Your safety and the safety of others is extremely important in the installation, use and servicing of this water heater.
Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and
others of a potential injury hazard. Read and obey all safety messages and instructions throughout this manual. It is very important
that the meaning of each safety message is understood by you and others who install, use or service this water heater.
This is the safety alert symbol. It is used to alert you to
potential personal injury hazards. Obey all safety
messages that follow this symbol to avoid possible
injury or death.
DANGER indicates an imminently
DANGER
WARNING
CAUTION
hazardous situation which, if not avoided,
could result in death or injury.
WARNING indicates a potentially hazardous
situation which, if not avoided, could result
in death or injury.
CAUTION indicates a potentially hazardous
situation which, if not avoided, may result
in minor or moderate injury.
CAUTION used without the safety alert
CAUTION
All safety messages will generally tell you about the type of hazard, what can happen if you do not follow the safety message and
how to avoid the risk of injury.
symbol indicates a potentially hazardous
situation which, if not avoided, could result
in property damage.
IMPORT ANT DEFINITIONS
• Maytag Customer Service Center: The Maytag Customer Service Center has the equivalent to a licensed tradesman in the
fields of plumbing, air supply, venting and gas supply, including a thorough understanding of the requirements of the Natural
Gas and Propane Installation Code as it relates to the installation of gas fired water heaters. The Service Specialist also has a
thorough understanding of this instruction manual, and is able to perform repairs strictly in accordance with the service guidelines
provided by the manufacturer.
• Gas Supplier: The natural gas or propane utility or service which supplies gas for utilization by the gas burning appliances within
this application. The gas supplier typically has responsibility for the inspection and code approval of gas piping up to and including
the natural gas meter or propane storage tank of a building. Many gas suppliers also offer service and inspection of appliances
within the building.
2
SAFETY PRECAUTIONS
3
TABLE OF CONTENTS
SAFE INSTALLATION, USE AND SERVICE ................................................................................................ 2
PREPARATIONS FOR INSTALLATION........................................................................................................ 7
Removing the Old Water Heater............................................................................................................................. 7
Get to Know Your Water Heater.............................................................................................................................. 8
Mixing V alve Usage ................................................................................................................................................ 9
LOCATING AND INSTALLING THE NEW HEATER...............................................................................10-18
Facts to Consider About the Location .............................................................................................................. 10,11
Located in Unconfined Spaces ............................................................................................................................. 12
Combustion Air and V entilation for Appliances
Located in Confined Spaces ............................................................................................................................ 12,13
Water Piping....................................................................................................................................................13,14
Temperature Pressure Relief Valve ................................................................................................................. 14,15
Filling the Water Heater ................................................................................................................................... 15,16
Gas Piping ....................................................................................................................................................... 17,18
Temperature Regulation ....................................................................................................................................... 21
SERVICE AND MAINTENANCE............................................................................................................. 22-24
Tank (Sediment) Cleaning .................................................................................................................................... 22
Vent System Inspection ........................................................................................................................................ 22
Anode Rod Inspection .......................................................................................................................................... 23
Start Up Conditions.......................................................................................................................................... 24,25
Smelly Water ............................................................................................................................................... 25
“AIR” In Hot Water Faucets.......................................................................................................................... 25
High Temperature Shut Off System ........................................................................................................ 25,26
Thank You for purchasing a Maytag water heater. Properly
installed and maintained, it should give you years of trouble free
service. It is strongly suggested that this new water heater be
professionally installed, contact Maytag Customer Service (1-
800-788-8899) for recommended installers.
Abbreviations Found In This Instruction Manual:
•UL - Underwriters Laboratories Inc.
•EPACT - Energy Policy Act
•CAN - Canada
•CSA - Canadian Standards Association
•NFPA - National Fire Protection Association
•ANSI - American National Standards Institute
•ASME - American Society of Mechanical Engineers
•GAMA - Gas Appliance Manufacturer’s Association
This gas-fired water heater is design certified by Underwriters
Laboratories Inc. under American National Standard/CSA
Standard for Gas Water Heaters ANSI Z21.10.3 • CSA 4.3
(current edition). The installation must conform with CAN/CSA B149.1, installation codes and/or Local Installation Codes.
• Read the “Safety Precautions” section, page 3 of this manual
first and then the entire manual carefully. If you don’t follow
the safety rules, the water heater will not operate properly. It
could cause DEATH, SERIOUS BODILY INJURY AND/OR
PROPERTY DAMAGE.
This manual contains instructions for the installation, operation,
and maintenance of the gas-fired water heater. It also contains
warnings through out the manual that you must read and be
aware of. All warnings and all instructions are essential to the
proper operation of the water heater and your safety. Since
we cannot put everything on the first few pages, READ THE
ENTIRE MANUAL BEFORE A TTEMPTING TO INST ALL OR
OPERATE THE WATER HEATER.
• The installation must conform with these instructions and local
code authority having jurisdiction. In the absence of local
codes, installations shall comply with the Natural Gas and
Propane Installation Code CAN/CSA - B149.1. This publication
is available from the Canadian Standards Association, 5060
Spectrum Wa y , Suite 100, Mississauga, Ontario, Canada L4W
5N6.
