MAT'L** Copper Tubing Copper Tubing
MAXIMUM STD.
OPERATING LIMITS
HI-F zzzzzzz z z zz z
E-F zzzzzzzz z z z z .0075 .0095 zzzzzzzz z z z z
.006 zzzzzzz z z z z z .0075 zzzzzzzz z z z z .0095
.020*
.025 zzzzzzz z z z z z
.035 zzzzzzz z z z z z
.049 zzzzzzz z z z z z
P 250 psig 250 psig T 300°F 300° F
zzzzzzzz z z z z
zzzzzzzz z z z z
zzzzzzzz z z z z
3,4,5,6, 8,10,12
6,7,8,9,10,11,12,13,14 6,7,8,9,10,11,12,13,14
4,5,6 4,6,8
8,10,12 10,12
2,3,4,5
6,8,10
6 3,4,6,8 4,8
z Feature Available * .020 is a nominal tube thickness ** Optional header materials are available, consult your representative
Flexibility
Along with the standard offerings, optional materials and special configurations are provided to meet many different needs. Extra long finned lengths, intermediate tube supports, along with a wide variety of tube wall and fin thicknesses are available. Casings can be constructed of heavy steel, aluminum, stainless steel or copper. Optional connection materials such as steel, Monel, red brass or copper (sweat) are offered along with butt-weld or flange type connections. Coil coatings are phenolic or Electro Fin. These are just a few of the options and specials that can be provided. Consult your local representative for your special coil needs.
*Note: Special application coils may be outside the scope of ARI standard 410.
McQuay Catalog 411-7 5
Circuiting arrangements
Chilled water circuitings
5 standard serpentine circuitings
Counterflow water circuits
Unique or universal hand of connection
5WH
1/2 Serpentine (H)
5WL
3/4 Serpentine (L)
1 (single) Serpentine (S)
Evaporator coil circuitings
NOTE: See page 24 for exact number and location of coil connections.
5EN
NORMAL
5WS
5ER
ROW CONTROL
5WM
1-1/2 Serpentine (M)
2 (double) Serpentine (D)
5WD
5EF
FACE CONTROL
6 McQuay Catalog 411-7
5EJ, 5EK INTERLACED (5EJ SHOWN)
Design features
5E, 5M, 5W coils
1. HEADERS - Extra-heavy seamless copper tubing. Tube
holes are intruded to provide the maximum brazing sur­face for added strength. Header end caps are heavy­gauge, die-formed copper. Cupro-nickel headers and Monel end caps are available for special applications.
2. CONNECTIONS - Unique hand or universal connections can be provided. Connection type must be specified. Water Coil Connections: Steel male pipe supply and return connections. Other materials available on request (red brass connections recommended on type 5W coils when used with non-ferrous piping). Evaporator Coil Connections: Male sweat type. Liquid connections are brass and suction connections are copper.
3. BRAZING - All joints are brazed with copper brazing alloys.
4. PRIMARY SURFACE - Round seamless copper tubes on 1-1/2" centers. Cupro-nickel tubes are recommended for applications where high acid or sand content tends to be corrosive or erosive.
5. SECONDARY SURF ACE - HI-F or E-F rippled aluminum or copper die-formed plate type fins.
General
VENTS & DRAINS - Furnished on all water coils. TESTS - Complete coil tested leak free under warm water
containing special wetting agent at 315 psig air pressure for 5W, 5M and 5E coils.
OPERATING CONDITIONS - Standard coils are suitable for use up to 250 psig and temperatures up to 300° F for 5W, 5M and 5E coils. Special high pressure construction is available for 5W coils (consult factory).
5A. FIN COLLARS - Full drawn to completely cover the
tubes for maximum heat transfer and to provide accurate control of fin spacing.
6. CASING - Die-formed, heavy-gauge, continu ous galva­nized steel with reinforced mounting flanges. (Other materials available on request.) Intermediate tube sheets position the core assembly to help prevent dam­age in shipment.
