Maytag UXT5330ADS0, UXT5336ADS0 Installation Guide

30" (76.2 CM) AND 36" (91.4 CM) RANGE HOOD
HOTTED'ASPIRATIONDE
30"(76,2 CM) ET36"(91,4 CM)
Table of Contents/Table des matieres ............................................................................. 2
IMPORTANT: READ AND SAVE THESE INSTRUCTIONS.
FOR RESIDENTIAL USE ONLY.
IMPORTANT : LIRE ET CONSERVER CES INSTRUCTIONS.
POUR UTILISATION Ri_SIDENTIELLE UNIQUEMENT.
TABLEOF CONTENTS
TABLEDESMATIERES
RANGE HOOD SAFETY ................................................................. 2
INSTALLATION REQUIREMENTS ................................................ 3
Tools and Parts ............................................................................ 3
Location Requirements ................................................................ 4
Venting Requirements .................................................................. 5
Electrical Requirements ............................................................... 6
INSTALLATION INSTRUCTIONS .................................................. 7
Prepare Location .......................................................................... 7
Install Range Hood ....................................................................... 8
Make Electrical Connection ....................................................... 10
Complete Installation................................................................. 11
RANGE HOOD USE ...................................................................... 12
Range Hood Controls ................................................................ 12
RANGE HOOD CARE ................................................................... 12
Cleaning ...................................................................................... 12
ASSISTANCE OR SERVICE ......................................................... 13
In the U.S.A................................................................................ 13
In Canada ................................................................................... 13
WAR RANTY .................................................................................. 14
SECURITE DE LA HOTTE DE CUlSINIERE ............................... 15
EXIGENCES D'INSTALLATION ................................................... 17
Outils et pieces ........................................................................... 17
Exigences d'emplacement ......................................................... 17
Exigences concernant I'evacuation ........................................... 18
Specifications electriques .......................................................... 20
INSTRUCTIONS D'INSTALLATION ............................................. 20
Preparation de I'emplacement ................................................... 20
Installation de la hotte ................................................................ 22
Raccordement electrique ........................................................... 24
Achever I'installation .................................................................. 24
UTILISATION DE LA HO'I-rE ....................................................... 26
Commandes de la hotte de cuisiniere ....................................... 26
ENTRETIEN DE LA HOTTE .......................................................... 26
Nettoyage ................................................................................... 26
ASSISTANCE OU SERVICE ......................................................... 27
GARANTIE ..................................................................................... 28
RANGE HOOD SAFETY
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety
messages.
This is the safety alert symbol. This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol and either the word "DANGER" or "WARNING."
These words mean:
You can be killed or seriously injured if you don't immediately
follow instructions.
You can be killed or seriously injured if you don't follow instructions.
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can happen if the instructions are not followed.
2
iMPORTANT SAFETY iNSTRUCTiONS
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC
SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer.
Before servicing or cleaning the unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When
the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag,
to the service panel.
Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction.
Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel
burning equipment to prevent backdrafting. Follow the heating equipment manufacturer's guideline and safety
standards such as those published by the National Fire Protection Association (NFPA), the American Society for
Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
When cutting or drilling into wall or ceiling; do not damage electrical wiring and other utilities.
Ducted fans must always be vented outdoors.
CAUTION: For general ventilating use only. Do not use
to exhaust hazardous or explosive materials and vapors.
CAUTION: To reduce risk of fire and to properly exhaust
air, be sure to duct air outside - do not vent exhaust air into spaces within walls or ceilings, attics or into crawl spaces,
or garages.
WARNING: TO REDUCE THE RISK OF FIRE, USE ONLY
METAL DUCTWORK.
WARNING: TO REDUCE THE RISK OF A RANGE TOP
GREASE FIRE: [] Never leave surface units unattended at high settings.
Boilovers cause smoking and greasy spillovers that may ignite. Heat oils slowly on low or medium settings.
[] Always turn hood ON when cooking at high heat or when
flambeing food (i.e. Crepes Suzette, Cherries Jubilee,
Peppercorn Beef Flamb6).
[] Clean ventilating fans frequently. Grease should not be
allowed to accumulate on fan or filter.
[] Use proper pan size. Always use cookware appropriate for
the size of the surface element.
