McQuay PTAC 106018561, 106018561 Installation Manual

Installation & Maintenance Data
Incremental® Comfort Conditioners
Suite II
®
With Top Mounted
Hydronic Heat Section
IM 422-4
©1999 AAF–McQuay Incorporated
IM 422-4 / Page 1 (Rev. 5/99)
Table of Contents
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Wall Opening Requirements . . . . . . . . . . . . . . . . . . . . . . 3
Wall Sleeve Installation . . . . . . . . . . . . . . . . . . . . . . . . 4–6
Panel Wall With Factory Louver . . . . . . . . . . . . . . . . . . 4
Panel Wall With Continuous Louver . . . . . . . . . . . . . . . 5
Frame and Brick Construction . . . . . . . . . . . . . . . . . . . 6
Heat Section Installation. . . . . . . . . . . . . . . . . . . . . . . . . . 7
Coil Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Steam Coils. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Hot Water Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Anchoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Installing Louvers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Installation of Cooling Chassis . . . . . . . . . . . . . . . . . . . . . 8
Adjusting Temperature Limiting Device . . . . . . . . . . . . . . 9
Electrical Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Installing Room Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Equipment Start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Scheduled Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . 10
Recommended Spare Parts . . . . . . . . . . . . . . . . . . . . . . 11
Refrigeration Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Troubleshooting Chart . . . . . . . . . . . . . . . . . . . . . . . 12–13
Approximate Shipping Weights . . . . . . . . . . . . . . . . . . . 13
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14–15
Normally Closed Valve (Steam) . . . . . . . . . . . . . . . . . 14
Normally Open Valve (Hot Water) . . . . . . . . . . . . . . . 15
Installation
The installation of this equipment shall be in accordance with the regulations of authorities having jurisdiction and all applicable codes. It is the responsibility of the installer to determine and follow the applicable codes. Sheet metal parts, self­tapping screws, clips, and such items inherently have sharp edges, and it is necessary that the installer exercise caution. This equipment is to be installed only by an experienced installation company which employs trained personnel.
Inspection
When the equipment is received, all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. All units should be carefully inspected for damage when received. If any damage is noticed, the carrier should make the proper notation on the delivery receipt acknowl­edging the damage. The carrier should also fill out a Carrier Inspection Report. The AAF–McQuay Incorporated Traffic De­partment should then be notified.
The unit nameplate should be checked to make sure the
voltage agrees with the power supply available.
This unit is designed and built for through-the-wall installa-
Figure 1. Exploded view of complete unit
tion in either new or existing buildings. The self-contained refrigerant system delivers cooling to the desired space. Heating is accomplished with a top mounted hydronic heating coil.
Each conditioner consists of the following components:
1. Cooling Chassis — Shipped separate in a single carton.
2. Wall Sleeve — Shipped separate in a single carton or in a multi-pack of 15.
3. Hydronic Heat Section — Shipped in a separate carton.
4. Outdoor Louver — Shipped in a separate carton.
5. Room Cabinet — Shipped in a separate carton with kickplate attached.
IM 422-4 / Page 2 (Rev 5/99)
WARNING
!
Residential and institutional cleaning compounds can cause permanent damage to the packaged terminal unit. To avoid damage to unit controls and heat transfer surfaces, do not spray cleaning compounds onto the discharge grille, return air opening, or unit controls. Normal cleaning can be accomplished by wiping the unit surface with a damp cloth. When using cleaning compounds on carpets, floors or walls, turn the unit off to avoid drawing potentially damaging vapors into the package terminal unit.
Wall Opening Requirements
Before installing the unit, check the wall opening to be sure the wall sleeve will slide into the opening unobstructed. For masonry walls, a lintel must be used to provide support over
each opening. The rough opening should measure 161⁄4" (413mm) high x 421⁄4" (1073mm) wide. The opening must be a minimum of 3" (76mm) above the finished floor (including carpeting).
