Maytag HN41250X, HN51240X, HN51250X, HP41250X, HP51250X User Manual

...
Page 1
1VIAYIAG
®
Series Twelve
GAS WATER HEATER
USER'S GUIDE @
For Your Safety
AN ODORANT ISADDED TO THE GAS USED BY THIS Model Numbers
HN51240X
WARNING: If the information in these instructions are not fol- HP41240X
lowed exactly, a fire or explosion may result, causing property HP51240X
damage, personalinjuryor death. HN41250X
HN51250X
-Do not store or use gasolineor other flammable vaporsand liq- HP41250X uids inthe vicinityof thisor any other appliance. HP51250X
-WHAT TO DOIFYOU SMELLGAS HN41250Q
HN51250Q
Do nottry to lightany appliance. HP41250Q
Do not touch any electrical switch; do not use any phone in HP51250Q your building. HN41275Q
Immediately callyour gas supplier from a neighbor's phone. HN51275Q Followthe gassupplier'sinstructions. HP41275Q
If you can not reachyour gassupplier,callthe fire department. HP51275Q
-Installation and servicemustbe performed by a qualified installer, serviceagencyorthe gassupplier. FOR POTABLE WATER
HEATINGONLY
AWARNING
Improper installation, adjustment, alteration, service or mainte- NOT SUITABLEFOR nance can cause DEATH,SERIOUSBODILYINJURY,OR PROPERTY SPACEHEATING DAMAGE. Refer to this manual for assistance or consult the local
gas utility for further information. NOT FOR USE IN
AWARNING I MANUFACTURED
(MOBILE)HOMES
Flammable vapors may be drawn by air currents from other
areas of the structure to th s app lance. Caution:
Readand Follow All
A,WARNING Safety Rules and
READ THE GENERAL SAFETY SECTION BEGINNING ON INSIDE Operating Instructions COVER AND THEN THIS ENTIREMANUAL BEFOREINSTALLING Before First Use of
OR OPERAT NG THIS WATER HEATER.
This Product.
Save this Manual for Future Reference.
Page 2
Safety Instructions
AWARNING AWARNING
Improper installation, adjustment, alteration, service At the time of manufacture this water heater was pro-
or maintenance can cause death, serious bodily vided with a combination temperature-pressures relief
injury, or property damage. Refer to this manual for valve certified by a nationally recognized testing labo- assistance consult your local gas utility or call ratory that maintains periodic inspection of production Maytag Customer Service at 1-800-788-8899 for an of listed equipment or materials, as meeting the
authorized servicer for further information.
requirements for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, and the latest edition of ANSI Z21.22 and the code require-
ments of ASME. If replaced, the valve must meet the
&WARNING requirements of local codes, but not lessthan a combi-
|WATER HEATERS EQUIPPED FOR ONE TYPE GAS nation temperature and pressure relief valve certified |ONLY: This water heater is equipped for one type as meeting the requirements for Relief Valves and
gas only. Check the model rating plate near the gas Automatic Gas Shutoff Devicesfor Hot Water Supply control valve for the correct gas. DO NOT USE THIS
Systems, ANSI Z21.22 by a nationally recognized test-
WATER HEATER WITH ANY GAS OTHER THAN THE ing laboratory that maintains periodic inspection of ONE SHOWN ON THE MODEL RATING PLATE.Failure production of listed equipment or materials. to use the correct gas can cause problems which can The valve must be marked with a maximum set pres- result in DEATH, SERIOUS BODILY INJURY, OR PROP- sure not to exceed the marked hydrostatic working
ERTY DAMAGE. If you have any questions or doubts pressure of the water heater (150 Ibs./sq. in.) and a consult your gas supplier or local utility, discharge capacity not less than the water heater
input rate as shown on the model rating plate. (Electric heaters - watts divided by 1000 x 3415 equal
BTU/Hr. rate.)
AWARNING Your local jurisdictional authority, while mandating the
INSTALLATIONS IN AREAS WHERE FLAMMABLE LIQ- use of a temperature-pressure relief valve complying UIDS (VAPORS)ARE LIKELYTO BEPRESENTOR STORED with ANSI Z21.22 and ASME, may require a valve model
different from the one furnished with the water heater.
(GARAGES, STORAGE, AND UTILITY AREAS, ETC):
I Flammable liquids (such as gasoline, solvents, propane Compliance with such local requirements must be sat-
(LP) or butane, etc.), all of which emit flammable isfied by the installer or end user of the water heater vapors, may be improperly stored or used in such with a locally prescribed temperature-pressure relief
areas. The gas water heater pilot light or main burner valve installed in the designated opening in the water can ignite suchvapors, The resulting flashback and fire heater in place of the factory furnished valve.. can cause death or serious burns to anyone in the For safe operation of the water heater, the rehef valve area, as well as property damage, must not be removed from it's designated opening or If installation in such areas is your only option, then plugged.
the installation must be accomplished in a way that The temperature-pressure relief valve must be the pilot flame and main burner flame are elevated installed directly into the fitting of the water heater
from the floor at least 18 inches,While this may reduce designated for the relief valve. Position the valve the chances of flammable vapors from a floor spill downward and provide tubing so that any discharge
being ignited, gasoline and other flammable sub- will exit only within 6 inches above, or at any distance stances should never be stored or used in the same below the structural floor. Becertain that no contact is
room or area containing a gas water heater or other made with any live electrical part. The discharge open- open flame or spark producing appliance, ing must not be blocked or reduced in size under any NOTE: Flammable vapors may be drawn by air currents circumstances.Excessivelength, over 30 feet, or useof
from other areas of the structure to the appliance, more than four elbows can cause restriction and
reduce the discharge capacity of the valve. No valve or other obstruction isto be placed between
the relief valve and the tank. Do not connect tubing
AWARNING directly to discharge drain unlessa 6_air gap is provic[-
If this water heater will be used in beauty shops, ed. To prevent bodily injury, hazard to life, or property barber shops, cleaning establishments, or self-serv- damage, the relief valve must be allowed to discharge ice laundries with dry cleaning equipment, it is water in quantities should circumstances demand. If imperative that the water heater or water heaters the discharge pipe is not connected to a drain or other
be installed so that combustion and ventilation air suitable means, the water flow may cause property be taken from outside these areas. Refer to the damage.
"Locating The New Water Heater" section of this The Discharge Pipe: manual and also the latest edition of the National Must notbe smaller in size than the outlet pipe size
Fuel Gas Code, ANSI Z223.1, also referred to as NFPA of the valve, or have any reducing couplings or 54 for specifics provided concerning air required, other restrictions.
Must not be plugged or blocked.
Must be of material listed for hot water distribution.
AWARNING Must be installed so as to allow complete drainage
of both the temperature-pressure relief valve, and
A fire can start if combustible materials such as the discharge pipe. clothing, cleaning materials, or flammable liquids Must terminate at an adequate drain.
are paced against or next to the water heater. Must not have any valve between the relief valve
and tank. I
2
Page 3
Safety Instructions
AWARNING AWARNING
A gas water heater cannot operate properly without This water heater must not be installed directly on the correct amount of air for combustion. Do not carpeting. Carpeting must be protected by a metal install in a confined area such a closet, unless you or wood panel beneath the appliance extending
provide air as shown in the "Locating The New beyond the full width and depth of the appliance by Water Heater" section. Never obstruct the flow of at least 3 inches (76.2mm) in any direction, or if the ventilation air. If you have any doubts or questions appliance is installed in an alcove or closet, the at all, call your gas company. Failure to provide the entire floor must be covered by the panel. Failure to proper amount of combustion air can result in a fire heed this warning may result in a fire hazard. or explosion and can cause DEATH, SERIOUS BODILY
INJURY,OR PROPERTYDAMAGE.
AWARNING
VENT DAMPERS - Any vent damper, whether it is
AWARNING operated thermally or otherwise must be removed if
HOTTER WATER CAN SCALD: Water heaters are its use inhibits proper drafting of the water heater.
intended to produce hot water. Water heated to a Thermally Operated Vent Dampers: Gas-fired water temperature which will satisfy clothes washing, dish heaters having thermal efficiency in excess of 80% washing, and other sanitizing needs can scald and may produce a relatively low flue gas temperature. permanently injure you upon contact. Some people Such temperatures may not be high enough to prop- are more likely to be permanently injured by hot erly open thermally operated vent dampers. This water than others. These include the elderly, children, would cause spillage of flue gases and may cause
the infirm, or physically/mentally handicapped. If carbon monoxide poisoning.
anyone using hot water in your home fits into one of Vent dampers must bear evidence of certification as these groups or if there is a local code or state law complying with the latest edition of American
requiring a certain temperature water at the hot National Standard ANSI Z21.68 (ANSI Z21.66 & 67,
water tap, then you must take special precautions. In respectively, cover electrically and mechanically actu-
addition to using the lowest possible temperature ated vent dampers). Before installation of any vent setting that satisfies your hot water needs, a means damper, consult your local gas utility for further
such as a mixing valve, should be used at the hot information.
water taps used by these people or at the water
heater. Mixing valves are available at plumbing sup- ply or hardware stores. Follow manufacturers instruc-
tions for installation of the valves. Before changing the factory setting on the thermostat, read the AWARNING
"Temperature Regulation" section in this manual.