WARNING: TO REDUCE THE RISK OF INJURY TO
PERSONS IN THE EVENT OF A RANGE TOP GREASE FIRE, OBSERVE THE FOLLOWING: a
[] SMOTHER FLAMES with a close fitting lid, cookie sheet, or
metal tray, then turn off the burner. BE CAREFUL TO PREVENT BURNS. If the flames do not go out
immediately, EVACUATE AND CALL THE FIRE
DEPARTMENT. [] NEVER PICK UP A FLAMING PAN -you may be burned. [] DO NOT USE WATER, including wet dishcloths or towels -
a violent steam explosion will result. [] Use an extinguisher ONLY if:
- You know you have a class ABC extinguisher, and you already know how to operate it.
- The fire is small and contained in the area where it started.
- The fire department is being called.
- You can fight the fire with your back to an exit.
aBased on "Kitchen Fire Safety Tips" published by NFPA. [] WARNING: To reduce the risk of fire or electrical shock,
do not use this fan with any solid-state speed control device.
SAVE THESE iNSTRUCTiONS
INSTALLATIONREQUIREMENTS
Gather the required tools and parts before starting installation. Read and follow the instructions provided with any tools listed
here. Tools needed
Drill
1V4" (3.0 cm) drill bit
1/8"(3.0 mm) drill bit for pilot holes
Pencil
Wire stripper or utility knife
Tape measure or ruler
Caulking gun and weatherproof caulking compound
Flat-blade screwdriver
Phillips screwdriver
For vented installations, you also need:
Saber or keyhole saw
Vent clamps
Metal snips
Compass or 8" (20.3 cm) circle template
Parts supplied
Remove parts from package. Check that all parts are included.
2 - Aluminum filters
4 - #10 x 5/8"mounting screws
2 - 1_" black damper screws
31/4"x 10" (8.3 x 25.4 cm) damper/vent connector
Parts needed For direct wire installation
UL listed or CSA approved 1/2"(12.5 mm) strain relief
2 - 75-watt max incandescent light bulbs or
1 - 75-watt max and 1 - 25-watt max incandescent light bulb (for use as a night light)
Power supply cable (if needed, for direct wire installation)
For power supply cord installation
UL Listed Power Supply Cord Connection Kit marked for range hood use.
2 - 75-watt max incandescent light bulbs or
1 - 75-watt max and 1 - 25-watt max incandescent light bulb (for use as a night light)
For vented installations you also need:
31/4"x 10" (8.3 x 25.4 cm) or 6" (15.2 cm) or larger round metal venting
6" (15.2 cm) or larger round damper, if using 6" (15.2 cm) or larger round vent system
31/4"x 10" (8.3 x 25.4 cm) to 6" (15.2 cm) or larger diameter transition piece
For cabinets with recessed bottoms:
Two 2" (5.1 cm) wide filler strips. Length and thickness determined by recess dimensions.
Four flat head wood screws or machine screws with washers and nuts (to attach filler strips).
Product Dimensions
12" _(3.8 ore)
(30.5 era) 9,,
9"
(22.9 cm)
29%"(75.9cm)- 30"(76.2cm)model 20" 35%"(91.t cm) - 36" (91.4 cm) mod_
Installation Clearances
11/2"
(2.5 crn)
(44.5cm)
IMPORTANT." Observe all governing codes and ordinances.
It is the installer's responsibility to comply with installation clearances specified on the model/serial rating plate. The model/serial rating plate is located inside the range hood on
the left wall.
Range hood location should be away from strong draft areas, such as windows, doors and strong heating vents.
Cabinet opening dimensions that are shown must be used. Given dimensions provide minimum clearance. Consult the cooktop/range manufacturer installation instructions before making any cutouts.
Grounded electrical outlet is required. See "Electrical Requirements" section.
The hood is factory-set for vented installations. For non- vented (recirculating) installations, charcoal filter pad Part
Number 4396390 is available. See the "Assistance or Service" section for information on ordering.
All openings in ceiling and wall where range hood will be installed must be sealed.
For Mobile Home Installations
The installation of this range hood must conform to the Manufactured Home Construction Safety Standards, Title 24 CFR, Part 328 (formerly the Federal Standard for Mobile Home Construction and Safety, title 24, HUD, Part 280) or when such standard is not applicable, the standard for Manufactured Home Installation 1982 (Manufactured Home Sites, Communities and Setups) ANSI A225.1/NFPA 501A*, or latest edition, or with local
codes.
18" (45.7 cm)
rain. clearance
upper cabinet
to countertop
I
24" (61.0 cm) rain.