42"
(1069mm)
5"
(127mm)
Note: Electrical rough-in should be located behind kickplate
(removable front) and below wall sleeve.
11⁄2"
(38mm)
191⁄2"
(495mm)
3"
(76mm) Min.
3"
(76mm)
Wall Sleeve
52" (1320mm)
Removable Cabinet
Front Panel
52" (1320mm)
Wall Space For Piping Rough-in (Typ. R.H. & L.H.)
Kickplate (Removable Front)
31⁄2" (89mm)
1
2" (13mm)
11⁄4" (32mm) (Architectural)
Cabinet
Floor Space For Piping Rough-in (Typ. R.H. & L.H.)
2" (51mm)
7
8"
(22mm)
11⁄4" RECESS FOR ARCHITECTURAL LOUVER
“A” – IN. (MM) “B” – IN. (MM) “C” – IN. (MM)
ROOM CABINET WALL SLEEVE WALL THICKNESS
3
4 (451) 133⁄4 (349) 53⁄4–63⁄4 (146–171)
17
3
4 (425) 133⁄4 (349) 63⁄4 –73⁄4 (171–197)
16
3
15
4 (400) 133⁄4 (349) 73⁄4 –83⁄4 (197–222)
3
4 (375) 133⁄4 (349) 83⁄4 –93⁄4 (222–248)
14
3
4 (349) 133⁄4 (349) 93⁄4 –103⁄4 (248–273)
13
3
12
4 (324) 133⁄4 (349) 103⁄4 –113⁄4 (273–298)
3
4 (298) 133⁄4 (349) 113⁄4 –123⁄4 (298–324)
11
3
4 (273) 133⁄4 (349) 123⁄4 –133⁄4 (324–349)
10
3
10
4 (273) 143⁄4 (375) 133⁄4 –143⁄4 (349–375)
3
4 (273) 153⁄4 (400) 143⁄4 –153⁄4 (375–400)
10
3
4 (273) 163⁄4 (425) 153⁄4 –163⁄4 (400–425)
10
3
10
4 (273) 173⁄4 (451) 163⁄4 –173⁄4 (425–451)
Standard Size Wall Sleeve
Wall
Thickness
“C”“A”
11⁄4 " (32mm)
27⁄8" (67mm)
16"
(406mm)
7
8" (22mm)
51⁄2"
(140mm)
15⁄16"
(33mm)
(232mm)
15⁄8"
(41mm)
“B”91⁄8"
3" (76mm) Min. Kickplate Height
IM 422-4 / Page 3 (Rev. 5/99)
Wall Sleeve Installation — Thin Wall Construction
The standard wall sleeve is designed to be easily installed in a variety of wall constructions. For panel wall and thin wall construction, it is recommended that the optional top angle be used and the wall sleeve be supplied with a turned down flange (see Figure 3).
The recommended procedure for installing units in panel
wall and thin wall construction is as follows:
1. Clean the opening of all debris that may interfere with installation.
2. Recess the wall opening so that the louver is flush with the exterior of the building (refer to Figure 3). The center of gravity is approximately 10
3
4" (273mm) from the rear face
of the standard wall sleeve. If a subbase is not used, field support must be provided up to the center of gravity. This support can be metal, wood or concrete.
3. Level wall sleeve in all directions and anchor with appro­priate fasteners. Use holes provided (see Figure 14, page
8) or drill additional holes as required to secure firmly. Caution: Do not drill holes in the base of the wall sleeve. Use shims between the wall and the wall sleeve to prevent wall sleeve distortion during anchoring.
4. Caulk the wall sleeve to the wall opening on both the inside and outside perimeter. This can be done from the inside of the building. Be careful not to plug the weep holes.
(406mm)
3"
(76mm)
Min .
16"
Optional Subbase
101⁄2"
(267mm)
Max.
