Maytag MDE28PDCYW Installation Guide

INSTALLATION INSTRUCTIONS
COMMERCIAL DRYER – GAS OR ELECTRIC
INSTRUCTIONS D’INSTALLATION
SÉCHEUSE COMMERCIALE – À GAZ OU ÉLECTRIQUE
Table of Contents/Table des matières ................................................................................ 2
www.maytagcommerciallaundry.com
W11311968A
TABLE DES MATIÈRES
DRYER SAFETY .......................................................................... 2
INSTALLATION REQUIREMENTS ............................................. 5
Tools and Parts ......................................................................... 5
Location Requirements ............................................................. 6
Electrical Requirements ............................................................ 7
Gas Supply Requirements ..................................................... 10
Venting Requirements ........................................................... 11
Leveling .................................................................................. 13
INSTALLATION INSTRUCTIONS – GAS DRYER ................. 14
Make Gas Connection ............................................................. 14
Gas Supply Line ....................................................................... 14
Connect Vent ........................................................................... 15
Complete Installation .............................................................. 15
INSTALLATION INSTRUCTIONS – ELECTRIC DRYER ...... 16
Power Supply Cord (U.S.A. Only) ........................................... 16
Direct Wire Method (U.S.A. Only) ............................................ 20
Connect Vent ........................................................................... 23
Complete Installation .............................................................. 23
REVERSING THE DOOR SWING .......................................... 24
Remove the Door Assembly ................................................... 24
Reverse Hinge ......................................................................... 24
Reverse The Strike .................................................................. 25
Reinstall The Door .................................................................. 25
MAINTENANCE INSTRUCTIONS ......................................... 25
ELECTRONIC CONTROL SETUP ......................................... 26
WARRANTY ............................................................................ 30
SÉCURITÉ DE LA SÉCHEUSE .................................................. 31
EXIGENCES D’INSTALLATION ................................................. 34
Outils et pièces ........................................................................ 34
Exigences d’emplacement ...................................................... 35
Spécifications électriques ........................................................ 36
Spécifications de l’alimentation en gaz ................................... 39
Exigences concernant l’évacuation ......................................... 40
Nivellement............................................................................... 42
INSTRUCTIONS D’INSTALLATION – SÉCHEUSE À GAZ ...... 43
Raccordement au gaz ............................................................. 43
Canalisation d’alimentation en gaz ......................................... 43
Raccordement du conduit d’évacuation ................................. 44
Fin de l’installation ................................................................... 44
INSTRUCTIONS D’INSTALLATION – SÉCHEUSE
ÉLECTRIQUE .............................................................................. 45
Cordon d’alimentation (É.-U. seulement) ................................ 45
Méthode de raccordement direct (É.-U. seulement) .............. 49
Raccordement du conduit d’évacuation ................................. 52
Fin de l’installation ................................................................... 52
INVERSION DU SENS D’OUVERTURE DE LA PORTE .......... 53
Retrait de la porte .................................................................... 53
Inversion de la charnière.......................................................... 53
Inversion de la gâche ............................................................... 54
Réinstallation de la porte ......................................................... 54
INSTRUCTIONS D’ENTRETIEN ................................................ 55
RÉGLAGE DE LA CARTE DE CIRCUITS ÉLECTRONIQUE ... 55
GARANTIE ................................................................................... 60
DRYER SAFETY
It is recommended that the owner post, in a prominent location, instructions for the customer’s use in the event the customer smells
gas. This information should be obtained from your gas supplier.
Post the following warning in a prominent location.
2
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury, death or property damage.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Clear the room, building, or area of all occupants.
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's
instructions. If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
3
In the State of Massachusetts, the following installation instructions apply:
Installations and repairs must be performed by a qualified or licensed contractor, plumber, or gas fitter qualified or licensed by
the State of Massachusetts.
Acceptable Shut-off Devices: Gas Cocks and Ball Valves installed for use shall be listed.
A flexible gas connector, when used, must not exceed 4 feet (121.9 cm).
Do not place items exposed to cooking oils in your dryer. Items contaminated with cooking oils may contribute to a chemical reaction that could cause a load to catch re. To reduce the risk of re due to contaminated loads, the nal part of a tumble dryer cycle occurs without heat (cool down period). Avoid stopping a tumble dryer before the end of the drying cycle unless all items are quickly removed and spread out so that the heat is dissipated.
IMPORTANT: The gas installation must conform with local codes, or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Propane Installation Code, CSA B149.1.
The dryer must be electrically grounded in accordance with local codes, or in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, Part 1, CSA C22.1.
