Maytag MGC4436BDW11 Installation Guide

SEALEDGASCOOKTOPS
30" and36"
IMPORTANT: Dimensions Shown in Both Inches and Centimeters.
IMPORTANT: Be sure the appliance being installed is equipped for the gas to be supplied. Refer to serial plate on
underside of burner box for this information. Do not attempt to convert this appliance for use with a gas other than the type specified.
.............. DIMENSIONS ..............
inches cm
B 1915/16 + 1/16 50.6 + 0.2 C 21/8 + 1/16 5.4 + 0.2
D 51/4 + 1/16 13.3 + 0.2 E 291/2 + 1/16 74.9 + 0.2
F 21 + 1/16 53.3 + 0.2 G 313/16 + 1/16 9.7 + 0.2
H 12 1/4 + 1/16 31.1 + 0.2
DIMENSIONS
inches cm
B 1915/16 +__1/16 50.6 +__0.2 C 21/8 +__1/16 5.4 +__0.2
F
\
D 51/4 +__1/16 13.3 +__0.2 E 36 +__1/16 91.4 +__0.2
F 21 +__1/16 53.3 +__0.2 G 3 13/16 +__1/16 9.7 +__0.2
H 151/4 +__1/16 38.7 +__0.2
CUTOUT DIMENSIONS
ARE CRITICAL
"-. 1,1"_ _
H-_'_
SPECIAL WARNING:
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE, MAINTENANCE OR USE OF RANGE CAN RESULT IN SERIOUS INJURY OR PROPERTY DAMAGE.
NOTICE TO INSTALLER: Leave these instructions with the appliance.
NOTICE TO CONSUMER: Retain these instructions for future reference.
W10187822
(01-08-00)
Location Of Your Appliance
Locate this appliance away from combustible materials such as window curtains and combustible wall
decorations. Minimum horizontal clearance between the edge of the
appliance and combustible construction extending from the cooking surface to 18" (45.72 cm) above the cooking
surface is:
1.0" (2.54 cm) at rear 6" (15.24 cm) at sides
(Dimensions apply to both 30" and 36" wide models).
Installing Cabinetry
Cooktop
A = 30" (76.2 cm) minimum
vertical clearance
between cooking surface and construction above
the appliance. This
clearance may be reduced to not less than
24 inches (60.96 cm) by protecting the underside
of the combustible material or metal cabinet
above the cooking surface with not less than
1/4 inch (.635 cm) insulating millboard
covered with sheet metal not less than 0.0122 inch
thick.
Over Your
A
L
FIGURE.2
2.54cm
FIGUREI
15.24cm
Preparation Of Countertop
The countertop cutout must be prepared according to the
illustration on page 1 of these instructions.
CAUTION: Cutout dimensions are critical. Dimensions
must be measured and cut accurately to within + 1/16" (.159 cm) to ensure proper fit.
Important Preparation Suggestions
1. Chamfer all exposed edges of decorative laminate to prevent damage from chipping.
2. Radius corners of cutout and file to insure smooth edges and prevent corner cracking. Recommend
1/4" or 3/8" diameter drill in each corner.
3. Rough edges, inside corners which have not been
rounded and forced fits can contribute to cracking of
the countertop laminate.
4. Countertop must be supported within 3" (7.62 cm) of cutout.
B = 13" (33.02 cm) maximum depth of cabinets installed
above cooktop.
Avoid use of cabinets above cooktop for storage space to
eliminate associated potential hazards such as reaching over open flames.
WARNING
THISPRODUCTSHOULDNOT BE INSTALLEDBELOWA
VENTILATIONTYPEHOOD SYSTEMTHATDIRECTSAIR
INA DOWNWARDDIRECTION.
(SEEFIGURE)
THESESYSTEMSMAYCAUSE
IGNITIONANDCOMBUSTION PROBLEMSWITHTHE GAS
BURNERSRESULTINGIN
PERSONALINJURYANDMAY
AFFECTTHECOOKING
PERFORMANCEOFTHEUNIT.
NOTE:THEFIGUREMAYNOTACCURATELYREPRESENT YOURRANGEORCOOKTOP;HOWEVER,THISWARNING
APPLIESTOALL GASCOOKINGPRODUCTS.
Required Adjustments At Time Of installation
The installation of this appliance must conform with local codes, or in the absence of local codes, with the latest edition
of the National Fuel Gas Code ANSI Z223.1 USA or current CAN/CGA-B149 INSTALLATION CODE. r-i This appliance was manufactured for use with Natural Gas. If LP gas is the fuel of choice, follow the conversion to
LP procedure found in the installation instructions. r-i Test all external connections for gas leaks. Never test for gas leaks with an open flame. I-] Test all electrical connections.
