TECHNICAL SPECIFICATIONS
Model MSH4BD-KA Series
M120 Product Line
High Efficiency R-410A Heat Pump
13 SEER — 3.5, 4, and 5 Ton Capacities
The MSH4BD-KA Series of
heat pumps offers exceptional
performance. The unit, when
combined with our engineered
coils or air handlers, offers a
full line of quality, split system
cooling equipment.
Features and Benefits
• Designed using galvanized steel – with a polyester urethane coat
finish. The 950 hour salt spray finish resists corrosion 50% better than
comparable units.
• Micro-Channel Coils – All aluminum coils in all models which provides
high corrosion resistance.
• Permanently Lubricated Motor – A heavy duty PSC motor for long lasting
reliability and quiet operation. Requires no maintenance and is completely
protected from rain and snow.
• Removable Top Grille Assembly – Allows ease of service from the top
without disconnecting fan motor leads.
• High Pressure Switch – Protects against abnormally high system
pressures. Auto-reset feature prevents nuisance service visits.
• Liquid Line Filter Drier – Included with unit, field installed.
• One Piece Top/Orifice – Designed for maximum airflow and quiet
operation.
• Easy Compressor and Control Access – Designed to make servicing
easier for the contractor, access panels are provided to all controls and
the compressor from the side of the unit.
• Composite Base Pan - Absorbs sound and is corrosion resistant. Composite
is also stronger and lighter than steel.
• Fixed Orice – Integrated in liquid line service valve for easy change-out.
2
DIMENSIONS/OUTDOOR SECTION
MSH4BD-KA 042KA 048KA 060KA
H 45 1/2 45 1/2 45 1/2
W 30 3/4 30 3/4 30 3/4
D 30 3/4 30 3/4 30 3/4
Air Discharge
Allow Adequate Clearance for Airow
D
W
IDENTIFICATION CODE
EX: MSH4BD-036KA
M S H 4 B D - 036 K A
H
M = Maytag
S = Split
H = Heat Pump
Design Series
Product
Identifier
BD = Braze 13 SEER
Nominal Capacity
(000) BTU
Revision
Electrical Code
K = 208/230-60-1
3
PHYSICAL AND ELECTRICAL SPECIFICATIONS / OUTDOOR UNITS
13 SEER — High Efficiency — Single Phase
Model Number MSH4BD-KA 042KA 048KA 060KA
SKU 922308L 922309L 922310L
Volts-Cycles-Phase (1) 208/230-60-1
Electrical
Data
Condenser
Data
Refrigerant suction line O.D.
Note: Liquid line is 3/8” O.D. for
entire length
Refrigerant Charge: (R-410A) in ounces for outdoor
unit, indoor unit, and 15' line set. (4)
Approximate Weight (lbs.)
Sound
Rating db
(1) Operating Voltage Range: 187v min. - 253v max.
(2) HACR Type Circuit Breakers may be used.
(3) Requires 7/8” to 1-1/8” reducer from line to unit.
(4) Additional charge for line sets above 15 feet.
Values based on suction line as follows with 3/8” liquid line.
a) 3/4” = 0.6 oz. per additional foot.
b) 7/8” = 0.7 oz. per additonal foot.
c) 1 1/8 = 0.8 oz. per additional foot.
* For other line set dimensions, refer to the Application
Guidelines for Refrigerant Lines Addendum
Total Amps 19.4 21.3 27.7
Delay Fuse Max. (2) 40 45 60
Min. Circuit Ampacity 23.9 26.3 34.3
Area 25.0 24.4 24.4
Coil
Fan Motor
Compressor Data
Max Total Sound Level 75 75 75
Rows-FPI 1-14 1-16 1-16
Tube Dia MC
Type PSC
Amps 1.5 1.5 1.5
HP 0.25 0.25 0.25
RLA 17.9 19.8 26.2
LRA 112.0 109.0 134.0
0-24 ft. 7/8 7/8 7/8
25-39 ft. 7/8 7/8 1-1/8 (3)
40-75 ft. 7/8 7/8 1-1/8 (3)
113.0 115.0 114.0
Net 182 204 206
Ship 191 213 215
ACCESSORIES - CONDENSING UNIT
Start Assist Kit - 912933
Provides additional starting torque for the compressor motor when operating with low line voltage or high operating
temperatures.
Outdoor Thermostat - 913852
Two stage logic provides ability to lock out electric strips
down to balance point and bring on in stages.
Snow Stand Kit - 920636
Extreme Wind Condition Mounting Kit - 920900
Fan Delay Kit (TDR) - 918476
4