4
INSTALLATION REQUIREMENTS
Tools & Parts
Tools Needed:
8" or 10" 8" or 10" Flat-blade screwdriver Phillips screwdriver
Pipe wrench Adjustable wrench that opens to 1"
TORX T20®† security 1" Hex-head 5⁄16" Socket wrench Pliers screwdriver or bit socket wrench (that open to 19/16")
Level Utility knife Pipe-joint compound Putty knife resistant to Propane gas
Caulk gun and caulk Vent clamps (for installing new exhaust vent)
Parts supplied:
Remove parts bag from dryer drum. Check that all parts were included.
Foot boot (4)
Dryer foot (4)
PD models: Cam for service door lock
Optional parts not included:
279810 Long dryer foot
LP Kit W10402145
208 V electric element:
U.S. – W10206352A, Canada – W10206351A
PR models: Card reader bezel, card reader wire harness, hardware
†® TORX and T20 are registered trademarks of Acument Intellectual Properties, LLC.
5
Location Requirements
WARNING
Explosion Hazard
Keep flammable materials and vapors, such as
gasoline, away from dryer.
Do not install in a garage.
Failure to do so can result in death, explosion, or fire.
IMPORTANT: Do not install or store the dryer where it will be exposed to the weather. Proper installation is your responsibility.
You will need:
A grounded electrical outlet located within 6 ft. (1.8 m) of
where the power cord is attached to the back of the dryer. See “Electrical Requirements.”
A level oor with a maximum slope of 1" (25 mm) under entire
dryer. Installing the dryer on soft oor surfaces, such as carpets or surfaces with foam backing, is not recommended.
If installing a gas dryer: IMPORTANT: Observe all governing codes and ordinances.
Check code requirements: Some codes limit or do not permit
installation of clothes dryers in garages, closets, or sleeping quarters. Contact your local building inspector.
Make sure that lower edges of the cabinet, plus the back and
bottom sides of the dryer, are free of obstructions to permit adequate clearance of air openings for combustion air. See “Recessed Area and Closet Installation Instructions” below for minimum spacing requirements.
NOTE: The dryer must not be installed in an area where it will be exposed to water and/or weather.
Recessed Area and Closet Installation Instructions
This dryer may be installed in a recessed area or closet. For recessed area and closet installations, minimum clearances can be found on the warning label on the rear of the dryer.
The installation spacing is in inches and is the minimum allowable. Additional spacing should be considered for ease of installation, servicing, and compliance with local codes and ordinances.
If closet door is installed, the minimum unobstructed air opening in the top and bottom is required. Louvered doors with equivalent air openings are acceptable.
The dryer must be exhausted outdoors. No other fuel-burning appliance may be installed in the same
closet as the dryer.
Minimum Installation Clearances
14" (356 mm) max.
15"
(381 mm)*
0" (0 mm)
Closet door
0" (0 mm)
1" (25 mm)
Recessed front view Closet side view
* Additional clearances for wall, door, and oor moldings may be required
or if external exhaust elbow is used.
3" (76 mm)
48 in2. (310 cm2)*
Front View
24 in2 (155 cm2)*
closet
door
3" (76 mm)
* Opening is the minimum
for a closet door. Louvered doors with equivalent air openings are acceptable.
Product Dimensions 27" (68.6 cm) Dryer
27" (686 mm)
61⁄4"
(159 mm)
41⁄4"
(108 mm)
BOTTOM
EXHAUST
141⁄8"
(359 mm)
77⁄8"
(200 mm)
35"
(889 mm)
63⁄4"
(152 mm)
11⁄4"
(32 mm)
29" (736 mm)
271⁄4" (695 mm)
SIDE VIEW
LEFT OR RIGHT SIDE EXHAUST
ELECTRIC
BACK
VIEW
13"
(330 mm)
4" (102 mm)
dia.
GAS
EXHAUST
71⁄4"
(184 mm)
101⁄4"
(260 mm)
0" (0 mm)
283⁄4"
(733 mm)
3/4" (21 mm)
41⁄4" (108 mm)
6
Electrical Requirements – Gas Dryer
IMPORTANT: The dryer must be electrically grounded in
accordance with local codes and ordinances or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, latest edition, or Canadian Electrical Code, CSA C22.1. If codes permit and a separate ground wire is used, it is recommended that a qualied electrical installer determine that the ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park, Quincy, MA 02269
CSA International
8501 East Pleasant Valley Road
Cleveland, Ohio 44131-5575
Do not ground to a gas pipe.
Do not have a fuse in the neutral or ground circuit.
A 120 V, 60 Hz, AC only, 15 or 20 A, fused electrical circuit
is required. A time-delay fuse or circuit breaker is also recommended. It is recommended that a separate circuit serving only this dryer be provided.