Checkthecooktopserialplatetoseeifthecooktopis approvedforinstallationinmobilehomesand/or
recreationalparktrailers.Serialplateislocatedonthe bottomoftheunit.
Ifapproved,thefollowingitemsareapplicable: Mobile Homes
The installation of a range designed for mobile home installation must conform with the Manufactured Home
Construction and Safety Standard, Title 24 CFR, Part 3280 [formerly the Federal Standard for Mobile Home
Construction and Safety, Title 24 HUD, (Part 280)] or, when such standard is not applicable, the Standard for
Manufactured Home Installations, ANSI A225.1/N FPA 501A, or with local codes.
In Canada the range must be installed in accordance with the current CSA Standard C22.1 - Canadian Electrical Code Part 1 and Section Z240.4.1 - Installation
Requirements for Gas Burning Appliances in Mobile Homes (CSA Standard CAN/CSA - Z240MH).
Recreational Park Trailers
The installation of a range designed for recreational park trailers must conform with state or other codes or, in the absence of such codes, with the Standard for
Recreational Park Trailers, ANSI Allg.5-1atest edition. In Canada the range must be installed in accordance with
CAN/CSA - Z240.6.2 - Electrical Requirements for R.V.'s (CSA Standard CAN!CSA - Z240 RV Series) and Section Z240.4.2 - Installation Requirements for Propane
Appliances and Equipment in R.V.'s (CSA Standard CAN/CSA - Z240 RV Series).
All supply piping, except as noted, should use common National Pipe Thread (N.P.T.). For all pipe connections
use an approved pipe joint compound resistant to the action of LP gas.
CAUTION: Warranty is void on Maytag equipment installed other than as recommended by manufacturer.
This appliance is designed for use with the appliance gas pressure regulator supplied with this appliance. It must be
installed inthe gas line ahead of the gas manifold entrance. It ispreset for use with natural gas and must be
converted, as described on pages 7 and 8, for use with LP gas. (See figures 6 - 11).
This appliance is designed to operate at a pressure of 5 inches of water column (36" models), 4 inches of water
column (30" models) on natural gas or, if converted for use with LP gas (propane or butane), 10 inches water
column. Make sure this appliance is supplied with and adjusted for the type of gas for which it is designed.
This appliance was adjusted at the factory for use with natural gas. If, at any time, this appliance isto be used with a different type of gas, all of the conversion
adjustments described on pages 7 and 8 must be made by a qualified service technician before attempting to
operate the cooktop on that gas. Natural gas should be supplied to the appliance pressure regulator at a line
pressure between 6 and 14 inches of water column or, if converted for LP gas, between 11 and 14 inches.
installation Of Appliance
The installation of this appliance must conform with local codes or, in the absence of local codes, with the National
Fuel Gas Code, ANSI Z223.1-Latest Edition, or, in Canada, CAN/CGA-B149 Installation Code, Latest Edition.
This appliance, when installed, must be electrically grounded in accordance with local codes or, in the
absence of local codes, with the National Electrical Code ANSI/NFPA No. 70-Latest Edition, or, in Canada, current
CSA Standard C22.1 Canadian Electrical Code, Part 1.
in The Commonwealth Of Massachusetts
This product must be installed by a licensed plumber or
gas fitter when installed within the Commonwealth of
Massachusetts. A ,,.i_,,handle type manual gas valve must be installed in
the gas supply line to this appliance.
A flexible gas connector, when used, must not exceed a length of three (3) feet / 36 inches.
WARNING
If the line pressure supplying the appliance pressure regulator exceeds 14" water column (any gas), an
external regulator must be installed in the gas line ahead of the appliance regulator to reduce the pressure to no
more than 14" water column. Failure to do this can result in malfunction and damage to the appliance.
Insure this appliance is adjusted for the type of gas supplied to it and that the gas supply pressure to the
appliance regulator is within the proper pressure range.
NOTE: In Canada, gas utilization codes prohibit use of street elbows. Use standard pipe elbows and make modifications to these instructions as necessary.
Connecting Appliance To Gas Supply
A QUALIFIED SERVICE TECHNiCiAN OR GAS APPLIANCE iNSTALLER MUST MAKE THE GAS
SUPPLY CONNECTION. Leak testing of the appliance shall be conducted by the installer
according to the instructions given.
