McPhiben CTX Instruction Manual

CEILING MTG
SCREW HOLES
FRONT COVER ASSY
TRANSFORMER
TRANSFORMER OUTPUT CABLE
BATTERY
MAIN PCA
OPERATOR PANEL
BATTERY
STRAP
LAMP
CABLE
BACK-PLATE ASSY
IMPORTANT SAFEGUARDS
SAVE THESE INSTRUCTIONS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
+
Do not use outdoors.
+
Do not mount near gas or electric heaters.
+
Do not let power supply wires touch hot surfaces.
+
Equipment should be mounted in locations and at heights where it will not readily be subjected
to tampering by unauthorized personnel.
+
The use of accessory equipment not authorized by the manufacturer may cause an unsafe
condition.
+
Do not use this equipment for other than its intended purpose.
+
Service of this equipment should be performed by qualified service personnel.
+
No rigid conduit.
Flexible conduit only
No rigid conduit
THERMOPLASTIC EMERGENCY
LIGHTING PRODUCTS
mcPhilben
CTX Series
INSTRUCTION MANUAL
p/n: 787625460
T 1 Std Local Lamps Only T 2 Local & Remote-A Lamps
Options
TD Re-strike TimeDelay RC Remote Control
Circuit Assembly Code
Self-Testing / Self-Dianostic
XX
test
1
1
2
2
INSTALLATION
> WALL MOUNT) Always verify the input voltage source. Open front cover as shown above. Route the required transformer input wires (BLACK=120V,
WHITE=common, RED=277V) out though the center K/O and make input connection in the box. Simply use the Box pattern K/O’s in the back panel as needed to mount to wall box and secure unit to the wall. If the unit is shipped with the battery disconnected, connect/verify at this time the battery is connected to the BAT location on the main PCA. Connect the small transformer cable to the PCA at the XFMR location and replace/snap covers, then proceed to Power-Up Sequence...
> CEILING MOUNT) CAUTION: (2) SCREWS MUST BE USED TO MOUNT THE BACK-PLATE TO THE CEILING SURFACE WITH SUITABLE HARDWARE( to
prevent sag and/or the unit falling). Route the proper two transformer input wires (BLACK=120V, WHITE=common, RED=277V) out through the hole in the back-plate, make input connection, and secure back-plate to the ceiling surface/box. Verify the battery is connected to the main PCA, and connect the small transformer cable. Replace/snap the unit closed and check security, then proceed to Power-Up Sequence...
WALL / CEILING INSTALLATION:
TO OPEN COVER
TO OPEN LAMP
Transformer Inputs: =================
BLACK - 120V WHITE - Common RED - 277V
REMOVE THE INPUT POWER IMMEDIATELY IF ALL RED LED’S ON THE OP-PANEL FLASH: This
indicates that the input power is incorrectly wired, and needs to be corrected. IF 277 is applied to the 120 tap for more than 7/sec, then the fusable-link may open requiring the transformer to be replaced. Note that this condition is not covered by warranty.
IMPORTANT NOTE:
> 1) Most likely the battery is not connected; verify that it is connected
to the BAT location of the main PCA.
> 2) If the battery is connected, then it is faulty and needs to be
replaced.
BATTERY LED FLASHING AFTER POWER-UP:
> It is normal for the CHARGER LED to go ON solid right after the power-up sequence from installation. > This indicates the battery is charging, and the LED will go out when the battery is at full charge ( this usually occurs within 24-96 hours after installation). > The charger LED may cycle from off to on solid as the system charging algorithm dictates. This is normal. > Before initiating manul tests, allow the system to fully charge until the CHARGER LED is off.