This dryer is equipped with a power supply cord having a
3-prong grounding plug.
To minimize the possibility of shock, the cord must be
plugged into a mating, 3 prong, grounding-type outlet, grounded in accordance with local codes and ordinances. If a mating outlet is not available, it is the personal responsibility and obligation of the customer to have the properly grounded outlet installed by a qualied electrician.
If codes permit and a separate ground wire is used, it is
recommended that a qualied electrician determine that the ground path is adequate.
Check with a qualied electrician if you are not sure the dryer
is properly grounded.
Gas Dryer Grounding
7
Electrical Requirements –
Electric Dryer (U.S.A. Only)
It is your responsibility:
To contact a qualied electrical installer.
To be sure that the electrical connection is adequate and in
conformance with the National Electrical Code, ANSI/NFPA 70-latest edition and all local codes and ordinances.
The National Electrical Code requires a 4-wire power supply
connection for homes built after 1996, dryer circuits involved in remodeling after 1996, and all mobile home installations.
A copy of the above code standards can be obtained from:
National Fire Protection Association, One Batterymarch Park, Quincy, MA 02269.
To supply the required 3 or 4 wire, single phase, 120/240 V,
60 Hz., AC only electrical supply (or 3 or 4 wire, 120/208 V electrical supply, if specied on the serial/rating plate) on a separate 30 A circuit, fused on both sides of the line. A time delay fuse or circuit breaker is recommended. Connect to an individual branch circuit. Do not have a fuse in the neutral or grounding circuit.
Do not use an extension cord.
If codes permit and a separate ground wire is used, it is
recommended that a qualied electrician determine that the ground path is adequate.
Electric Dryer Grounding
Electrical Connection
To properly install your dryer, you must determine the type of electrical connection you will be using and follow the instructions provided for it here.
This dryer is manufactured ready to install with a 3-wire
electrical supply connection. The neutral ground conductor is permanently connected to the neutral conductor (white wire) within the dryer. If the dryer is installed with a 4-wire electrical supply connection, the neutral ground conductor must be removed from the external ground connector (green screw), and secured under the neutral terminal (center or white wire) of the terminal block. When the neutral ground conductor is secured under the neutral terminal (center or white wire) of the terminal block, the dryer cabinet is isolated from the neutral conductor.
If local codes do not permit the connection of a neutral
ground wire to the neutral wire, see “Optional 3-wire connection” section.
A 4-wire power supply connection must be used when the
appliance is installed in a location where grounding through the neutral conductor is prohibited. Grounding through the neutral is prohibited for (1) new branch-circuit installations (2) areas where local codes prohibit grounding through the neutral conductor.
8
Electric Dryer Power Supply Cord
If using a power supply cord:
Use a UL listed power supply cord kit marked for use with clothes dryers. The kit should contain:
A UL listed 30 A power supply cord, rated 120/240 V
minimum. The cord should be type SRD or SRDT and be at least 4 ft. (1.22 m) long. The wires that connect to the dryer must end in ring terminals or “U” shaped spade terminals with upturned ends.
A UL listed strain relief.
Direct Wire
Fire Hazard Use 10 gauge copper wire. Use a UL listed strain relief. Disconnect power before making electrical connections. Connect neutral wire (white or center wire) to center
terminal. Ground wire (green or bare wire) must be connected
to green ground connector. Connect remaining 2 supply wires to remaining
2 terminals (gold). Securely tighten all electrical connections. Failure to do so can result in death, fire, or
electrical shock.
If connecting by direct wire:
Power supply cable must match power supply (4-wire or 3-wire) and be:
Flexible armored cable or nonmetallic sheathed copper
cable (with ground wire), covered with exible metallic conduit. All current-carrying wires must be insulated.
10-gauge solid copper wire (do not use aluminum).
At least 5 ft. (1.52 m) long.
If your outlet looks like this:
Then choose a 4-wire power supply cord with ring or spade terminals and UL listed strain relief. The 4-wire power supply cord, at least 4 ft. (1.22 m) long, must have four 10-gauge copper wires and match a 4-wire receptacle of NEMA Type 14-30R.
4-Wire
Receptacle
(14-30R)
The ground wire (ground conductor) may be either green or bare. The neutral conductor must be identied by a white cover.
If your outlet looks like this:
Then choose a 3-wire power supply cord with ring or spade terminals and UL listed strain relief. The 3-wire power supply cord, at least 4 ft. (1.22 m) long, must have three 10-gauge copper wires and match a 3-wire receptacle of NEMA Type 10-30R.