Gas supply piping MUST conform to all local, municipal and state building codes and local utility
regulations.
IF NO OTHER APPLIANCE IS TO BE iNSTALLED BELOW THIS COOKTOP
Join the appliance pressure regulator supplied with this appliance to the entrance threads of the Gas Manifold.
The appliance regulator is marked with a directional arrow indicating correct direction of gas flow. Ensure the appliance regulator is installed with the arrow pointing
toward the gas manifold entrance. Tighten the appliance regulator to 20 to 30 ft-lbs of torque.
Never tighten to more than 35 ft-lbs of torque. Always use an approved pipe joint compound resistant to the
action of LP gas.
Install the appliance in its counter cutout. Make the gas connection to the inletof the appliance
pressure regulator with 1/2" NPT male pipe threads.
iLLUSTRATiVE GAS SUPPLY PiPiNG
(NOOTHER APPLIANCE BELOW COOKTOP)
BURNER BOX
U MANIFOLD (3/8"N.P.T.)
I
I_ APPLIANCE
, REGULATOR
I
I
ALL SUPPLY SIDE
=T-
ELBOW
ENTRANCE
_ PRESSURE
PIPE JOINTS
1/2" N.P.T.
FIGURE3
MANUAL
SHUTOFF
VALVE
TO GAS
iNLET
Install a manual shut-off valve in an accessible location in the gas line ahead of the appliance pressure regulator
and external to this appliance for the purpose of turning on or shutting off gas to the appliance.
Make additional pipe connections as necessary ahead of the shut-off valve to the gas supply source. Assure all
pipe joint connections are gas tight.
Apply a non-corrosive leak detection fluid to all joints and fittings in the gas connection between the supply line
shut-off valve and the cooktop. Include gas fittings and joints in the cooktop if connections were disturbed
during installation. Check for leakst Bubbles appearing around fittings and connections will indicate a leak. If a
leak appears, turn off supply line gas shut-off valve,
tighten connections, turn on the supply line gas shut off valve, and retest for leaks. Never test for gas leaks with
an open flame.
WARNING
Gas leaks may occur in your system and result in a dangerous situation. Gas leaks may not be detected by
smell alone. Gas suppliers recommend you purchase and install an UL approved gas detector. Install and use in
accordance with the manufacturer's instructions.
Alternative Piping Methods To Connect Appliance To Gas Supply
A TRAINED SERVICE TECHNiCiAN OR GAS APPLIANCE iNSTALLER MUST MAKE THE GAS
SUPPLY CONNECTION. Leak testing of the appliance shall be conducted by the installer
according to the instructions given.
Unless prohibited by local codes or ordinances, a new A.G.A. - Certified, flexible metal appliance connector may be used to connect this appliance to its gas supply. The
connector must be no more than 5 feet in length. Per figure 5, use appropriate flare union adapter at each end
of the flexible connector. If a flexible connector is used assure that both the appliance pressure regulator and
manual shut-off valve are joined solidly to other permanent hard piping (either gas supply or the appliance manifold) so as to be physically stationary. See
illustrations below.
CAUTION: Do not aiternpt t0 attach the flex bid
connector directlY to an external piPe thread. I Connection requires flare union adapters.
Apply a non-corrosive leak detection fluid to all joints and fittings in the gas connection between the supply line
shut-off valve and the range. Include gas fittings and
joints in the range if connections were disturbed during
installation. Check for leaks! Bubbles appearing around
fittings and connections will indicate a leak. If a leak
appears, turn off supply line gas shut-off valve, tighten connections, turn on the supply line gas shut off valve,
and retest for leaks. Never test for gas leaks with an open
flame.
Pressure Testing
The appliance must be isolated from the gas supply piping system by closing its individualmanual shut-off
valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 pounds
per square inch (3.5 kPa). This appliance, as well as its individual shut-off valve,
must be disconnected from the gas supply piping system during any pressure testing of the system at test
pressures in excess of 1/2 pounds per square inch (3.5 kPa).
When checking appliance regulator function, make certain pressure of natural gas supply is between 6 and 14 inches of water column or, if converted for LP gas,
between 11 and 14 inches of water column.
iLLUSTRATiVE ALTERNATIVE PiPiNG
Entrance
| |
_ _!="- AppliancePressure
Regulator,Supplied ._ _"[_1; J
(Observe directionality ._::_ ,_)
ofGasFlow) _ - -_, '_
!;_ _ FlareUnion Elbow
-,,_1-Flare UnionAdaptor _ Adaptor
1/2" N.P.T.Flexible _ _ ApplianceConnector
J
_ _ 3/8"N.P.T.