(25mm)
(1069mm)
1"
42"
Optional
Top Angle
Y*
Turndown
Flange
(See Detail)
Wall
Sleeve
Outside Edge of Sleeve
133⁄4"
(349mm)
11⁄4" (38mm)
Fininish Floor
Including Carpet
Turndown
Flange
16"
(406mm)
37⁄8" (98mm)
Min.
Optional
Top Angel
Wall Sleeve
B**
Support By Others (2 Req’d).
Caulk
C**
Outside Louver
Notes:
** See Figure 2, page 3, for dimensions “B” and “C”.
* Dimension “Y” is field determined or specified. Angle is factory welded at
given dimension when option is designated.
IM 422-4 / Page 4 (Rev 5/99)
Wall Sleeve Installation — Thin Wall Construction
Applications utilizing field supplied louvers require additional considerations:
1. Louvers supplied by others must have 70% free area or a pressure drop not exceeding 0.05 in. w.g. (12.45 Pa) at 300 fpm (1.524 m/sec) face velocity, and a blade design that will not cause recirculation of air.
2. McQuay does not warrant the rain and water leakage resistance of its equipment when used with louvers by others.
3. All louvers by others must be approved by the manufac­turer prior to installation.
Figure 4 illustrates a typical installation using a field
supplied, continuous louver. This method is for illustration purposes only. Other variations may be employed as long as they meet manufacturer’s louver specifications listed above and so long as adequate wall support is achieved. All struc­tural supports and fasteners (except the optional top angle and turned down flange) are field supplied.
Installation of wall sleeves with continuous louvers is very
similar to that of applications with factory furnished louvers. Assuming the louver meets the manufacturer’s criteria, as stated previously, proceed to install the wall sleeve as follows:
Figure 4. Wall sleeve installation using top angles and field supplied continuous louver
1. Clean the opening of all debris that may interfere
with installation.
2. Position the wall sleeve into the wall so that it is flush with the exterior wall. Important: If the wall sleeve has been installed into a thick wall, make certain the wall sleeve protrudes into the room a minimum of 1 the finished wall surface. This is to accommodate the heat section and room cabinet. The center of gravity is 10 (273mm) from the rear face of the standard wall sleeve. If no subbase is being employed, adequate support for the wall sleeve up to the center of gravity must be provided at the job site. This support can be wood, metal or concrete.
3. Level wall sleeve in all directions and anchor with appro­priate fasteners using holes provided (see Figure 14, page
8), or drill additional holes as required to secure firmly. Caution: Do not drill holes in the base of the wall sleeve. Use shims between the wall and the wall sleeve to prevent wall sleeve distortion during anchoring.
4. Caulk the wall sleeve to the wall opening on both the inside and outside perimeter. This can be done from the inside of the building. Be careful not to plug the weep holes.
1
8" (29mm) beyond
3
4"
(406mm)
3"
(76mm)
Min.
16"
Optional Subbase
101⁄2"
(267mm)
Max.
(25mm)
1"
42"
(1069mm)
Optional
Top Angle
Y*
Turndown
Flange
(See Detail)
Wall
Sleeve
Outside Edge of Sleeve
Finished Floor
Including Carpet
133⁄4"
(349mm)
(38mm)
11⁄4"
16"
(406mm)
Min. 37⁄8"
(98mm)
Insulated
Panel
Optional
Top Angle
Wall Sleeve
Supports By Others
(2 Req’d.)
Sleeve
Outside Louver By Others
Turndown Flange
Wall
Wall
Frame
By Others
Resilient Caulking
Resilient Caulking
Notes:
1. Caulk entire perimeter of wall sleeve after installation.
2. Seal area between louver and wall sleeve to prevent con­denser air recirculation.
3. Dimensions shown in table on page 3 do not apply to this application.
*Dimension “Y” is field determined or specified. Angle is factory welded at given dimension when option is designated.
Insulated
Panel
IM 422-4 / Page 5 (Rev. 5/99)
Loading...
+ 11 hidden pages