3-Wire
Receptacle
(10-30R)
9
Electrical Requirements – Canada only
It is your responsibility:
To contact a qualied electrical installer.
To be sure that the electrical connection is adequate
and in conformance with the Canadian Electrical Code, C22.1 – latest edition and all local codes. A copy of the above codes standard may be obtained from: Canadian Standards Association,178 Rexdale Blvd., Toronto, ON M9W 1R3 CANADA.
To supply the required 4 wire, single phase, 120/240 V,
60 Hz., AC only electrical supply on a separate 30 A circuit, fused on both sides of the line. A time-delay fuse or circuit breaker is recommended. Connect to an individual branch circuit.
This dryer is equipped with a CSA International
Certied Power Cord intended to be plugged into a standard 14-30R wall receptacle. The cord is 5 ft (1.52 m) in length. Be sure wall receptacle is within reach of dryer’s nal location.
Do not use an extension cord. If you are using a replacement power supply cord, it is
recommended that you use Power Supply Cord Replacement Part Number 9831317. For further information, please reference the service numbers located in the “Assistance or Service” section.
4-Wire
Receptacle
(14-30R)
GROUNDING INSTRUCTIONS
For a grounded, cord-connected dryer:
This dryer must be grounded. In the event of malfunction or breakdown, grounding will reduce the risk of electric shock by providing a path of least resistance for electric current. This dryer is equipped with a cord having an equipment­grounding conductor and a grounding plug. The plug must be plugged into an appropriate outlet that is properly installed and grounded in accordance with all local codes and ordinances.
WARNING: Improper connection of the equipment-
grounding conductor can result in a risk of electric shock. Check with a qualied electrician or service representative or personnel if you are in doubt as to whether the dryer is properly grounded. Do not modify the plug provided with the dryer: if it will not t the outlet, have a proper outlet installed by a qualied electrician.
Gas Supply Requirements
WARNING
Explosion Hazard Use a new CSA International approved gas supply line. Install a shut-off valve. Securely tighten all gas connections. If connected to propane, have a qualified person make
sure gas pressure does not exceed 13" (33 cm) water column.
Examples of a qualified person include: licensed heating personnel,
authorized gas company personnel, and authorized service personnel.
Failure to do so can result in death, explosion, or fire.
IMPORTANT: Observe all governing codes and ordinances. This installation must conform with all local codes and
ordinances. In the absence of local codes, installation must conform with American National Standard, National Fuel Gas Code ANSI Z223.1/NFPA 54 or CAN/CSA B149.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park, Quincy, MA 02269
CSA International
8501 East Pleasant Valley Road
Cleveland, Ohio 44131-5575
The design of this dryer has been certied by CSA International for use at altitudes up to 10,000 feet (3048 m) above sea level at the B.T.U. rating indicated on the model/serial plate. Burner input adjustments are not required when the dryer is operated up to this elevation.
When installed above 10,000 feet (3048 m), a four percent (4%) reduction of the burner B.T.U. rating shown on the model/serial plate is required for each 1,000 foot (305 m) increase in elevation. For assistance when converting to other gas types and/or installing above 10,000 feet (3048 m) elevation, contact your local service company.
Type of Gas
This dryer is equipped for use with natural gas. It is design­certied by CSA International for propane and butane gases with appropriate conversion. No attempt shall be made to convert the dryer from the gas specied on the serial/rating plate for use with a different gas without consulting the serving gas supplier. Conversion must be done by a qualied service technician. Gas conversion kit part number is W10402145. This part number is also available on a label on the gas valve burner base.
10
SAVE THESE INSTRUCTIONS
Venting Requirements
WARNING: To reduce the risk of re, this dryer MUST BE
EXHAUSTED OUTDOORS. IMPORTANT: Observe all governing codes and ordinances.
The dryer exhaust must not be connected into any gas vent,
chimney, wall, ceiling, attic, crawlspace, or a concealed space of a building. Only rigid or exible vent shall be used for exhausting.
Only a 4" (102 mm) heavy, metal exhaust vent and clamps
may be used.
Do not use an exhaust hood with a magnetic latch.
Use clamps to seal all joints. Do not use screws or other
fastening devices that extend into the interior of the duct and catch lint. Do not use duct tape.
Do not use plastic or metal foil vent.
Rigid metal vent:
Recommended for best drying performance and to avoid
crushing and kinking.
Flexible metal vent (acceptable only if accessible to clean):
Must be fully extended and supported in nal dryer location.
Remove excess to avoid sagging and kinking that may result
in reduced airow and poor performance.
Do not install in enclosed walls, ceilings, or oors.