_f4_ _--- 3/8" N.P.T.Flexible
|
_ _" Flare Union Adaptor
|
'_- Gas Shut-Off Valve
|
-"_-1/2" N.P.T. Pipe (Stationary Supply Pipe)
NO APPLIANCE
MOUNTED BELOW
THiS COOK'FOP
FIGURE4
|
_-_F- Flare Union
|
Regulator,Supplied
-qF- ppliance Pressure
(Observe
directionality of Gas
| Flow)
i-1/2" N.P.T. Pipe
Nipple
I
Gas Shut-Off Valve
I
1/2" N.P.T.Pipe (Stationary Supply
Pipe)
Adaptor
Electrical Wiring information
This appliance is equipped with a grounded type power cord. A grounded outlet must be provided. It is
recommended, for convenience, the outlet be located within either the shaded area or the cross hatched area
shown in figure 5. User may experience occasional circuit tripping if Ground
Fault Circuit Interrupter (GFCI) outlet or breaker is in use.
In planning any installation, note that the free length of this appliance's power cord, extending beyond a point
3-3/4" (9.53 cm) left of the nominal center of the rear wall of the burner box, when viewed from the front of the unit,
is approximately 46" (117 cm).
WARNING
WARNING
Electrical Grounding Instructions
This appliance is equipped with a (three-prong)
grounding plug for your protection against shock hazard and should be plugged directly into a
properly grounded receptacle. Do not cut or remove the grounding prong from this plug.
=================================================================================================================
iiiiiiiiiiii!_ii!!i!!!i!!!!!!!!!!!!!!!!_!ii!!!!iiiiii!iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii!!
iii!ii!!!!!i!i__i________N_______;;;______________;______ii;i_____i_iii!iii!!!!iiiiiiiiiiiiii_iiiii!!i!i!!ii____
i;________i_)_iiiiiiiii______iii_iiiiiiiiiiiiiiiiiiiiii_iiiii}i_i__i__________ii__iii_i__i__ii_;__iiii}ii___iiiii !iii_ii_!_!iiiiiiiiiiiiiiiiiiiiiiiiiiii_ii_iiiiiiiiiiiiiiiiiiiiiiiiiiii_!!;!_!_!_!_iiii_iii
!!!!!!!!!!!!!!_;_iiiiiiiiiiiiiiiiiiiiiiii!iiiiiiiiiiiiiii_iii_;_;;_;_;_;_;_iiii..
THIS APPLIANCE MUST BE DISCON-
NECTED FROM ITS ELECTRICAL SUPPLY
AT THE WALL RECEPTACLE BEFORE
SERVICING THE APPLIANCE.
3 13/16"
9.7 cm
_!!!!iiiiiiiiiii_iiiiiiiiii_iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii_iiii_iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii!!!!!!_ _!!!i!i!!iiiiii_iiiiiiiiiiiiiii!!!ii!g!!!i!!i!iiiiiiiiii_iiii_i!_i!iii!!iii_iiii!iiiiiiiiii_i_!i!i_i!_!_!!!!_!!:.
i.........i.iiiiiiiiiiiiiii!iiiiii!_iiiiiiiiiiii!_!!!i!!i_i_i_i_i_iii_$_i_ii_29 a/8"
!iiiiiiiii_ii__i_}_;_iiiiiiii!iiiiiiiiiiiiii; 74.61 cm
!i_iii_;;_;_!!;_;_;_;_;_;_;_;_;_;;_;_;i_;;;;;;;_;_i1_i;_i;i_i_;;_!;_!!!i!!!!!i!i!!!iii!!!i
!!!!!!i!!i___i__i_iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii_iiiiiiiiiiiiiiiiiiiii___!!!!;!
!_ii_iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii_ii_ii_[_i
!!!_!!iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii_ii_iiiiiiii_i_ii_i_i_ii_i_!_i_ii_iii_iii_ii
_!!!!!!!i!ii!iiiiii_i_iii_iii_iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii_iii_iii_iiii_[_[i_!!!!!!!! _!!!!!!!!!i_!iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii_i_ii_!_!!!!_!_!!!_!!_!_
i_._iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii!iiiiiiiiiii!!!i_;_
_iiiiii_iii[ii[[i!![!_!!!!![!_!![!!!!!!!!!!!!!!!!!!!!!!!!!![!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!_i_iiiiiiiiii_iii
3 1/2" (8.89 cm) WIDE __J 4" MAX.
