McDaniel Metals DNECONGS3672B Installation Manual

DNECONGS3672B INSTALLATION AND OPERATION GUIDE
DOW
to cool the space. (Go to step 5.)
Outdoor air dampers open to minimum position and the 4. compressor engages to provide mechanical cooling. When the thermostat is satisfi ed the outside air dampers 5. return to a closed position.
ECONOMIZER 101
Economizers are designed to provide “free” air conditioning
when outside conditions are appropriate. When the outside air is cool and dry enough, the economizer automatically opens to introduce the cool air to the interior space, thereby eliminating the need to run the air conditioning compressor. If the outside air becomes too warm or humid, the economizer automatically closes the fresh air damper and the compressor engages to begin cooling the space mechanically. If a two stage thermostat is used it is possible to use a combination of economizer and mechanical cooling to condition the space. The economizer can also be set to allow a minimum amount of fresh air to enter the space when the equipment’s indoor blower is operating. Economizers are valuable tools to enhance indoor air quality, save energy and prolong the life of the air conditioning equipment.
SEQUENCE OF OPERATION
This sequence assumes employment of a single enthalpy
economizer using a two stage thermostat.
Figure 1
INSTALLATION
Open carton and inspect contents for shortages and damage.1. Remove fi lter access and bottom evaporator access panel 2. from package unit. Keep the screws from the bottom panel. Slide internal damper rack into the opening until the outside 3. anges of the assembly nest inside of the posts framing the opening. (Figure 1)
A call for cooling comes from room thermostat.1. The enthalpy sensor determines if the atmospheric condi-2. tions are conducive for using outside air for cooling. If YES, go to step 3. If NO, or if outdoor air temperature rises above enthalpy set point, go to step 4. The outside air dampers open and modulate to maintain a 3. mixed air temperature (outside air + indoor air) of 53 degrees F. If the outdoor air is insuffi cient to satisfy the thermostat alone and a second stage of cooling is required, the com­pressor starts and works in conjunction with the economizer
Figure 2
Rev 2
4. Plug 6-pin economizer plug into matching 6-pin plug in the unit.
CONTENTS
NOTE: Ensure neither the wire nor the plugs interfere with the
movement of the dampers during operation.
Assemble hood kit per the instructions on page 4.5. Secure hood kit to the unit with the screws removed in Step 2.6. Refer to psychrometric chart included with controller check 7. out literature to determine the A, B, C, or D setting for the controller. The factory setting is the D position. Use the Minimum Set Point Equation below to determine the 8. minimum position setting on the controller. The factory setting is closed or full CCW. Replace fi lter access panel on unit.9.
MINIMUM SET POINT EQUATION
(To X OA) + (Tr X RA) = Tm To = Outdoor air temperature OA= Percent of outdoor air Tr = Return air temperature RA= Percent of return air Tm= Resulting mixed air temperature
1 Damper rack w/ economizer controls 1 Hood Kit 1 Fresh Air Mist Eliminator 1 Screw package and control jumpers 1 Installation/Component Manual
ACCESSORIES / CAPABILITIES
Dual Enthalpy - Requires an additional C7400 enthalpy control installed in the return air duct.
Demand Control Ventilation - Requires a CO2 sensor. Power Exhaust - PE3672(2/4) power exhaust used in
applications where barometric relief is not suffi cient. Remote Minimum Positioner - For applications requiring
minimum position adjustments inside the conditioned space.
Example:
Fresh air required is 10% outdoor air. Outdoor air temperature is 60 degrees F. Return air temperature is 75 degrees F. (0.1 X 60) + (0.9 X 75) =
6.0 + 67.5 = 73.5 Mixed air temperature will be 73.5 degrees F when the OA is 60 degrees F and the RA is 75 degrees F with 10% outdoor air.
Important Notes
The economizer will open to minimum posi-• tion in heating unless the MAT drops below 45F at which point the fresh air dampers will close completely. See the enclosed brochure for additional information. Please see enclosed brochure for Honeywell • component trouble shooting instructions. The fresh air mist eliminator should be ushed periodically with warm soapy water. A two stage thermostat is recommended with • this accessory. If Power Exhaust of Demand Control Ventila-• tion are not included in the system please ensure the DCV Set and DCV Max pots are turned full counterclockwise.