* The appliance and its individual shutoff valve must
be disconnected from the gas supply piping system during any pressure testing of the gas system at test pressures in excess ofl/2 pound per square
AWARNING inch (3,5kPa).
The appliance must be isolated from the gas sup-
Soot build-up indicates a problem that requires cor- ply piping system by closing its individual manual rection before further use. Turn "off" gas to water shutoff valve during any pressure testing of the
heater and leave "off" until repairs are made, gas supply piping system at test pressures equal or because failure to correct the cause of the sooting lessthan 1/2 pound per square inch (3.SkPa).
can result in a fire or explosion causing DEATH, SERI-
OUS BODILY INJURY, OR PROPERTYDAMAGE.
AWARNING AWARNING
Chemical vapor corrosion of the flue and vent sys- BEFORE LIGHTING [PROPANE (L.P.) GAS WATER tem may occur if air for combustion contains certain HEATERS]: Propane (L.R) gas is heavier than air. chemical vapors. Spray can propellants, cleaning sol-
Should there be a leak in the system, the gas will set-
vents, refrigerator and air conditioner refrigerants,
tie near the ground. Basements, crawl spaces, skirted swimming pool chemicals, calcium and sodium chlo-
areas under manufactured (mobile) homes (even ride, waxes, bleach, and process chemicals are typJ-
when ventilated), closets and areas below ground cal compounds which are potentially corrosive,
level will serve as pockets for the accumulation of this gas. Before attempting to light or relight the water
eater's pilot or turning on a nearby electrical light
switch, be absolutely sure there is no accumulated
gas in the area. Search for odor of gas by sniffing at _,WARNING pres-
ground level in the vicinit_ of the appliance. If odor is Obstructed or deteriorated vent systems may detected, follow steps indicated at "For Your Safety" ent a serious health riskor asphyxiation.
on the cover page of this manual then leave the
premises.
3 Safety Instructions continued on page 4.
Page 4
Safety Instructions
_,WARNING _WARNING
The water heater with draft hood installed must be INSULATING JACKETS; When installing an external
properly vented to a chimney which terminates out- water heater insulation jacket on a gas water heater:
doors. Never operate the water heater unless it is DO NOT coverthe temperature-pressure relief valve. vented to the outdoors and has adequate air supply DO NOT put insulation over any part of the top of to avoid risks of improper operation, explosion or the gas water heater. asphyxiation. DO NOT put insulation over the gas control valve or
gas control valve/burner cover, or any accessareas to the burner.
DO NOT let insulation around the gas water heater
AWARNING to get within 8 inches of the floor (air must get to
Minimum clearances between the water heater and the burner). combustible and noncombustible construction are 1'p DO NOT cover or remove operating instructions, at the sides and rear, 4" at the front, and 6" from the and safety related warning labels and materials
vent pipe. Clearance from the top of the jacket is 18" affixed to the water heater. on most models. Note that a lesser dimension may be Failure to heed this will result in the possibility of a
allowed on some models. Refer to the label on the fire or explosion. water heater adjacent to the gas control valve for all
clearances.
ACAUTION
AWARNING WATER HEATERS EVENTUALLY LEAK: Installation of
Flood damage to a water heater may not be readily the water heater must be accomplished in such a
visible or immediately detectible. However, over a manner that if the tank or any connections should period of time a flooded water heater will create leak, the flow of water will not cause damage to dangerous conditions which can cause DEATH, SERI- the structure. For this reason, it is not advisable to
OUS BODILY INJURY OR PROPERTY DAMAGE. install the water heater in an attic or upper floor. Contact the Maytag dealer from whom the appli- When such locations cannot be avoided, a suitable
ance was purchased or call Maytag Customer Service drain pan should be installed under the water at 1-800-788-8899 for an authorized servicer to heater. Drain pans are available at your local hard-
replace a flooded water heater, Do not attempt to ware store. Such a drain pan must be not greater repair the unit! It must be replaced! than 1½ inches deep, have a minimum length and
width of at least 2 inches greater than the water heater dimensions and must be piped to an ade- quate drain. The pan must not restrict combustion
AWARNING air flow. Under no circumstances is the manufactur-
er to be held liable for any water damage in con-
HYDROGEN GAS: Hydrogen gas can be produced in a hot water system that has not been used for a nection with this water heater.
long period of time (generally two weeks or more).
Hydrogen gas isextremely flammable and explosive. To prevent the possibility of injury under these con-
ditions, we recommend the hot water faucet be opened for several minutes at the kitchen sink
before any electrical appliances which are connected to the hot water system are used (such as a dish- washer or washing machine). If hydrogen gas is
present, there will probably be an unusual sound similar to air escaping through the pipe as the hot water faucet is opened. There must be no smoking
or open flame near the faucet at the time it isopen.
Page 5
Table of Contents
Safety Instructions ..................................................................................................................................2-4
Table of Contents ..........................................................................................................................................5
Customer Information .......................................................................................................................6
Product Specifications ...........................................................................................................................7
Accessories and Tools Needed .................................................................................................7
Accessories ........................................................................................................................................................................ .7
Tools ..................................................................................................................................................................................... 7
Instructions for Installation ...........................................................................................8-17
Removing the Old Water Heater .......................................................................................................................................... 8
Typical Installation ............................................................................................................................................................... 9
Locating the New Water Heater. ..................................................................................................................................... 10
Combustion Air and Ventilation for Appliances in Unconfined Spaces ............................................................................. 11
Combustion Air and Ventilation for Appliances in Confined Spaces ........................................................................... 11-12
Water Piping ................................................................................................................................................................. 13
Temperature-Pressure Relief Valve ................................................................................................................................. 14
Filling the Water Heater ............................................................................................................................................... 15
Venting ........................................................................................................................................................................ 15-16
Gas Piping ................................................................................................................................................................. 16-17
Installation Checklist ........................................................................................................................................................ 18
Instru cfion.s...fo.r.._pe::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::
Temperature Regulation ................................................................................................................................................. .21
Service and Maintenance ..........................................................................................................2>z4
Venting System Inspection. .............................................................................................................................................. .22
Burner Inspection ........................................................................................................................................................ .22
kP. Gas Control Valve and Burner Assembly Replacement Information ......................................................................... .23
Burner Cleaning ........................................................................................................................................................... 23
Draining. ......................................................................................................................................................................... 23
Temperature-Pressure Relief Valve Operation ............................................................................................................... 23
Drain Valve Washer Replacement .................................................................................................................................. .24
Housekeeping ................................................................................................................................................................ 24
Service ............................................................................................................................................................................. .24
Condensation ............................................................................................................................................................. .25
Smoke/Odor ............................................................................................................................................................... .25
Thermal Expansion ................................................................................................................................................... .25
Strange Sounds. ............................................................................................................................................................ .25
Operational Conditions ................................................................................................................................................ .26-27
Smelly Water ................................................................................................................................................................ 26
Air in Hot Water Faucets .............................................................................................................................................. 26
High Temperature Shut Off System ............................................................................................................................ .26
Not Enough Hot Water .............................................................................................................................................. 26
Water is too Hot ........................................................................................................................................................ ..27
Leakage Checkpoints ................................................................................................................................................ 28
Repair Parts List .................................................................................................................................. 29-35
Warranty ...................................................................................................................................................................36
Page 6
Customer Information
Thank You for purchasing a Maytag water heater, and be aware of.All warnings and all instructions are essential
Properly installed and maintained, it should giveyou years of to the proper operation of the water heater and your safety. trouble free service. It is strongly suggested that this new water Since we cannot put everything on the first few pages, READ heater be professionally installed, contact Maytag Customer THE ENTIRE MANUAL BEFORE ATTEMPTING TO
Service (1-800-788-8899) for recommended installers. INSTALL OR OPERATETHE WATER HEATER.