• If after reading this manual you have any questions or do not
understand any portion of the instructions, call Maytag
Customer Service at 1-800-788-8899 for an authorized
servicer.
• Carefully plan the place where you are going to put the water
heater. Correct combustion, vent action, and vent pipe
installation are very important in preventing death from
possible carbon monoxide poisoning and fires, see
Figures 9 through 14.
Examine the location to ensure the water heater complies
with the Locating and Installing the New Water Heater
section in this manual.
PRODUCT SPECIFICATIONS
TANKRECOVERYMINIMUMDIMENSIONS
CAPACITYTYPERATE GALS.VENT PIPEDIAMETER IN INCHES (mm)
IN GALSOFBTUPER HOURINCHESINCHES HEIGHT TOP OF
MODEL NUMBER (LTRS)GASRATE@ 90°F RISE(mm)(mm)DRAFT HOOD
* Adding suffix “D” denotes high altitude (Example: HRX75XQRSCGAD). High altitude models have a B.TU./ Recovery Rate 10% less than shown.
5
ACCESSORIES AND TOOLS NEEDED
Accessories
T o simplify the inst allation Maytag has available the installation p art s shown below. You may or may not need all of these accessories
depending on your type of installation. Call Maytag Customer Service at 1-800-788-8899 for an authorized installer.
EXPANSION TANKS FOR THERMAL EXPANSION CONDITIONS
AVAILABLE IN 2 GALLON (7.6 LITERS), Part No. 66001013 AND
5 GALLON (18.9 LITERS), Part No. 66001014 CAPACITY.
Tools
You may or may not need all these tools, depending on your
type of installation. These tools can be purchased at your local
hardware store.
• Pipe Wrenches (2) 14” (356 mm)
• Screwdriver
• Tin Snips
• 6’ (1.82 m) Tape or Folding Ruler
• Garden Hose
• Drill
• Pipe Dope or Teflon Tape
DRILL
SLOT-HEAD SCREWDRIVER
PHILLIPS SCREWDRIVER
TIN SNIPS
DRAIN PANS AVAILABLE IN 22” (559 mm) DIAMETER (PART NO.
66001011) FOR WATER HEATERS HAVING A DIAMETER 20” (508
mm) OR LESS, 24” (610mm) DIAMETER (PART NO. 66001105) FOR
WATER HEATERS HAVING A DIAMETER 22” (559 mm) OR LESS
AND 28” (711 mm) DIAMETER (PART NO. 66001012) FOR WATER
HEATERS HAVING A DIAMETER 26” (660 mm) OR LESS.
Additional T ools Needed
When Sweat Soldering
• Tubing Cutters or Hacksaw
• Propane Tank
• Soft Solder
• Solder Flux
• Emery Cloth
• Wire Brushes
PROPANE
TUBING CUTTER
TORCH
ROLL OF TEFLON
TAPE (USE ONLY ON
WATER HEATER
CONNECTIONS)
GARDEN HOSE
6 FOOT TAP E
PIPE DOPE
(SQUEEZE TUBE)
USE FOR WATER AND GAS
CONNECTIONS
PIPE WRENCH
3/4” (19 mm) WIRE BRUSH
1/2” (13 mm) WIRE BRUSH
6
HACKSAW
EMERY CLOTH
ROLL OF LEAD-FREE
SOFT SOLDER
ROLL OF
SOLDER
FLUX
PREPARA TIONS FOR INSTALLA TION
Removing the Old Water Heater
FIGURE 1.
4. Attach a hose to the water heater
drain valve and put the other end
in a floor drain or outdoors. Open
the water heater drain valve. Open
a nearby hot water faucet which
will relieve pressure in the water
heater and speed draining. The
water passing out of the drain
valve may be extremely hot. To
avoid being scalded, make sure all
connections are tight and that the
water flow is directed away from
any person, see Figures 1 and 4.
5. Disconnect the vent pipe from the draft hood where they
connect to the water heater. In most installations the vent
pipe can be lifted off af ter any screw or other attached devices
are removed. Dispose of the draft hood. The new water
heater has the draft hood which must be used for proper
operation.
6. If you have copper piping to the water heater, the two copper
water pipes can be cut with a hacksaw approximately four
inches away from where they connect to the water heater.
This will avoid cutting off pipes too short. Additional cuts can
be made later if necessary. Disconnect the temperaturepressure relief valve drain line. When the water heater is
drained, disconnect the hose from the drain valve. Close the
drain valve. The water heater is now completely disconnected
and ready to be removed, see Figure 5.
FIGURE 4.
1. Turn “OFF” the gas supply to the
water heater.
If the main gas line Shut-off valve
serving all gas appliances is used,
also shut “OFF” the gas at each
appliance. Leave all gas
appliances shut “OFF” until the
water heater installation is
completed, see Figures 1 and 2.
2. Turn “OFF” the water supply to the
water heater at the water shut-off
valve or water meter. Some
installations require that the water
be turned off to the entire house,
see Figures 1 and 3.