McQuay Catalog 411-7 7
Coil Selection
General Considerations
The cooling process should always be plotted on a psychro­metric chart to be sure that desired psychrometric changes are feasible. When selecting a coil, it should be remembered that if the required leaving wet bulb temperature is attained, the total load is satisfied and vice versa. Also, when the required leav­ing dry bulb temperature is met, the sensible load require­ment is satisfied. A coil must meet both the total and sensible load requirement in order to achieve the conditions desired in the space to be cooled. Normally, the total load capacity is checked first. However, the leaving dry bulb should always be checked. When the sensible to total load ratio (S/T ratio) is low, the coil selection is normally controlled by the total load even though the sensible cooling capacity may exceed the requirement. In some cases, if the leaving dry bulb temperature is too low, reheat may be required. When the S/T ratio is high, the coil selection is normally con­trolled by the sensible cooling even though the total capacity may exceed that required. If the total capacity far exceeds the requirement, a recheck on the system should be made to be sure sufficient system capacity is available.
HI-F5 versus E-F5
Two different corrugated coil surfaces are offered to provide the most economical coil for a given application.
Normal cooling coil face velocities range from 300 to 700 FPM. For most applications, 500 to 600 FPM is recom­mended. See the individual air pressure drop curves (pages 11 & 14). to determine under what conditions moisture carry­over might be a consideration. Water velocity in the tubes of approximately 3 to 6 FPS is desirable to attain high heat transfer rates with a reasonable water pressure drop. Water velocity above 8 FPS may cause erosion in copper tube coils. Cooling coils should not normally exceed 54" fin height as the condensate draining from the top portion of the coil tends to load up on the lower portion of the coil and a significant reduction in airflow and performance may result. Where the fin height exceeds 54", we recommend two or more coils banked one above the other and installed in accordance with the recommendations shown below. Cooling coils are normally selected to have a finned length of three to four times the fin height for economy. Coils of several different face dimensions are usually available to meet the required face area.
Type Tube
Dia.
HI-F5 5/8” HI-F
E-F5 5/8” E-F
Fin Type Application
Provides highest heat transfer rate for a given amount of surface.
Hi-Efficiency
Smoother fin corrugation than the HI-F5 results in a lower air pressure drop and lower fan
Energy
Efficient
BHP requirements. The cost of additional surface can be amortized by the KW savings.
Application recommendations, water cooling coils
1. Piping should be in accordance with accepted industry standards.
2. When drainable coils are desired, tubes should be installed in a horizontal position using a spirit level. If the tubes cannot be installed level, special drain headers are available on request.
3. Coils are unique for either right- or left-hand airflow. The coil hand must be specified. CONNECT THE WATER SUPPLY T O THE CONNECTION ON THE AIR LEAVING SIDE AND THE WATER RETURN TO THE CONNEC­TION ON THE AIR ENTERING SIDE.
4. When cooling coils are banked two or three hi gh, a drain gutter should be installed on the air leaving side of each coil to collect the condensate. On high latent installations, the condensate draining from top coils would load the lower coils with condensate and a reduction in airflow and performance may result. All individually installed water cooling coils and the bottom coils of all cooling coi l banks should be mounted in drain pans extending at least 10 inches from the leaving air edge of the coil.
5. When fresh air and return air are to be cooled by a water coil, care should be exercised in the design of the duct­work to provide thorough mixing before the air enters the
coil. If large quantities of fresh air below 40°F are intro­duced into the system, steam distributing coils should be installed in the fresh air duct or mixing plenum as pre­heaters to raise the air temperature to a minimum of 40°F. This holds true unless the wate r coil is drained and filled with antifreeze. Even though the coil is drained, there may be enough water remaining to cause freeze damage. The coil should be drained and flushed with antifreeze. On any system that has fresh air introduced in the winter season, all possible precaution must be taken to prevent freezing.
6. Control of water cooling coils can be accomplished by two-position control valves, modulating valves, three-way valves, face and bypass dampers, or a combination of these controls. Follow the recommendations of the con­trol manufacturer regarding types, sizing and locations.
7. The pipe size for the system must be selected on the basis of the head (pressure) available from the circulating pump. It is recommended that the velocity should not generally exceed 8 feet per second and that the pressure drop should be approximately 3 feet of water per 100 feet of pipe.