The installation must conform with the instructions in this
Abbreviations Found In This Instruction Manual manual; gas company rules; and Local Codes, or in the
CSA - Canadian Standards Association absence of Local Codes, with the latest edition of the
National Fuel Gas code, ANSI Z223.1, alsoreferred to as
ANSI - American National Standards Institute
NFPA - National Fire Protection Association NFPA 54. This publication is available from your local gov-
ernment or public library or gas company or by writing NFPA, Batterymarch Park, Quincy, MA 02269.
After reading this manualyou have any questions or do not
&WARNING understand anyportion of the instructions, callMaytag
This gas-fired water heater is design certified by CSA Customer Service at 1-800-788-8899 for an authorized servicer.
INTERNATIONALunder American National Standard/CSA Carefully plan the place where you are going to put thewater
Standard ANS Z21,10.1 CSA4.1 (latest edition) for gas water heaters. The installation must conform with this heater. Correct combustion, vent action, and vent pipe instal-
manual,Local Codesand with the latest edition of the lation arevery important in preventing death from possible
National Fuel GasCode,ANSI Z223.1. carbon monoxide poisoning and fires. Thispublication is available from your localgovernment Examine the location to ensure the water heater complies with
or public library, gas company, or by writing NFPA, BatterymarchPark,Quincy, MA 02269. the "Locating the New Water Heater" section in this manual.
For California installation this water heater must be braced, anchored, or strapped to avoid falling or moving during an
earthquake. See instructions for correct installation proce-
Read the "Safety Instructions" section, pages 2, 3 and 4 of this dures. Instructions may be obtained from your local dealer,
manual first and then the entire manual carefully.If you don't wholesaler, public utilities or California Office of the State follow the safety rules, the water heater will not operate prop- Architect, 400 P Street, Sacramento, CA 95814.
erly. It could cause DEATH, SERIOUS BODILY INJURY Massachusetts Code requires this water heater to be installed AND/OR PROPERTY DAMAGE. in accordance with Massachusetts 248-CMR 2.00: State
This manual contains instructions for the installation, opera- Plumbing Code and 248-CMR 5.00. tion, and maintenance of the gas-fired water heater. It also Compiles with SCAQMD rule#1121 and districts having contains warnings through out the manual that you must read equivalent NOx requirements.
Product Specifications
Model HN41240X HP41240X HN41250X HP41250X HN41250Q. HP41250Q HN41275Q. HP51275Q.
HN51240X *HP51240X 'HN51250X *HP51250X *HN51250Q *HP51250Q *HN51275Q *HPS1275Q
Tank Capadty
In Gallons 40 40 50 50 50 50 75 75
Type of
Gas Natural Propane Natural Propane Natural Propane Natural Propane
B.T.U.
Rate 40,000 38_000 40,000 39_000 52fi00 48_000 75_100 75,200
RecoveryRate
In GalsPer Hour
@90°FRise 46 44 46 45 57 52 79 79
Minimum
Vent Pipe 3" or 4" 3"or 4" 3" or4" 3" or 4" 4" 4" 4" 4"
Diameter 20" 20" 22" 22" 22" 22" 265" 26.5"
Height To
Top of
Draft Hood 65" 65" 64" 64" 64" 64" 67.5" 67.5"
High altitude models have a B,T.U./Recovery Rate 10% less than shown.
6
Page 7
Accessoriesand ToolsNeeded
Accessories
To simplify the installation Maytag has available the instaLla- tion parts shown below. You may or may nor need all of these
accessories depending on your type of installation. Call Ma_ag Customer Service at 1-800-788-8899 for an author-
ized installen
DRAINPANSAVAILABLEIN 22" DIAMETER
EXPANSIONTANKSFORTHERMALEXPANSION (PARTNUMBER66001011) FORWATER
CONDITIONSAVAILABLEINZ GALLON(PART HEATERSHAVINGA DIAMETER20" ORLESS,
24" DIAMETER(PARTNUMBER66001105) FOR
NUMBER66001013) AND 5 GALLON(PART NUMBER66001014) CAPACITY WATERHEATERSHAVINGA DIAMETER22"
OR LESSAND AVAILABLEIN 28" DIAMETER (PARTNUMBER66001012) FORWATER
HEATERSHAVINGA DIAMETER26" OR LESS
Tools
Youmayor maynot need all of these tools, depending on your ADDITIONALTOOLSNEEDED
type of installation. These tools can be purchased atyour local WHEN SWEATSOLDERING
hardware store.
Tubing Cutters or Hacksaw
Propane Torch
Pipe Wrenches (2) 14" Soft Solder
Screwdriver Solder Flux
Tin Snips _ i _ EmervCIoth
6 Foot Tape of Folding Rule
Wire -Brushes
Garden Hose
Drill
Pipe dope or Teflon Tape GARDENHOSE
HACKSAW
P,PE
6 FOOTTAPE WRENCH
ROLLOFTEFLONTAPE 3/4" WIREBRUSH
(USEONLYON WATER
CONNECTIONS)
1/2" WIREBRUSH
_ _ PROPANETORCH
SLOT-HEADSCREWDRIVER
TIN SNIPS
_ _
PHILLIPSSCREWDRIVER ROLLOELEADFREE
SOFTSOLDER
PIPEDOPE(SQUEEZETUBE) ] [1 ROLLOFEMERY
(USEFORWATERAND _._ SOLDERFLUX TUBINGCUTTER
CLOTH
GASCONNECTIONS)
7
Page 8
Instructions for Installation
Removing the Old Water Heater
Turn "OFF" the gas supply to the water heater. @ Disconnect the vent pipe from the draft hood where they
connect to the water heater. In most installations the vent
A,WARNING pipe can be lifted off after any screw or other attached
If the maingasline shutoffservingall gasappliancesisused, devices are removed. Dispose of the draft hood. The new alsoshut"off" the gas at eachappliance.Leaveall gasappli- water heater has the draft hood which must be used for
ancesshut"off" unti/thewaterheaterinstallationiscomplete, proper operation.
a. If you have copper piping to the water
_ _ heater, the two copper water pipes can
be cut with a hacksaw approximately
four inches away from where they con- nect to the water heater. This will
"- @ @ avoid cutting off the pipes too short.
i_IIIZ:__t'_ [_ __ Additional cuts can be made later if
necessary. Disconnect the temperature- pressure relief valve drain line. When
Turn "OFF" the water to the water _ the water heater is drained, disconnect
the hose from the drain valve. Close
heater. Some installations require that _ the drain valve. The water heater is the water he turned off to the entire
I now completely disconnected and
house. @ ready to be removed.
Check again to make sure the gas sup- ply is "OFF" to the water heater. Then I _ _ @ b. If you have galvanized pipe to the water
disconnect the gas supply connection __ heater, loosen the two galvanized pipes
from the gas control valve, with a pipe wrench at the union in each
I line. Also disconnect the piping
t remaining to the water heater. These
Attach a hose to the water heater drain pieces should be saved since they may
valve and put the other end in afloor _ _ be needed when reconnecting the new
drain or outdoors. Open the water water heater. Disconnect the tempera- heater drain valve. Open a nearby hot ture-pressure reliefvalve drain fine.
water faucet which will relieve pressure When the water heater is drained, dis- in the water heater and speed draining, connect the hose from the drain valve.
Close the drain valve. The water heater
I__ is now completely disconnected and
ready to be removed.
AWARNING [ &CAUTION
1"hewaterpassingout_may beextremelyhot. |Mineral buildupor sedimentmayhaveaccumulatedin theold
Toavoidbeingscalded,makesureallconnectionsaretight and /water heater,Thiscausesthe water heaterto be muchheavier thatthewater flow isdirectedawayfromanyperson. ] thannormalandthisresidue,ifspilledout,couldcausestaining.
8
Page 9
Instructions for Installation (cont'd)
Typical Installation
CHECKALL CONNECTIONS FOR LEAKS.CONSULTTHE LOCAL UTILITY COMPANY TO EXAMINE INSTALLATIONFOR PRO- PRIETYAND SAFETY.
VACUUMRELIEFREQUIREDBYSOMECODES
HOTWATEROUTLET ___ (REFERTOLOCALCODES)
_ [J-_j _l_ COLDWATERINLET
ooc
TEMPEREDWATEROUTLET_ _ iL_
*MIXINGVALVE _
i = TEMPERATURE-PRESSURE
RELIEFVALVE
SUPPLY
DISCHARGEPIPE (Donotcapor plug)
DRAINPAN" -- S TOSUI,A.,EDRA..
This appliance has been design certified as complying with American National Standard/CSA Standard forwater heaters and is con-
sideredsuitable for: Water (Potable) Heating: All models are "considered suitable for water (potable) heating."
AWAR.,NG ] [
HOTTER WATER CAN SCALD: Water heaters are I /This water heater shall not be connected to any heat- intended to produce hot water. Water heated to a ling systems or component(s) previously used with a
temperature which will satisfy clothes washing, I [non-potable water heating appliance.
dish washing, and other sanitizing needs can scald and permanently injure you upon contact. Some l
people are more likely to be permanently injured by hot water than others. These include the elderly, | A WARNING
children, the infirm, or physically/mentally handi- _ --- capped. If anyone using hot water in your home fits /Toxicchemicals such as used for treatment of boilers into one of these groups or if there is a local code or |or non-potable water heating appliances shall never state law requiring a certain temperature water at |be introduced into a potable water space heating
the hot water tap, then you must take special pre- /system. cautions. In addition to using the lowest possible
temperature settingthat satisfies your hot water needs, a means such as a mixing valve, should be used at the hot water taps used by these people or NOTE: To protect against untimely corrosion of hot and
at the water heater. Mixing valves are available at cold water fittings, it is strongly recommended that di-elec-
plumbing supply or hardware stores. Follow manu- tricunions orcoupfingsbeinstaUedonthiswaterheater
acturers instructions for installation of the valves.
Before changing the factory setting on the thermo- when connected to copper pipe. stat, read the "Temperature Regulation" section in
this manual.
9
Page 10
Instructions for Installation (cont'd)
Locating the New Water Heater
Yon should carefully choose an indoor location for the new AWARNING water heater, because the placement is a very important con- This water heater must not be installed directly on
sideration for the safety of the occupants in the building and carpeting. Carpeting must be protected by a metal for the most economical use of the appliance. This water or wood panel beneath the appliance extending
heater is not for use in manufactured (mobile) homes or out- beyond the full width and depth of the appliance
by at least 3 inches (76.2mm) in any direction, or if
doorinstaUation, the appliance is installed in an alcove or closet, the
entire floor must be covered by the panel. Failure to
Whether replacing an old water heater or putting the water heed this warning may result in a fire hazard.
heater in a new location, the following critical points must be observed.
AWARNING [
The location selected should be indoors as close as practical to Minimum clearances between the water heater and [
the gas vent or chimney to which the water heater vent is going combustible and noncombustible construction are to be connected, and as centralized with the water piping system 1" at the sides and rear, 4" at the front, and 6 from
aspossible. The water heater, as all water heaters, will eventually the vent pipe. Clearance from the top of the jacket [
leak. Do not install without adequate drainage provisions where is 18" on most models. Note that a lesser dimension
may be allowed on some models. Refer to the label
water flow will cause damage, valve°ntheforWaterallclearances.heateradjacent to the gas contro
&CAUTION
WATER HEATERS EVENTUALLY LEAK: Installation of the water heater must be accomplished in such a
manner that if the tank or any connections should ,2,,HAX. [_- I" L_- I" MIN.
leak, the flow of water will not cause damage to _ the structure. For this reason, it is not advisable to 1_
install the water heater in an attic or upper floor. VENTILATION When such locations cannot be avoided, a suitable AiR
OPENINGS O
drain pan should be installed under the water ) TOPVIEW
OF CLOSET TOP VIEW I" HIN.
heater, Drain pans are available at your local hard- _ WITHOUTDOOR OFCLOSET ware store. Such a drain pan must be not greater _'MAX WITHDOOR
than 1'/2inches deep, have a minimum length and
FRONT VIEW
width of at least 2 inches greater than the water OFOOOg _CTm_ULAR3"
heater dimensions and must be piped to an ade- HIN.
quate drain. The pan must not restrict combustion I Figure 1 I AmOUCT air flow. Under no circumstances isthe manufactur-
I I
er to be held liable for any water damage in con-
nection with this water heater.
AWARNING AWARNING
Propellants of aerosol sprays and volatile com- A gas water heater cannot operate properly with-
out the correct amount of air for combustion. Do
pounds, (cleaners, chlorine based chemicals, refrig-
erants, etc.) in addition to being highly flammable not install in a confined area such a closet, unless
n many cases, will also change to corrosive you provide air as shown in the "Locating The New
lydrochloric acid when exposed to the combustion Water Heater" section. Never obstruct the flow of :)roducts of the water heater. The results can be ventilation air, If you have any doubts or questions
_azardous, and also cause _roduct failure, at all, call your gas company. Failure to provide the
proper amount of combustion air can result in a fire
or explosion and can cause DEATH, SERIOUS BODI-
LYINJURY, OR PROPERTY DAMAGE.
The location selection must provide adequate clearances for servicing and proper operation of the water heater.
10
Page 11
Instructions for Installation (cont'd)
Locating the New Water Combustion Air and Ventilation Heater (cont'd) for Appliances Located in
Unconfined Spaces
&WARNING Unconfined Space is a space whose volume is not less than
If this water heater will be used in beauty shops, 50 cubic feet per 1,000 Btu per hour of the aggregate input
barber shops, cleaning establishments, or self-serv- rating of all appliances installed in that space. Rooms com ice laundries with dry cleaning equipment, it is mnnicating directly with the space in which the appliances are
imperative that the water heater or water heaters installed, through openings not furnished with doors, are con-
be installed so that combustion and ventilation air be taken from outside these areas. Refer to the sidered a part of the unconfined space
"Locating The New Water Heater" section of this In unconfined spaces in buildings, infiltration may be ade-
manual and also the latest edition of the National quate to provide air for combustion, ventilation and dilution Fuel Gas Code, ANSI Z223.1, also referred to as NFPA
54 for specifics provided concerning air required, of flue gases. However, in buildings of tight construction (for
example weather stripping heavily insulated, caulked, vapor barrier, etc.), additional air may need to be provided using the
methods described in Combustion Air and Ventilation for
&WARNING Appliances Located in Confined Spaces, b.
INSTALLATIONS IN AREAS WHERE FLAMMABLE LIQ-]
UIDS(VAPORS)ARE LIKELYTO BE PRESENTOR STORED[
(GARAGES, STORAGE, AND UTILITY AREAS, ETC): I Combustion Air and Ventilation
Flammable liquids (such as gasoline, solvents, propane I
for
A__ __ I-i
Located in
(LP) or butane, etc.), all of which emit flammable I /ppllances
vapors, may be improperly stored or used in such
Confined
areas. The gas water heater pilot light or main burner =paces
can ignite such vapors. The resulting flashback and fire Confined Space is a space whose volume is less than 50 cubic
can cause death or serious burns to anyone in the area, as well as property damage, feet per 1,000 Btu per hour of the aggregate input rating of all
If installation in such areas is your only option, then appliances installed in that space. the installation must be accomplished in a way that a. ALL AIR FROM INSIDE BUILDINGS:
the pilot flame and main burner flame are elevated from the floor at least 18 inches. While this may (See Page 10 Figure 1, and Figure 2 below)
reduce the chances of flammable vapors from a floor The confined space shall be provided with two permanent spill being ignited, gasoline and other flammable sub- openings communicating directly with an additional
stances should never be stored or used in the same room or area containing a gas water heater or other room(s) of sufficient volume so that the combined volume open flame or sparkproducing appliance, of all spaces meets the criteria for an unconfined space. The NOTE: Flammable vapors may be drawn by air currents total input of an gas utilization equipment installed in the
from other areas of the structure to the appliance, combined space shall be considered in making this deter-
mination. Each opening shall have a minimum free area of one square inch per 1,000 BTU per hour of the total input rating of all gas utilization equipment in the confined space, but not less than 100 square inches. One opening
shall commence within 12 inches of the top and one com- mencing within 12 inches of the bottom of the enclosure.
-,,4_ CHIMNEY OR GAS VENT
FUR OPENINQ8
W/_TER
R
[ Figure 2 ]
11
Page 12
Instructions for Installation (cont'd)
b. ALl. AIR FROM OUTDOORS: (see Figures 3-5) 3. When communicating with the outdoors through horizon-
The confined space shall be provided with two permanent tal ducts, each opening shall have a minimum free area of 1
openings, one commencing within 12 inches of the top and square inch per 2,000 BTU per hour of total input rating of one commencing within 12 inches from the bottom of the all equipment in the enclosure. (See Figure 5.) enclosure. The openings shall communicate directly, or by
ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
Figure 5 I
IFigure3I
4. When ducts are used, they shall be of the same cross-sec-
N-T. INLETAIR VENTILAT_N
tional area as the free area of the openings to which they connect. The minimum short side dimension of rectangular
1.When directly communicating with the outdoors, each air ducts shall not be less than 3 inches. (See Figure 5.) opening shall have a minimum free area of 1 square inch
per 4,000 BTU per hour of total input rating of all equip- 5. Louvers and Grilles: In calculating free area, consideration ment in the enclosure. (See Figure 3.) shall be given to the blocking effect of louvers, grilles or
screens protecting openings. Screens used shall not be
2. When communicating with the outdoors through vertical smaller than 1/4inch mesh. If the free area through a design
ducts, each opening shall have a minimum free area of 1 of louver orgrille is known, it should be used in calculating square inch per 4,000 BTU per hour of total input rating of the size opening required to provide the free area specified. all equipment in the enclosure. (See Figure 4.) If the design and free area is not known, it may be assumed
that wood louvers will be 20-25 percent free area and metal louvers and grilles will have 60-75 percent free area.
