Maytag TC UPFLOW/HORIZONTAL, TL DOWNFLOW Installation Manual

TWO-STAGE CONDENSING GAS FURNACES WITH FIXED & VARIABLE SPEED BLOWERS - 95.1 % AFUE
Installation Instructions
*TC UPFLOW/HORIZONTAL MODEL
WARNING:
FIRE OR EXPLOSION HAZARD
• Failure to follow safety warnings exactly could result in serious injury or property damage.
• Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier.
• Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fi re department.
*TL DOWNFLOW MODEL
AVERTISSEMENT
RISQUE D’INCENDIE OU D’ EXPLOSION
• Le non-respect des avertissements de sécurité pourrait entraîner des blessures graves, la mort ou des dommages matériels.
• L’installation et l’entretien doivent être effectués par un installateur qualifié, un organisme de service ou le fournisseur de gazstaller, service agency or the gas supplier.
• Ne pas entreposer ni utiliser de l’essence ni d’autres vapeurs ou liquides infl ammables dans le voisinage de cet appareil, ni de tout
autre appareil.
QUE FAIRE S’IL Y A UNE ODEUR DE GAZ
• Ne pas tenter d’allumer aucun appareil.
• Ne toucher à aucun interrupteur électrique; n’utiliser aucun téléphone dans le bâtiment.
• Évacuer l’immeuble immédiatement.
• Appeler immédiatement le fournisseur de gaz en employant le téléphone d’un voisin. Respecter à la lettre les instructions du fournisseur de gaz.
• Si personne ne répond, appeler le service des incendies.
DO NOT DESTROY THIS MANUAL. KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
TABLE OF CONTENTS
IMPORTANT SAFETY INFORMATION .......................4
Upfl ow/Horizontal Furnaces ..............................15
REQUIREMENTS & CODES .......................................4
Combustion Air Quality ............................................. 5
Operation of Furnace During Construction ............... 5
Heating Load ............................................................5
Clearances to Combustible Materials ....................... 6
Installation in a Garage ............................................6
COMBUSTION AIR & VENTING REQUIREMENTS ....7
General Information .................................................8
Direct Vent Furnaces ................................................8
Conventional Furnaces - Confi ned Spaces ..............8
Air From Inside .....................................................8
Outdoor Air from a Crawl Space or
Vented Attic...........................................................9
Outdoor Air Using Vertical Ducts .......................... 9
Outdoor Air Using Horizontal Ducts ......................9
Air Directly Through an Exterior Wall .................. 10
Alternate Method of Providing Air from
Outside ............................................................... 10
Conventional Furnaces - Unconfi ned Spaces ........ 10
Category IV Venting ...............................................10
Vent Pipe Material .............................................11
Vent Pipe Length & Diameter ............................11
Vent Pipe Installation .........................................12
Outdoor Terminations - Horizontal Venting ........12
Outdoor Terminations - Vertical Venting ............13
Vent Freezing Protection ...................................13
Side Return Installations ..............................15
Bottom Return Installations ..........................15
Downfl ow Furnaces ............................................15
Acoustical Treatments ............................................15
FURNACE INSTALLATION .......................................16
General Requirements ...........................................16
Upfl ow Installation ..................................................16
Side Return Air Inlet ...........................................16
Bottom Return Air Inlet .......................................16
Downfl ow Installation ..............................................16
Installation on a Concrete Slab ..........................16
Horizontal Installation .............................................16
Inducer & Venting Options ......................................17
Inducer Assembly Rotation ................................17
Pressure Switch Tubing......................................18
Accessories ............................................................19
Finish Flange ......................................................19
Rubber Grommets ..............................................19
PVC Tee, Reducer, & Hose Barb ........................19
Condensate Drain Lines .....................................20
Bottom Panel Removal ...........................................20
Alternate Bottom Panel Removal .......................20
GAS SUPPLY & PIPING ............................................21
Leak Check ...........................................................21
High-Altitude Application ........................................22
Conversion to LP / Propane ...................................24
Existing Installations ..........................................14
Condensate Disposal ............................................14
CIRCULATING AIR REQUIREMENTS ...................... 14
Plenums & Air Ducts ............................................... 14
Supply Air Connections .......................................... 15
Upfl ow/Horizontal Furnaces ............................... 15
Downfl ow Furnaces ............................................ 15
Return Air Connections ..........................................15
2
ELECTRICAL WIRING ...............................................24
Line Voltage Wiring .................................................24
Grounding ...............................................................25
Thermostat / Low Voltage Connections .................25
Single Stage AC & Single Stage Heat
Thermostat .........................................................26
Single Stage AC & Two - Stage Heat
Thermostat .........................................................26
Two - Stage AC & Two - Stage Heat
Thermostat .........................................................26
Autostaging for Single Stage Thermostats .............26
Autostaging for Two-Stage Thermostats .................27
Heat Anticipator ......................................................27
Dehumidifi cation Options .......................................27
Table 10 -
Nominal Cooling / Heat Pump CFM -
Variable Speed .....................................36
Gas Information .....................................................37
Table 11 - Gas Flow Rates .................................37
Blower Speed Confi guration ...................................27
Fixed Speed Blower Applications .......................27
Variable Speed Blower Applications ...................27
START-UP & ADJUSTMENTS ...................................28
Pre-Start Checklist..................................................28
Start-Up Procedures ...............................................28
Verifying & Adjusting Input Rate .............................28
Verifying & Adjusting Temperature Rise .................28
Verifying Burner Operation .....................................29
Verifying Operation of the Supply Air
Limit Switch ............................................................29
OPERATING SEQUENCE .........................................29
Heating Cycle .........................................................29
Cooling Cycle .........................................................30
Fan Mode ................................................................30
DESCRIPTION OF COMPONENTS ..........................30
MAINTENANCE .........................................................30
Air Filters ................................................................31
Blower Compartment ..............................................31
Cleaning of Burners ................................................31
Heat Exchanger & Burner Maintenance .................31
Lubrication ..............................................................31
Vent System ...........................................................31
TROUBLESHOOTING ...............................................32
FIGURES & TABLES .................................................33
Figure 28 - Furnace Dimensions ........................33
Airfl ow Data ...........................................................34
Table 8 - Heating / Cooling Airfl ows &
Temperature Rises - Fixed
Table 9 -
Nominal CFM & Temperature Rises -
Speed .......34
Variable Speed .....................................35
Table 12 - Gas Pipe Capacities ..........................37
Table 13 - High Altitude Deration Chart for
Propane Gas .....................................38
Table 14 - Natural Gas Heating Values ..............38
Table 15 - High Altitude Deration Chart for
Nat. Gas - High Heating Value ...........39
Table 16 - High Altitude Deration Chart for
Nat. Gas - Low Heating Value ...........39
Electrical Information .............................................40
Figure 29 - Two-Stage Fixed Speed Motor
Control Board ....................................40
Figure 30 - Two-Stage Variable Speed
Motor Control Board ..........................40
Figure 31 - Two-Stage Furnace Control Board ....40
Figure 32 - Wiring Diagram - Two Stage Fixed
Speed Upfl ow / Horiz. Furnaces .......41
Figure 33 - Wiring Diagram - Two Stage Fixed
Speed Downfl ow Furnaces ...............42
Figure 34 - Wiring Diagram - Two Stage Variable
Speed Upfl ow / Horiz. Furnaces .......43
Figure 35 - Wiring Diagram - Two Stage Variable
Speed Downfl ow Furnaces ...............44
Venting Information .................................................45
Table 17 -
Vent Termination Clearances .............45
Figure 36 - Horizontal & Vertical Venting ............46
Figure 37 - Upfl ow Options .................................47
Figure 38 - Horizontal Options ..........................48
Figure 39 - Downfl ow Options ............................49
Location of Furnace Components .........................50
Figure 40 - Furnace Components ....................50
INSTALLATION / PERFORMANCE CHECKLIST .....52
3
IMPORTANT SAFETY INFORMATION
Please read all instructions before servicing this equipment. Pay attention to all safety warnings and any other special notes highlighted in the manual. Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored. WARNING indicates a potentially hazardous situation that if not avoided, could result in personal injury or death. CAUTION indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage.
