24(3EdwarasStreet,SE
Cleveland,Tennessee37311
Tel:423477__3333
Fax:423478-6710
If at all possible, USE A MINIMUM OF 4 INCH DIAMETER RIGID ALUMINUM OR
RIGID GALVANIZED STEEL DUCT. Do not use smaller duct. If flexible metal must be
used, use the type with a stiff sheet metal wall. Do not use flexible duct with a thin foil wail.
Serious blockage can result if flexible metal duct is bent too sharp. Never instail any type of •
flexible duct in walls, ceilings, or other concealed spaces.
EXHAUST HOOD TYPE
of
90° Turns 12lt2
Maximum lengthof4-inch diameter
riqidmetal duct
0 54 ft. 44 ft.
1 43 ft. 33 ft.
2 36 ft. 26 ft.
3 30 ft. 20 ft.
4 24ft. 14ft.
Maximum )ength of 4-inch diameter
flexible stiff walled metal duct.
0 26ft. 19ft.
1 22 ft. 17 ft.
2 18ft. 15ft.
3 15ft. 13ft.
Keep exhaust duct as straight and short as possible. Exhaust systems longer than recom-
mended can extend drying times, affect machine operation and may collect lint.
DO NOT EXHAUST DRYER INTO ANY WALL, CEILING, CRAWL SPACE OR A
CONCEALED SPACE OF A BUILDING, GAS VENT, ANY OTHER COMMON
DUCT OR CHIMNEY. THIS COULD CRATE A FIRE HAZARD FROM LINT
EXPELLED BY THE DRYER.
The exhaust duct should end with an exhaust hood with a swing out damper to prevent back-
drafts and entry of wildlife. Never use an exhaust hood with a magnetic damper. The hood
should have at least 12 inches of clearance between the bottom of the hood and the ground or
other obstruction. The hood opening should point down. Never install a screen over the
exhaust outlet.
When possible, do not exhaust the dryer directly into a window well in order to avoid lint
build-up. Do not exhaust under a house or porch.
If exhaust ductwork must run through an unheated area. the duct should be insulated and
slope slightly down towards the exhaust hood to reduce condensation and lint build-up.
If an existing exhaust system is to be used with you new dryer you must be sure the exhaust
,_TAG Admiral 71 _._E_N-A_ _'_lagic Chef
.i
Sdstemer e_'r '°_ ,ilt_llll__
240EdwarusStreet,SE
Cleveland,Tennessee37311
Tel:422-472-,1333
Fax:423-478-67!0
system meets all local codes and exhaust requirements.
- That plastic flexible duct is not used.
- To completely inspect and clean all lint accumulation from the interior of the duct.
- The duct is not kinked or crushed.
- The exhaust hood damper opens and closes freely.
The back pressure in any exhaust system must not exceed 0.58 inches of water column. This
can be measured with a manometer at the point where the exhaust duct connects to the dryer.
A no heat setting should be used.
Inspect and clean the interior of the exhaust system at least once a year. Disconnect electric
service prior to cleaning. Check gas line on gas dryers anytime the dryer is moved. Fre-
quently check to be sure the exhaust hood damper opens and closes freely.
NONEXHAUSTED INSTALLATIONS
NOTE: In Canada, all dryers must be exhausted to the outside.
If the dryer is not exhausted to the outside, an exhaust deflector should be installed along
with a dacron mesh lint bag (see Accessories). Maintain a 6" clearance between the back of
the control panel and the wall. Although the lint screen and lint bag will retain most of the
lint, a certain amount will be expelled into the laundry area.
WARNING: IF THE DRYER IS NOT EXHAUSTED TO THE OUTSIDE, SOME FINE
LINT WILL BE EXPELLED INTO THE LAUNDRY AREA. AN ACCUMULATION OF
DUST OR LINT IN ANY AREA OF THE HOME CREATES A FIRE HAZARD. ANY
LINT ACCUMULATIONS MUST BE CLEANED OR VACUUMED FREQUENTLY.
GAS REQUIREMENTS
Use only Natural or LP gases.
THE INSTALLATION MUST CONFORM WITH LOCAL CODES, OR IN THE
ABSENCE OF LOCAL CODES, WITH THE NATIONAL FUEL GAS CODE
ANSI/Z223.1, LATEST REVISION (FOR THE UNITED STATES), OR WITH THE
CAN/CGA-B149 INSTALLATION CODES (FOR CANADA).
MA_ FAG Admiral 71 _ENN-_I_ _'Magi¢ _l_ef
240EdwardsStreet,SE
Cleveland,Tennessee3731;
Tel:423-4723333
Fax:423-478-6710
Read this before you start......
TOOLS needed for Installation
z_.-___ _ • Cuffing Knife
_ _ • Pipe Wrench
- '_ "_-"-". " Nut Driver
_..\ '_'%J
_)_',_!t • Duct Tape
ITEMS PROVIDED
• TeflonTape or Pipe Joint
Compound
.Leve,
• Screw Driver (Standard)
• Crescent Wrench
._, ,I._) Io')N ""-_"
. , . O r,;_ X.
Electric Dryer Only _ Gas Dryer Only
Proper installation is the responsibility of the purchaser.
SERVICE CALLS PERFORMED AS A RESULT OF POOR INSTALLATION ARE
THE RESPONSIBILITY OF THE INSTALLER.
Make sure you have everything necessary for proper installation.
1. GROUNDED ELECTRICAL OUTLET is required. See Electrical Requirements.
2. GAS LINES (if a gas dryer) must meet National and Local codes.
3. EXHAUST SYSTEM must be rigid metal or flexible stiff walled metal exhaust ducting.
See Exhaust Requirements.