APPLY
INPUT
POWER
WITHIN ~7/sec
GREEN STATUS - ON
WITHIN ~25/sec
GREEN LED - FLASH
IT PERFORMS 5/sec
AUTO-DIAG TEST
TO
NORMAL
OPERATION
Y
N
IS THE
BATTERY LED
FLASHING
VERIFY
BATTERY
CONNECTED
Y
N
ARE ALL
RED DIAG LED’S
FLASHING
REMOVE
INPUT POWER
IMMEDIATELY
~30/sec
~7/sec
~0/sec
Normal Power-Up Sequence
> The unit automatically performs diag testing at all power-up, and initializes itself.
> The system is capable of instantaneously detecting lamp failures, and is indicated by a flashing LAMP LED.
> The system also constantly monitors and controls all functions: the charging circuit, the battery, the input power
level, the EXIT LED’s, and operator manual tests.
> The charge circuit is computer controlled by an algorithm that is monitoring the environment, levels of the battery,
and curves associated to each. The system learns these parameters and then remembers them to provide better life and performance of the emergency lighting system.
> The units monthly 30/min discharge testing is randomized according to Ul924. Then within each 30/day period
thereafter the unit shall perform the 30/min test.
AUTO-DIAG TESTING:
REMOVE THE INPUT POWER IMMEDIATELY IF ALL RED LED’S ON THE OP-PANEL FLASH. This indicates that the input power is incorrectly wired, and needs to be corrected. IF 277 is applied to the 120 tap for more than 7/sec, then the fusable-link may open requiring the transformer to be replaced. Note that this condition is not covered by warranty.
IMPORTANT NOTE:
CH
AR
GE
R
BA
TTE
RY
LAM
PS
CH
G
- TE
ST
SELF-TEST
/ DIAGNOSTIC
REMOTE SENSOR
(IF EQUIPPED)
> GREEN - Status: Solid indicates system normal and flashes during any manual/auto
test cycle.
> RED - CHARGER FLASHING: a charger failure requires the main system PCA to be
replaced.
> RED - BATTERY FLASHING: battery may be disconnected or if it is connected
replacement is needed.
> RED - LAMPS FLASHING: indicates that a Lamp(s) has failed.
OP-PANEL INDICATORS:
TRANSFORMER
Cable
LAMP Cable
BATTERY
Cable
LAMP Cable
REMOTE Lamp
(IF EQUIPPED)
Factory Cable: YELLOW - Signal from system BLACK - Return line from system
PCA Configuration CODE (see front page for the table of codes)
TROUBLE INDICATIONS / TROUBLESHOOTING
WIRING INFORMATION
Transformer Inputs: =================
BLACK - 120V WHITE - Common RED - 277V
mcPhilben / Day-Brite
776 S.Green Street - Tupelo, Ms 38804 - ph: 662.842.7212 - fx: 662.680.6619
NORMAL OPERATION / MANUAL TESTS
> GREEN - Status: Solid indicates system normal and charging current from the input source is available.
> NOTE: To reset/cancel a test, simply press the button once during any test.
> 1 Press: performs a 5/sec brief test, all lamps operating from battery only.
> 2 Presses: performs a 1/min test, all lamps operating from battery only.
> 3 Presses: performs a 30/min discharge test, all lamps operating from battery only. The system allows only one 30/min test each 24/hr period.
> CONTINUOS MONITORING: The system monitors the battery for proper levels and performs periodic low-level charger and battery exercising. Constant
LAMP checking, should a LAMP fail, the system will flash the LAMPS indicator until repaired . The charger is fully checked once per day by a internally disconnected/isolated integrity check, at this time the battery is also completely isolated and then check for proper capacity levels.
> OPTIONAL FACTORY EQUIPPED ITEMS:
> Remote-A: Unit will be supplied with a circuitry and pigtail connector cable require to control and operate a remote of up to 6/w (per wiring diagram).
> Re-strike Time Delay: After a power failure and power is restored, the units lamps will remain lighted for a 15/min period (provided battery capacity remains) .
> Remote Control: To operate, use a laser pen passing the laser over the remote sensor; simply duplicate the manual button (1, 2, 3) pushes.
OP-PANEL INDICATORS / OPERATION: