ECONOMIZER 101
Economizers are designed to provide “free” air condioning when outside condions are appropriate. When the outside air is cool and dry enough, the economizer automacally opens to introduce the cool air to the interior space, thereby eliminang the need to run the air condioning compressor.
If the outside air becomes too warm or humid, the economiz-
er automacally closes the fresh air damper and the compressor engages to begin cooling the space mechanically.
If a two stage thermostat is used it is possible to use a combi-
naon of economizer and mechanical cooling to condion the space.
The economizer can also be set to allow a minimum amount of fresh air to enter the space when the equipment’s indoor
blower is operang.
Economizers are valuable tools to enhance indoor air quality,
save energy and prolong the life of the air condioning equip­ment.
SEQUENCE OF OPERATION
This sequence assumes employment of a single enthalpy
economizer using a two stage thermostat.
1. A call for cooling comes from room thermostat.
2. The enthalpy sensor determines if the atmospheric condi- ons are conducive for using outside air for cooling. If YES, go to step 3. If NO, or if outdoor air temperature rises above enthalpy set point, go to step 4.
3. The outside air dampers open and modulate to maintain
a mixed air temperature (outside air + indoor air) of 53
degrees F. If the outdoor air is insucient to sasfy the
thermostat alone and a second stage of cooling is required,
the compressor starts and works in conjuncon with the
economizer
DHZECNJPGCHL
HORIZONTAL JADE ECONOMIZER FOR DAIKIN DP**G/DM**, DP**C/H**M AND GOODMAN GPG-APG****M, GPG/ H-APG/H****M LARGE CHASSIS UNITS
to cool the space. In a system with two compressors, if the thermostat is sll not sased by the economizer and stage
1 compressor, the Jade control will energize the second
compressor. (Go to step 5.)
4. Outdoor air dampers open to minimum posion and the compressor engages to provide mechanical cooling.
5. When the thermostat is sased the outside air dampers return to a minimum posion.
INSTALLATION
1. Open carton and inspect contents for shortages and damage.
2. Disconnect power to the package unit.
3. On the M series unit, remove the large blower (GPG/DPG) or evaporator (GPC/HM-DPC/HM) panel.
4. Aach the damper secon to the side of the unit over the horiziontal return opening. (Figure 2)
5. Connect the return duct to the economizer. See the chart below for the return opening size. (Figure 1)
6. Remove the jumper from the economizer plug in the unit.
7. Connect the jumper harness to the economizer and plug the economizer into the unit female molex plug.
NOTE: Some single phase units do not come with a plug for the
economizer. The male plug from the economizer may be removed and the unit hard wired per the wiring diagram included.
8. Feed the red power wire from the jumper harness to the con- trol secon of the unit and connect it R on the terminal strip.
9. Feed the pink mixed air sensor wire into the blower secon
of the unit and secure the mixed air sensor to the side of the
blower toward the outer edge of the housing. (Figure 3)
10. Connect the pink wires to the mixed air sensor and the Jade economizer control. (Figure 4)
11. Restore power to the unit.
12. Determine the minimum posion seng using the minimum set point equaon on page two.
13. Seal connecon between the fresh air hood and plenum unl water ght.
14. Install Goodman IRKT-01 Isolaon Relay Kit for heat pumps per the instrucons included with the IRKT-01.
This product is warrantied to be free from defects due to workmanship or materials, under normal use, for a period of sixty (60) months from date of installation.
Figure 1
A B C D E F G
DHZECNJPGCHL
35 1/4 18 1/8 18 16 15 7/8 18 1/4 16 1/8
CONTENTS
1 Damper rack w/ economizer controls 1 Installaon/Component Manual 1 Mixed Air Sensor
The equaon below may be used to set the minimum posion.
The mixed air temperature and outside air temperature may be
discerned by looking at the status menu on the Jade controller.
MINIMUM SET POINT EQUATION
(To X OA) + (Tr X RA) = Tm To = Outdoor air temperature OA= Percent of outdoor air Tr = Return air temperature RA= Percent of return air
Tm= Resulng mixed air temperature
ACCESSORIES / CAPABILITIES
Dual Enthalpy - Requires an addional C7400 enthalpy control installed in the return air duct.
Demand Control Venlaon - Requires a CO2 sensor.
IRKT-01 Isolaon relay kit is required for heat pump ap­plicaons
Example:
Fresh air required is 10% outdoor air. Outdoor air temperature is 60 degrees F. Return air temperature is 75 degrees F. (0.1 X 60) + (0.9 X 75) =
6.0 + 67.5 = 73.5 Mixed air temperature will be 73.5 degrees F when the
OA is 60 degrees F and the RA is 75 degrees F with 10%
outdoor air.