3. Check again to make sure the gas supply is “OFF” to the
water heater . Then disconnect the gas supply connection from
the gas control valve.
FIGURE 2.
FIGURE 3.
FIGURE 5.
If you have galvanized pipe to the water heater, loosen the
two galvanized pipes with a pipe wrench at the union in each
line. Also disconnect the piping remaining to the water
heater. These pieces should be saved since they may be
needed when reconnecting the new water heater.
Disconnect the temperature-pressure relief valve drain line.
When the water heater is drained, disconnect the hose from
the drain valve. Close the drain valve. The water heater is
now completely disconnected and ready to be removed.
Mineral buildup or sediment may have accumulated in the
old water heater. This causes the water heater to be much
heavier than normal and this residue, if spilled out, could
cause staining, see Figure 6.
7
FIGURE 6.
TYPICAL INST ALLATION
GET TO KNOW YOUR WATER HEA TER - GAS MODELS
AVent Pipe
BDraft Hood
CAnode
DHot Water Outlet
EOutlet
FWater Connections
GGas Supply
HManual Gas Shut-off Valve
SFlue Baffle(s)
TThermostat
UDrain Valve
VPilot and Main Burner
WFlue
XDrain Pan
YThermostat Shield (optional)
(T) THERMOST AT
* ALL PIPING MATERIALS TO BE
SUPPLIED BY CUSTOMERS.
** CLOSED WATER SYSTEMS ARE THOSE WITH
BACK FLOW PREVENTION DEVICES INSTALLED
IN THE INLET WATER SERVICE LINE.
Y
THERMOSTAT
SHIELD
(OPTIONAL)
FIGURE 7.
(V) PILOT & MAIN BURNER- NATURAL GAS
(V) PILOT & MAIN BURNER - PROPANE GAS
THERMOCOUPLE
PILOT
BURNER
8
MAIN
BURNER
TYPICAL INSTALLATION
MIXING V ALVE USAGE
FIGURE 8.
This appliance has been design certified as complying with
American National St andard/CSA S tandard for water heaters and
is considered suitable for:
Water (Potable) Heating: All models are considered suitable
for water (potable) heating.
HOTTER WATER CAN SCALD:
Water heaters are intended to produce hot water . Water heated
to a temperature which will satisfy clothes washing, dish
washing, and other sanitizing needs can scald and permanently
injure you upon contact. Some people are more likely to be
permanently injured by hot water than others. These include
the elderly, children, the infirm, or physically/mentally
handicapped. If anyone using hot water in your home fits into
one of these groups or if there is a local code or province law
requiring a certain temperature water at the hot water tap, then
you must take special precautions. In addition to using the
lowest possible temperature setting that satisfies your hot water
needs, a means such as a *Mixing Valve, shall be used at the
hot water taps used by these people or at the water heater.
Mixing valves are available at a plumbing supply distributor,
see Figure 8. Valves for reducing point of use, temperature by
mixing cold and hot water are also available. Consult MaytagCustomer Service at 1-800-788-8899. Follow mixing valve
manufacturer’s instructions for installation of the valves. Before
changing the factory setting on the thermostat, read the
“Temperature Regulation” section in this manual, see Figures
22 and 23 on page 21.
9
LOCATING AND INSTALLING THE NEW WATER HEATER
Facts to Consider About the Location
Carefully choose an indoor location for the new water heater,
because the placement is a very important consideration for the
safety of the occupants in the building and for the most
economical use of the appliance. This water heater is not for
use in manufactured (mobile) homes or outdoor installation.
Whether replacing an old water heater or putting the water heater
in a new location, the following critical points must be observed:
• Select a location indoors as close as practical to the gas vent
or chimney to which the water heater vent is going to be
connected, and as centralized with the water piping system
as possible.
• Selected location must provide adequate clearances for
servicing and proper operation of the water heater.
water pipes connected to the water heater.
• Devices that will turn off the gas supply to a gas water heater
while at the same time shutting off its water supply.
Installation of the water heater must be accomplished in such a
manner that if the tank or any connections should leak, the flow
will not cause damage to the structure. For this reason, it is not
advisable to install the water heater in an attic or upper floor.
When such locations cannot be avoided, a suitable drain pan
should be installed under the water heater. Drain pans are
available at your local distributor. Such a drain pan must have a
minimum length and width of at least 2 inches (51 mm) greater
than the water heater dimensions and must be piped to an
adequate drain. The pan must not restrict combustion air flow.
Water heater life depends upon water quality, water pressure
and the environment in which the water heater is installed. Water
heaters are sometimes installed in locations where leakage may
result in property damage, even with the use of a drain pan piped
to a drain. However, unanticipated damage can be reduced or
prevented by a leak detector or water shut-off device used in
conjunction with a piped drain pan. These devices are available
from some plumbing supply wholesalers and retailers, and detect
and react to leakage in various ways:
• Sensors mounted in the drain pan that trigger an alarm or
turn off the incoming water to the water heater when leakage
is detected.
