DDNECNJ90150
DOWNFLOW JADE ECONOMIZER FITS DAIKIN DCG090-150, DCH090­150, DCC090-150
to cool the space. (Go to step 5.)
4. Outdoor air dampers open to minimum posion and the compressor engages to provide mechanical cooling.
5. When the thermostat is sased the outside air dampers return to a closed posion.
Economizers are designed to provide “free” air condioning when outside condions are appropriate. When the outside air is cool and dry enough, the economizer automacally opens to introduce the cool air to the interior space, thereby eliminang the need to run the air condioning compressor.
If the outside air becomes too warm or humid, the economiz-
er automacally closes the fresh air damper and the compressor engages to begin cooling the space mechanically.
If a two stage thermostat is used it is possible to use a combi-
naon of economizer and mechanical cooling to condion the space.
The economizer can also be set to allow a minimum amount of fresh air to enter the space when the equipment’s indoor
blower is operang. Economizers are valuable tools to enhance
indoor air quality, save energy and prolong the life of the air
condioning equipment.
SEQUENCE OF OPERATION
This sequence assumes employment of a single enthalpy
economizer using a two stage thermostat.
1. A call for cooling comes from room thermostat.
2. The enthalpy sensor determines if the atmospheric condi- ons are conducive for using outside air for cooling. If YES, go to step 3. If NO, or if outdoor air temperature rises above enthalpy set point, go to step 4.
3. The outside air dampers open and modulate to maintain a
mixed air temperature (outside air + indoor air) of 53 de­grees F. If the outdoor air is insucient to sasfy the ther­mostat alone and a second stage of cooling is required, the
rst stage compressor starts and works in conjuncon with
the economizer
Figure 1
INSTALLATION
1. Open carton and inspect contents for shortages and damage.
2. Remove large evaporator access panel from package unit and discard. Remove the smaller lter access panel and the horizontal return panel.
3. Slide the damper rack into the large opening and pivot the damper into posion around the post between the evapora­tor opening and the lter access opening. (Figure 1)
4. Posion the dampers in the opening unl the front anges are ush with the corner post and divider post between the lter access panel and the evaporator access panel. (Figure 2)
Figure 2
REV. B Effective 3-28-2014
5. Feed the pink wires for the mixed air sensor through the unit economizer plug mousehole into the blower secon of the unit. Mount the mixed air sensor to the blower housing away from the center to avoid interferring with the rotaon of the blower wheel and plug in the wires. (Figure 3)
6. Aach the pink mixed air senor wires to the controller. (Fig-
ure 4)
7. From the horizontal return opening, plug 9-pin economizer plug into matching 9-pin plug in the unit.
NOTE: Ensure neither the wire nor the plugs interfere with the
movement of the dampers during operaon.
8. Replace the horizontal return cover.
9. Install the new evaporator access panel on the unit.
10. Secure access panel to the unit with the screws from step 2. New holes must be drilled to secure the panel to the 12.5 ton unit.
11. Assemble the barometric relief hood and the fresh air hoods with the screws provided. Be sure to install the mist elimina­tors before installing the front lter access piece. (Figure 6)
12. Install gasket material on the economizer panel outside of the hood openings using the hood mounng holes as a guide.
13. Refer to enclosed documentaon for the Jade controller for set up.
14. Use the minimum set point equaon (see below) to deter­mine the minimum posion seng on the controller.
15. Install barometric relief hood with screws provided through access panel and economizer.
16. Install the fresh air hood with the screws provided through the access panel and economizer.
17. Install the blocko panel above the hoods on the 12.5 ton unit. (Figure 5)
18. Run a bead of silicone or other approved sealant along the hood anges to ensure a waterght seal.
19. Replace lter access panel.
Figure 4
Figure 5
Figure 3
MINIMUM SET POINT EQUATION
(To X OA) + (Tr X RA) = Tm To = Outdoor air temperature OA= Percent of outdoor air Tr = Return air temperature RA= Percent of return air
Tm= Resulng mixed air temperature
Example:
Fresh air required is 10% outdoor air. Outdoor air temperature is 60 degrees F. Return air temperature is 75 degrees F. (0.1 X 60) + (0.9 X 75) =
6.0 + 67.5 = 73.5 Mixed air temperature will be 73.5 degrees F when the
OA is 60 degrees F and the RA is 75 degrees F with 10%
outdoor air.