Triple Bay Conventional Gas
Prostyle TM Grill Cooktop
=JENN-AIR,I
Model JGD8348CDP
Dimensions shown in both inches and centimenters
NOTICE TO INSTALLER: Leave these instructions with the appliance.
NOTICE TO CONSUMER" Retain these instructions for future reference.
13_6"
34.11 cm
403WEST FOURTHSTREET,NORTH • NEWTON,IA5020
Blower may be
rotated for horizontal
or vertical direction by
loosening nuts
around blower inlet.
Accessible inside
ventilation chamber.
SEE PAGE 2
)_
I
I
I
3 13/16+ [118.90 cm]
[9.68 cm] _
[40.16 cm] ' '_ IL 3 5/16"
M_N { BOTTOU 3 APPLIANCE [8 41 cm]
CL,R*NC,........ ,--?-II 'I--PRESSURE,.+----.JLBO+,O,OE
REQUIRED ........ _ I IREGULATOR EACH END II BURNER BOX
SELECT APPROPRIATE
DUCT CUTOUT
INSTALLATION INSTRUCTIONS.)
(SEE DUCTING
[38.1 cm]
f APPLIANCE15" PRESSURE REGULATOR
46 13/16"
FOR CUTOUT
DIMENSIONS
i .BLOWER--"II_W,RE COVER I
II I cox I
I LDRAIN JAR I LEND OF
I I I_BURNER
AI_I 14" I 28 11/16 ° __l BOX
INSTRUCTIONS TO INSTALLER:
• Dimension "A" - provide 2" min. (5.08 cm) cabinet clearance to motor for cooling purpose.
• NOTE: Where possible, 6" (15.54 cm)is recommended for motor/blower service.
• Side Clearance: Grills installed near a side wall must allow a minimum clearance of
8" (20.32 cm).
• Access must be provided to remove and empty grease container.
[35.86 cm] I [72+87 cm] -I
8101 P658-60
(11-04-00)
CABINET and COUNTERTOP CUTOUTS
9[ (116.2 cm) r
I _ 22Y8" Ref
45¾"
E
(F__CUTLINES _ (58.11 cm) r i
©
I
' t
(17.46-22 cm)
\
*Recommend 8" for
Custom Cabinetry.
NOTE: LOWER CONTROL
PANEL IS REQUIRED
IF THIS DIMENSION
EXCEEDS 53/_'' (14.60 cm).
SEE PAGE 3 ABOUT
REINFORCING CABINET FRONT
CABINET
(FRONTVIEW)
See cutout suggestions 1-4 on page 6.
NOTE: Tolerances for Cutout
Dimensions are _+1/16 in (.16 cm)
IT
I-
0.
LU
t'_ =
LU
I--
Z
8
As required by installation
(116.2 cm)l __
< <[ (76.2 cm) 453/k" t
< 46 13/16"
(118,90
C0UNTERTOP
I,
/ \
. E &4oo
o3._ Lo
TOP
VIEW
\
REMOVE CORNER SUPPORTS AS NEEDED
TYP. (4) PLS.
Installing Cabinetry Over Your
Jenn-Air Grill
Minimum horizontal clearance between the edge of the
appliance and combustible construction extending from
the cooking surface to 18" (45.7 cm) above the cooking
surface is:
13/4" (4.45 cm) at rear
8" (20.32 cm) at sides
NOTE: This is not the recommended clearance, but
minimum allowable clearance.
__
18"
@
(45._ cm)
8"--'1
(20.3 cm)
MIN. CLEARANCE
*A
= 30" (76.2 cm) minimum vertical clearance
between cooking surface and construction above
the appliance.
B
= 13" (33.02 cm) maximum depth of cabinets
installed above cooking top.
Avoid use of cabinets above cooktop for storage space to
eliminate associated potential hazards such as reaching
over open flames.
Dotted lines indicate range
hood construction.
* To eliminate the risk of burns or fire by reaching over
heated surface units, cabinet storage space located
above the surface units should be avoided. If cabinet
storage is to be provided, the risk can be reduced by
installing a range hood that projects horizontally a
minimum of 5 inches beyond the bottom of the
cabinets.