The total length should not exceed 7
An exhaust hood should cap the vent to prevent rodents and insects from entering the home or business.
Exhaust hood must be at least 12" (305 mm) from the ground or any object that may be in the path of the exhaust (such as owers, rocks, or bushes).
If using an existing vent system, clean lint from the entire length of the system and make sure exhaust hood is not plugged with lint. Replace any plastic or metal foil vent with rigid metal or exible metal vent.
Plan installation to use the fewest number of elbows and turns.
3
/4 ft. (2.4 m).
Allow as much room as possible when using elbows or making turns. Bend vent gradually to avoid kinking.
Vent outlet is located at the back of the dryer, at bottom center. The vent can be routed up, down, left, right, behind the dryer,
or straight out the back of the dryer. See “Product Dimensions” in the “Location Requirements” section.
Make-up air:
Although each single-load dryer should have an unobstructed outdoor air opening of 24 in2 (154 cm2) (based on 1 square inch [6.5 cm2] per 1,000 Btu [252 kcal]), common make-up air openings are also acceptable. Set up common openings so that the make-up air is distributed equally to all of the dryers. Keep in mind that the coverage area must be increased by 33% to account for use of registers or louvers over the openings. Also, make-up air openings should not be installed near the location of exhaust vents exiting the building.
Vent System Length
Maximum length of vent system depends upon the type of vent used, number of elbows, and type of exhaust hood. The maximum length for rigid vent is shown in the chart.
Maximum Vent Length
4" (102 mm) Diameter Exhaust Hoods
Box Louvered
21⁄2" (63.5 mm) Angled
Vent System Chart (Rigid Metal Vent)
No. of 90° Box Hood and Turns Louvered Style Angled Hood Style
0 130 ft. (39.6 m) 129 ft. (39.3 m) 1 125 ft. (38.1 m) 119 ft. (36.3 m) 2 115 ft. (35.1 m) 109 ft. (33.2 m) 3 106 ft. (32.3 m) 100 ft. (30.5 m) 4 98 ft. (29.9 m) 92 ft. (28.0 m)
For vent systems not covered by the vent specication chart, see your parts distributor.
Provision must be made for enough air for combustion and ventilation. (Check governing codes and ordinances.) See “Recessed Area and Closet Installation Instructions” in the “Location Requirements” sections.
A 4" (102 mm) outlet hood is preferred. However, a 21⁄2" (64 mm) outlet exhaust hood may be used. A 21/2" (64 mm) outlet creates greater back pressure than other hood types. For permanent installation, a stationary vent system is required.
Connect Vent
1. If connecting to existing vent, make sure the vent is clean.
2. Using a 4" (102 mm) clamp, connect vent to exhaust outlet
in dryer.
Vent Collar
Good
Better
NOTE: Do not remove vent collar.
11
3. Tighten hose clamp with Phillips screwdriver.
4. Make sure the vent is secured to exhaust hood with
a 4" (102 mm) clamp.
5. Move dryer into nal position. Do not crush or kink vent.
Make sure dryer is level.
Multiple Dryer Venting
A main vent can be used for venting a group of dryers. The
main vent should be sized to remove 200 CFM of air per dryer. Large-capacity lint screens of proper design may be used in the main vent if checked and cleaned frequently. The room where the dryers are located should have make-up air equal to or greater than the CFM of all the dryers in the room.
A back-draft damper kit is needed and is available from a
commercial laundry distributor; it should be installed in the vent of each dryer to prevent exhausted air from returning into the dryers and to keep the exhaust in balance within the main vent. Unobstructed return air openings are required.
Each vent should enter the main vent at an angle pointing in the direction of the airow. Vents entering from the opposite side should be staggered to reduce the exhausted air from interfering with the other vents.
The maximum angle of each vent entering the main vent should be no more than 30°.
NOTE: Testing for proper ventilation should be done with a Manometer. Minimum: 0.01" (0.2 mm). Maximum: 0.6" (16 mm).
For vent systems not covered by the vent specication chart, see your parts distributor.
If dryer is installed in a conned area, such as a bedroom, bathroom, or closet, provision must be made for enough air for combustion and ventilation. (Check governing codes and ordinances.) See “Recessed Area and Closet Installation Instructions” in the “Location Requirements” section.
A 4" (102 mm) outlet hood is preferred. However, a 21⁄2" (64 mm) outlet exhaust hood may be used. A 21⁄2" (64 mm) outlet creates greater back pressure than other hood types. For permanent installation, a stationary vent system is required.
If An Exhaust Hood Cannot Be Used
The outside end of the main vent should have a sweep elbow directed downward.