REQUIREMENTS & CODES
WARNING:
The safety information listed below must be followed during the installation, service, and operation of this furnace. Failure to follow safety recommendations could result in possible damage to the equipment, serious per
injury or death
• This furnace must be installed in accordance with these instructions, all applicable local building codes and the current revision of the National Fuel Gas Code (NFPA54/ANSI Z223.1) or the Natural Gas and Propane Installation Code, CAN/CGA B149.1.
• Use only with type of gas approved for this furnace. Refer to the furnace rating plate.
• Install this furnace only in a location and position as specifi ed in Table 1 (page 6).
• Provide adequate combustion and ventilation air to the furnace space as specifi ed on pages 7 - 14.
• Provide adequate clearances around the vent air intake terminal as specifi ed in Figures 6 - 9 (pages 12 - 13).
• Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specifi ed on pages 10 - 14.
• Never test for gas leaks with an open fl ame. Use a commercially available soap solution to check all connections. See page 21.
• This furnace is designed to operate with a maximum external pressure rise of 0.5 inches of water column. Consult Tables 8 - 10 (pages 34 - 36), and the rating plate for the proper circulating air fl ow and temperature rise. It is important that the duct system be designed to provide the correct fl ow rates and external pressure rise. An improperly designed duct system can result in nuisance shutdowns, and comfort or noise issues.
• When supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating in the conditioned space. See pages 14 - 15.
• A gas-fi red furnace for installation in a residential garage must be installed as specifi ed on page 6.
.
sonal
• This furnace may be used for temporary heating of buildings or structures under construction. See the guidelines listed on pages 5.
• This furnace is not approved for installation in mobile homes. Installing this furnace in a mobile home could cause fi re, property damage, and/or personal injury.
• The Commonwealth of Massachusetts requires compliance with regulation 248 CMR 4.00 and 5.00 for installation of through – the – wall vented gas appliances
as follows:
1. For direct-vent appliances, mechanical-vent heating
appliances or domestic hot water equipment, where the bottom of the vent terminal and the air intake is installed below four feet above grade the following requirements must be satisfi ed:
a.) A carbon monoxide (CO) detector and alarm shall be
placed on each fl oor level where there are bedrooms. The detector shall comply with NFPA 720 (2005 Edition) and be mounted in the living area outside the bedroom(s).
b.) A (CO) detector shall be located in the room that
houses the appliance or equipment and shall:
• Be powered by the same electrical circuit as the
appliance or equipment. Only one service switch shall power the appliance and the (CO) detector;
• Have battery back-up power;
• Meet ANSI/UL 2034 Standards and comply with
NFPA 720 (2005 Edition); and Approved and listed by a Nationally Recognized Testing Laboratory as recognized under 527 CMR.
c.) A Product-approved vent terminal must be used,
and if applicable, a product-approved air intake must be used. Installation shall be in strict compliance with the manufacturer’s instructions. A copy of the installation instructions shall remain with the appliance or equipment at the completion of the installation.
d.) A metal or plastic identifi cation plate shall be mounted
at the exterior of the building, four feet directly above the location of vent terminal. The plate shall be of suffi cient size, easily read from a distance of eight feet away, and read “Gas Vent Directly Below”.
2. For direct-vent appliances, mechanical-vent heating
appliances or domestic hot water equipment where the bottom of the vent terminal and the air intake is installed above four feet above grade the following requirements must be satisfi ed:
a.) A (CO) detector and alarm shall be placed on each
fl oor level where there are bedrooms. The detector shall comply with NFPA 720 (2005 Edition) and be mounted in the living area outside the bedroom(s).
b.) The (CO) detector shall:
• Be located in the room that houses the appliance or
equipment;
• Be hard-wired or battery powered or both.
• Shall comply with NFPA 720 (2005 Edition).
c.) A product-approved vent terminal must be used,
and if applicable, a product-approved air intake must be used. Installation shall be in strict compliance
4
with the manufacturer’s instructions. A copy of the installation instructions shall remain with the appliance or equipment at the completion of the installation.
Combustion Air Quality
CAUTION:
Combustion air must not be drawn from a corrosive atmosphere.
To maximize heat exchanger life, the combustion air must be free of chemicals that can form corrosive acidic compounds in the combustion gases. The recommended source of combustion air is to use outdoor air. However, the use of indoor air in most applications is acceptable except as listed:
• If the furnace is installed as a single pipe installation in a confi ned space, it is required that the necessary combustion air come from the outdoors by way of attic, crawl space, air duct, or direct opening. For Installations in confi ned spaces, see pages 7 - 10 for combustion
air requirements.
• Installations in these locations may require outdoor air for combustion, due to chemical exposures:
Commercial buildings Buildings with indoor pools Furnaces installed in laundry rooms Furnaces installed in hobby or craft rooms
Furnaces installed near chemical storage areas
• Exposure to the following substances in the combustion air supply may require outdoor air for combustion:
Permanent wave solutions Chlorinated waxes and cleaners Chlorine based swimming pool chemicals Water softening chemicals De-icing salts or chemicals Carbon Tetrachloride Halogen type refrigerants Cleaning solvents (perchloroethylene) Printing inks, paint removers, varnishes, etc. Hydrochloric Acid Cements and glues Antistatic fabric softeners Masonry acid washing materials
Operating gas furnaces in construction environments can cause a variety of problems with the furnace. Proper use of commercial portable space heating equipment during construction is recommended. This gas furnace may be used during construction if it is not in violation of any applicable codes and the following criteria are met:
• The installation must meet all applicable codes. The furnace must be permanently installed according to the instructions supplied with the furnace including electrical supply, gas supply, duct work and venting. The furnace must be controlled by a thermostat properly installed according to the instructions supplied with the furnace and thermostat. The installation must include a properly installed fi lter in the return air system with no by-pass air. The fi lter must be inspected frequently and replaced when necessary.