Cabinets Above Cooking Top
Maximum depth of cabinets installed above cooking top is
3 inches.
CAUTION:SOME CABINETS AND BUILDING
MATERIALS ARE NOT DESIGNED TO WITHSTAND
THE HEAT PRODUCED BY THE NORMAL SAFE
COLORATION OR DAMAGE, SUCH AS DELAMINA,
TION, MAY OCCUR:
Installation Of Appliance
In The Commonwealth Of Massachusetts
This product must be installed by a licensed plumber or
gas fitter when installed within the Commonwealth of
Massachusetts.
A "T" handle type manual gas valve must be installed in
the gas supply line to this appliance.
NOTE: For some cabinet styles, it may be necessary to
reinforce the front of the cabinet by attaching a brace
from front to rear inside the cabinet under the Burner Box.
Install ductwork per ducting instructions provided. Duct
openings in cabinet are shown in the drawing on page 1.
Make electrical and gas connections as described below
in this section of the instructions.
A flexible gas connector, when used, must not exceed a
length of three (3) feet / 36 inches.
Follow accompanying ducting instructions carefully.
This appliance is designed to always be vented outdoors.
The Countertop Cutout, Cabinet Front Cutout and Duct
Opening should be prepared according to the illustration
on pages 1 and 2.
Install the Lower Control Panel in the bottom of the
Cabinet Cutout as shown using screws from Hardware
pack. (Figure 1).
Top View LOWER CONTROL PANEL
Figure 1
Position unit in the Countertop Cutout. Main Control Panel
should overlap top of Lower Control Panel as shown.
(Figure 2).
The installation of this appliance must conform with local
codes or, in the absence of local codes, with the latest
edition of the National Fuel Gas Code, ANSI Z.223.1 USA
or current CAN/CGA-B149 INSTALLATION CODE.
The electrical supply required is 110/120-volt, A.C., 15
amp, 60 Hz. This appliance is equipped with a grounded
type power cord. A grounded outlet must be provided. It is
recommended, for convenience, this outlet be located in
the area shown in the shaded illustration. This appliance,
when installed, must be electrically grounded in
accordance with local codes or, in the absence of local
codes, with the latest edition of the National Electrical
Code ANSI/NFPA No. 70 USA or current CSA
STANDARD C22.1 Canadian Electrical Code part 1.
User may experience occasional circuit tripping if Ground
Fault Circuit Interrupter (GFCI) outlet or breaker is in use.
®® @ @® @@
10 1/16"
(25.56 cm)
4,
46 13/16" (118.90 cm)
Figure 2
Servicing Cooktop
When servicing cooktop it is necessary to remove the
main top, prior to removing the control panel.
LOWER CONTROL PANEL
Connecting Appliance To Gas Supply
A QUALIFIED SERVICEMAN OR GAS APPLIANCE
INSTALLER MUST MAKE THE GAS SUPPLY
CONNECTION. Leak testing of the appliance shall be
conducted by the installer according to the instructions
given.
Install a manual shutoff valve in an accessible location in
the gas line external to this appliance for the purpose of
turning on or shutting off gas to the appliance.
Make the gas connection to the inlet of the appliance
pressure regulator on this appliance with a 1/2" male pipe
thread. Use an approved pipe joint compound resistant to
the action of LP gas at pipe connections. Test all joints for
gas leaks with a soap and water solution or other
accepted leak detection means. Never test for gas leaks
with an open flame.
CAUTION: WARRANTY IS VOID ON JENN.AIR
EQUIPMENT INSTALLED OTHER THAN AS
RECOMMENDED BY MANUFACTURERI RECOM-
MENDED WALL CAPS AND TRANSITIONS MUST BE
STALLATION.
,WARNING
Air Shutter Adjustment
This appliance is shipped from the factory with air shutters
adjusted for use with Natural Gas. If further adjustment is
necessary, or to reset for use with LP, adjust air shutters as
follows:
Grill Burner and Surface Burner
Cartridge Air Shutters
(See Illustrations "A" & "B")
The left hand air shutter controls the rear half of the burner.
The right hand shutter controls the front half. Access to air
shutters on the surface burner cartridge may be found
through openings on the bottom of the cartridge housing.
