DPE3672*
DOWNFLOW POWER EXHAUST FITS DAIKIN
D*G036-072, D*H036-072, D*C036-072,
DP16C/H60M, DP16G/D60M, AND GOODMAN
GPH/APH1660M, GPG/APG1660M
SEQUENCE OF OPERATION
This sequence assumes employment of a single enthalpy economizer
using a two stage thermostat.
1. A call for cooling comes from room thermostat.
2. The enthalpy sensor determines if the atmospheric condi-
ons are conducive for using outside air for cooling. If YES,
the fresh air damper secon of the economizer begins to
open.
3. The EXH SET potenometer should be set such that when
the fresh air dampers are open approximately 70% of their
full open capacity, EXH1 is energized and the power exhaust
is powered to draw the relief air from the space. There is a
60 +/-30 second me delay built into the economizer control
before the fan motor actually energizes.
4. When the dampers modulate below the 70% open posion
due to a sased thermostat or atmospheric condions, the
power exhaust disengages immediately.
DPE3672
W/ UNIT
INSTALLATION
WITH ECONOMIZER
1. Open carton and inspect contents for shortages and damage.
2. Disconnect the power to the unit.
3. If the economizer is already fully installed, remove the
economizer hoods. If a new installaon, do not install the
economizer hood.
4. If installing in conjuncon with an economizer, install the
damper secon.
5. Remove the horizontal duct cover panel.
6. Slide the support legs through the guides. (Figure 1)
7. Feed the line voltage and low voltage wires through the
knockouts provided in the damper secon of the economizer.
8. Aach the power exhaust hood over the barometric relief
opening. Extend the support legs and secure them using the
screws provided.
9.
eed the line voltage leads to the control secon of the
F
package unit and aach them to T1 and T2 on the unit con-
tactor per the included wiring diagram.
10.
Aach the low voltage control leads to the Jade economizer
controller per the included wiring diagram using the side
connectors provided. (Figure 3)
11.
On the Jade control, set the posion at which the exhaust
will ener
Reinstall the horizontal duct cover panel and the filter access
12.
panel.
gize under the SETPOINTS menu.
REV. E 2/24/2017
![](/html/42/42b8/42b879dd2ce84743afe527aa7caa241fb58ff28d23707f1620f505aebac0490b/bg2.png)
Figure 1
CONTENTS
Figure 2
1 Power Exhaust Hood
2 Support Legs
2 Side Connectors
1 Installaon Instrucons
Figure 3
Motor
Model
DPE36722 208/230-1-60 1/3 1625 Direct Drive 3.4 3
DPE36724 460-1-60 1/4 1625 Direct Drive 1.2 2
DPE36727 575-1-60 1/2 1625 Direct Drive 1 1
Voltage
HP RPM Type FLA Speeds
REV. E 2/24/2017