Maytag MMW5530DAW Installation Guide

Built-In 30" Electric
il_il r,__i iE_i[o
il_ ii." !_ii[o]_
in cm
A 30 MIN 76.20 MIN
B 24 MIN 60.96 MIN C 47 + 1/16 119.38 +.16
D 24 MIN 60.96 E 28-1/2 + 1/16 72.39 + .16
F 47-5/8 120.97 G 29-3/4 75.57
H 24-7/16 62.07 I 4 to 20 10.2 to 50.8
* Hole must be cut as close to corner of cabinet as possible.
Combination Wall Ovens
403 WEST FOURTH STREET, NORTH |
NEWTON, IA 50208
COMBINATION WALLOVEN CUTOUT
r'--D _.._
C
1
v
!
I
J
Do not block air intake slots along bottom of oven.
INSTALLATION
1. Cut hole in cabinet to mount oven. Cutout in cabinet should be level and straight.
NOTE: There are no provisions to level the unit after it is installed. An oven that is not level could
cause poor baking results.
2. Install plywood floor as shown above.
3. Attach unit to the cabinet with 4 No. 8" flat head screws supplied inside of envelope containing
these instructions. Pre-drill holes in cabinet for attachment screws using 1/8" drill. Oven
mounting holes are provided in side trim.
4. See instructions "Electrical Connections" for electrical hook-up.
5. See figure 1 for lower trim installation.
6. See User's Manual for operating instructions.
FIGURE 1
Remove lower screws from hinge receptacle plates. Align lower trim and reinstall screws.
NOTE: Lower trim overlaps front edge of cabinet by 9/16".
CAUTION
For European style cabinets (flush front) the required clearance for operation of the oven door is minimum
spacing of 7/8" between the cutout and the door, hinge or drawer of the cabinet. Some built-in cabinets may not be wide enough, due to their construction, to allow this installation.
8101 P565-60
(07-03-00)
ELECTRICAL CONNECTIONS
Unit to be properly circuit protected and wired according to local electrical code and National Electrical Code.
It is advisable that the electrical wiring and hookup be accomplished by a competent electrician.
120/240 VAC or 120/208 VAC 60 Hz. See serial plate on
each unit for power requirements.
Improper installation of the grounding
circuit can result in a risk of electric shock,
The neutral of the lower unit is grounded to the frame through the green or solid grounding wire. (The green
and the white wires are twisted together at the termination of the conduit.) If used on new branch-circuit
installations (1996 NEC), mobile homes, recreational vehicles, or in an area where local codes prohibit
grounding through the neutral conductor, untwist or disconnect the green wire and connect the green wire to
ground in accordance with local code. Connect the white neutral to the service neutral. Connect all wires to the
branch circuit with approved connectors. Use copper or aluminum wire. If aluminum wire is used, use connectors
recognized for joining aluminum to copper. The chart below recommends the minimum circuit
protection and wire size if the appliance is the only unit on the circuit.
RECOMMENDEDMINIMUM
KW RATING CIRCUITPROTECTION WIRESIZE
ONSERIALPLATE INAMPRES (AWG)
0 48 20 12
4.9 - 6.9 30 10
7.0 - 9.9 40 8
10.0 - 11.9 50 8
12.0 - 14.9 60 6
Consult a qualified electrician or serviceman if the
grounding instructions are not completely understood, or
if doubt exists as whether the appliance is properly
grounded.
SERVICE
Interrupt the source of electricity to the unit when
attempting to repair or service the oven. Failure to do this could result in a dangerous or even fatal shock.
IMPORTANT SAVE FOR LOCAL ELECTRICAL INSPECTOR'S USE
Loading...
+ 4 hidden pages