8 McQuay Catalog 411-7
T able 1: Standard water coil circulating (number of tubes fed) - for calculating water velocity for types 5W and 5M coils
TYPE ROWS
5MS 2 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 5MH 2 456789101112261415161718 5WH 3, 4, 5, 6, 8, 10, 12456789101112131415161718 5WL 3, 4, 5, 6, 8, 10, 12 6 7 9 10 12 13 15 16 18 19 21 22 24 25 27
5WS 3, 4, 5, 6, 8, 10, 128 10121416182022 24 262830323436 5WM 4, 5, 6, 8, 10, 12 12 15 18 21 24 27 30 33 36 39 42 45 48 51 54 5WD 4, 6, 8, 10, 12 16 20 24 28 32 36 40 44 48 52 56 60 64 68 72
12 15 18 21 24 27 30 33 36 39 42 45 48 51 54
FIN HEIGHT (INCHES)
Table 2: Coil sizes face area in square feet
FIN HEIGHT
12 15 18
21 24 27
30 33 36
39 42 45
48 51 54
FIN HEIGHT
12 15 18
21 24 27
30 33 36
39 42 45
48 51 54
12 15 18 21 24 30 36 42 48 54 60 66
1.00 1.25
72 78 84 90 96 102 108 114 120 129 135 141
6.0
7.5
9.0
10.5
12.0
13.5
15.0
16.5
18.0
19.5
21.0
22.5
24.0
25.5
27.0
1.56
6.5
8.1
9.7
11.4
13.0
14.6
16.2
17.9
19.5
20.1
22.7
24.4
26.0
27.6
29.2
1.60
1.87
2.25
7.0
8.7
10.5
12.2
14.0
15.7
17.5
19.2
21.0
22.7
24.5
26.2
28.0
29.7
31.4
1.75
2.19
2.62
3.06 3.50
7.5
9.4
11.2
13.1
15.0
16.9
18.7
20.6
22.5
24.4
26.2
28.1
30.0
31.8
33.8
FINNED LENGTH – FL (INCHES)
2.00
2.50
3.00
4.00
8.0
10.0
12.0
14.0
16.0
18.0
20.0
22.0
24.0
26.0
28.0
30.0
32.0
34.0
36.0
2.50
3.12
3.75
4.37
5.00
5.62
FINNED LENGTH – FL (INCHES)
8.5
10.6
12.7
14.9
17.0
19.1
21.2
23.4
25.5
26.7
29.7
31.9
34.0
36.1
38.2
3.00
3.75
4.50
5.25
6.00
6.75
7.50
8.25
9.00
9.0
11.2
13.5
15.7
18.0
20.2
22.5
24.7
27.0
29.2
31.5
33.7
36.0
38.2
40.4
3.50
4.87
5.25
6.12
7.00
7.87
8.75
9.62
10.50
11.37
12.25
9.5
11.9
14.2
16.6
19.0
21.4
23.7
26.1
28.5
30.9
33.2
35.6
38.0
40.4
42.8
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
13.0
14.0
15.0
16.0
17.0
10.0
12.5
15.0
17.5
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
42.5
45.0
4.5
5.6
6.7
7.9
9.0
10.1
11.2
12.4
13.5
14.6
15.7
16.8
18.0
19.1
20.2
10.7
13.4
16.1
18.8
21.5
24.1
26.8
29.6
32.2
34.9
37.6
40.3
43.0
45.7
48.2
5.0
6.2
7.5
8.7
10.0
11.2
12.5
13.7
15.1
16.2
17.5
18.7
20.0
21.2
22.4
11.2
14.0
16.9
19.7
22.5
25.3
28.0
30.9
33.8
36.5
39.4
42.2
45.0
47.8
50.6
5.5
6.9
8.2
9.6
11.0
12.4
13.7
15.1
16.5
17.9
19.2
20.6
22.0
23.3
24.8
11.7
14.7
17.6
20.5
23.5
26.4
29.5
32.3
35.2
38.2
41.0
44.1
47.0
49.9
52.8
NOTE: In addition to the standard finned l engths listed above, any required finned length can be supplied.
McQuay Catalog 411-7 9
HI-F5 & E-F5 water cooling coils
HI-F5 and E-F5 water cooling coils are designed for use with chilled or well water on comfort cooling, process, dehumidify­ing and special applications. All water cooling coils have vents and drains to aid drainability. 5W Water Cooling Coils are designed for general purpose cooling. All 5W coils have heavy-gauge seamless drawn cop­per tube headers with carbon steel connections. This proven header design can lengthen coil life by providing necessary header flexibility to compensate for normal expansion and contraction during operation. Intermediate drain headers are available for coils that cannot be installed level.