• Sensors mounted in the drain pan that turn off the water
supply to the entire home when water is detected in the
drain pan.
INST ALLATIONS IN AREAS WHERE FLAMMABLE LIQUIDS
(VAPORS) ARE LIKELY TO BE PRESENT OR STORED
(GARAGES, STORAGE AND UTILITY AREAS, ETC.):
Flammable liquids (such as gasoline, solvents, propane [LP or
butane, etc.] and other substances such as adhesives, etc.) emit
flammable vapors which can be ignited by a gas water heater’s
pilot light or main burner. The resulting flashback and fire can
cause death or serious burns to anyone in the area, as well as
property damage. If installation in such areas is your only option,
then installation must be accomplished in a way that the pilot
flame and main burner flame are elevated from the floor at least
18 inches. While this may reduce the chances of flammable
vapors, from a floor spill being ignited, gasoline and other
flammable substances should never be stored or used in the
same room or area containing a gas water heater or other open
flame or spark producing appliance. NOTE: Flammable vapors
may be drawn by air currents from other areas of the structure to
the appliance.
• Water supply shut-off devices that activate based on the
water pressure differential between the cold water and hot
Also, the water heater must be located and/or protected so it is
not subject to physical damage by a moving vehicle.
10
This water heater must not be installed directly on carpeting.
Carpeting must be protected by metal or wood panel beneath
the appliance extending beyond the full width and depth of the
appliance by at least 3 inches (76.2 mm) in any direction, or if
the appliance is installed in an alcove or closet, the entire floor
must be covered by the panel. Failure to heed this warning may
result in a fire hazard.
A gas water heater cannot operate properly without the correct
amount of air for combustion. Do not install in a confined area
such as a closet, unless you provide air as shown in the Locatingand Installing The New Water Heater section. Never obstruct
the flow of ventilation air. If you have any doubts or questions at
all, call your gas supplier. Failure to provide the proper amount
of combustion air can result in a fire or explosion and cause
death, serious bodily injury, or property damage.
FIGURE 10.
If this water heater will be used in beauty shops, barber shops,
cleaning establishments, or self-service laundries with dry
cleaning equipment, it is imperative that the water heater or water
heaters be installed so that combustion and ventilation air be
taken from outside these areas.
Minimum clearances between the water heater and combustible
construction are 0 inch at the sides and rear, 4 inches (102 mm)
at the front, and 6 inches (153 mm) from the vent pipe. Clearance
from the top of the jacket is 12 inches (305 mm) on most models.
Note that a lesser dimension may be allowed on some models,
refer to the label attached adjacent to the gas control valve on
the water heater, see Figure 9.
FIGURE 9.
Propellants of aerosol sprays and volatile compounds, (cleaners,
chlorine based chemicals, refrigerants, etc.) in addition to being
highly flammable in many cases, will also change to corrosive
hydrochloric acid when exposed to the combustion products of
the water heater. The results can be hazardous, and also cause
product failure.
Insulation Blankets
Insulation blankets available to the general public for external
use on gas water heaters are not necessary with Maytag
products. The purpose of an insulation blanket is to reduce the
standby heat loss encountered with storage tank heaters. Your
Maytag water heater meets or exceeds the NRCan standards
with respect to insulation and standby loss requirements, making
an insulation blanket unnecessary.
WARNING
Should you choose to apply an insulation blanket to this heater,
you should follow these instructions (See Figure 7 for
identification of components mentioned below). Failure to follow
these instructions can restrict the air flow required for proper
11
combustion, potentially resulting in fire, asphyxiation, serious
personal injury or death.
• Do not apply insulation to the top of the water heater, as this
will interfere with safe operation of the draft hood.
• Do not cover the outer door, thermostat or temperature &
pressure relief valve.
• Do not allow insulation to come within 2” (50.8 mm) of the
floor to prevent blockage of combustion air flow to the burner.
commence within 12 inches (30 cm) of the top and one
commencing within 12 inches (30 cm) of the bottom of the
enclosures.
• Do not cover the instruction manual. Keep it on the side of
the water heater or nearby for future reference.
• Do obtain new warning and instruction labels from Maytag
for placement on the blanket directly over the existing labels.
• Do inspect the insulation blanket frequently to make certain
it does not sag, thereby obstructing combustion air flow.
Combustion Air and Ventilation for
Appliances Located in Unconfined Spaces
UNCONFINED SP ACE is space whose volume is not less than
50 cubic feet per 1,000 Btu per hour (4.8 m
aggregate input rating of all appliances installed in that space.
Rooms communicating directly with the space in which the
appliances are installed, through openings not furnished with
doors, are considered a part of the unconfined space.
In unconfined spaces in buildings, infiltration may be adequate
to provide air for combustion, ventilation and dilution of flue
gases. However, in buildings of tight construction (for example,
weather stripping, heavily insulated, caulked, vapor barrier , etc.),
additional air may need to be provided using the methods
described in Combustion Air and Ventilation for AppliancesLocated in Confined Spaces.
3
per kW) of the
FIGURE 11.
B. ALL AIR FROM OUTDOORS: (See Figures 12, 13 and 14)
The confined space shall be provided with two permanent
openings, one commencing within 12 inches (30 cm) of the top
and one commencing within 12 inches (30 cm) from the bottom
of the enclosure. The openings shall communicate directly, or
by ducts, with the outdoors or spaces (crawl or attic) that freely
communicate with the outdoors.
Combustion Air and Ventilation for
Appliances Located in Confined Spaces
CONFINED SPACE is a space whose volume is less than
50 cubic feet per 1,000 Btu per hour (4.8 m
aggregate input rating of all appliances installed in that space.
A. ALL AIR FROM INSIDE BUILDINGS:
(See Figures 10 and 11)
The confined space shall be provided with two permanent
openings communicating directly with an additional room(s)
of sufficient volume so that the combined volume of all spaces
meets the criteria for an unconfined space. The total input of
all gas utilization equipment installed in the combined space
shall be considered in making this determination. Each
opening shall have a minimum free area of one square inch
per 1,000 Btu per hour (22 cm
2
/kW) of the total input rating of
all gas utilization equipment in the confined space, but not
less than 100 square inches (645 cm
3
per kW) of the
2
). One opening shall
FIGURE 12.
• When directly communicating with the outdoors, each opening
shall have a minimum free area of 1 square inch per 4,000 Btu per
hour (5.5 cm
2
/kW) of total input rating of all equipment in the
enclosure, see Figure 12.
• When communicating with the outdoors through vertical
ducts, each opening shall have a minimum free area of
1 square inch per 4,000 BTU per hour (5.5 cm
2
/kW) of total
input rating of all equipment in the enclosure, see
Figure 13.
12
Water Piping
FIGURE 13.
• When communicating with the outdoors through horizontal
ducts, each opening shall have a minimum free area of
1 square inch per 2,000 BTU per hour (11 cm
2
/kW) of total
input rating of all equipment in the enclosure, see
Figure 14.
• When ducts are used, they shall be of the same crosssectional area as the free area of the openings to which they
connect. The minimum short side dimension of rectangular
air ducts shall not be less than 3 inches
(76.2 mm), see Figure 14.
HOTTER WATER CAN SCALD:
Water heaters are intended to produce hot water. Water
heated to a temperature which will satisfy clothes washing,
dish washing, cleaning and other sanitizing needs can scald
and permanently injure you upon contact. Some people are
more likely to be permanently injured by hot water than others.
These include the elderly, children, the infirm, or physically/
mentally handicapped. If anyone using hot water in your home
fits into one of these groups or if there is a local code or
province law requiring a certain temperature water at the hot
water tap, then you must take special precautions. In addition
to using the lowest possible temperature setting that satisfies
your hot water needs, a means such as a *mixing valve, shall
be used at the hot water taps used by these people or at the
water heater. Mixing valves are available at a plumbing supply
distributor, see Figure 8 on p age 9 and Figure 15 below. V alves
for reducing point of use temperature by mixing cold and hot
water are also available. Consult Maytag Customer Serviceat 1-800-788-8899. Follow manufacturer’s instructions for
installation of the valves. Before changing the factory setting
on the thermostat, read the Temperature Regulation section
in this manual.
FIGURE 14.
• Louvers and Grilles: In calculating free area, consideration
shall be given to the blocking effect of louvers, grilles or
screens protecting openings. Screens used shall not be
smaller than 1/4 inch (6.4 mm) mesh. If the free area through
a design of louver or grille is known, it should be used in
calculating the size opening required to provide the free area
specified. If the design and free area is not known, it may be
assumed that wood louvers will be 20-25 percent free area
and metal louvers and grilles will have 60-75 percent free
area. Louvers and grilles shall be fixed in the open position
or interlocked with the equipment so that they are opened
automatically during equipment operation.
• Special Conditions Created by Mechanical Exhausting or
Fireplaces: operation of exhaust fans, ventilation systems,
clothes dryers or fireplaces may create conditions requiring
special attention to avoid unsatisfactory operation of installed
gas utilization equipment.
FIGURE 15.
This water heater shall not be connected to any heating systems
or component(s) used with a non-potable water heating
appliance.
13
Toxic chemicals, such as those used for boiler treatment shall
not be introduced into this system.
Water supply systems may, because of such events as high
line pressure, frequent cut-offs, the effects of water hammer
among others, have installed devices such as pressure reducing
valves, check valves, back flow preventers, etc. to control these
types of problems. When these devices are not equipped with
an internal by-pass, and no other measures are taken, the
devices cause the water system to be closed. As water is heated,
it expands (thermal expansion) and closed systems do not allow
for the expansion of heated water.
The water within the water heater tank expands as it is heated
and increases the pressure of the water system. If the relieving
point of the water heater’s temperature-pressure relief valve is
reached, the valve will relieve the excess pressure. The
temperature-pressure relief valve is not intended for the
constant relief of thermal expansion. This is an unaccept able
condition and must be corrected. It is recommended that any
devices installed which could create a closed system have a
by-pass and/or the system have an expansion tank to relieve
the pressure built by thermal expansion in the water system.