Slide air shutters backward or forward to increase or
decrease the size of the air opening. Air shutters fit snugly,
so ascrewdriver blade or needle nose pliers may be required
to make this adjustment (see illustration).
Observe change in flame appearance as the air shutter is
moved. Adjustment is satisfactory when a clearly defined,
even blue flame results at the high flame setting. The snug
fit of the air shutter assures it will remain positioned correctly.
Grill Burner Air Shutter and Surface Burner
(if so equipped)
ELECTRICAL GROUNDING INSTRUCTIONS
THIS APPLIANCE IS EQUIPPED WITH A THREE-
PRONG GROUNDING PLUG FOR YOUR
PROTECTION AGAINST SHOCK HAZARD AND
SHOULD BE PLUGGED DIRECTLY INTO A
PROPERLY GROUNDED RECEPTACLE. DO NOT
CUT OR REMOVE THE GROUNDING PRONG FROM
THIS PLUG.
"%;"
INSERT SCREWDRIVER
BLADE IN SLOT AND TWIST
WITH SLIGHT PRESSURE TO
ALLOW AIR SHUTTER TO
SLIDE EASILY
Illustration "A"
On any burner, closing the air shutter too far will cause the
flame to become soft and yellow tipped. Opening the air
shutter too wide will cause the flame to blow away from the
burner ports. Proper adjustment will produce a sharp, clearly
defined, even blue flame.
AIR SHUTTER
Illustration "B"
Important Installation Suggestions
1. Chamfer all exposed edges of decorative laminate to
prevent damage from chipping•
2. Radius corners of cutout and file to insure smooth
edges and prevent corner cracking•
3. Rough edges, inside corners which have not been
rounded and forced fits can contribute to cracking of the
countertop laminate•
4. Countertop must be supported within 31 of cutout•
On any burner, closing the air shutter too far will
cause the flame to become soft and yellow tipped•
Opening the air shutter too wide will cause the flame
to blow away from the burner ports. Proper adjustment
will produce a sharp, clearly defined, even blue flame•
Low Flame Adjustment
(See Illustration "C")
This appliance is shipped from the factory with low and
medium flame settings adjusted for use with Natural Gas.
If further adjustment is necessary, or to re-adjust for use
with LP, proceed as follows:
1. Light burner and set control knob for low flame•
2. Remove control knob from valve stem.
CAUTION:NEVER USE A METAL BLADE TO PRY
KNOB OFF: IF KNOB CANNOT BE EASILY
REMOVEDI TUCK THE FOLDS OF A CLOTH
DISHTOWEL UNDER THE KNOB AND PULL THE
TOWEL UPWARD WITH STEADY, EVEN PRESL
SURE.
Pressure Testing
The maximum gas supply pressure for the appliance
pressure regulator supplied on this appliance is 141 W.C.
The test pressure for checking this appliance pressure
regulator must be at least 61 W.C. for Natural Gas, and at
least 111 W.C. for LP. It is shipped from the factory set for
Natural Gas at 51 W.C.
This appliance and its individual shutoff valve must be
disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in
excess of 1/21 PSIG (3.5 k Pa).
This appliance must be isolated from the gas supply
piping system by closing its individual manual shutoff
valve during any pressure testing of the gas supply piping
system at test pressures equal to or less than 1/21 PSIG
(3.5 k Pa).
Appliance Pressure Regulator
Conversion
(See Illustration "D")
This unit is supplied with a Maxitrol Appliance Pressure
Regulator• Follow the instructions in illustration "D".