Louvers and grilles shall be fixed in the open position or interlocked with the equipment so that they are opened
automatically during equipment operation.
6. Special Conditions Created by Mechanical Exhausting or Fireplaces: Operation of exhaust fans, ventilation systems,
clothes dryers or fireplaces may create conditions requiring
Figure I special to unsatisfactory operation
4
attention avoid
of
installed gas utilization equipment.
12
Page 13
Instructions for Installation (cont'd)
Water Piping
AWARNIN G 2. Look at the top cover of the water heater. The cold water
HOTTER WATER CAN SCALD: Water heaters are inlet is marked cold. Connect the cold water pipe to the intended to produce hot water. Water heated to a cold water inlet of the water heater.
temperature which will satisfy clothes washing, dish washing, and other sanitizing needs can scald NOTE:This water heater is superinsulated to minimize
Ind permanently injure you upon contact. Some mople a re more likely to be permanently injured by heat loss from the tank. Further reduction in heat loss Dot water than others. These include the elderly, canbeaccomplishedbyinsulatingthehotwaterlines
children, the infirm, or physically/mentally handi- from the water heater. capped. If anyone using hot water in your home fits
into one of these groups or if there isa local code or state law requiring a certain temperature water at the hot water tap, then you must take special pre- cautions. In addition to using the lowest possible
temperature settingthat satisfies your hot water needs, a means such as a mixing valve, should be
used at the hot water taps used by these people or at the water heater. Mixing valves are available at THREADEDTO
_alumbing supply or hardware stores, Follow manu- SWEATCOUPLING
cture rsin structions for installat ion of the valves, i-_I_IID S;UTOFF
Before changing the factory setting on the thermo- VALVE stat, read the "Temperature Regulation" section in
this manual.
HOTOUTLET COLDINLET
This water heater shall not be connected to any heating sys- TOHOUSE _ _ __g__ WATERLINE
terns or component(s) used with a non-potable water heating
appliance. PIPE _ -.at-,-- PIPE
INSULATION INSULATION
If a water heater is installed in a closed water supply system; such as one having a back-flow preventer, check valve, water
3/4" THREADED 3/4"THREADED
meter with a check valve, etc.., in the cold water supply; COUPLING COUPLING
means shall be provided to control thermal expansion. (1"ON75 GAL.) (1"ON75GAL.) Contact the local utility or call Maytag Customer Service _
Center at 1-800-788-8899 for an authorized installer on how to control this situation. ( 'r_ TEMPERATURE-
PRESSURERELIEF
NOTE: To protect against untimely corrosion of hot and VALVE cold water fittings, it is strongly recommended that di-elec-
tric unions or couplings be installed on this water heater -_ _ DISCHARGEPiPE when connected to copper pipe. (Do not cap
or plug)
The illustration shows the attachment of the water piping to the water heater. The water heater is equipped with 3/4inch water connections for 40 and 50 gallon models and 1 inch water connections on 75 gallon models.
NOTE: If using copper tubing, solder tubing to an adapter
before attaching the adaptor to the coldwater inlet connection. _,_ _ 6" AIRGAP
Do not solderthe cold water supply line directly to the cold water inlet. It will harm the dip tube and damage the tank. ' ' I_FLOOR DRAIN
1. Look at the top cover of the water heater. The water outlet is marked hot. Connect the hot water pipe to the hot
water outlet on the water heater.
13
Page 14
Instructions for Installation (cont'd)
Temperature-Pressure Relief Valve
AWARNING &WARNING
At the time of manufacturethis water heaterwas provid- The temperature-pressure relief valve must be manu-
ed with a combination temperature-pressuresrelief valve ally operated at least once a year. Caution should be
certified by a nationally recognizedtesting laboratorythat taken to ensure that (1) no one is in front of or maintains periodic inspection of production of listed around the outlet of the temperature-pressure relief
equipment or materials,as meeting the requirementsfor valve discharge line, and (2) the water manually dis- Relief Valves and Automatic Gas Shutoff Devicesfor Hot charged will not cause any bodily injury or property
Water Supply Systems, and the latest edition of ANSI damage because the water may be extremely hot. Z21.22 and the code requirements of ASME. If replaced, If after manually operating the valve, it fails to com-
the valve must meet the requirementsof localcodes,but pletety reset and continues to release water, immedi- not lessthan a combination temperature and pressure ately close the cold water inlet to the water heater,
relief valve certified as meeting the requirements for follow the draining instructions, and replace the Relief Valves and Automatic Gas Shutoff Devicesfor Hot temperature-pressure relief valve with a new one.
Water SupplySystems,ANSIZ21.22 by a nationally recog- nizedtesting laboratory that maintainsperiodicinspection of productionof listedequipment or materials. The valve must be marked with a maximum set pressure not to exceedthe marked hydrostaticworking pressureof SHUTOFF the water heater (150 Ibs./sq.in.) and a dischargecapacity _ _r_VALVE not lessthan the water heater input rate as shown on the , i<_ =__
model rating plate. (Electric heaters - watts divided by '_ _ '_
1000x 3415 equal BTU/Hr.rate.) HOT COLD Your local jurisdictional authority, while mandating the useof a temperature-pressurerelief valve complyingwith ANSIZ21.22 and ASME,may requirea valve model differ-
ent from the one furnishedwith the water heater. Compliancewith suchlocalrequirementsmustbe satisfied
by the installer or end user of the water heater with a -' locally prescribed temperature-pressure relief valve installedin the designated opening in the water heater in _ _ TEMPERATURE- placeof the factory furnished valve. \ PRESSURE
For safe operation of the water heater, the relief valve RELIEFVALVE must not be removed from it's designated opening or
plugged. = DISCHARGEPIPE The temperature-pressure relief valve must be installed (Donotcapor plug)
directly into the fitting of the water heater designatedfor the relief valve. Positionthe valve downward and provide
tubing so that any dischargewill exit only within 6 inches above, or at any distance below the structural floor. Be certain that no contact is made with any live electrical part. The discharge opening must not be blocked or reducedin size under any circumstances.Excessivelength,
over 30 feet, or use of more than four elbows can cause restrictionand reducethe dischargecapacityof the valve.
No valve or other obstructionisto be placedbetween the _ _ _/ _6_AIRGAP relief valve and the tank. Do not connecttubing directlyto _ ' 'm dischargedrain unlessa 6" air gap isprovided.To prevent -- O FLOORDRAIN bodily injury,hazardto life, or property damage,the relief valve must be allowed to discharge water in quantities shouldcircumstancesdemand. If the dischargepipe is not RELIEF VALVE OPENING connectedto a drain or other suitable means, the water Atthetimeof manufacture,thiswaterheaterwas providedwithacombination
flow may causepropertydamage, temperature-pressurereliefvalvelistedascomplyingwiththestandardforrelief The DischargePipe: valvesandautomaticgasshut-offdevicesforhotwatersupplysystems,ANSI
Must not he smaller in size than the outlet pipe size of z21.22.Forsafeoperationof thewaterheater,thereliefvalvemustnotbe
removedfromitsdesignatedpointofinstallationorplugged.
the valve, or have any reducing couplings or other Yourlocalurisdictionalauthority, while mandating theuseof a temperature- restrictions, pressurereliefvalvecomplyingwithANSIZ21.22andASME,mayrequireavalve
modeldifferentfromtheonefurnishedwiththewaterheater.
Must not be plugged or blocked. Compliancewithsuchlocalrequirementsmustbesatisfiedbytheinstalleror
Must be of material listed for hot water distribution, enduserofthewaterheaterwithalocallyprescribedtemperature-pressure
Must be installed so as to allow complete drainage of reliefvalveinstalledinthedesignatedopeninginthewaterheater.
both the temperature-pressurerelief valve, and the dis- Seemanualheading-"Temperature-PressureReliefValves"forinstallationand chargepipe. maintenanceofreliefvalve,dischargeline,andethersafetyprecautions, i
Must terminate at an adequate drain.