General Formulas
TOTAL BTUH:
Total BTUH = 4.5 X SCFM X (Total Heat Ent. Air ­ Total Heat Lvg. Air)
Where: 4 .5 = Density Std. Air x Min. / hr. Density Std. Air = .075 lbs / cu. ft. Minutes/hr. = 60
TOTAL BTUH:
Total BTUH = 500 x GPM x (Lvg. Water Temp. ­ En t. Water Temp.)
Where: 500 = lbs. / gal. x min. / hr. x Specific heat water Lbs. / gal. = 8.33 Min. / hr. = 60 Specific Heat Water = 1
SENSIBLE BTUH:
Sensible BTUH = 1.09 x SCFM x (Ent. Air DB -Lvg. Air DB)
Where: 1.09 = (Specific heat of air at 70° F) x (Min/hr.) x Density Std. Air Specific heat of air = .242 at 70° F Min./hr. = 60 Density Std. Air = .075 lbs. / cu ft.
Example water cooling coil rating
The capacity data tables in this catalog rate a given coil at the ARI conditions. For example, rate the following coil:
Coil model........................... ... ... .... ... ... ... ... 5WS0804C
Coil size.................. ... .... ... ... ... ............................24x48
Entering dry bulb..................................................80°F
Entering wet bulb .................................................67°F
Entering water temperature..................................45°F
Airflow ...........................................500 feet per minute
Water velocity...................................4 feet per second
On page 9, find the table for 4-row coils, 24 x 48 inches. Fol­low the 5WS, 1 Serpentine column down until you reach the 08 fpi (8 fins per inch) row. This coil will provide 138.52 MBH with 57.5°F leaving dry bulb temperature and 56.0°F leaving wet bulb temperature.
WATER VELOCITY:
5/8" Tubes: Water Velocity FPS = No. of Tubes Fed
FACE AREA: F.A . =
Face Velocity (FPM)
FACE VELOCITY: F.V . =
Face Area (Sq. Ft.)
SENSIBLE TOTAL RATIO: S/T Ratio. =
Total BTUH
1.07 X GPM
SCFM
SCFM
Sensible BTUH
MBH PER SQUARE FOOT OF FACE AREA:
MBH / Sq. Ft. = Face Area (Sq. Ft. ) x 1000
Total BTUH
Next, calculate the coil GPM:
FPS x No. Circuits = GPM
1.07 (5/8 tubes) = 60 GPM
1.07
Where: FPS = Feet per second water velocity
Circuits = Number of tubes fed with 1.5” tube centers. 24” high coil /1.5” = 16 tubes; from page 7, table 1. single serpentine feeds all 16 tubes.)
Find the water and air pressure drops by following the exam­ples on pages 15 and 11 respectively. For our example, coil rating the water pressure drop equals 5.4 feet and the air pressure drop equals 0.68 inches w.g.
4 x 16
To select a water cooling coil to meet specific performance requirements, contact your local representative.
10 McQuay Catalog 411-7
HI-F5 5/8 water cooling ari coil capacity data
45° F Entering Water Temperature 500 FPM Air Velocity Table 3.
FPI