* Minimum
clearance above
12" min.
(305 mm)*
any accumulation of snow, ice, or debris such as leaves
30˚ max.
Air ow
Air flow
Keep air openings free of dry cleaning uid fumes. Fumes create acids which, when drawn through the dryer heating units, can damage dryers and items being dried.
A clean-out cover should be located on the main vent for periodic cleaning of the vent system.
If the main vent travels vertically through the roof, rather than through the wall, install a 180° sweep elbow on the end of the vent at least 2 ft. (610 mm) above the highest part of the building. The opening in the wall or roof shall have a diameter 1/2" (13 mm) larger than the vent diameter. The vent should be centered in the opening.
Do not install screening or cap over the end of the vent.
12
24" min.
(610 mm)
Leveling
Leveling your dryer properly reduces excess noise and vibration.
1. Remove cardboard from beneath dryer. Place a level on top
edges of dryer, checking each side and front. If not level, tip dryer and adjust legs up or down as shown in Step 3, repeating as necessary.
2. Grip dryer from top and rock back and forth, making sure all
four legs are rmly on oor. Repeat, rocking dryer from side to side. If dryer rocks, go to Step 3 and adjust leveling legs.
(appearance may vary)
3. If dryer is not level, use a 1" or 25 mm open-end or adjustable
wrench to turn the leveling leg counterclockwise to lower the dryer or clockwise to raise the dryer. Recheck levelness of dryer and that all four legs are rmly in contact with the oor. Repeat as needed.
HELPFUL TIP: You may want to prop up front of dryer about 4" (102 mm) with a wood block or similar object that will support weight of dryer.
(appearance may vary)
Not Level LEVEL Not Level
13
INSTALLATION INSTRUCTIONS – GAS DRYER
Make Gas Connection
WARNING
Explosion Hazard Use a new CSA International approved gas supply line. Install a shut-off valve. Securely tighten all gas connections. If connected to propane, have a qualified person make
sure gas pressure does not exceed 13" (33 cm) water column.
Examples of a qualified person include: licensed heating personnel,
authorized gas company personnel, and authorized service personnel.
Failure to do so can result in death, explosion, or fire.
1. Remove red cap from gas pipe.
2. Connect gas supply to dryer. Use pipe-joint compound
resistant to the action of propane for gas connections. If exible metal tubing is used, be certain there are no kinks.
If necessary for service, open the toe panel by removing the
21⁄4" hex-head screws from the bottom of the panel. Then lift up on the panel while pulling the bottom of the panel away from the dryer.
3. Open the shutoff valve in the gas supply line.
4. Test all connections by brushing on an approved
noncorrosive leak-detection solution. Bubbles will show a leak. Correct any leak found.
Gas Supply Pressure Testing
A 1/8" (3 mm) NPT minimum plugged tapping, accessible for gauge testing, must be installed immediately downstream of the installed shut-off valve to the dryer (as shown above). The dryer must be disconnected from the gas supply piping system during any pressure testing of the system at test pressures in excess of 1/2" psig (352 kg/m2). The expected pressures for the gas supply are listed in inches of water in the table below:
Natural Gas Propane Gas
Minimum
Maximum
Alternate method
The gas supply may also be connected using 3/8" approved
copper or aluminum tubing. If the total length of the supply line is more than 20 ft. (6.1 m), larger tubing will be required. If using natural gas, do not use copper tubing. Pipe joint compounds that resist the action of Propane gas must be used.
Flexible metal appliance connector:
It is recommended that a new exible stainless steel gas line,
design-certied by CSA International, be used for connecting the dryer to the gas supply line. (The gas pipe, which extends through the lower rear of the dryer, is provided with 3/8"male pipe thread.)
5.2" (132.1 mm) 8.0" (203.2 mm)
10.5" (266.7 mm) 13.0" (330.2 mm)
Gas Supply Line
Recommended method
Provide a gas supply line of 1/2" rigid (IPS) pipe to the dryer
location. Pipe joint compounds that resist the action of Propane gas must be used. Do not use TEFLON®† tape. With Propane gas, piping or tubing size can be 1/2" minimum. Usually, Propane gas suppliers determine the size and materials used in the system.
†®TEFLON is a registered trademark of Chemours.
14
Do not kink or damage the exible stainless steel gas line
when moving the dryer.
Rigid pipe connection:
The rigid pipe connection requires a combination of pipe ttings to obtain an in-line connection to the dryer.