• Combustion air must be supplied from outside the structure and located such that dust and gases from construction activity are not introduced into the combustion system.
• Provisions must be made to insure that condensate does not freeze in the furnace or condensate drain lines during operation and during idle times; for example, overnight if turned off. (Condensing furnaces only)
• Before occupying the structure: The filter must be replaced or cleaned, the duct work must be inspected and cleaned of any construction debris, and the furnace must be cleaned and/or repaired if found to be dirty, damaged, or malfunctioning in any way by a qualifi ed HVAC technician. The furnace shall be inspected and approved by applicable local authority even if this requires redundant inspections.
• Serial numbers for furnaces used during construction must be submitted in writing (fax and email also acceptable). This information will be used to track the long-term affects of the use during construction on furnaces. Proof of this submittal shall be available for the fi nal inspection of the furnace prior to occupancy.
• This furnace is designed to operate with return air temperatures in ranges normally found in occupied residences, including setbacks. Minimum continuous return temperature must not be below 60° F (15° C). Occasionally a temporary return temperature of 55° F (12° C) is acceptable. However, operation with a return temperature below 55° F (12° C) is not allowed.
Operation of Furnace During Construction
CAUTION:
Failure to follow these instructions will void the factory warranty and may signifi cantly reduce the life or the performance of the furnace, and/ or result in other unsafe conditions. It is the responsibility of the installing contractor to insure these provisions are met.
Heating Load
This furnace should be sized to provide the design heating load requirement. Heating load estimates can be made using approved methods available from Air Conditioning Contractors of America (Manual J); American Society of Heating, Refrigerating, and Air Conditioning Engineers; or other approved engineering methods. Excessive
oversizing of the furnace could cause the furnace and/or vent to fail prematurely. The ductwork should
be appropriately sized to the capacity of the furnace to ensure its proper airfl ow rating.
5
For installations above 2,000 ft., the furnace should have a sea level input rating large enough that it will meet the heating load after deration for altitude.
Two-stage furnaces operate at two input rates to better meet heating loads. The lower heating rate (low fi re) is 65% of the high fi re rate. The greatest degree of control over the furnace can be gained by controlling it with a two stage thermostat. This allows the thermostat to directly request either high or low fi re. However, it is possible to operate the furnace using a single stage thermostat. In this application the furnace control can be set to increase from low to high fi re, based on a timer. See Autostaging for Single Stage Thermostats (page 26).
Furnaces are properly sized to meet the expected maximum heating load. But this load occurs infrequently. So, during more moderate weather, the furnace is likely to use low fi re a considerable part of the time. This is normal and has the benefi t of quieter and more effi cient operation.
Clearances to Combustible Materials
This furnace is Design Certifi ed in the U.S. and Canada by CSA International for the minimum clearances to combustible materials. NOTE: The furnace is listed for installation on combustible or non-combustible fl ooring. However, wood is the only combustible fl ooring allowed for installation. Downfl ow models must use the appropriate subase kit when installing over a wood fl oor. To obtain model number and specifi c clearance information, refer to the furnace rating plate, located inside of the furnace cabinet.
Access for positioning and servicing the unit must be considered when locating unit. The need to provide clearance for access to panels or doors may require clearance distances over and above the requirements.
Allow 24 inches minimum clearance from the front of the unit. However 36 inches is strongly recommended.
See Table 1 for minimum clearance requirements.
Installation in a Garage
This Gas-fi red furnace may be installed in a residential garage with the provision that the burners and igniter are located no less than 18 inches (457mm) above the fl oor. The furnace must be located or protected to prevent physical damage by vehicles.
WARNING:
Do not place combustible material on or against the furnace cabinet or within 6 inches of the vent pipe. Do not place combustible materials, including gasoline or any other fl ammable vapors and liquids, in the vicinity of the furnace.
CLEARANCES TO COMBUSTIBLE MATERIALS
Left Side..................0 Inches Top ..........................0 Inches
Right Side ...............0 Inches Front ......................
4 Inches
Vent ......................... 0 Inches Back ........................ 0 Inches
Allow 24 in. minimum clearance for servicing. Recommended
clearance is 36 in.
BOTTOM
DOWNFLOW
APPLICATIONS
BACK
TOP
LEFT SIDE
FRONT
RIGHT SIDE
UPFLOW
APPLICATIONS
BACK
TOP
LEFT SIDE
FRONT
TOP
RIGHT SIDE
VENT
VENT
HORIZONTAL
APPLICATIONS
SIDE
FRONT
SIDE
Table 1. Minimum Clearances to
Combustible Materials
The information listed below is for reference purposes only and does not necessarily have jurisdiction over local or state codes. Always consult with local authorities before installing
any gas appliance.
Combustion and Ventilation Air
• US: National Fuel Gas Code (NFGC), Air for Combustion and Ventilation
• CANADA: Natural Gas and Propane Installation Codes (NSCNGPIC), Venting Systems and Air Supply for Appliances
Duct Systems
• US and CANADA: Air Conditioning Contractors Association (ACCA) Manual D, Sheet Metal and Air Conditioning Contractors National Association (SMACNA), or American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) Fundamentals Handbook
Electrical Connections
• US: National Electrical Code (NEC) ANSI/NFPA 70
• CANADA: Canadian Electrical Code CSA C22.1
Gas Piping and Gas Pipe Pressure Testing
• US: NFGC and National Plumbing Codes
• CANADA: NSCNGPIC
General Installation
• US: Current edition of the NFGC and the NFPA 90B. For copies, contact the National Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269; or American Gas Association, 400 N. Capitol, N.W., Washington DC 20001 or www.NFPA.org
• CANADA: NSCNGPIC. For a copy, contact Standard Sales, CSA International, 178 Rexdale Boulevard, Etobicoke (Toronto), Ontario, M9W 1R3 Canada
Safety
• US: (NFGC) NFPA 54–1999/ANSI Z223.1 and the Installation Standards, Warm Air Heating and Air Conditioning Systems ANSI/NFPA 90B.
• CANADA: CAN/CGA-B149.1 and .2–M00 National Standard of Canada. (NSCNGPIC)
VENT
6
COMBUSTION AIR & VENTING REQUIREMENTS
WARNING:
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed with each individual appliance connected to the venting system being placed in operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National
Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CSA B149.1, Natural Gas and Propane Installation Codes and these instructions.
Determine that there is no blockage or restriction, leakage, corrosion and other defi ciencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.
4. Close fi replace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the fl ame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel
Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Natural Gas and Propane Installation Codes.
9. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fi replace dampers and any other gas-fi red burning appliance to their previous conditions of use.