MAXITROL APPLIANCE PRESSURE REGULATOR
APPLY DOWNWARD
FINGER PRESSURE
AT DISC EDGES TO
ER_I LP REPLACE PIN IN CAP
CONVERT
_,1_ AND PI_..- ° SIDEWARD
NAT t ,,--r"° N.__A_A PRESSURE TO I LP
CAP I T I_ APPLY
i_oJ I , REMOVE PIN , --
FINGER
3. Insert a slender, thin-blade screwdriver into the recess
at center of valve stem and engage blade with slot in
adjusting screw•
4. Turn center stem adjusting screw to set flame size.
•.. clockwise to reduce•
•.. counterclockwise to increase•
5. Replace control knob when adjustment is completed•
Proper adjustment will produce a stable, steady blue flame
of minimum size. The final adjustment should be checked
by turning knob from high to low several times without
extinguishing the flame•
This adjustment, at low setting, will automatically provide
the proper flame size at medium setting•
CLOCk, VISE
I1 FLAME SIZE
Illustration "C"
TO REDUCE
COU NTERCLOC_,VISE
TO INCREASE FLAME
SIZE
_ _FROM CAP @
Illustration "D"
High Altitude Notice
The specified gas burner ratings typically apply to
elevations up to 2000 feet. For higher altitudes, the rates may
need to be reduced to achieve satisfactory operation• A
local certified gas servicer will be able to advise if a reduction
is necessary.
Conversion To LP Gas
This appliance is shipped from the factory equipped for
use with Natural Gas. To convert it from Natural Gas for
use with LP Gas, perform steps 1 through 4.
1. Remove Natural Gas orifice hoods. Install color coded
orifice hoods supplied. Located in a pack attached to
the outer plenum area of this appliance.
(See Illustration "E", below, and LP Gas Conversion
instructions page 8).
2. Invert cap in convertible pressure regulator (if so
equipped) located at entrance to gas manifold.
3. Adjust air shutters on individual burners for proper
flame appearance.
4. Adjust low flame setting at each burner by turning
adjustment screw in center of valve stem.
To make these conversions adjustments follow the
instructions and illustrations ("A" through "E", pages
5-7).
This appliance is shipped from the factory with orifice
hoods drilled for use with Natural Gas. To convert from
Natural Gas to LP, apply a 1/21 open-end wrench to hex
section of orifice hood. Turn counterclockwise to remove.
Save the Natural Gas orifice hoods just removed from this
appliance for future use. Install color coded orifice hoods
supplied. (See LP Gas Conversion instructions above and
page 8). Turn clockwise to install. Hold dimension
specified in illustration "E".
1/2t OPEN END
WRENCH
TURN
CLOCKWISE
TO TIGHTEN
COU NTETRUc_NcKwlSE _
TO REMOVE
ORIFICE HOOD
Illustration "E"
Apply a non-corrosive leak detection fluid to all joints
and fittings in the gas connection between the supply
line shut-off valve and the range. Include gas fitting
and joints in the range if connections were disturbed
during installation. Check for leaks! Bubbles appearing
around fittings and connections will indicate a leak. If a
leak appears, turn off supply line gas shut-off valve,
tighten connections, turn on the supply line gas shut
off valve, and retest for leaks. Never test for gas leaks
with an open flame.
,WARNING
Gas leaks may occur in your system and result in a
dangerous situation. Gas leaks may not be detected
by smell alone. Gas suppliers recommend you
purchase and install a UL approved gas detector.
Install and use in accondance with the
manufacturer's instructions
Control Settings
The size and type of cookware and the amount and type
of food being cooked will influence the setting needed for
best cooking results. The setting indicated should serve as
a guide while you become familiar with your cooktop.
Use the HI flame setting to
quickly bring foods to a boil or to
begin a cooking operation. Then
reduce to a lower setting to
continue cooking. Never lease
food unattended over a HI flame
setting.
Med setting is used to continue a
cooking operation. Food will not
cook any faster when a HI flame
setting is used than that needed
to maintain a gentle boil.
Remember, water boils at the
same temperature whether boiling
gently or vigorously.
Use LO setting to keep food at
serving temperatures without
further cooking You may find that
some cooking may take place if
the cookware is covered.
__,._,,,v.._
|
TO CONVERTAPPLIANCEFOR USEWITH PROPANEGAS
Natural GasTo Propane Gas (LP) ConversionInstructions
Models- JGD8348CDP
Manifold - Propane Gas pressure required - 10" W.C.
Incoming Propane Gas pressure required to appliance
pressure regulator- 11"- 12" W.C.
Propane Conversion Orifice Hoods are supplied with this
model.
Propane Gas input specified - 46,000 BTU/hr.
