CH
AR
GE
R
BA
TTE
RY
LAM
PS
CH
G
- TE
ST
SELF-TEST
/ DIAGNOSTIC
REMOTE SENSOR
(IF EQUIPPED)
> GREEN - Status: Solid indicates system normal and flashes during any manual/auto
test cycle.
> RED - CHARGER FLASHING: a charger failure requires the main system PCA to be
replaced.
> RED - BATTERY FLASHING: battery may be disconnected or if it is connected
replacement is needed.
> RED - LAMPS FLASHING: indicates that a Lamp(s) has failed.
OP-PANEL INDICATORS:
TRANSFORMER
Cable
LAMP Cable
BATTERY
Cable
LAMP Cable
REMOTE Lamp
(IF EQUIPPED)
Factory Cable:
YELLOW - Signal from system
BLACK - Return line from system
PCA Configuration CODE (see front page for the table of codes)
TROUBLE INDICATIONS / TROUBLESHOOTING
WIRING INFORMATION
Transformer Inputs:
=================
BLACK - 120V
WHITE - Common
RED - 277V
mcPhilben / Day-Brite
776 S.Green Street - Tupelo, Ms 38804 - ph: 662.842.7212 - fx: 662.680.6619
NORMAL OPERATION / MANUAL TESTS
> GREEN - Status: Solid indicates system normal and charging current from the input source is available.
> NOTE: To reset/cancel a test, simply press the button once during any test.
> 1 Press: performs a 5/sec brief test, all lamps operating from battery only.
> 2 Presses: performs a 1/min test, all lamps operating from battery only.
> 3 Presses: performs a 30/min discharge test, all lamps operating from battery only. The system allows only one 30/min test each 24/hr period.
> CONTINUOS MONITORING: The system monitors the battery for proper levels and performs periodic low-level charger and battery exercising. Constant
LAMP checking, should a LAMP fail, the system will flash the LAMPS indicator until repaired . The charger is fully checked once per day by a internally
disconnected/isolated integrity check, at this time the battery is also completely isolated and then check for proper capacity levels.
> OPTIONAL FACTORY EQUIPPED ITEMS:
> Remote-A: Unit will be supplied with a circuitry and pigtail connector cable require to control and operate a remote of up to 6/w (per wiring diagram).
> Re-strike Time Delay: After a power failure and power is restored, the units lamps will remain lighted for a 15/min period (provided battery capacity remains) .
> Remote Control: To operate, use a laser pen passing the laser over the remote sensor; simply duplicate the manual button (1, 2, 3) pushes.
OP-PANEL INDICATORS / OPERATION:
TEST
Button