AVERTISSEMENT:
RISQUE D’EMPOISONNEMENT AU
MONOXYDE DE CARBONED
Le non-respect des consignes suivantes portant
sur chacun des appareils raccordés au système d’évacuation mis en service pourrait entraîner l’empoisennement au monoxyde de carbone ou la mort. Les consignes suivantes doivent être observées pour chaque appareil raccordé au système d’évacuation mis en service si les autres appareils raccordés au système ne sont pas en service:
1. Sceller toute ouverture non utilisée de la systéme d’évacuation;
2. S’assurer que la systéme d’évacuation présente des dimensions et une pente horizontale conformes à la norme ANSI Z223.1/NFPA 54, intitulée National Fuel Gas Code ou aux codes d’installation CSA-B149.1, ainsi qu’aux présentes instructions. S’assurer que la systéme d’évacuation n’est pas bloquée, restreinte, corrodée, qu’elle ne fuit pas et qu’elle ne présente aucun autre défaut potentiellement dangereux;
3. Dans la mesure du possible, fermer toutes les portes et fenêtres du bâtiment, et toutes les portes entre la pièce où se trouve l’appareil raccordé à la systéme d’évacuation et les autres pièces du bâtiment.
4. Fermer les registres des foyers;
5. Mettre en service les sécheuses et tout autre appareil qui n’est pas raccordé à la systéme d’évacuation. Faire fonctionner à régime maximal tout ventilateur d’évacuation, tel que les hottes de cuisinière et les ventilateurs de salles de bains. Ne pas mettre en service les ventilateurs d’été.
6. Respecter les instructions d’allumage. Mettre en service l’appareil à l’essai. Régler le thermostat de manière à ce que l’appareil fonctionne sans interruption;
7. Vérifi er s’il y a débordement à l’orifi ce d’évacuation du coupe tirage des appareils dotés d’un coupe tirage 5 minutes après l’allumage du brûleur principal. Utiliser la fl amme d’une allumette ou d’une chandelle.
8. Si l’on constate, au cours de l’un des essais qui précèdent, que l’évacuation est défi ciente, corriger le système d’évacuation conformément à la norm ANSI Z223.1/NFPA 54, National Fuel Gas Code, et (ou) aux codes d’installation CSA B149.1.
9. Après avoir déterminé que tous les appareils raccordés à la systéme d’évacuation évacuent correctement tel que prescrit ci-dessus, rouvrir les portes et les fenêtres et remettre les ventilateurs d’évacuation, les registres de foyers et tout autre appareil fonctionnant au gaz à leur état de fonctionnement initial.
7
General Information
WARNING:
Furnace installation using methods other than those described in the following sections must comply with the National Fuel Gas Code (NFGC) and all applicable local codes.
• Instructions for determining the adequacy of combustion air for an installation can be found in the current revision of the NFGC (ANSI Z223.1 / NFPA54). Consult local codes for special requirements. These requirements are for US installations as found in the NFGC.
• The requirements in Canada (B149.1) are structured differently. Consult with B149.1 and local code offi cials for Canadian installations.
This condensing furnace is certifi ed for installation either as a Direct Vent (2-pipe) or Conventional (1-pipe) appliance. Direct Vent appliances draw combustion air from the outdoors and vent combustion products back outside. Installation with air taken from around the furnace is often referred to as Conventional installation - i.e. only the vent (exhaust) pipe is provided.
Provisions must be made during the installation of this furnace that provide an adequate supply of air for combustion. The combustion air from the outside needs to be clear of chemicals that can cause corrosion. The inlet pipe should not be placed near corrosive chemicals such as those listed on page 5.
Another important consideration when selecting one or two pipe installation is the quality of the Indoor air which can sometimes be contaminated with various household chemicals . These chemicals can cause severe corrosion in the furnace combustion system. A 2-pipe installation has the additional advantage that it isolates the system from the effects of negative pressure in the house.
CAUTION:
Exhaust fans, clothes dryers, fi replaces and other appliances that force air from the house to the outdoors can create a negative pressure inside the house, resulting in improper furnace operation or unsafe conditions such as fl ame roll out. It is imperative that suffi cient air exchange with the outdoors is provided to prevent depressurization. Additional information about testing negative pressure problems can be found in the National Fuel Gas Code.
burners. NOTE: This safety device is a manually reset switch. DO NOT install jumper wires across these switches to defeat their function or reset a switch without identifying and correcting the fault condition. If
a switch must be replaced, use only the correct sized part specifi ed in the Replacement Parts List provided online.
Direct Vent Furnaces
Direct Vent (2-pipe) furnaces draw combustion air directly from the outdoors and then vent the combustion products back outside, isolating the entire system from the indoor space. It is important to make sure that the whole system is sealed and clearances to combustibles are maintained regardless of the installation being in a confi ned or unconfi ned space.
Conventional Furnaces - Confi ned Spaces
A confi ned space is an area with volume less than 50 cubic feet per 1,000 Btuh of the combined input rates of all appliances drawing combustion air from that space. Furnace closets, small equipment rooms and garages are confi ned spaces. Furnaces installed in a confi ned space which supply heated air to areas outside the space must draw return air from outside the space and must have the return air ducts tightly sealed to the furnace. Ducts must have cross - sectional area at least as large as the free area of their respective openings to the furnace space. Attics or crawl spaces must connect freely with the outdoors if they are the source of air for combustion and ventilation.
The required sizing of these openings is determined by whether inside or outside air is used to support combustion, the method by which the air is brought to the space, and by the total input rate of all appliances in the space. In all cases, the minimum dimension of any combustion air opening is 3 inches.
Air From Inside
If combustion air is taken from the heated space, the two openings must each have a free area of at least one square inch per 1,000 Btuh of total input of all appliances in the confi ned space, but not less than 100 square inches of free area (Figure 1, page 9).
Example:
If the combined input rate of all appliances is less than or equal to 100,000 Btuh, each opening must have a free area of at least 100 square inches. If the combined input rate of all appliances is 120,000 Btuh, each opening must have a free area of at least 120 square inches.
Air openings on top of the furnace and openings in closet doors or walls must never be restricted. If the furnace is operated without adequate air for combustion, the fl ame roll-out switch will open, turning off the gas supply to the
8
Vent or
Chimney
Vent or
Chimney
Ventilation Louvers at each end of attic
Attic
Insulation
Air Duct must be at least 1 sq. in. per 4,000 Btuh of total input rating.
NOTES: Each opening must be at least 100 sq. in. or 1 sq. in. per 1,000 Btuh of total input rating, whichever is greater.
Openings must start at no more than 12 inches from the top and bottom of the enclosure.
Total Input Rating
(Btuh)
Water Heater
Minimum Free Area
(Each Opening)
12” Max.
Furnace
See
Notes
See
Notes
12” Max.
Round Duct
Diameter
40,000 100 sq. In 12 inches 60,000 100 sq. In 12 inches
80,000 100 sq. In 12 inches 100,000 100 sq. In 12 inches 120,000 120 sq. In 13 inches 140,000 140 sq. In 14 inches 160,000 160 sq. In 15 inches
Figure 1. Combustion Air Drawn from Inside
Outdoor Air from a Crawl Space or Vented Attic
When the openings can freely exchange air with the outdoors, each opening shall have a minimum free area of 1 square inch per 4,000 Btuh of total appliance input. The openings shall exchange directly, or by ducts, with the outdoor spaces (crawl or attic) that freely exchange with the outdoors (Figure 2).