Must include a shutoff valve:
DC
A B
The supply line must be equipped with a manual shutoff
valve installed within 6 ft. (1.8 m) of dryer in accordance with National Fuel Gas Code, ANSI Z223.1. In Canada, an individual manual shutoff valve must be installed in accordance with the B149 installation codes CAN/CGA B149.1 and CAN/CGA B149.2. This valve should be located in the same room as the dryer. It should be in a location that allows ease of opening and closing. Do not block access to shutoff valve. The valve is for turning on or shutting off gas to the dryer.
A. Gas supply line B. Shutoff valve in “open” position C. To dryer D. NPT 1/8" min. plugged tapping
Installed in a conned area:
If the dryer is installed in a conned area such as a
bathroom or closet, provision must be made for enough air for combustion and ventilation. Check governing codes and ordinances or refer to the “Recessed Area and Closet Installation Instructions” in the “Location Requirements” section.
Complete Installation
1. With dryer in nal position, place level on top of the dryer, rst
side to side; then front to back. If the dryer is not level, adjust the legs of the dryer up or down until the dryer is level.
2. Check the electrical requirements. Be sure that you have the
correct electrical supply and the recommended grounding method. See “Electrical Requirements.”
3. Check that all parts are now installed. If there is an extra part,
go back through the steps.
4. Check that you have all of your tools.
5. Dispose of/recycle all packaging materials.
WARNING
Electrical Shock Hazard Plug into a grounded 3 or 4 prong outlet. Do not remove ground prong. Do not use an adapter. Do not use an extension cord. Failure to follow these instructions can result in death,
fire, or electrical shock.
Connect Vent
1. Using a 4" (102 mm) clamp, connect vent to exhaust outlet
on the dryer. If connecting to existing vent, make sure the vent is clean. The dryer vent must t over the dryer exhaust outlet and inside the exhaust hood. Make sure the vent is secured to exhaust hood with a 4" (102 mm) clamp.
2. Using two or more people, move dryer to desired installation
location. Do not crush or kink vent, and remove any excess exible vent to improve airow. Make sure dryer is level.
3. Check to be sure there are no kinks in the exible gas line.
6. Plug into a grounded outlet, or connect power.
7. Check dryer operation:
Insert coins. Select a cycle. Using the WHITES & COLORS
cycle, let the dryer run for at least ve minutes. Dryer will stop when time is used up.
Note: Dryer door must be closed for dryer to operate.
When door is open, dryer stops, but timer continues to run. To restart dryer, close door and reselect a cycle.
8. If the burner does not ignite and there is no heat inside the
dryer, shut off dryer for ve minutes. Check that all gas supply valves are in the “ON” position and that the electrical cord is plugged in. Repeat ve-minute test.
9. If drying time is too long, make sure that the lint screen is
clean and that there are no obstructions to airow in the dryer vent system.
15
D
C
INSTALLATION INSTRUCTIONS – ELECTRIC DRYER
Power Supply Cord (U.S.A. Only)
1. Disconnect power.
2. Remove the hold-down screw and terminal block cover.
B
E
A. Terminal block cover B. External ground
conductor screw
3. Install strain relief.
C. Center terminal block screw D. Hold-down screw E. Neutral ground wire
A
16
Electrical Connection Options
(127 mm)
If your location has: And you will be Go to Section connecting to:
4-wire receptacle A UL listed, 120/240 V 4-wire connection: (NEMA Type 14-30R) minimum, 30 A, Power supply cord dryer power supply cord*
3-wire receptacle A UL listed, 120/240 V 3-wire connection: (NEMA type 10-30R) minimum, 30 A, Power supply cord dryer power supply cord*
4-wire direct A fused disconnect or 4-wire connection: circuit breaker box* Direct Wire
1"
(25 mm)
5"
3-wire direct A fused disconnect or 3-wire connection: circuit breaker box* Direct Wire
31⁄2
(89 mm)
*If local codes do not permit the connection of a cabinet-ground conductor to the neutral wire, go to “Optional 3-wire connection” section.
Power supply cord strain relief:
Remove the screws from a 3/4" (19 mm)
UL listed strain relief (UL marking on strain relief). Put the tabs of the two clamp sections into the hole below the terminal block opening so that one tab is pointing up and the other is pointing down, and hold in place.
Tighten strain relief screws enough to hold the two clamp sections together.
A
B
C
A. Strain relief tab
pointing up
B. Hole below terminal
block opening C. Clamp section D. Strain relief tab
pointing down
D
Put power supply cord through the strain
relief. Be sure that the wire insulation on the power supply cord is inside the strain relief. The strain relief should have a tight t with the dryer cabinet and be in a horizontal position. Do not further tighten strain relief screws at this point.
17
Power supply cord, 4-wire connection:
IMPORTANT: A 4-wire connection is
required for mobile homes and where local codes do not permit the use of 3-wire connections.