Must not have any valve between the relief valve and
tank.
14
Page 15
Instructions for Installation (cont'd)
Filling the Water Heater
&CAUTION For proper venting in certain installations, a larger diameter
Never use this water heater unless it is completely vent pipe may be necessary. Due to great variances in installa- filled with water. To prevent damage to the tank, tions, unforeseeable by the manufacturer of the water heater,
the tank must be filled with water. Water must flow you must consult your gas company to aid you in determining from the hot water faucet before turning "ON" gas the proper venting for your water heater from the vent tables
to the water heater.
in the latest edition of the National Fuel Gas Code ANSI
To fill the water heater with water: Z223.1, also referred to as NFPA 54.
Close the water heater drain valve by turning the handle to
the right (clockwise). The drain valve is on the lower front Check the venting system for signs of obstruction or deterio- of the water heater, ration and replace if needed.
Open the cold water supply valve to the water heater.
NOTE:The cold water supply valve must he left open The combustion and ventilation air flow must nor be when the water heater is in use. obstructed.
To insure complete fdling of the tank, allow air to exit by opening the nearest hot water faucet. Allow water to run [ &WARNING ] until a constant flow is obtained. This will let air out of the I_Obstructed or deteriorated vent systems may pres-
water heater and the piping, lent a serious health riskor asphyxiation. Check all new water piping for leaks. Repair as needed.
Place the draft hood legs in the receiving holes on the top
Venting of the water heater. The legs will snap in the holes to give a
tight fir.
Place the vent pipe over the draft hood. With the vent pipe
AWARNING in position, drill a small hole through both the vent pipe
VENT DAMPERS - Any vent damper, whether it is and draft hood. Secure them together with a sheet metal operated thermally or otherwise must be removed screw.
if its use inhibits proper drafting of the water heater.
Thermally Operated Vent Dampers: Gas-fired water heaters having thermal efficiency in excess of 80% DRAFTHOOD _ VENTq
may produce a relatively low flue gas temperature. _
SCREWp J
DRAFTHOOD
Such temperatures may not be high enough to %
proper,yopentherma,,yoperatedventdampers
This wouldcause spillage of flue gases and may
VENTTOOUTDOORSOR
DRAFTED CHIMNEY
cause carbon monoxide poisoning. 0uuu,j_=_ -, Vent dampers must bear evidence of certification as
complying with the latest edition of American National Standard ANSI Z21.68 (ANSI Z21.66 & 67,
respectively, cover electrically and mechanically actu-
ated vent dampers). Before installation of any vent damper, consult your local gas utility or local codes &WARNING
for further information.
The water heater with draft hood installed must be properly vented to a chimney which terminates out-
doors, Never operate the water heater unless it is vented to the outdoors and has adequate air supply
AWARNIN_G to avoid risks of improper operation, explosion or
To insure proper venting of this gas-fired water I asphyxiation,
heater, the correct vent pipe diameter must be uti-I lized. Any additions or deletions of other gas appli- _ r ances on a common vent with this water heater I I _&WARNING
may adversely affect the operation of the water I |The vent pipe from the water heater must be no heater. Consult the local gas utility or call Maytag I |less than the diameter of the draft hood outlet on
Customer Service at 1-800-788-8899 for an author- /the water heater, and must slope upward to the ized servicer if any such changes are panned. ] I chimney at least ¼ inch per linear foot.
15
Page 16
Instructions for Installation (cont'd)
Gas Piping
All vent gases must be completely vented to the outdoors of &WARNING [ the structure (dwelling). Install only the draft hood provided Make sure the gas supplied is the same type listed [
with the new water heater and no other draft hood. on the model rating plate. The inlet gas pressure I Vent pipes must be secured at each joint with sheet metal must not exceed 10.5 inches water column (2.6 kPa)] I
for natural gas or 13 inches water column (3.2 kPa) I
screws, for Propane (L.R) gas. The minimum inlet gas pres-
sure listed on the model rating plate is for the pur-
TO pose of input adjustment.
I
CHIMNEY
t &WARNING
If thegas control valve is subjected to pressures I
PERLINEARFOOT
, t exceeding 1/=pound per square inch (3.5kPa), the I
damage to the gas control valve could result in a
VENT PIPEINSTALLATION f re or explos on from eak ng gas.
There mustbe a minimum of 6" clearancebetween singlewall vent AWARNING [ pipe and any combustiblematerial.Fill and sealanyclearance If the main gas line shutoff serving all gas appli-
between single wallvent pipe and combustible material with mortar ances is used, also turn "off" the gas at each appli- mix, cement, or other noncombustible substance.For other than sin- ance. Leave all gas appliances shut off until the
gle wall, followvent pipe manufacturer'sclearancespecifications.To water heater installation is complete. insurea tight fit of the vent pipe in a brickchimney;seal around the vent pipe with mortar mix cement. A gas line of sufficient size must be run to the water heater.
Consult the latest edition of National Fuel Gas Code ANSI Z223.1, also referred to as NFPA 54 and the gas company
] concerning pipe size.
AWARNING
I
Failure to have required clearances between vent piping and combustible material will result in a fire There must be:
hazard, A readily accessible manual shut off valve in the gas supply
line serving the water heater, and
_,WARNING ] A drip leg (sediment trap) ahead of the gas control valve to
Be sure vent pipe is properly connected to prevent help prevent dirt and foreign materials from entering the gas escape of dancjerous flue gases which could cause controlvalve.
deadly asphyxlat on. A flexible gas connector or a ground joint union between the
shutoffvalve and control valve to permit servicing of the unit.
A,WARNING ] Be sure to check all the gas piping for leaks before lighting the
Chemical vapor corrosion of re" flue and vent sys-I1 water heater. Use a soapy water solution, not a match or open tern may occur if air for combustion contains certain I flame. Rinse offsoapy solution and wipe dry.
chemical vapors. Spray can propellants, cleaning sol- I
vents, refrigerator and air conditioner refrigerants, I swimming pool chemicals, calcium and sodium chlo- [ StandardModels are for installation up to 3,300 feet above
ride, waxes, bleach, and process chemicals are typi- sea level.
cal compounds which are potentially corrosive. I High Altitude Models are for installation from 3,300 to
5,500 feet above sea level. Ifa standard model is installed above 3,300 feet or a high alti-
tude model is installed above 5,500 feet, the input rating must be reduced at the rate of 4 percent for each 1,000 feet above sea level. Contact your local gas utility for further information.
&WARNING I
The appliance and its gas connection must be leak tested before placing the appliance in operation.
16
Page 17
Instructions for Installation (cont'd)
Gas Piping (cont'd)
GAS PIPING WITH
,WARNING FLEXIBLE CONNECTOR
The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of the gas sys- GASSUPPLYPIPING
tem at test pressures in excess of 1/2 pound per square inch (3.SkPa).
The appliance must be isolated from the gas sup- ply piping system by closing its individual manual [_ shutoff valve during any pressure testing of the MANUAL
gas supply piping system at test pressures equal SHUTOFF or less than 1/2 pound per square inch (3.5kPa). VALVE
ELEX,BLEGASCONNECrOR
1 _,WARNING I LABELEDASCOMPLYING
WITH ANSI STANDARDS
I Use pipe joint compound or teflon tape marked as I GROUNDJOINT I being resistant to the action of petroleum [Propane I UNION(OPTIONAL)
I (L'R)]gases" I
SEDIMENT TRAP
3" MIN. DRIP LEG GAS
A sediment trap shall be installed as close to the inlet of the (SEDIMENT CONTROL
TRAP) CAP
water heater as practical at the time of water heater instaUa~
tion. The sediment trap shall be either a tee fitting with a capped nipple in the bottom outlet or other device recognized as an effective sediment trap. Ira tee fitting is used, it shall be
installed in conformance with one of the methods ofinstaUa- GAS PIPING WITH ALL BLACK IRON PIPE TO tion shown below. GAS CONTROL
Connecting the gas piping to the gas control valve of the
GAS SUPPLY PIPING
water heater can be accomplished by either of the two meth-
ods shown.