Ducts must extend above
Water
Furnace
Heater
Total Input Rating
(Btuh)
40,000 10 sq. In 4 inches
60,000 15 sq. In 5 inches
80,000 20 sq. In 5 inches
100,000 25 sq. In 6 inches
120,000 30 sq. In 6 inches
140,000 35 sq. In 7 inches
160,000 40 sq. In 8 inches
Minimum Free Area
(Each Opening)
attic insulation.
Air Duct must be at least 1 sq. in. per 4,000 Btuh of total input rating.
12" Max
Round Duct
Diameter
Figure 3. Combustion Air Drawn from Outside
Through Vertical Ducts
Outdoor Air Using Horizontal Ducts
If combustion air is taken from outdoors through horizontal ducts, the openings and ducts must have a minimum free area of one square inch per 2,000 Btuh of total appliance input (Figure 4). Ducts must have cross - sectional area at least as large as the free area of their respective openings to the furnace space.
Outdoor Air Using Vertical Ducts
If combustion air is taken from outdoors through vertical ducts, the openings and ducts must have a minimum free area of one square inch per 4,000 Btuh of total appliance input (Figure 3).
Vent or
Chimney
Ventilation Louvers (each end of attic)
---------
Outlet Air
Water
Furnace
Alternate
Air Inlet
---------
Ventilation Louvers For Unheated Crawl Space
Heater
Inlet Air
---------
Figure 2. Combustion Air Drawn from a Crawl
Space or Vented Attic
NOTE: Air openings shall
each have a free area of not less than one square inch per 4,000 Btuh of the total input rating of all equipment in the enclosure.
---------
Vent or
Chimney
Water Heater
Air Duct
Furnace
Air Ducts must be at least 1 sq. in. per 2,000 Btuh of total input rating.
Air Duct
Total Input Rating
(Btuh)
Minimum Free Area
(Each Opening)
Round Duct
Diameter
40,000 20 sq. In 5 inches 60,000 30 sq. In 6 inches
80,000 40 sq. In 7 inches 100,000 50 sq. In 8 inches 120,000 60 sq. In 9 inches 140,000 70 sq. In 10 inches 160,000 80 sq. In 10 inches
Figure 4. Combustion Air Drawn from Outside
Through Horizontal Ducts
9
Air Directly Through an Exterior Wall
If combustion air is provided directly through an exterior wall, the two openings must each have free area of at least one square inch per 4,000 Btuh of total appliance input (Figure 5).
Vent or
Chimney
-
-
-
-
-
See
-
-
-
-
Note
Note
12" Max.
Total Input Rating
12"
Max
See
-
-
-
-
-
-
-
-
-
(Btuh)
40,000 10 sq. In 4 inches 60,000 15 sq. In 5 inches
80,000 20 sq. In 5 inches 100,000 25 sq. In 6 inches 120,000 30 sq. In 6 inches 140,000 35 sq. In 7 inches 160,000 40 sq. In 8 inches
Water Heater
Minimum Free Area
(Each Opening)
NOTE: Each opening to outside
must be at least 1 sq. in. per 4,000 Btuh of total input rating.
Furnace
Round Duct
Diameter
Figure 5. Combustion Air Drawn from Outside
Through an Exterior Wall
Alternate Method of Providing
Air from Outside:
If acceptable under local Codes, it is permitted to provide outside air using one opening (See NFGC). Generally, confi ned spaces must have two openings in the space for combustion air. One opening must be within 12 inches of the ceiling, and the other must be within 12 inches of the fl oor. However, an alternative method recently adopted by the NFGC uses one opening within 12 inches of the top of the space. This method may be used if it is acceptable to the local codes.
Conventional Furnaces - Unconfi ned Spaces
An unconfi ned space is an area including all rooms not separated by doors with a volume greater than 50 cubic feet per 1,000 Btuh of the combined input rates of all appliances which draw combustion air from that space.
In general, a furnace installed in an unconfi ned space will not require outside air for combustion. However, in homes built for energy effi ciency (low air change rates), it may be necessary to provide outside air to ensure adequate combustion and venting, even though the furnace is located in an unconfi ned space. See example.
Example:
A space with a water heater rated at 45,000 Btuh input and a furnace rated at 75,000 Btuh requires a volume of 6,000 cubic feet [50 x (45 + 75) = 6,000] to be considered unconfi ned. If the space has an 8 foot ceiling, the fl oor area of the space must be 750 square feet (6,000 / 8 = 750).
Category IV Venting
This furnace is classifi ed as a “Category IV” appliance, which requires special venting materials and installation procedures. This section specifi es installation requirements for Conventional (1-pipe) and Direct Vent (2-pipe) piping.
WARNING:
Upon completion of the furnace installation, carefully inspect the entire fl ue system both inside and outside the furnace to assure it is properly sealed. Leaks in the fl ue system can result in serious personal injury or death due to exposure of fl ue products, including carbon monoxide.
• This furnace must be vented in compliance with the current revision of the National Fuel Gas Code (ANSI-Z223.1/NFPA54) and the instructions provided below. Consult local codes for special requirements.
• In Canada, venting shall conform to the requirements of the current (CAN/CGA B149.1 or .2) installation codes.
Consult local codes for special requirements.
The following conditions must be met:
1. The opening must start within 12” of the top of the structure and connect with the out of doors through vertical or horizontal ducts or be ducted to a crawl or attic space that connects with the out of doors.
2. The opening must have a minimum free area of 1 sq. in. per 3,000 Btu per hour of the total input rating of all equipment located in the enclosure.
3. The free area must not be less than the sum of all the areas of the vent connectors in the enclosure.
10
WARNING:
This furnace must not be vented with other appliances, even if that appliance is of the condensing type. This includes water heaters of any effi ciency. Common venting can result in severe corrosion of other appliances or their venting and can allow combustion gases to escape through such appliances or vents. Do not vent the furnace to a fi replace chimney or building chase.
For 1- pipe installations, install vent piping as described in this section and provide air for combustion and ventilation according to pages 7 - 10. Table 2 contains the maximum length of vent and combustion air piping for either type of installation.
Category IV appliances operate with positive vent pressure and therefore require vent systems which are thoroughly sealed. They also produce liquid condensate, which is slightly acidic and can cause severe corrosion of ordinary venting materials. Furnace operation can be adversely affected by restrictive vent and combustion air piping.
The inducer assembly on this furnace can be rotated to vent the fl ue products out of the left or right side of the furnace. This increases the fl exibility of which direction the vent pipe can exit the furnace.
In Canada, all plastic vent pipes and fi ttings including any cement, cleaners, or primers must be certifi ed as a system to ULC S636. However this requirement does not apply to the fi nish fl anges or piping internal to the furnace.
Vent Pipe Length & Diameter
In order for the furnace to operate properly, the combustion air and vent piping must not be excessively restrictive.