SLATSWHEN A WALL
OVEN IS INSTALLED _>_y._'<_x_o_ z,_2_;_
BELOW80" MODEL CABINET BOTTOM T
FIGURE 5
10.16
_t
37 3/16"
94.46 cm
cm
Converting Appliance For Use With LP Gas
WARNING
Propane conversion is to be performed by a
AUTHORIZED SERVICER (or other qualified agency) in
accordance with the manufacturer's instructions and all codes and requirements of the authority having
jurisdiction. Failure to follow instructions could result in
serious injury or property damage. The qualified agency performing this work assumes responsibility for this
conversion.
WARNING
Electrical power and gas must be turned off
prior to conversion.
This appliance was adjusted at the factory for use with natural gas. To convert itfor use with LP gas (propane or
butane), each of the following modifications must be performed: (A, B, and C)
A. REPLACE ALL ORIFICE SPUDS
Step 1: Remove the grates and burner caps. Step 2: Remove burner base by removing 2 screws.
(See figure 6).
Step 3: Firmly press 9/32" (or 7mm) nut driver over the
orifice spud (figures 6 and 7) and loosen spud by turning counter- clockwise. Carefully lift nut
driver out of burner throat. Orifice spud should be captured in the nut driver. Repeat steps 2 &
3 for each burner.
Installation Of LP Orifice Spud
0.91 _]
o.91_ J
Step 4:
Step 5:
Step 6:
0.91
_Z] 0.91
O
O O
O O
L _Z]0.97
FIGURE8
Locate the LP orifice spud packet included in
the literature packet. The spuds have small
numbers stamped on the side. This number codes the orifice diameter and its correct
burner location. Figures 8 and 9 show the correct LP orifice spud location.
Carefully installthe orifice spud in the appropriate burner throat by turning clockwise
to tighten. Tighten to a torque of 15 to 20
inch-lbs.
Replace burner base, caps, and grates.
Tighten screws (do not cross thread) to 25-30
in Ibs.
REMOVAL OF ORiFiCE SPUD
Burner Cap,
Locating
Ring
Head
Oriflce==_
Orifice Holder
FIGURE6
Holder O ""
Electrode
ART#9215-156-0
FIGURE7
Step 7:
091_ J
Save the orifices removed from the appliance
for future use.
(.__ 1_o.91,,
ARTet_mS- ig$.0
0.91
FIGURE9
B. INVERT CAP IN APPLIANCE PRESSURE
REGULATOR (See figure 10)
With the appliance installed, the appliance regulator should be located as shown in figures 3 or 4.
CONVERSION OF APPLIANCE APPLYDOWNWARD
PRESSURE REGULATOR FINGERPRESSURE
CONVERTE APPLYSIDEWARD
_'AND PiN J TOREMOVEPiN
NAT' J'_ NAT J J LP
L.j_ -- _
C. LOW FLAME ADJUSTMENT (See figure 11)
This appliance is shipped from the factory with low and
high flame settings adjusted for use with natural gas.
To set for use with LP proceed as follows:
R._LP REPLACEPiNiNCAP.
CAP I _ FINGERPRESSURE
.t/" (_ FROMCAP
ATDISCEDGESTO
tr
After adjusting the screw the burner should produce a stable, steady blue flame of minimum size. The setting
should be checked by turning knob from high to low several times without extinguishing the flame.
This operation will automatically provide the proper flame size at medium setting.
After Conversion Steps A, B and C have been completed, check the appearance of each burner flame at the Hi and
Lo settings against figure 12. If the flames appear too large or too small, review each step to make sure it was
completed correctly.
FLAME APPEARANCE AT Hi AND LO
1. Remove control knob from valve stem.
CAUTION: NEVER USE A METAL BLADE TO
PRY KNOB OFE IF KNOB CANNOT BE EASILY
R EMOV ED; TUC K TH E FO LDS O F A CLOTH
DISHTOWEL UNDER THE KNOB AND PULL THE TOWEL UPWARD WITH STEADY, EVEN PRES,
SURE.
2. Carefully remove rubber grommet.
3. Locate the valve adjustment screw. See figure 11.
4. Insert a slender, thin-blade screwdriver into knob hole and engage blade with slot in adjusting screw.
5. Turn the adjusting screw clockwise until tight (5-7 in-lbs max.). Do not over tighten.
6. Replace rubber grommet and control knob.
7. Repeat for remaining burners.
KNOB
FIGURE12
_KNOBHOLE _
(KNOB AND GROMMET REMOVED)
FIGURE11
To Convert Appliance For Use With Natural Gas
WARNING
155_L] --_
f
4 BURNER MODEL (30" WIDE[
_[_] 1.55
Electrical power and gas must be turned off prior to conversion.