Refer to the Thermal Expansion section under Troubleshooting
Guide or contact local plumbing authority or call Maytag
Customer Service at 1-800-788-8899 for an authorized
installer on how to control this situation.
can be accomplished by insulating the hot water lines
from the water heater.
NOTE: To protect against untimely corrosion of hot and cold
water fittings, it is strongly recommended that di-electric
unions or couplings be installed on this water heater when
connected to copper pipe.
Figure 16 shows the typical attachment of the water piping to
the water heater. The water heater is equipped with 1” NPT
water connections for 75 gallon models.
NOTE: If using copper tubing, solder tubing to an adapter
before attaching the adapter to the water connections. Do
not solder the water lines directly to the water connections
on the tank. It will harm the dip tube and damage the tank.
• Look at the top cover of the water heater. The water outlet is
marked “HOT”. Put two or three turns of teflon tape around
the exposed end of the 1” NPT threaded nipple. Connect the
hot water pipe to the hot water outlet on the water heater.
• Look at the top of the water heater. The cold water inlet is
marked “COLD”. Put two or three turns of teflon tape around
the exposed end of the 1” NPT threaded nipple. Connect the
cold water pipe to the cold water inlet of the water heater.
NOTE: This water heater is super insulated to minimize
heat loss from the tank. Further reduction in heat loss
FIGURE 16.
Temperature-Pressure Relief Valve
This heater is provided with a properly certified combination
temperature - pressure relief valve by the manufacturer.
The valve is certified by a nationally recognized testing laboratory
that maintains periodic inspection of production of listed
equipment of materials as meeting the requirements for Relief
Valves for Hot Water Supply Systems, ANSI Z21.22 • CSA 4.4
and the code requirements of ASME.
14
If replaced, the valve must meet the requirements of local
codes, but not less than a combination temperature and
pressure relief valve certified as indicated in the above
paragraph.
The valve must be marked with a maximum set pressure not to
exceed the marked maximum working pressure of the water
heater (150 psi = 1,035 kPa) and a discharge capacity not less
than the water heater input rate as shown on the model rating
plate.
The Discharge Pipe:
For safe operation of the water heater, the relief valve must not
be removed from its designated opening nor plugged.
The temperature-pressure relief valve must be installed directly
into the fitting of the water heater designed for the relief valve.
Position the valve downward and provide tubing so that any
discharge will exit only within 6 inches (153 mm) above, or at
any distance below the structural floor. Be certain that no cont act
is made with any live electrical part. The discharge opening must
not be blocked or reduced in size under any circumstances.
Excessive length, over 30 feet (9.14 m), or use of more than
four elbows can cause restriction and reduce the discharge
capacity of the valve, see Figure 17.
No valve or other obstruction is to be placed between the relief
valve and the tank. Do not connect tubing directly to discharge
drain unless a 6 inch air gap is provided. To prevent bodily
injury, hazard to life, or property damage, the relief valve must
be allowed to discharge water in quantities should
circumstances demand. If the discharge pipe is not connected
to a drain or other suitable means, the water flow may cause
property damage.
• Shall not be smaller in size than the outlet pipe size of the
valve, or have any reducing couplings or other restrictions.
• Shall not be plugged or blocked.
• Shall be of material listed for hot water distribution.
• Shall be installed so as to allow complete drainage of both
the temperature-pressure relief valve, and the discharge
pipe.
• Shall terminate at an adequate drain.
• Shall not have any valve between the relief valve and tank.
The temperature-pressure relief valve must be manually
operated at least once a year. Caution should be taken to ensure
that (1) no one is in front of or around the outlet of the
temperature-pressure relief valve discharge line, and (2) the
water manually discharged will not cause any bodily injury or
property damage because the water may be extremely hot.
If after manually operating the valve, it fails to completely reset
and continues to release water, immediately close the cold
water inlet to the water heater, follow the draining instructions,
and replace the temperature-pressure relief valve with a new
one.
Filling the Water Heater
FIGURE 17.
15
Never use this water heater unless it is completely full of water.
T o prevent damage to the tank, the t ank must be filled with water .
Water must flow from the hot water faucet before turning “ON”
gas to the water heater.
To fill the water heater with water:
• Close the water heater drain valve by turning the handle to
the right (clockwise). The drain valve is on the lower front of
the water heater.
• Open the cold water supply valve to the water heater.
NOTE: The cold water supply valve must be left open
when the water heater is in use.
• To insure complete filling of the tank, allow air to exit by
opening the nearest hot water faucet. Allow water to run
until a constant flow is obtained. This will let air out of the
water heater and the piping.
• Check all water piping and connections for leaks. Repair as
needed.
Venting
VENT DAMPERS - Any vent damper, whether it is operated
thermally or otherwise must be removed if its use inhibits proper
drafting of the water heater.
Thermally Operated Vent Dampers: This gas-fired water
heater has a thermal efficiency at or above 80% which may
produce a relatively low flue gas temperature. Such
temperatures may not be high enough to properly open thermally
operated vent dampers. This would cause spillage of the flue
gases and may cause carbon monoxide poisoning.