• The venting system should be designed to have the minimum number of elbows or turns.
• All horizontal runs must slope upwards from the furnace at 1/4 inch minimum per running foot of vent.
• Transition to the fi nal vent diameter should be done as close to the furnace outlet as practical.
• Always use the same size or a larger pipe for combustion air that is used for the exhaust vent.
Vent Pipe Material
Vent and combustion air pipe and fi ttings must be one of the following materials in the list and must conform to the indicated ANSI/ASTM standards. Cement must conform to ASTM Standard D2564 for PVC and Standard D2235 for ABS. PVC primer must meet standard ASTM F656. When joining PVC piping to ABS, use PVC solvent cement. (See procedure specifi ed in ASTM Standard D3138)
Materials Standards
Schedule 40PVC .............................. D1785
PVC-DWV ..........................................D2665
SDR-21 & SDR-26 .............................D2241
Table 2 indicates the maximum allowable pipe length for a furnace of known input rate, when installed with piping of selected diameter and number of elbows. To use the table, the furnace input rate, the centerline length and the number of elbows on each pipe must be known.
When estimating the length of vent runs, consideration must be made to the effect of elbows and other fi ttings. This is conveniently handled using the idea of “equivalent length”. This means the fi ttings are assigned a linear length that accounts for the pressure drop they will cause. For example: a 2” diameter, long radius elbow is worth the equivalent of 2.5 feet of linear run. A 90 degree tee is worth 7 ft.
ABS-DWV ..........................................D2661
Schedule 40 ABS ...............................F628
Foam/Cellular Core PVC ....................F891
FURNACE
MODELS
(BTU)
60,000
80,000
100,000
120,000
1. Subtract 2.5 ft. for each additional 2 inch long radius elbow, 5 ft. for each additional 2 inch short radius elbow, 3.5 ft. for each additional 3 inch long radius elbow, and 7 ft. for each additional 3 inch short radius elbow. Subtract 5 ft for each 2” tee and 8 ft for each 3” tee. Two 45 degree elbows are equivalent to one 90 degree elbow.
FURNACE
INSTALLATION
Upfl ow 90 90 90 90
Horizontal 50 90 50 90
Downfl ow 30 90 30 90
Upfl ow 90 90 90 90
Horizontal 30 90 30 90
Downfl ow 30 90 30 90
Upfl ow 60 90 60 90
Horizontal 30 90 30 90
Downfl ow 30 90 25 90
Upfl ow N/A 90 N/A 90
Horizontal N/A 90 N/A 90
Downfl ow N/A 90 N/A 90
SINGLE VENT PIPE LENGTH (FT.)
with 1 long radius elbow**
OUTLET
2” Diameter
The equivalent lengths of tees and various elbows are listed in Table 2. Measure the linear length of the vent run
DUAL VENT PIPE LENGTH (ft.)
with 1 long radius elbow on each pipe**
OUTLET
3” Diameter
*NOTES:
INLET / OUTLET
2” Diameter
INLET / OUTLET
3” Diameter
2. This table applies for elevations from sea level to 2,000 ft. For higher elevations, decrease pipe lengths by 8% per 1,000 ft of altitude.
Table 2. Vent Pipe Lengths
11
and then add in the equivalent length of each fi tting. The
18” Min.
36” Max.
total length, including the equivalent fi tting lengths, must be less than the maximum length specifi ed in Table 2.
Condensing furnace combustion products have very little buoyancy, so Table 2 is to be used without consideration of any vertical rise in the piping.
Vent Pipe Installation
CAUTION:
Combustion air must not be drawn from a corrosive atmosphere.
This furnace has been certifi ed for installation with zero clearance between vent piping and combustible surfaces. However, it is good practice to allow space for convenience in installation and service.
• The quality of outdoor air must also be considered. Be sure that the combustion air intake is not located near a source of solvent fumes or other chemicals which can cause corrosion of the furnace combustion system. (See list of substances on page 5).
• Route piping as direct as possible between the furnace and the outdoors. Longer vent runs require larger diameters. Vent piping must be sloped upwards 1/4” per foot in the direction from the furnace to the terminal. This is to ensure that any condensate fl ows back to the condensate disposal system.
• If a Direct Vent (2-pipe) system is used, the combustion air intake and the vent exhaust must be located in the same atmospheric pressure zone. This means both pipes must exit the building through the same portion of exterior wall or roof as shown in Figures 6 - 9 (pages 12 - 13) and Figure 37 (page 46).
• Piping must be mechanically supported so that its weight does not bear on the furnace. Pipe supports must be installed a minimum of every 5 feet along the vent run to ensure no displacement after installation. Supports may be at shorter intervals if necessary to ensure that there are no sagging sections that can trap condensate. It is recommended to install couplings along the vent pipe, on either side of the exterior wall (Figure 37). These couplings may be required by local code.
• If breakable connections are required in the combustion air inlet pipe (if present) and exhaust vent piping, then straight neoprene couplings for 2” or 3” piping with hose clamps can be used. These couplings can be ordered through your local furnace distributor. To install a coupling:
1. Slide the rubber coupling over the end of the pipe that
is attached to the furnace and secure it with one of the hose clamps.
2. Slide the other end of the rubber coupling onto the
other pipe from the vent.
3. Secure the coupling with the second hose clamp,
ensuring that the connection is tight and leak free.
Outdoor Terminations - Horizontal Venting
Vent and combustion air intake terminations shall be installed as depicted in Figures 6 & 7 (page 13) and in accordance with these instructions:
• Vent termination clearances must be consistent with the NFGC, ANSI 2223.1/NFPA 54 and/or the CSA B149.1, Natural Gas and Propane Installation Code. Table 17 (page 45) lists the necessary distances from the vent termination to windows and building air intakes.
• All minimum clearances must be maintained to protect building materials from degradation by fl ue gases as shown in Figure 7.
• Vent and combustion air intake terminations must be located to ensure proper furnace operation and conformance to applicable codes. A vent terminal must be located at least 3 feet above any forced air inlet located within 10 feet. This does not apply to the combustion air inlet of a direct vent (two pipe) appliance. In Canada, CSA B149.1, takes precedence over these instructions. See Table 17 (page 45).
• For optimal performance, vent the furnace through a wall that experiences the least exposure to winter winds.
• The vent termination shall be located at least 3 ft. horizontally from any electric meter, gas meter, regulator and any relief equipment. These distances apply ONLY to U.S. installations. In Canada, CSA B149.1, takes precedence over these instructions.
• Do not install the vent terminal such that exhaust is directed into window wells, stairwells, under decks or into alcoves or similar recessed areas, and do not terminate above any public walkways.
• If venting horizontally, a side wall vent kit is available according to the pipe diameter size of the installation. For 2 inch pipe use side wall vent kit #904617, and for 3 inch pipe use kit #904347. Please follow the
instructions provided with the kit.
18” Min.
36” Max.