MANUAL t
SHUTOFF
_WARNING VALVE
Contaminants in the gas lines may cause improper operation of the gas control valve.that may result
=in fire or explosion. Before attaching the gas line
be sure that all gas pipe is clean on the inside. To trap any dirt or foreign material in the gas supply
line, a drip leg (sometimes called a sediment trap) GROUNDJOINT must be incorporated in the piping. The drip leg UNION
must be readily accessible. Install in accordance mACK PIPE _ GAS
with the "Gas Piping" section. Refer to the latest _ CONTROL
edition of the National Fuel Gas Code, ANSI Z223.1 VALVE also referred to as NFPA 54. DRIPLEG
(SEDIMENT
3" MIN. TRAP)
CAP
17
Page 18
Instructions for Installation (cont'd)
Installation Checklist
BEFORE LIGHTING THE PILOT: CHECK FOR LEAKS
Check the gas lines for leaks. Be sure to check all your gas pipes for leaks before lighting a. Use a soapy water solution. DO NOT test for gas leaks your water heater. Use a soapy water solution, not a match or
using a match or open flame, open flame. Check the factory gas fittings after pilot is lit and
b, Brush the soapy water solution on all gas pipes, joints gas control knob is still in "PILOT" position. Then, check the
and fittings, fittings when the main burner is mrued "ON". Use a soapy
c. Check for bubbling soap. This means you have a leak. water solution for this, too.
Turn "OFF" gas and make the necessary repairs. VENTPIPETO
d. Recheck for leaks. OUTDOORS
e. Rinse offsoapy solution and wipe dry. ORCHIMNEY
SHUTOFFVALVE
Is the new temperature-pressure relief valve properly FI _) .
installed and piped to an adequate drain? See _ "Temperature-Pressure Refief Valve" section. HOT COLD
IINION
Are the cold and hot water lines connected to the water
heater correctly? See "Water Piping" instructions in the "Instructions for Installation" section. (_2- 22_i)
DRAFTHOOD
GAS SUPPLY" ii ez_z_ '!
Is the water heater completely filled with water? See _",Fzz=* I " / TEMPERATURE-
i _=z--_ _ PRESSURE
"Filling" instructions in the "Instructions for Installation" i, , t RELIEFVALVEi t_zG 1 I
, E --_
section. ' )---- '
SHUTOFF
VALVE
Will a water leak damage anything? See the "Locating the ' "_ -- DISCHARGEPIPE
New Water Heater" section. (Do not capor plug)
Is there proper clearance between the water heater and TEE }= anything that might catch fire? See the "Locating the New DRIPLEG l=,
water Heater" section. (Sedimenttrap) / DRAINVALVE
PIPECAP I_ i ]
Do you have adequate ventilation so that the water heater 6 INCHAIR GAP will operate properly? See "Combustion Air and Ventilation"
in the Instructions for Installation section. FLOORDRAIN
/
Is the draft hood vent piping properly secured? See I "Venting" instructions in the "Instructions for InstaLlation"
" @
section. SUITABLEFORWAVER(POTAStE)
HEATING ONLY
_C_ELr_MeEp C_P_IrV
]s there proper clearance between the vent pipe and any- I J
thing that might catch on fire? See "Venting" instructions ......
yon SE_N_pINPUT _oov_qy
in the "Instructions for Installation" section. _ [ ._ I .... ]
M_XlMU__T_C C_S_R_SSU_INWC
Is the vent pipe properly sloped and does the vent termi- 50 [ l [
" g'i
1PwesJ wc w
nate outdoors? See Ventin nstructions in the "Instructions for Installation" section.
AUTOMATIC STORAGE WATER HEATER
Do you need to call your gas company to check the gas
_Vlaytag is a Trademarkof May_9 eorpora_onand is
pipe and its hookup? u_,d under Licenseto State Industries,Inc.
18
Page 19
Instructions for Operation
Lighting
&WARNINGbe _ Figure 6 ' __
BEFORE LIGHTING [PROPANE (L.P.) GAS WATER HEATERS]: Propane (L.P.) gas is heavier than air.
Should there be a leak in the system, the gas will
settle near the ground. Basements, crawl spaces, skirted areas under manufactured (mobile) homes
(even when ventilated), closets and areas below ground level will serve as pockets for the accumula-
tion of this gas. Before attempting to light or relight the water heater's pilot or turning on a nearby elec-
trical
light switch, absolutely sure there is no I I
accumulated gas in the area. Search for odor of gas by sniffing at ground level in the vicinity of the appliance. If odor is detected, follow steps indicated
at "For Your Safety" on the cover page of this man- _
ual then leave the premises.
Lighting and operating instructions are located on front of _i the water heater, above the gas control valve.
E
AWARNING Figure 7 I
AN ODORANT IS ADDED TO THE GAS USED
BY THIS WATER HEATER.
FORYOUR SAFETY IF YOU SMELL GAS:
Do not try to light any appliance.
phoneD°nOtintOUChyouranYbuilding.electricalswitch; do not use any / _
Immediately call your gas supplier from a neigh-
bor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire _=
department.
Figure 8 I
AWARNING
DO NOT force the gas control knob. Use only your
hand to push it down to light the pilot, or to turn it to "ON", "OFF" or "PILOT". Never use a tool such as
a lever, wrench or pliers. Do not hit or damage the knob. A damaged knob may result in an explosion and serious injury. If you have problem turning the
knob, call the gas supplier immediately.
I
INNERDOOR
I Figure91
19
Page 20
Instructions for Operation (cont'd)
Lighting label on the water heater as it appears above the thermostat
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING
If you do not follow these instructions exactly,a fire or explosion
may resu t causing propertydamage,personal injuryor loss of life.
A.Thisappliancehasa pilotwhichmustbelightedby If youcannotreachyourgassupplier,callthefire
hand.Whenlightingthepilot,followtheseinstructions department. exactly. C,Useonlyyourhandtopushinorturnthegascontrol
B.BEFORELIGHTINGsmellallaroundtheappliancearea knob.Neverusetools.Iftheknobwillnotpushinor
forgas.Besureto smellnextto thefloorbecause turnbyhand,don'ttryto repairit,calla qualified somegasisheavierthanairandwillsettleonthefloor, servicetechnician.Forceorattemptedrepairmay
WHATTODOIFYOUSMELLGAS resultinafireorexplosion.
Donottrytolightanyappliance. D.Do notusethisapplianceifanyparthasbeenunder
Donottouchanyelectricswitch;donotuseany water.Immediatelycalla qualifiedservicetechnician
phoneinyourbuilding, toinspecttheapplianceandto replaceanypartofthe
Immediatelycallyourgassupplierfromaneighbor's controlsystemandanygascontrolwhichhasbeen phone.Followthegassuppliar'sinstructions, underwater.
LIGHTING INSTRUCTIONS
1,STOP!Readthesafetyinformationaboveonthislabel. 9. Pushin controlknoballthe wayandholddown.
2,Removeouterdoor. Immediatelylightthepilotwithamatch.Continueto
3.Setthethermostatto lowestsettingbyturningthe holdcontrolknobinforaboutone(1)minuteafter
watertemperaturedialclockwise,(f _,)to itslowest thepilotislit,Releaseknobanditwillpopbackup. temperaturesetting(witharrowondial)asshown.DO Pilotshouldremainlit.If it goesout,repeatsteps3
NOTFORCE. through8.
Ifknobdoesnotpopupwhenreleased,stopand
immediatelycallyourservicetechnicianor gas supplier,
If the pilotwill notstay lit afterseveraltries,
depress
andturnthe
gas
controlknob
clockwise
4.Turngascontrolknobclockwise_' to"OFF"posi- tion.Knobcannotbeturnedfrom"PILOT"to "OFF" _' j to "OFF"andcallyourservicetechnician
unlessknobisdepressedslightly.DO NOT FORCE, orgassupplier.(Figure6,page19) (Figure6,page19) 10.Replace(orclose)innerdoor,(Figure9,page19)
5.Waitfive(5)minutestoclearoutanygas.Ifyouthen 11.Atarmslengthaway,turngascontrolknobcounter- smellgas,STOP!Follow"B" inthesafetyinformation O
aboveonthislabel,If youdon'tsmellgas,gotothe clockwise__ tothefull"ON"position.Warning
donot use gas controlknobto regulate gas
nextstep.
6.Remove(oropen)innerdoorlocatedbelowthe gas flow.(Figure8,page19) controlunit. 12.Atarmslengthaway,setthethermostatto desired
7.Findpilot-followmetaltubefromgascontrol.Thepilot setting.Themark( ) indicativeofapproximate islocatedinfrontoftheburner. 120°Fis preferredstartingpoint.Somelocallaws
PILOTBURNER_ n THERMOCOUPLE mayrequirea lowerstartingpoint.If hotterwateris
II
desired,seeinstructionmanualand"warning"below,
13.Closetheouterdoor.