B
A
3. Connect ground wire (B) (green or bare)
of power supply cord to external ground conductor screw (A). Tighten screw.
A
F
B
C
D
E
F
C
D
A. 4-wire receptacle (NEMA type 14-30R) B. 4-prong plug C. Ground prong D. Neutral prong E. Spade terminals with upturned ends F.
3/4"
(19 mm) UL listed strain relief
G. Ring terminals
E
1. Remove center terminal block screw (B).
2. Remove neutral ground wire (C) from
external ground conductor screw (A). Connect neutral ground wire and the neutral wire (white or center wire) of power supply cord under center terminal block screw (B). Tighten screw.
A
B
G
A. External ground conductor screw B. Ground wire (green or bare) of power supply cord C.
3/4"
(19 mm) UL listed strain relief D. Center terminal block screw E. Neutral ground wire F. Neutral wire (white or center wire)
4. Connect the other wires to outer terminal
block screws. Tighten screws.
C
5. Tighten strain relief screws.
6. Insert tab of terminal block cover into
slot of dryer rear panel. Secure cover with holddown screw.
7. You have completed your electrical
D
connection. Now go to “Venting Requirements.”
18
E
A. External ground conductor screw - Dotted line shows position
of NEUTRAL ground wire before being moved to center
terminal block screw. B. Center terminal block screw C. Neutral ground wire D. Neutral wire (white or center wire) E.
3/4"
(19 mm) UL listed strain relief
Power supply cord, 3-wire connection:
B
A
C
A. 3-wire receptacle (NEMA type 10-30R) B. 3-wire plug C. Neutral prong D. Spade terminals with upturned ends E. 3/4" (19 mm) UL listed strain relief F. Ring terminals G. Neutral (white or center wire)
Use where local codes permit connecting cabinet-ground conductor to neutral wire.
1. Loosen or remove center terminal
D
E
block screw (C).
2. Connect neutral wire (white or center
wire) of power supply cord (D) to the center terminal screw (C) of the terminal block. Tighten screw.
3. Connect the other wires to outer terminal
G
F
block screws. Tighten screws.
A
C
4. Tighten strain relief screws.
5. Insert tab of terminal block cover into
slot of dryer rear panel. Secure cover
D
B
E
A. External ground conductor screw B. Neutral ground wire C. Center terminal block screw D. Neutral wire (white or center wire) E. 3/4" (19 mm) UL listed strain relief
with holddown screw.
6. You have completed your electrical
connection. Now go to “Venting Requirements.”
19
D
C
Direct Wire Method (U.S.A. Only)
Fire Hazard Use 10 gauge copper wire. Use a UL listed strain relief. Disconnect power before making electrical connections. Connect neutral wire (white or center wire) to center
terminal. Ground wire (green or bare wire) must be connected
to green ground connector. Connect remaining 2 supply wires to remaining
2 terminals (gold). Securely tighten all electrical connections. Failure to do so can result in death, fire, or
electrical shock.
Direct wire cable must match power supply (4-wire or 3-wire) and be:
Flexible armored cable or nonmetallic sheathed copper cable
(with ground wire), protected with exible metallic conduit. All current-carrying wires must be insulated.
10-gauge solid copper wire (do not use aluminum).
At least 5 ft. (1.52 m) long.
1. Disconnect power.
2. Remove hold-down screw and terminal block cover.
B
E
A. Terminal block cover B. External ground
conductor screw
C. Center terminal block screw D. Hold-down screw E. Neutral ground wire
A
3. Install 3/4" conduit connector into the hole below the terminal
block opening. Connect exible metallic conduit and tighten connector screw. Install direct wire cable through the exible metallic conduit.
4. Complete installation following instructions for your type
of electrical connection:
• Four-wire (recommended method)
• Three-wire (if four-wire is not available)
Direct wire strain relief:
Unscrew the removable conduit
connector (A) and any screws from a 3/4" (19 mm) UL listed strain relief (UL marking on strain relief). Put the threaded section of the strain relief through the hole (B) below the terminal block opening. Reaching inside the terminal block opening, screw the removable conduit connector onto the strain relief threads (C).
Put direct wire cable through the strain
A
B
4. Now complete installation following
4-wire (recommended) 3-wire (if 4-wire is not available)
A. Removable conduit connector
C
B. Hole below terminal block opening C. Strain relief threads
relief. The strain relief should have a tight t with the dryer cabinet and be in a horizontal position. Tighten strain relief screw against the direct wire cable.
instructions for your type of electrical connection:
20
Loading...
+ 44 hidden pages