30" (76.2 cm)
suggested max.
bottom of cabinet
g surface
36" (91.4 cm)
base cabinet
height
opemnc
ss_S._;_ss_4 su, _+<;) ,,.,*,,.J, ¢4]1. . _J
Vent system must terminate to the outdoors, except for non- Roof Venting vented (recirculating) installations.
Do not terminate the vent system in an attic or other enclosed area.
Do not used a 4" (10.2 cm) laundry-type wall cap. Use a 6" (15.2 cm) or larger round metal vent or a 3V4" x 10"
(8.3 x 25.4 cm) rectangular metal vent. Rigid metal vent is recommended. Plastic or metal foil vent is not recommended.
The length of vent system and number of elbows should be kept to a minimum to provide efficient performance.
For the most efficient and quiet operation:
D
Use no more than three 90° elbows.
Make sure there is a minimum of 24" (61 cm) of straight vent between the elbows if more than 1 elbow is used.
Do not install 2 elbows together.
Use clamps to seal all joints in the vent system.
The vent system must have a damper. Ifroof or wall cap has a damper, do not use damper supplied with the range hood.
Use caulking to seal exterior wall or roof opening around the cap.
Cold Weather Installations
An additional back draft damper should be installed to minimize backward cold air flow and a thermal break should be installed to
A. 6" (15.2 cm) or larger round
vent or a 31/4''x 10" (8.3 x
25.4 cm) rectangular vent through roof
B.Round vent: use 6" (15.2 cm)
or larger round damper
(purchased separately)
C. Round vent: use 31/4''x 10"
(8.3x25.4 cm) to 6" (15.2 cm)
or larger diameter transition ptece
(purchased separately)
D. 24" (61.0 cm) - 30" (76.2 cm)
above cooking surface
E.Roof cap
minimize conduction of outside temperatures as part of the vent system. The damper should be on the cold air side of the thermal
break. The break should be as close as possible to where the vent
system enters the heated portion of the house.
Calculating Vent System Length
To calculate the length of the system you need, add the
equivalent feet (meters) for each vent piece used in the system.
Wall Venting
D
A. 6" (15.2 cm) or larger round
vent or a 31/4'' x 10" (8.3 x
25.4 cm) rectangular vent through the wall
B. Round vent: use 31/4"x 10" (8.3
x 25.4 cm) to 6" (15.2 cm) or
larger diameter transition piece (purchased separately)
C. 31/4"x 10" (8.3x25.4 cm)
through the wall
D. 24" (61.0 cm) - 30" (76.2 cm)
above cooking surface
E. Wall cap
Makeup Air
Local building codes may require the use of make up air systems when using ventilation systems greater than specified CFM of air movement. The specified CFM varies from locale to locale. Consult your HVAC professional for specific requirements in your
area.
Venting Methods
Vent system can terminate either through the roof or wall. Use 3V4"x 10" (8.3 x 25.4 cm) with a maximum vent length of 35 ft (10.7 m) or 6" (15.2 cm) or larger round vent with a maximum length of 50 ft (15.2 m) for vent system.
NOTE: Flexible vent is not recommended. Flexible vent creates back pressure and air turbulence that gently reduces
performance.
6" (15.2 cm) or Larger Round Vent System
Vent Piece Round
45° elbow 2.5 ft
(0.8m)
90° elbow 5.0 ft
(1.5m)
6" (15.2 cm) or larger 0.0 ft wall cap (0.0 m)
3V4"x 10" (8.3 cm x 25.4 cm) 4.5 ft to 6" (15.2 cm) or larger (1.4 m)
3V4"x 10" (8.3 cm x 25.4 cm) 5.0 ft to 6" (15.2 cm) or larger (1.5 m)
90° elbow
Example vent system
90°elbow i_ i 6.(1.8m) _l
Wall cap
]
Maximum Recommended Length = 50 ft (15.2 m)
1 - 90 ° elbow 1 - wall cap
8 ft (2.4 m) straight Length of 7" (17.8 cm) system
3Y4"x 10" (8.3 cm x 25.4 cm) Vent System
VentPiece
31/4"x 10" (8.3 cm x 25.4 cm) 5.0 ft 90° elbow (1.5 m)
31/4"x 10" (8.3 cm x 25.4 cm) 12.0 ft flat elbow (3.7 m)
31/4"x 10" (8.3 cm x 25.4 cm) 0.0 ft wall cap (0.0 m)
Example vent system
= 5.0 ft (1.5 m) = 0.0 ft (0.0 m) = 8.0 ft (2.4 m) = 13.0 ft (3.9 m)
E cQ sts
Observe all governing codes and ordinances. Ensure that the electrical installation is adequate and in
conformance with National Electrical Code, ANSl/NFPA 70 (latest edition), or CSA Standards C22.1-94, Canadian Electrical Code, Part 1 and C22.2 No. 0-M91 (latest edition) and all local codes
and ordinances. If codes permit and a separate ground wire is used, it is
recommended that a qualified electrician determine that the ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park
Quincy, MA 02269
CSA International
8501 East Pleasant Valley Road
Cleveland, OH 44131-5575
A 120 Volt, 60 Hz., AC only, 15-amp, fused electrical circuit is required.