If this appliance has been converted for use with LP gas, each of the following modifications must be performed to
convert the unit back to natural gas. A. REPLACE ALL ORIFICE SPUDS.
1. Perform Steps 1 and 2 on page 7.
2. Perform Step 3 on page 7.
3. For Step 4: Locate the brass natural gas orifice spuds that were originally installed in this appliance before its conversion for use with LP gas. Observe the number on each of the spuds and note the
correct burner location for each spud as shown in figures 13 and 14.
installation Of Natural Gas Orifice Spuds
5 BURNER MODEL (36" WIDE[
1.55I_
- _]1.42
_] 1.42
0 0
0 0
ART,S2 a5- a _3- I1
155_ J
FIGURE14
4. Complete Steps 5, 6 and 7 on page 7 to complete the installation of natural gas main spuds intheir
correct locations.
5. Save the orifices removed from the appliance for future use. They will be needed if this appliance is
again converted for use with LP gas.
B. INVERT CAP IN APPLIANCE PRESSURE
REGULATOR. (See figure 10).
With the appliance installed the appliance regulator should be located as shown in either figure 3 or 4
(pages 4 & 5). Identify the type of appliance regulator
and follow the instructions in the appropriate illustration.
_] 1.85
1.42I_
0
0 0
0 0
FIGURE13
_- _] 1.61
C. RESET THE VALVES FOR NATURAL GAS
1. Light one burner, and set on low.
2. Remove the knob.
,
Remove the rubber grommets.
4.
Locate the valve adjustment screw. See figure 11.
5.
Insert a slender, thin-blade screwdriver into knob
hole and engage blade with slot in adjusting screw.
,
Starting from the LP position (see #5 on page 8, under C. LOW FLAME ADJUSTMENT), turn the
screw counter clockwise until the flame stabilizes and matches the pictured "low" setting on figure 12.
Proper adjustment will produce a stable, steady blue
flame of minimum size. The final adjustment should be checked by turning the knob from high to low
several times without extinguishing the flame.
After Steps A, B and C have been completed, check the appearance of each burner's flame at the Hi and Lo
settings against figure 12. If the flames appear too
large or too small, make sure all steps were completed
correctly.
Burner Performance
CAUTION: Never cover control knobs or surrounding
control surface with utensils, towels, or other objects. Never obstruct free air passage past the control knobs.
The knob openings have been sized to properly control air entry to the interior of the appliance during operation.
This appliance has no air shutters. Primary air adjustments are unnecessary. The burners are designed
to provide optimum aeration for all gases without air
5 BURNERMODEL(36" Wide)_ 4 BURNERMODEL(30" Wide).
f
©©©
© ©
= "'*'== "='° !
AIT_ZUS-aO3-O
shutters. When operating properly, burners should produce clearly defined, even blue flames. If the flames
have yellow tips or are hazy and otherwise appear to have insufficientair, obtain the services of a qualified
service technician. Some yellow tipping on LP gas is normal.
Specified input rates are as shown in figures 15 and 16 below.
© ©
© ©
r i
o =
RGURE 15
36"Cooktop
INPUTRATES - NATURALGAS / LP GAS (BTU/HR)
BURNERLOCATION Hi Lo RightFront
RightRear LeftFront
LeftRear Center
12,500/ 10,500
9,200 / 9,100 9,200 / 9,100
10,500/ 9,100
9,200 / 9,100
High Altitude Notice
The specified gas burner ratings typically apply to
elevations up tO2000 feel For highe[ altitudes, the rates may need to be reduced to achieve satisfactory operation _
A local certified gas servicer will be able to advise if a reduction is necessary,
1300/ 1300 1300/ 1300 1300/ 1300 1300/ 1300 1300/ 1300
FIGURE16
30"Cooktop
INPUT RATES- NATURALGAS/ LPGAS (BTU/HR)
BURNERLOCATION Hi Lo RightFront
RightRear Left Front
Left Rear Center
12,500 / 10,500
9,200 / 9,100 9,200 / 9,100 9,200 / 9,100
1300/ 1300 1300/ 1300 1300/ 1300 1300/ 1300
Loading...
+ 23 hidden pages