Vent dampers must bear evidence of certification as complying
with the current edition of the American National Standard
ANSI Z21.66/CGA 6.14, (covering electrically and mechanically
actuated vent dampers). Before installation of any vent damper ,
consult your Maytag Customer Service Center at 1-800-7888899 or the local gas supplier for further information.
T o insure proper venting of this gas-fired water heater, the correct
vent pipe diameter must be utilized. Any additions or deletions
of other gas appliances on a common vent with
this water heater may adversely affect the operation of the
water heater. Consult your Maytag Customer Service Center
at 1-800-788-8899 or gas supplier if any such changes are
planned.
For proper venting in certain installations, a larger diameter vent
pipe may be necessary. Consult your Maytag Customer
Service Center at 1-800-788-8899 or gas supplier to aid you
in determining the proper venting for your water heater from
the vent tables in the current edition of CAN/CSA - B149.1
Installation Code.
Periodically check the venting system for signs of obstruction or
deterioration and replace if needed.
The combustion and ventilation air flow must not be obstructed.
The water heater with draft hood installed must be connected to
a chimney or listed vent pipe system, which terminates to the
outdoors. Never operate the water heater unless it is vented to
the outdoors and has adequate air supply to avoid risks of
improper operation, explosion or asphyxiation.
• For proper draft hood attachment, the draft hood legs may
be angled slightly inward.
• Place the draft hood legs in the receiving holes on the top of
the water heater. The legs will snap in the holes to give a
tight fit. Secure draft hood with the supplied brackets.
• Place the vent pipe over the draft hood. With the vent pipe in
position, drill a small hole through both the vent pipe and
draft hood. Secure them together with a sheet metal screw,
see Figure 18.
Obstructed or deteriorated vent systems may present serious
health risk or asphyxiation.
FIGURE 18.
The vent pipe from the water heater must be no less than the
diameter of the draft hood outlet on the water heater and must
slope upward at least 1/4 inch per linear foot (21 mm per meter),
see Figure 19.
FIGURE 19.
16
All vent gases must be completely vented to the outdoors of the
structure (dwelling). Install only the draft hood provided with the
new water heater and no other draft hood.
Vent pipes must be secured at each joint with sheet metal
screws.
There must be a minimum of 6 inches (153 mm) clearance
between single wall vent pipe and any combustible material.
Fill and seal any clearance between single wall vent pipe and
combustible material with mortar mix, cement, or other
noncombustible substance. For other than single wall, follow
vent pipe manufacturer’s clearance specifications. To insure a
tight fit of the vent pipe in a brick chimney , seal around the vent
pipe with mortar mix cement.
Make sure the gas supplied is the same type listed on the
model rating plate. The inlet gas pressure must not exceed
14 inch water column (2.6kPa) for natural and propane (L.P.)
gas. If the gas control valve is subjected to pressures exceeding
1/2 pound per square inch (3.5kPa), the damage to the gas
control valve could result in a fire or explosion from leaking
gas.
If the main gas line Shut-off serving all gas appliances is used,
also turn “OFF” the gas at each appliance. Leave all gas
appliances shut “OFF” until the water heater installation is
complete.
A gas line of sufficient size must be run to the water heater.
Consult the current edition of the CAN/CSA - B149.1 Inst allation
Codes and/or your gas supplier concerning pipe size.
There must be:
• A readily accessible manual shut off valve in the gas supply
line serving the water heater, and
• A drip leg (sediment trap) ahead of the gas control valve to
help prevent dirt and foreign materials from entering the gas
control valve.
• A flexible gas connector or a ground joint union between the
shut off valve and control valve to permit servicing of the unit.
Failure to have required clearances between vent piping and
combustible material will result in a fire hazard.
Be sure vent pipe is properly connected to prevent escape of
dangerous flue gases which could cause deadly asphyxiation.
Chemical vapor corrosion of the flue and vent system may occur
if air for combustion contains certain chemical vapors. Spray
can propellants, cleaning solvents, refrigerator and air
conditioner refrigerants, swimming pool chemicals, calcium and
sodium chloride, waxes, bleach and process chemicals are
typical compounds which are potentially corrosive.
Gas Piping
Be sure to check all the gas piping for leaks before lighting the
water heater. Use a soapy water solution, not a match or open
flame. Rinse off soapy solution and wipe dry.
The minimum inlet gas pressure shown on the rating plate is
that which will permit firing at the rated input.
Standard Models are for installation up to 2,000 feet (610 m)
above sea level.
High Altitude models are for installation from 2,000 feet
(610 m) to 4,500 feet (1,370 m) above sea level.
If a standard model is installed above 2,000 feet (610 m) or high
altitude model is installed above 4,500 feet (1,370 m), the input
rating should be reduced at the rate of 4 percent for each 1000
feet (305 m) above sea level which requires replacement of the
burner orifice in accordance with CAN/CSA - B149.1. Contact
Maytag Customer Service Center at 1-800-788-8899 or your
local gas supplier or call for further information.