Exhaust vent
option C
Mounting kit faceplate
secured to wall with screws
(both pipes)
Exhaust vent
option B
Combustion
air inlet
12’ min. to maximum
expected snow level
(both pipes)
Figure 6. Inlet and Exhaust Pipe Clearances
90° Elbow
(all positions)
Exhaust vent
option A
8” Min.
36” Max.
12
• Concentric vent termination kits are available for use with these furnaces. For 2 Inch pipe use kit #904177 and for 3 inch pipe use kit # 904176. Please follow the
instructions provided with the kit.
• When the vent pipe must exit an exterior wall close to the grade or expected snow level where it is not possible to obtain clearances shown in Figure 6, a riser may be provided as shown in Figure 8. Insulation is required to prevent freezing of this section of pipe. See Table 3 for vent freezing protection.
Outdoor Terminations - Vertical Venting
Termination spacing requirements from the roof and from each other are shown in Figure 9. The roof penetration must be properly fl ashed and waterproofed with a plumbing roof boot or equivalent fl ashing. Vent and combustion air piping may be installed in an existing chimney which is not in use provided that:
• Both the exhaust vent and air intake run the length of the chimney.
Direct vent terminal
50,000 Btuh
or less
Mechanical
9 in.
Note 2
Mechanical draft vent terminal
NOTES:
1. All dimensions shown are minimum requirements.
2. Exterior vent terminations must be located at least 12” above the maximum expected snow level.
4 ft
Note 2
Figure 7. Vent Locations
19" Max.
(See Note)
Support
Outside
Wall
4 ft
draft vent
terminal
12 in.
Note 2
12" Above
Maximum
Expected
Snow Level
1/2" Armaflex Insulation or Equivalent (if required)
Mechanical
draft vent
12 in.
than 50,000 Btuh
3 ft.
Forced air inlet
Direct vent
terminal - more
terminal
Less
10 ft.
than
• The top of the chimney is sealed and weatherproofed.
• The termination clearances shown in Figure 9 are maintained.
• No other gas fi red or fuel-burning equipment is vented through the chimney.
Vent Freezing Protection
CAUTION:
When the vent pipe is exposed to temperatures below freezing (i.e., when it passes through unheated spaces, chimneys, etc.) the pipe must be insulated with 1/2 inch thick sponge rubber insulation, Armafl ex-type insulation or equivalent. Insulating pipe is important to avoid condensate icing.
• Table 3 lists the maximum length of fl ue pipe that can travel through an unconditioned space or an exterior space. The total vent length must not exceed the lengths noted in Table 2 (page 11). For Canadian installations, please refer to the Canadian Installation Code (CAN/ CGA-B149.1 or 2) and/or local codes.
• For extremely cold climates or for conditions of short furnace cycles (i.e. set back thermostat conditions) the last 18 inches of vent pipe can be reduced. It is acceptable to reduce from 3” to 2-1/2”, 3” to 2”, or 2” to 1-1/2” if the total vent length is at least 15 feet in length and the vent length is within the parameters specifi ed in Table 2 (page 11). The restriction should be counted as 3 equivalent feet. Smaller vent pipes are
Winter Design
Temperature
20 45 70
020 70
-20 10 60
*NOTE: Insulation thickness greater than 3/8 inch, based on an
R value of 3.5 (ft x F x hr) / (BTU x in.)
Table 3. Vent Protection
Elbows on the combustion air
inlet must be positioned pointing
away from the exhaust vent.
Maximum Flue Pipe Length (FEET)
in Unconditioned & Exterior Spaces
Without Insulation With Insulation*
Plumbing Vent Roof Boot
(Both Pipes)
12” Above Maximum
Expected Snow Level
(Both pipes)
Combustion Air
Exhaust Vent
NOTE: Vent Configuration to Provide 12" Minimum height above Snow Level.
Figure 8. Alternate Horizontal Vent Installation
8" Min. 36" Max.
Figure 9. Vertical Vent Termination
13
less susceptible to freezing, but must not be excessively restrictive. The length of the 2 inch pipe must not be longer than 18 inches.
• If furnace is installed horizontally, make sure the drainage port on the in-line drain assembly is pointed downward to ensure proper drainage of condensate. See Figure 39 on page 48.
• To prevent debris or creatures from entering the combustion system, a protective screen may be installed over the combustion air intake opening. The screens hole size must be large enough to prevent air restriction.
Existing Installations
When an existing furnace is removed from a vent system serving other appliances, the existing vent system may not be sized properly to vent the remaining appliances (For example: water heater). An improperly sized venting system can result in the formation of condensate, leakage, or spillage. The existing vent system should be checked to make sure it is in compliance with NFGC and must be brought into compliance before installing the furnace.
NOTE: If replacing an existing furnace, it is possible you will encounter an existing plastic venting system that is subject to a Consumer Product Safety Commission recall. The pipes involved in the recall are High Temperature Plastic Vent (HTPV). If your venting system contains these pipes DO NOT reuse this venting system! This recall does not apply to other plastic vent pipes, such as white PVC or CPVC. Check for details on the CPSC website or call their toll-free number (800) 758-3688.
CIRCULATING AIR REQUIREMENTS
WARNING:
Do not allow combustion products to enter the circulating air supply. Failure to prevent the circulation of combustion products into the living space can create potentially hazardous conditions including carbon monoxide poisoning that could result in personal injury or death.
All return ductwork must be secured to the furnace with sheet metal screws. For installations in confi ned spaces, all return ductwork must be adequately sealed. When return air is provided through the bottom of the furnace, the joint between the furnace and the return air plenum must be air tight.
The surface that the furnace is mounted on must provide sound physical support of the furnace with no gaps, cracks or sagging between the furnace and the fl oor or platform.
Return air and circulating air ductwork must not be connected to any other heat producing device such as a fi replace insert, stove, etc. This may result in fi re, explosion, carbon monoxide poisoning, personal injury, or property damage.
Condensate Disposal
The method for disposing of condensate varies according to local codes. Consult your local code or authority having jurisdiction.
Each of the condensate drain lines must be J-trapped using fi eld supplied parts. After the condensate lines are J-trapped, they may be combined together into a single run to the drain. The drain lines must be routed downward to ensure proper drainage from furnace.
Neutralizer kit P/N 902377 is available for use with this furnace. Please follow the instructions provided with
the kit.
Plenums & Air Ducts
• Plenums and air ducts must be installed in accordance with the Standard for the Installation of Air Conditioning and Ventilating Systems (NFPA No. 90A) or the Standard for the Installation of Warm Air Heating and Air Conditioning Systems (NFPA No. 90B).
• Tables 8 - 10 (pages 34 - 36) contain the maximum airfl ow and temperature rise data for fi xed and variable speed motors. If the maximum airfl ow is 1,600 CFM or more, it is recommended that two openings be used for return air on upfl ow furnaces. Downfl ow furnaces can only use one return opening.
• It is recommended that the outlet duct contain a removable access panel. The opening should be accessible when the furnace is installed in service and shall be of a size that smoke or refl ected light may be observed inside the casing to indicate the presence of leaks in the heat exchanger. The cover for the opening shall be attached in such a way as to prevent leaks.