MBH LVG. DB / WB MBH LVG. DB / WB MBH LVG. DB / WB MBH LVG. DB / WB MBH LVG. DB / WB
6 69.09 67.9 / 61.7 72.58 67.6 / 61.5 95.09 63.6 / 59.7 99.12 63.3 / 59.3 101.38 63.1 / 59.1 7 74.89 66.7 / 61.3 79.35 66.3 / 60.9 101.88 62.4 / 59.1 106.34 62.0 / 58.7 108.99 61.7 / 58.5 8 79.99 65.6 / 60.9 85.10 65.2 / 60.5 107.94 61.3 / 58.6 113.20 60.8 / 58.2 115.53 60.6 / 58.0 9 84.75 64.6 / 60.5 89.95 64.2 / 60.1 113.36 60.3 / 58.1 118.86 59.8 / 57.7 121.80 59.6 / 57.4
10 88.84 63.8 / 60.2 94.74 63.2 / 59.7 118.23 59.5 / 57.7 123.96 59.0 / 57.2 127.01 58.7 / 57.0
11 92.58 63.0 / 59.9 98.87 62.4 / 59.3 122.62 58.8 / 57.3 128.58 58.3 / 56.8 131.73 58.0 / 56.6 12 96.01 62.3 / 59.6 102.68 61.7 / 59.0 126.60 58.2 / 57.0 132.76 57.6 / 56.5 136.01 57.3 / 56.2 13 98.83 61.8 / 59.4 106.20 61.0 / 58.7 130.21 57.7 / 56.7 136.57 57.1 / 56.1 139.92 56.8 / 55.8 14 101.77 61.2 / 59.1 109.44 60.5 / 58.5 133.50 57.2 / 56.4 140.05 56.6 / 55.8 143.48 56.3 / 55.5
FPI
MBH LVG. DB / WB MBH LVG. DB / WB MBH Lvg. DB / WB MBH Lvg. DB / WB MBH Lvg. DB / WB
6 114.60 60.7 / 58.0 120.03 60.2 / 57.6 123.16 59.9 / 57.3 126.17 59.6 / 57.0 127.67 59.5 / 56.9 7 122.00 59.5 / 57.4 128.54 58.9 / 56.8 131.46 58.6 / 56.6 134.82 58.3 / 56.3 136.50 58.1 / 56.1 8 128.48 58.4 / 56.8 135.37 57.8 / 56.2 138.52 57.5 / 56.0 142.28 57.1 / 55.6 144.11 57.0 / 55.5 9 134.19 57.6 / 56.3 141.40 56.9 / 55.7 145.22 56.5 / 55.4 148.83 56.2 / 55.0 150.52 56.0 / 54.9
10 139.25 56.8 / 55.9 147.02 56.1 / 55.2 150.55 55.8 / 54.9 154.78 55.4 / 54.5 156.52 55.2 / 54.3
11 144.09 56.2 / 55.5 151.34 55.5 / 54.8 155.61 55.1 / 54.4 159.79 54.7 / 54.0 161.91 54.5 / 53.8 12 147.84 55.7 / 55.1 155.82 54.9 / 54.4 160.01 54.5 / 54.0 164.27 54.1 / 53.6 166.43 53.9 / 53.4 13 151.37 55.2 / 54.8 159.68 54.4 / 54.0 163.95 54.0 / 53.6 168.30 53.6 / 53.2 170.49 53.4 / 53.0 14 154.69 54.8 / 54.5 163.15 54.0 / 53.7 167.51 53.6 / 53.3 171.93 53.2 / 52.9 174.15 53.0 / 52.7
FPI
MBH LVG. DB / WB MBH LVG. DB / WB MBH Lvg. DB / WB MBH Lvg. DB / WB
6 130.50 58.4 / 56.7 137.28 57.8 / 56.1 141.19 57.5 / 55.7 144.98 57.1 / 55.4 7 138.17 57.3 / 56.0 146.35 56.5 / 55.3 149.71 56.2 / 55.0 153.92 55.8 / 54.6 8 144.95 56.3 / 55.4 152.90 55.6 / 54.7 157.48 55.1 / 54.2 161.50 54.8 / 53.9
9 150.54 55.5 / 54.9 158.98 54.7 / 54.1 163.38 54.3 / 53.7 167.98 53.9 / 53.3 10 155.77 54.9 / 54.4 164.64 54.0 / 53.6 169.25 53.6 / 53.2 174.06 53.1 / 52.7 11 160.05 54.4 / 54.0 169.30 53.5 / 53.1 174.04 53.0 / 52.7 178.80 52.6 / 52.2 12 164.01 53.9 / 53.6 173.48 53.0 / 52.8 178.29 52.5 / 52.3 183.08 52.1 / 51.8 13 167.54 53.5 / 53.3 177.19 52.6 / 52.4 182.06 52.1 / 51.9 186.87 51.7 / 51.5 14 170.71 53.2 / 53.0 180.51 52.3 / 52.1 185.41 51.8 / 51.6 190.21 51.3 / 51.1
FPI