BURNER
Left Rear (LR)
Left Front (LF)
Center Rear (CR)
Center Front (CF)
Right Rear (RR)
Right Front (RF)
BTU/hr
7500
7500
6500
9000
6500
9000
ORIFICE
#66
#66
#68
#63
#68
#63
DIAMETER
.033
.033
.031
.037
.031
.037
JGD8348CDP
COLOR
Zinc
Zinc
Red
Blue
Red
Blue
TO CONVERTAPPLIANCEFOR USEWITHNATURALGAS
PropaneGas(LP)ToNaturalGas
Conversion Instructions
If this appliance has been converted for use with LP Gas,
each of the following modifications must be performed to
convert the unit back to Natural Gas.
Model- JGD8348CDP
Manifold - Natural Gas pressure required - 5" W.C.
Incoming Natural Gas pressure required to appliance
pressure regulator - 6" - 7" W.C.
Natural Gas input specified - 56,000 BTU/hr.
A. Replace all orifice hoods - Perform steps 1through 4 on
page 7. Locate the (6) six Natural Gas hoods (with small
numbers stamped on their sides saved from the original
Natural Gas unit). Page 5 Illustration "E". The two
hoods with .0520 (#55 orifice) stamped on them are for
the left front and left rear burners. The four hoods with
the .0595 (#53 orifice) stamped on them are for the two
right burners.
To make these conversion adjustments follow the
instructions and illustrations ("A" through "E") pages
5-7.
B. Invert cap in appliance pressure regulator (see
Illustration "D", page 6). With the appliance installed,
the appliance pressure regulator is located on the right
underside of the appliance at the inlet to the gas
manifold. Identify the type of appliance pressure
regulator on the unit and follow the instructions in the
appropriate illustration.
C. Adjust low flame setting for each burner. Follow the
instructions for burner low flame adjustment on page 7
to increase the simmer flame size.
BURNER ...........................i BTU/hr ORIFICE ....
Left Rear (LR) 8,000 #55
Left Front (LF) 8,000 #55
Center Rear (CR) 10,000 #53
Center Front (CF) 10,000 #53
Right Rear (RR) 10,000 #53
Right Front (RF) 10,000 #53
DIAMETER
.0520
.0520
.0595
.0595
.0595
.0595
JGD8348CDP
COLOR
Green
Green
Brass
Brass
Brass
Brass
MINIMUMSPACINGREQUIREMENT
GAS GRILL COOKTOPS
For installing a Triple Bay Downdraft Cooktop in combination with another Downdraft Cooktop, the mini-
mum spacing between adjacent units must be provided, as shown, for satisfactory performance.
4 3/8"
\ /
(11.1 cm)
Pk
\ /
/G\
ANY
PROSTYLE COOKTOP
i 18"
(45.7 cm)
\/
I o.I
\/
--I/ .1
ANY DOUBLE BAY
<
(45.7 cm)
18"
A 31 li
(11.1 cm)
;I
(SINGLE, DOUBLE OR TRIPLE BAY
\/
\/
Ic,,
\I
\I
/ok
PROSTYLE COOKTOP
ANY SINGLE BAY
16 1/8"
(41 cm)
\ /
/ok
%=,
N:' N:' N:' ':iF _ ':ii"
PROSTYLE COOKTOP
10
\ /
S,,
\/
REQUIREDADJUSTMENTSATTIME OF INSTALLATION
The installation of this appliance must conform with local codes, or in the absence of local codes, with
the latest edition of the National Fuel Gas Code ANSI Z223.1 USA or current CAN/CGA-B149 Installation
Code.
This range was manufactu red for use with Natural Gas. If LP gas is the fuel of choice, follow the conversion
to LP procedure found in the installation instructions.
Test all external connections for gas leaks. Never test for gas leaks with an open flame.
Test all electrical connections.
Adjust all air shutters for proper flame.
Adjust all valves for low flame settings.
[_ Test the ventilation system for proper installation.
If a problem exists with the downdraft system, check the ducting installation to make sure it conforms to
the Jenn-Air specifications. Most downdraft system problems are attributed to poor ducting practices.
Contact your installer if the ventilation system will not remove smoke or cooking fumes from well trimmed
cuts of meat.
If ventilation problems persist contact your authorized Jenn-Air Service Contractor.
11