• If outside air is used as return air to the furnace for ventilation or to improve indoor air quality, the system must be designed so that the return air is not less than 60° F (15° C) during operation. If a combination of indoor and outdoor air is used, the ducts and damper system must be designed so that the return air supply
14
to the furnace is equal to the return air supply under normal, indoor return air applications.
• When a cooling system is installed which uses the furnace blower to provide airfl ow over the indoor coil, the coil must be installed downstream (on the outlet side) of the furnace or in parallel with the furnace.
• If a cooling system is installed in parallel with the furnace, a damper must be installed to prevent chilled air from entering the furnace and condensing on the heat exchanger. If a manually operated damper is installed, it must be designed so that operation of the furnace is prevented when the damper is in the cooling position and operation of the cooling system is prevented when the damper is in the heating position.
• It is good practice to seal all connections and joints with industrial grade sealing tape or liquid sealant. Requirements for sealing ductwork vary from region to region. Consult with local codes for requirements specifi c to your area.
Supply Air Connections
The supply air must be delivered to the heated space by duct(s) secured to the furnace casing, running full size and without interruption.
Upfl ow and Horizontal Furnaces
To attach the supply air duct to the furnace, bend the furnace fl anges (Figure 29, page 33) upward 90° with a pair of wide duct pliers. Position the duct on top of the furnace and secure together with sheet metal screws. The screws must penetrate the sheet metal casing and furnace fl ange. Tape or seal all seams if required by local code.
Downfl ow Furnaces
To attach the supply air duct to the downfl ow furnace, position the furnace over the duct and secure together with sheet metal screws. The screws must penetrate the duct and furnace cabinet.
Return Air Connections
In applications where the supply ducts carry heated air to areas outside the space where the furnace is installed, the return air must be delivered to the furnace by duct(s) secured to the furnace casing, running full size and without interruption.
Upfl ow Horizontal Furnaces
For upfl ow installations, the return air ductwork may be connected to the left side, right side, or bottom. The bottom panel (Figure 29) must be installed for left or right return air. NOTE: Do not use the back of the furnace
for return air.
the opening in the side and secure together with sheet metal screws. The screws must penetrate the duct and furnace cabinet.
WARNING:
The solid base of the furnace must be in position when the furnace is installed with side return air ducts. Removal of all or part of the base could cause circulation of combustible products into the living space and create potentially hazardous conditions, including carbon monoxide poisoning that could result in personal injury or death.
Bottom Return Installations
The bottom panel (Figure 29) must be removed from the bottom of the furnace for bottom return air. If bottom panel is installed, go to page 15 for removal instructions. Position the furnace over the return air duct and secure together with sheet metal screws. The screws must penetrate the duct and furnace cabinet.
Downfl ow Furnaces
To attach the return air duct to the furnace, bend the furnace fl anges (Figure 29, page 33) upward 90° with a pair of wide duct pliers. Position the duct on top of the furnace and secure together with sheet metal screws. The screws must penetrate the sheet metal cabinet and furnace fl ange. Tape or seal all seams if required by local code.
Acoustical Treatments
Damping ducts, fl exible vibration isolators, or pleated media-style fi lters on the return air inlet of the furnace may be used to reduce the transmission of equipment noise eminating from the furnace. These treatments can produce a quieter installation, particularly in the heated space. However, they can increase the pressure drop in the duct system. Care must be taken to maintain the proper maximum pressure rise across the furnace, temperature rise and fl ow rate. This may mean increasing the duct size and/or reducing the blower speed. These treatments must be constructed and installed in accordance with NFPA and SMACNA construction standards. Consult with local codes for special requirements. For best sound performance, be sure to install all the needed gaskets and grommets around penetrations into the furnace, such as for electrical wiring
Side Return Installations
To attach the return air duct to the left or right side of the furnace, punch out the four knockouts (Figure 29) from the preferred side of the furnace. Using sharp metal cutters, cut an opening between all four knockouts to expose the blower assembly. Position the return air duct over
15
FURNACE INSTALLATION
*TC series gas furnaces offer a wide range of installation options, including installation in the upfl ow or horizontal positions with either right, left, or upfl ow return air. The *TL series gas furnaces may only be installed as a down fl ow application.
General Requirements
• The furnace must be leveled at installation and attached to a properly installed duct system. See Table 1 (page 6) for the required clearances needed to move the furnace to its installation point (hallways, doorways, stairs, etc).
• The furnace must be installed so that all electrical components are protected from water.
• The furnace must be installed upstream from a refrigeration system. (If applicable)
• The cabinet plug must always be used to close the hole in the side of the furnace when rotating the inducer.
• The furnace requires special venting materials and installation procedures. See pages 10 -14 for venting guidelines and specifi cations.
Upfl ow Installation
letter of the furnace. For ‘B’, ‘C’, and ‘D’ size cabinets use Kit #904911. Please follow the instructions provided
with the kit.
A downfl ow sub-base kit is not necessary if the furnace is installed on a factory or site-built cased air conditioning coil. However, the plenum attached to the coil casing must be installed so that its surfaces are at least 1” from combustible construction.
Installation on a concrete slab
1. Create an opening in the fl oor according to the dimensions in Figure 10.
2. Position the plenum and the furnace as shown in Figure 11.
Opening in concrete floor
“A”
“B”
WARNING:
The furnace must not be installed directly on carpeting, tile, or any combustible material other than wood fl ooring.
Side Return Air Inlet
*TC series gas furnaces are shipped with the bottom panel installed (Figure 29). If the upfl ow furnace is installed using both side return air inlets, the bottom panel must not be removed. The bottom panel must be in place if the bottom of the furnace is not being used as a return.
Bottom Return Air Inlet
If the *TC series gas furnace is installed using the bottom as a return air inlet and 1 side return, the bottom panel (Figure 29) must be removed.
Downfl ow Installation
WARNING:
The furnace must not be installed directly on carpeting, tile, or any combustible material other than wood fl ooring.
WARNING:
Failure to install the downfl ow sub-base kit may result in fi re, property damage or personal injury.
To install the furnace on combustible fl ooring, a special sub-base is required. Downfl ow sub-base kits are factory supplied accessories and are listed according to the cabinet
Cabinet Size Dim. “A” Dim. “B”
B 16 5/8 19 1/4 C 20 1/8 19 1/4 D 23 5/8 19 1/4
NOTE: Dimensions shown in Inches.
Figure 10. Cutout Dimensions
Concrete
Floor
Figure 11. Furnace on a Concrete Slab
Furnace
Sheet
Metal
Plenum
Horizontal Installation
WARNING:
The furnace must not be installed directly on carpeting, tile, or any combustible material other than wood fl ooring.
The *TC series gas furnace can be installed horizontally (Figure 12, page 17) in an attic, basement, crawl space or alcove. It can also be suspended from a ceiling in a basement or utility room in either a right to left airfl ow or left to right airfl ow as shown in Figure 13.
16
Loading...
+ 36 hidden pages