[] ,_,bxYrAG Admiral _J IJENN-_ _aq¢ C_
C,_0merSe_,i_e A_dl_f]_ll _
240EdwardsStreet,SE
Cieveiand.Tennessee3731:
Tei:423-472-3333
Fax:423-478-67!0
EXHAUSTING
Exhausting the dryer to the outside is recommended to prevent large amounts of moisture and "
lint being blown into the room. When located in a confined area such as a bedroom, bath-
room, or closet, the dryer must be exhausted outside.
NEVER USE PLASTIC, NONMETAL OR COMBUSTIBLE DUCTWORK
If your existing ductwork is plastic, nonmetal or combustible, replace it with metal. Use
only metal exhaust duct that will not support combustion to insure the containment of exhaust
air, heat and lint.
Plastic exhaust material can kink, sag, collapse, be easily punctured, reduce airflow, cause
lint build-up, extend drying times, and effect dryer operation.
I'*-_ 26 3/4"_ ,o 281/2" 72.39 cm =
!_ 67'95 cm 71 m_
L_ cm
.... _ _"
1 314"
,o,21cm om
LI °0.3°,,,,,,
-4 _- 33/," 9.5cm _4"1016cml_34.12crn-,
WARNING- The
dryer must be
exhausted to the
outside to reduce
the risk of fire,
CustomerSe_i_ __
240£dwardsStreet,SE
Cleveland,Tennessee3731i
Tel:423-472-3333
Fax:423-,:t786710
NOTE: DRYER DOOR REVERSAL INSTRUCTIONS ARE IN USERS GUIDE.
IMPORTANT TO INSTALLER
PLEASE READ THE FOLLOWING INSTRUCTIONS CAREFULLY BEFORE
STARTING TO INSTALL THE DRYER.
REMOVE THE DOOR FROM ALL DISCARDED APPLIANCES SUCH AS DRYERS
TO AVOID THE DANGER OF A CHILD SUFFOCATING.
LOCATION CONSIDERATIONS
The dryer should be located to permit 18" in front for removal of the front panel for access,
and sufficient room behind the dryer for the exhaust system.
This dryer is factory-ready for rear exhaust. To exhaust out the bottom or left side use the
accessory exhaust kit (see Accessories). Instructionsare included with the kit.
It is important to make sure the room has adequate make-up air.
On gas dryers, adequate clearance as noted on the data plate must be maintained to insure
adequate air for combustion and proper operation of the dryer. The area where the dryer is
located must not obstruct the flow of combustion or ventilating air.
THE DRYER MUST NOT BE INSTALLED OR STORED IN AN AREA WHERE IT
WILL BE EXPOSED TO WATER AND/OR WEATHER. THE DRYER AREA IS TO BE
KEPT CLEAR AND FREE FROM COMBUSTIBLE MATERIALS, GASOLINE AND
OTHER FLAMMABLE VAPORS AND LIQUIDS. A DRYER PRODUCES COMBUS-
TIBLE LINT. THE AREA AROUND THE DRYER SHOULD BE KEPT FREE OF LINT.
[] MA_TAG Admiral _l _u., ds=r,iN.,._d_ "_ t4acJ/c Chet
240EdwarDsStreet,SE
Cleveiane.Tennessee27317
TeL:423-472-3333
Fax:423-_78-_710
ALCOVE OR CLOSET INSTALLATION
An appliance installed in a closet shall have no other fuel-burning appliance installed in the
same closet. Each opening area in the door must have a minimum of 36 square inches.
These openings must not be obstructed. (Louvered door with equivalent air opening is
acceptable.)
CLOSET DOOR
36 sq.
inches
l
17"
2-
Inches
D 36sq.
0"-- -0" //
n rt n
FRONT VIEW -- P2" SIDE VIEW
i
, l
ze
Minimum installation clearances. If possible, more clearance is recommended.
240EdwarasStreet.SE
Cleveland,Tennessee37311
Tel:423-47Z-3333
Fax:a23-478-67,0
Gas dryers are equipped with a burner orifice for operation on NATURAL gas. If the dryer
is to be operated on LP (liquid propane) gas, it must be converted for safe and proper
performance and must be converted by a qualified service technician. Conversion kits
from NATURAL to LP, or LP to NATURAL are available through your local Maytag
dealer (see Accessories). If other conversions are required, check with the local gas utility
for specific information concerning conversion requirements.
a 1/2" gas supply line is recommended and must be reduced to connect to the 3/8" gas line
on the dryer.
Additionally, a 1/8" N.P.T. (National Pipe Thread) plugged tapping, accessible for test
gauge connection, must be installed immediately upstream of the gas supply connection to the
dryer.
HIGH PRESSURE TESTING
The dryer and its individual shutoff valve must be disconnected from the gas supply piping
system during any pressure testing of the system at test pressures in excess of 1/2 psig
(3.45kPa).
LOW PRESSURE TESTING
The dryer must be isolated from the gas supply piping system by closing its individual
manual shutoff valve during any pressure testing of the gas supply piping system at test pres-
sures equal to or less than 1/2 psig (3.45 kPa).
DO NOT re-use old flexible metal gas line. Flexible gas line must be design certified by
American Gas Association (CGA in Canada). NOTE: Any pipe joint compound used must
be resistant to the action of any liquifled petroleum gas.
NOTE: As a courtesy, most local gas utilities will inspect a gas appliance installation.
GAS IGNITION
This dryer uses an automatic ignition system to ignite the burner. There is no constant
burning pilot.