17
Failure to replace the standard orifice with a high altitude orifice
when installed at elevations above 2,000 feet (610 m) or above
4,500 feet (1,370 m) for high altitude model could result in
improper and inefficient operation of the appliance, producing
carbon monoxide gas in excess of safe limits, which could result
in serious injury or death. Contact Maytag Customer Service
at 1-800-788-8899 or your local gas supplier for any specific
changes which may be required in your area.
Use pipe joint compound or teflon tape marked as being resistant
to the action of petroleum (Propane [L.P.]) gases.
The appliance and its gas connection must be leak tested before
placing the appliance in operation.
Contaminants in the gas lines may cause improper operation of
the gas control valve that may result in fire or explosion. Before
attaching the gas line be sure that all gas pipe is clean on the
inside. To trap any dirt or foreign material in the gas supply line,
a drip leg (sometimes called a sediment trap) must be
incorporated in the piping. The drip leg must be readily
accessible. Install in accordance with the Gas Piping section.
Refer to the current edition of CAN/CSA - B149.1 and/or Local
Installation Code.
A sediment trap shall be installed as close to the inlet of the
water heater as practical at the time of water heater installation.
The sediment trap shall be either a tee fitting with a capped
nipple in the bottom outlet or other device recognized as an
effective sediment trap. If a tee fitting is used, it shall be installed
in conformance with one of the methods of installation, shown
in Figures 20 and 21.
The appliance and its individual Shut-off valve shall be
disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess of 1/
2 pound per square inch (3.5kPa). It shall be isolated from the
gas supply piping system by closing its individual manual Shutoff valve during any pressure testing of the gas supply piping
system at test pressures equal to or less than 1/2 pound per
square inch (3.5kPa).
Connecting the gas piping to the gas control valve of the water
heater can be accomplished by either of the two methods, shown
in Figures 20 and 21.
Sediment Traps
FIGURE 20. GAS PIPING WITH FLEXIBLE CONNECTOR.
18
FIGURE 21. GAS PIPING WITH ALL
BLACK IRON PIPE TO GAS CONTROL.
OPERATING INSTRUCTIONS
19
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING:If you do not follow these instructions exactly, a fire or explosion
may result causing property damage, personal injury or loss of life.
BEFORE LIGHTING: ENTIRE SYSTEM MUST BE FILLED WITH WATER AND AIR PURGED AT FAUCETS.
A.This appliance has a pilot which must be lighted by hand.
When lighting the pilot, follow these instructions exactly.
B. BEFORE LIGHTING: smell all around the appliance
area for gas. Be sure to smell next to the floor because
some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
•Do not try to light any appliance.
•Do not touch any electric switch; do not use
any phone in your building.
•Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
LIGHTING INSTRUCTIONS
FIGURE 1.
1. STOP! Read the safety information above on
this label.
2. Set the thermostat to the lowest setting by turning
thermostat dial fully clockwise
3. Push the gas control knob down slightly and turn
clockwise
NOTE: Gas control knob CANNOT be turned from "PILOT"
to "OFF" unless it is pushed down slightly . Do not force.
4. Remove the inner and outer doors located below and
behind the gas control unit.
5. Wait five (5) minutes to clear out any gas. If you then
smell gas STOP! Follow "B" in the safety information
above on this label. If you do not smell gas, go to the
next step.
6. Find Pilot. Follow metal tube from the bottom , right of
the gas control to the pilot burner. (Figure D).
7. Turn gas control knob counterclockwise
(Figure B).
8. Push gas control knob down all the way and hold it down.
Immediately light the pilot with a match. Continue to hold
to "OFF" (Figure A).
until it stops.
TOP VIEWFIGURE D.
to "PILOT"
•If you cannot reach your gas supplier, call the
fire department.
C. Use only your hand to push down or turn the gas
control knob. Never use tools. If the knob will not
push down or turn by hand, don’t try to repair it, call a
qualified service technician. Force or attempted repair
may result in a fire or explosion.
D. Do not use this appliance if any part has been under
water. Immediately contact a qualified installer or
service agency to replace a flooded water heater. Do
not attempt to repair the unit! It must be replaced!
the gas control knob down for about one (1) minute
after the pilot is lit. Release the gas control knob and it
will pop back up. Pilot should remain lit. If it goes out,
repeat Steps 3 through 8. It may take several minutes for
air to clear the lines, before the pilot will light.
•If knob does not pop up when released, stop and
immediately call your service technician or gas
supplier.
•If the pilot will not stay lit after several tries, turn the
gas control knob to "OFF" (Figure A) andcall your
service technician or gas supplier.
9. Replace inner and outer burner doors.
10. At arm's length away, turn the gas control knob
counterclockwise
11. Set thermostat to desired setting (See Figure 1).
CAUTION: Hotter water increases the risk of
scald injury. Consult the instruction manual
before changing temperature.
to on (Figure C).
TO TURN OFF GAS T O APPLIANCE
1. Set the thermostat to lowest setting.
2. Push gas control knob down slightly and turn clockwise
to “OFF”. Do not force, see Figure A.
20
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.