MBH LVG. DB / WB MBH LVG. DB / WB MBH Lvg. DB / WB MBH Lvg. DB / WB MBH Lvg. DB / WB
6 143.87 56.7 / 55.5 152.24 55.9 / 54.7 155.85 55.6 / 54.4 160.68 55.1 / 54.0 162.87 54.9 / 53.7 7 151.49 55.6 / 54.8 160.61 54.7 / 54.0 164.77 54.3 / 53.6 169.22 53.9 / 53.2 171.92 53.7 / 52.9 8 158.05 54.7 / 54.2 167.54 53.8 / 53.3 172.44 53.4 / 52.9 176.95 52.9 / 52.4 179.40 52.7 / 52.2 9 163.73 54.0 / 53.7 173.55 53.1 / 52.7 178.54 52.6 / 52.3 183.49 52.1 / 51.8 185.62 51.9 / 51.6
10 168.67 53.5 / 53.2 178.74 52.5 / 52.3 183.78 52.0 / 51.8 188.74 51.5 / 51.3 191.12 51.3 / 51.1
11 173.00 53.0 / 52.8 183.25 52.0 / 51.8 188.31 51.5 / 51.3 193.20 51.1 / 50.9 196.05 50.8 / 50.6 12 176.81 52.6 / 52.4 187.18 51.6 / 51.4 192.22 51.1 / 50.9 197.56 50.6 / 50.4 200.04 50.4 / 50.2 13 180.20 52.3 / 52.1 190.63 51.3 / 51.1 195.99 50.8 / 50.6 201.07 50.3 / 50.1 203.52 50.0 / 49.8 14 183.21 52.0 / 51.8 193.66 51.0 / 50.8 199.10 50.5 / 50.3 204.14 50.0 / 49.8 206.56 49.7 / 49.5
FPI
MBH LVG. DB / WB MBH LVG. DB / WB MBH Lvg. DB / WB MBH Lvg. DB / WB MBH Lvg. DB / WB
6 164.44 54.1 / 53.6 174.83 53.1 / 52.6 179.48 52.7 / 52.2 184.69 52.2 / 51.7 187.21 51.9 / 51.4 7 171.98 53.2 / 52.9 182.70 52.2 / 51.9 187.88 51.7 / 51.4 193.09 51.2 / 50.9 195.71 50.9 / 50.6 8 178.31 52.5 / 52.3 189.18 51.4 / 51.2 194.78 50.9 / 50.7 199.77 50.4 / 50.2 202.36 50.1 / 49.9 9 183.68 52.0 / 51.8 194.53 50.9 / 50.7 200.29 50.4 / 50.2 205.52 49.8 / 49.6 207.72 49.6 / 49.4
10 188.26 51.5 / 51.3 199.46 50.4 / 50.2 204.89 49.9 / 49.7 209.88 49.4 / 49.2 212.71 49.1 / 48.9
11 192.22 51.1 / 50.9 203.42 50.0 / 49.8 208.71 49.5 / 49.3 214.07 49.0 / 48.8 216.56 48.7 / 48.5 12 195.64 50.8 / 50.6 206.80 49.7 / 49.5 212.30 49.1 / 48.9 217.20 48.6 / 48.4 219.44 48.4 / 48.2 13 198.60 50.5 / 50.3 209.62 49.4 / 49.2 215.27 48.8 / 48.6 219.92 48.4 / 48.2 222.41 48.1 / 47.9 14 201.15 50.3 / 50.1 212.49 49.1 / 48.9 217.67 48.6 / 48.4 222.54 48.1 / 47.9 224.74 47.9 / 47.7
80° F/67° F Entering Air Temperature 4 Feet Per Second Water Velocity
2-ROW - 24" X 48" FACE AREA 3-ROW - 24" X 48" FACE AREA
5MH 1/2 SERPENTINE 5MS 1 SERPENTINE 5WH 1/2 SERPENTINE 5WL 3/4 SERPENTINE 5WS 1 SERPENTINE
4-ROW - 24" X 48" FACE AREA
5WH 1/2 SERPENTINE 5WL 3/4 SERPENTINE 5WS 1 SERPENTIN E 5WM 1-1/2 SERPENTINE 5WD 2 SERPENTINE
5-ROW - 24" X 48" FACE AREA
5WH 1/2 SERPENTINE 5WL 3/4 SERPENTINE 5WS 1 SERPENTINE 5WM 1-1/2 SERPENTINE
6-ROW - 24" X 48" FACE AREA
5WH 1/2 SERPENTINE 5WL 3/4 SERPENTINE 5WS 1 SERPENTINE 5WM 1-1/2 SERPENTINE 5WD 2 SERPENTINE
8-ROW - 24" X 48" FACE AREA
5WH 1/2 SERPENTINE 5WL 3/4 SERPENTINE 5WS 1 SERPENTINE 5WM 1-1/2 SERPENTINE 5WD 2 SERPENTINE
McQuay Catalog 411-7 11
Loading...
+ 25 hidden pages