If the house has aluminum wiring follow the procedure below:
1. Connect a section of solid copper wire to the pigtail
leads.
2. Connect the aluminum wiring to the added section of
copper wire using special connectors and/or tools
designed and UL listed for joining copper to aluminum. Follow the electrical connector manufacturer's recommended procedure. Aluminum/copper connection must conform with
local codes and industry accepted wiring practices.
Wire sizes and connections must conform with the rating of the appliance as specified on the model/serial rating plate. The model/serial plate is located behind the filter on the rear wall of the range hood.
Wire sizes must conform to the requirements of the National Electrical Code, ANSl/NFPA 70 (latest edition), or CSA Standards C22.1-94, Canadian Electrical Code, Part 1 and C22.2 No. 0-M91 (latest edition) and all local codes and
ordinances.
31/4,,x 10,,
(8.3 x 25.4 cm)
elbow
m_ 6ft(1.Sm)
Maximum Recommended Length = 35 ft (10.7 m)
1 - 90° elbow 8 ft (2.4 m) straight
1 - wall cap Length of 31/4'' x 10" (8.3 cm x 25.4 cm)
system
Wall cap
= 5.0 ft (1.5 m) = 8.0 ft (2.4 m) = 0.0 ft (0.0 m) = 13.0 ft (3.9 m)
6
INSTALLATIONINSTRUCTIONS
NOTE: For vented installations, it is recommended that the vent system be installed before hood is installed.
Before making cutouts, make sure there is proper clearance within the ceiling or wall for exhaust vent.
1. For vented installations, determine which venting method to use: roof or wall.
2. Select a flat surface for assembling the range hood. Place covering over that surface.
r
Excessive Weight Hazard
Use two or more people to move and install range hood.
Failure to do so can result in back or other injury.
3.
Using 2 or more people, lift the range hood and set it upside down onto covered surface.
4.
If cabinet has recessed bottom, add wood filler strips on each side. Install screws to attach filler strips in locations shown.
Wood filler strips (recessed cabinet bottoms only)
y,oom,j \
2.
To wire through top: Mark a line 71/2'' (19.0 cm) from the right of the centerline on
the underside of the cabinet. Mark the point on this line that is 2" (5.0 cm) from back wall. Drill a 11¼'' (3.0 cm) diameter hole
through the cabinet at this point.
7 1/2"
(19 cm) ,
To wire through rear wall:
Mark a line 71/2'' (19.0 cm) from the right of the centerline on the wall. Mark the point on this line that is %" (1.9 cm) from
underside of cabinet. Drill a 11¼'' (3.0 cm) diameter hole through wall at this point.
'1!
i
i i
Centerlne
2" (5.1cm)
from wall, not cabinet
frame
-'.....IH I÷ ll
3" (7.6 cm) Wall
Determine Wiring Hole Location
Cut only one 1V4"(3.2 cm) diameter wiring access hole. See Step 2 for wiring hole location instructions. Either wiring hole can
be used.
1. Determine and clearly mark a vertical centerline on the wall and cabinet in the area the vent opening will be made.
f
I
A. Centerline
(I
Centerline
Style 1 - Cut Openings for 31/4'' x 10" (8.3 cm x 25.4 cm) Rectangular Vent System
Roof Venting
To make a 4" x 101/2'' (10.2 cm x 26.7 cm) rectangular cutout
on the underside of cabinet top and bottom:
1. Mark lines 11/2"(3.8 cm) and 51/2"(14.0 cm) from the back wall on the centerline of the underside of cabinet.
2.
Mark lines 51¼'' (13.3 cm) to the right and left of the centerline on the underside of cabinet.
