DDNECNJ90150
DOWNFLOW JADE ECONOMIZER
FITS DAIKIN DCG090-150, DCH090150, DCC090-150
to cool the space. (Go to step 5.)
4. Outdoor air dampers open to minimum posion and the
compressor engages to provide mechanical cooling.
5. When the thermostat is sased the outside air dampers
return to a closed posion.
ECONOMIZER 101
Economizers are designed to provide “free” air condioning
when outside condions are appropriate. When the outside air
is cool and dry enough, the economizer automacally opens to
introduce the cool air to the interior space, thereby eliminang
the need to run the air condioning compressor.
If the outside air becomes too warm or humid, the economiz-
er automacally closes the fresh air damper and the compressor
engages to begin cooling the space mechanically.
If a two stage thermostat is used it is possible to use a combi-
naon of economizer and mechanical cooling to condion the
space.
The economizer can also be set to allow a minimum amount
of fresh air to enter the space when the equipment’s indoor
blower is operang. Economizers are valuable tools to enhance
indoor air quality, save energy and prolong the life of the air
condioning equipment.
SEQUENCE OF OPERATION
This sequence assumes employment of a single enthalpy
economizer using a two stage thermostat.
1. A call for cooling comes from room thermostat.
2. The enthalpy sensor determines if the atmospheric condi-
ons are conducive for using outside air for cooling. If YES,
go to step 3. If NO, or if outdoor air temperature rises above
enthalpy set point, go to step 4.
3. The outside air dampers open and modulate to maintain a
mixed air temperature (outside air + indoor air) of 53 degrees F. If the outdoor air is insucient to sasfy the thermostat alone and a second stage of cooling is required, the
rst stage compressor starts and works in conjuncon with
the economizer
Figure 1
INSTALLATION
1. Open carton and inspect contents for shortages and damage.
2. Remove large evaporator access panel from package unit
and discard. Remove the smaller lter access panel and the
horizontal return panel.
3. Slide the damper rack into the large opening and pivot the
damper into posion around the post between the evaporator opening and the lter access opening. (Figure 1)
4. Posion the dampers in the opening unl the front anges
are ush with the corner post and divider post between the
lter access panel and the evaporator access panel. (Figure 2)
Figure 2
REV. B Effective 3-28-2014
![](/html/b4/b459/b459e177740fca4045cbf5f0df5dde7d600b627255259967a7867875fb2c3718/bg2.png)
5. Feed the pink wires for the mixed air sensor through the unit
economizer plug mousehole into the blower secon of the
unit. Mount the mixed air sensor to the blower housing away
from the center to avoid interferring with the rotaon of the
blower wheel and plug in the wires. (Figure 3)
6. Aach the pink mixed air senor wires to the controller. (Fig-
ure 4)
7. From the horizontal return opening, plug 9-pin economizer
plug into matching 9-pin plug in the unit.
NOTE: Ensure neither the wire nor the plugs interfere with the
movement of the dampers during operaon.
8. Replace the horizontal return cover.
9. Install the new evaporator access panel on the unit.
10. Secure access panel to the unit with the screws from step 2.
New holes must be drilled to secure the panel to the 12.5 ton
unit.
11. Assemble the barometric relief hood and the fresh air hoods
with the screws provided. Be sure to install the mist eliminators before installing the front lter access piece. (Figure 6)
12. Install gasket material on the economizer panel outside
of the hood openings using the hood mounng holes as a
guide.
13. Refer to enclosed documentaon for the Jade controller for
set up.
14. Use the minimum set point equaon (see below) to determine the minimum posion seng on the controller.
15. Install barometric relief hood with screws provided through
access panel and economizer.
16. Install the fresh air hood with the screws provided through
the access panel and economizer.
17. Install the blocko panel above the hoods on the 12.5 ton
unit. (Figure 5)
18. Run a bead of silicone or other approved sealant along the
hood anges to ensure a waterght seal.
19. Replace lter access panel.
Figure 4
Figure 5
Figure 3
MINIMUM SET POINT EQUATION
(To X OA) + (Tr X RA) = Tm
To = Outdoor air temperature
OA= Percent of outdoor air
Tr = Return air temperature
RA= Percent of return air
Tm= Resulng mixed air temperature
Example:
Fresh air required is 10% outdoor air.
Outdoor air temperature is 60 degrees F.
Return air temperature is 75 degrees F.
(0.1 X 60) + (0.9 X 75) =
6.0 + 67.5 = 73.5
Mixed air temperature will be 73.5 degrees F when the
OA is 60 degrees F and the RA is 75 degrees F with 10%
outdoor air.