3.
Use saber or keyhole saw to cut a rectangular opening for vent.
4.
Repeat steps 1-3 for the underside of the tc
CaMnet
cUt.otsi
............."11_(3.8 ore}
) of the cabinet.
,'", J,
*From wall, not cabinet frame
Wall Venting To make a 4" x 101/2'' (10.2 cm x 26.7 cm) rectangle in the wall:
1. Make 2 lines by measuring from floor 657/8"(167.3 cm) and 623/8'' (158.4 cm) or 1/8"(3.2 mm) and 3%" (9.2 cm) down from
underside of cabinet and mark on the centerline on the back wall.
2. Mark lines 51¼"(13.3 cm) to the right and left of the centerline on the wall.
3. Use saber or keyhole saw to cut a rectangular opening in the wall for the vent.
/ Centerline
I . Cabinet I/ |l , front i_ J
* ....... !..........
'/o" I i I
3%" i_4, 51/2'
(9.2 crn) i (13.3 crn)
4. Use saber or keyhole saw to cut the circular vent opening.
Circular vent opening
Cabinet
}( i
__,/',i _ ...............l _utOuts
Install Vent System
Style 2 - Cut Openings for 3%" x 10" (8.3 x 25.4 cm) Rectangular Vent to 7" (17.8 cm) Round Vent Transition
Roof Venting To make a 4" x 101/2'' (10.2 x 26.7 cm) rectangular cutout on
the underside of cabinet bottom:
1. Mark lines 11/2'' (3.8 cm) and 51/2'' (14.0 cm) from the back wall on the centerline of the underside of cabinet.
2. Mark lines 51¼"(13.3 cm) to the right and left of the centerline on the underside of cabinet.
3. Use saber or keyhole saw to cut a rectangular opening for vent.
"11/2" (3.8 Cm)
*From wall, not cabinet frame
To make a circular vent opening on the underside of the cabinet top:
1. Mark a centerline on the underside of the top of cabinet.
2. Mark a line 5" (12.7 cm) from the back wall on the underside of the top of cabinet.
3. Use a compass or a circle template to draw a circle with a diameter that is W' (0.64 cm) larger than the vent.
1. Install vent through the vent opening in upper cabinet or wall. Complete venting system according to the selected venting method. See "Venting Requirements" section.
2. Use caulking to seal exterior wall or roof opening around the cap.
@5_. ..... ± ....
/f%cl J4 (sngeHo
1. Remove bottom cover screws and bottom cover.
%%
......S
A. Bottom cover screws
B. Bottom cover
2. Remove filters. See "Range Hood Care" section.
3. Remove terminal box cover.
A. Terminal box cover screws
B. Terminal box cover
8
4,
It is recommended that the blower assembly be removed to make the range hood lighter and easier to install.
To remove:
Disconnect blower wiring plug.
i i
If using rectangular vent, attach rectangular damper/vent
connectors to the range hood using 2 black sheet metal screws.
.............................................A
A. Blower
B. Blower wiring plug
Loosen, but do not remove, knurled nuts on mounting rods. Slip rods out of blower mounting brackets.
7//• //_
J
f S
A
E %
A. Vertical vent
B.Black sheet metal screws
C. Hinge pin D. Vent knockouts
E. Horizontal vent
If using round vent, attach vent transition piece
(purchased separately) to range hood top using 2 black sheet metal screws.
NOTE: If the wall cap is directly behind the vent connector, the dampers in the connector and wall cap must not interfere with each other. Remove the vent connector damper if they
interfere.
7,
Lift the range hood up under cabinet and determine final location by centering beneath cabinet. Mark on the underside of cabinet the location of the 4 keyhole mounting slots on the range hood. Set range hood aside on a covered surface.
A
A. Mounting rod
B. Knurled nut
IMPORTANT: To avoid damage, do not grasp blower by blower wheels.
Lift blower out and set aside.
5. Depending on your installation, remove either back or top wiring knockout.
6. For vented installations:
Check that the louver cover is installed in front of hood.
Depending on your installation, remove either top or rear rectangular vent knockout. If using round vent, remove top rectangular knockout.
NOTE: Do not remove rectangular knockouts if installation of range hood is to be non-venting (recirculating).
A. Keyhole slot
8.
Use 1/8"(3 mm) drill bit and drill 4 pilot holes as shown.
A
A. Drill pilot hole
Loading...
+ 19 hidden pages