8.Ifyoudon'tsmellgas,turnknobongascontrolcounter
clockwiae[_) to"PILOT"position.(Figure7,page19)
WARNING
Hotterwaterincreasesthe riskof scaldinjury.Beforechangingtemperaturesettingseeinstructionmanual.
TO TURN OFF GAS TO APPLIANCE
1.Setthe thermostatto lowestsettingbyturningthe 2.Turngascontrolknobclockwise_ 1to"OFF"posi-
watertemperaturedialclockwise(;_",) to itslowest tion.Knobcannotbeturnedfrom"PILOT"to "OFF" temperaturesetting(witharrowondial)asshown.DO unlessknobisdepressedslightly.DONOTFORCE.
NOTFORCE. 3.Closeouterdoor.
20
Page 21
Instructions for Operation (cont'd)
Temperature Regulation
Due to the nature of the typical gas water heater, the water Turn the water temperature dial clockwise (ff"-_) to temperature in certain situations may vary up to 30°F higher or decrease the temperature, or counterclockwise (_'-"_) to
lower at the point of use such as, bathtubs, showers, sink, etc. increase the temperature.
This means that when the temperature adjustment dial is set at the mark approximating 120 ° F, the actual water tempera-
ture at any hot water tap could be as high as 150°F or as low as 90°E
Any water heater's intended purpose is to heat water. Hot _f_- _o
water is needed for cleaning (bodies, dishes, clothing). Hot o water will present a scald hazard. Depending on the time ele- ment, and the people involved (normal adults, children, tod- dlers, elderly, infirm, etc.) scalding may occur at different temperatures.
_,WARNING
HOTTER WATER CAN SCALD: Water heaters are A- Is a thermostat setting of approximately
intended to produce hot water. Water heated to a 120°F, which will supply hot water at the
temperature which will satisfy clothes washing, dish most economical temperatures. The tempera- washing, and other sanitizing needs can scald and ture adjustment knob can be turned lower
permanently injure you upon contact. Some people are more likely to be permanently injured by hot than 120°Fifdesired.
water than others. These include the elderly, children, the infirm, or physically/mentally handicapped. If
anyone using hot water in your home fits into one of A- Is athermostat setting of approximately these c_roupsor if there is a local code or state law 130 °F.
reqmrmg a certain temperature water at the hot
water tap, then you must take special precautions. In B- Is a thermostat setting of approximately addition to using the lowest possible temperature
setting that satisfiesyour hot water needs, a means 140°F. such as a mixing valve, should be used at the hot
water taps used by these people or at the water C- Is a thermostat setting of approximately
heater. Mixing valves are available at plumbing sup- 150OE
ply or hardware stores. Follow manufacturers instruc- tions for installation of the valves. Before changing
the factory setting on the thermostat, read the VERYHOT- Is a thermostat setting of 160°F. It is recom-
"Temperature Regulation" section in this manual, mended that the dial be set lower whenever
possible.
NOTE: Water temperature range of 120"-140°F recom-
AWARNING
Never allow small children to use a hot water tap, mended by most dishwasher manufacturers.
or to draw their own bath water. Never leave a child or handicapped person unattended in a bath-
tub or shower.
The thermostat of this water heater has been factory set at its _WARNING lowest position, to reduce the risk of scald injury. It is Should overheating occur or the gas supply fail to shut off,
adjustable and must be reset to the desired temperature set- turn "OFF the manualgascontrolvalveto the appliance. I ting. The mark (A) indicative of approximately 120°F is the preferred starting point. Some states have a requirement for a lower setting. If you need hotter water, follow directions for temperature adjustment, but beware of the warnings in this
section.
21
Page 22
Service and Maintenance
Venting System Inspection Burner Inspection
At least once a year a visual inspection should be made of the [ _WARNING
venting system.You should look for: _|Flood damage to a_may not be readily
Obstructions which could cause improper venting. The |visible or immediately detectible. However, over a
combustion and ventilation air flow must not be obstructed. "period of time a flooded water heater will create
dangerous conditions which can cause DEATH, SERI- OUS BODILY INJURY OR PROPERTY DAMAGE.
Damage or deterioration which could causeimproper vent- Contact the Maytag dealer from whom the appli- ing or leakage of combustion products, ance was purchased or call Maytag Customer Service
at 1-800-788-8899 for an authorized servicer to replace a flooded water heater. Do not attempt to
Rusted flakes around top of water heater, repair the unit! It must be replaced!
At least once a year a visual inspection should be made of the
AWARNING main burner and pilot burner. The drawing is for your reference.
Chemical vapor corrosion of the flue and vent sys-
tem may occur if air for combustion contains certain You should check for sooting which is not normal and will chemical vapors. Spray can propellants, cleaning sol- vents, refrigerator and air conditioner refrigerants, impair proper combustion.
swimming pool chemicals, calcium and sodium chlo- ride, waxes, bleach, and process chemicals are typi-
[ca compounds wh ch are potent a y corros ve.
Obstructed or deteriorated vent systems may pres- ent a serious health risk or asphyxiation.
NATURAL GAS BURNER - 40 AND 50 GALLON
I ]
Be sure the vent _erly connected to I _)_
prevent escape of dangerous flue gasses which
could cause deadly asphyxiation.
AWARNING
If after inspection of the vent system you found PROPANE(L.R)GASBURNER-40AND50GALLON
sooting or deterioration, something is wrong. Call the local gas utility or Maytag Customer Service at
1-800-788-8899 for an authorized servicer to correct
the problem and clean or replace the flue and vent-
ing before resuming operation of the water heater. Failure to make corrections can result in a fire, or
explosion causing DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE.
NATURAL AND PROPANE (L.R) GAS BURNER - 75 GALLON
AWARNING
Soot build-up indicates a problem that requires cor-
rection before further use. Turn "OFF" gas to water heater and leave "OFF" until repairs are made, because failure to correct the cause of the sooting can result in a fire or explosion causing DEATH,
SERIOUS BODILY INJURY, OR PROPERTY DAMAGE.
22
Page 23
Service and Maintenance (cont'd)
L.P.GasControl Valve & Burner Burner Cleaning
Assembly Replacement
Information In the event your burner needs cleaning, usethe following
AWARNING instructions:
PROPANE (L.P.) GAS CONTROL VALVE AN BURNER
ASSEMBLY REPLACEMENT INFORMATION. If inspection of the burner shows that cleaning is required,
For Propane (L.R) Gas Models Only: turn the gas control knob clockwise ((_",) to the "OFF"
Your water heater is equipped with a Propane (L.R) position, depressing slightly. gas control valve and a main burner assembly with left hand threads for the following fittings and their NOTE: The knob cannot be turned from "PILOT" to
connections. "OFF" unless knob is depressed slighdy. DO NOT
FORCE.
The connection between the manifold and the gas control valve (A to B) are left hand threads. Loose deposits on or around the burner can be removed by
carefully using the hose of a vacuum cleaner inserted through
The connection between the main burner orificeand the mani- the access door of the water heater. If the burner needs to be
fold (C to D) are left hand threads, removed for additional cleaning, call Maytag Customer Service
at 1-800-788 8899 for an authorized servicer to remove and
For ordering these replacement parts, please refer to the "Repair clean the burner and correct the problem that required the PartsList" section of this manual, burner to be cleaned.
Draining
The water heater should be drained if being shut down during
freezing temperatures. Also periodic draining and cleaning of sediment from the tank may be necessary.
A _ Turn the gas control knob to the "OFF" position.
CLOSE the cold water inlet valve to the water heater.
OPEN a nearby hot water faucet and leave open to allow
C for draining.
Connect a hose to the drain valve and terminate to an ade-
quate drain.
OPEN the water heater drain valve to allow for tank draining.
NOTE: If the water heater is going to be shut down and drained for an extended period, the drain valve should be left open with hose connected allowing water to terminate to an adequate drain.
Close the drain valve.
Follow instructions in the "Filling The Water Heater" section.
Follow the lighting instructions in the "Lighting" section to restart the water heater.
23
Page 24
Service and Maintenance (cont'd)
Temperature-Pressure Relief Drain Valve Washer Valve Operation Replacement
The temperature-pressure rebef valve must be manually oper- NOTE: For replacement, use a l_2ttx 1_64t'x 1/_"thick washer ated at least once a year. available at your nearest hardware store. For ordering replace-
ment washers, referto the "Repair Parts List" section.
t TEMPERATURE-PRESSURE
1. Turn "OFF" gas supply to water heater.
2. Follow"Draining" instructions.
3. Turning counter clockwise, remove the hex cap below the screw handle.
4. Remove the washer and put the new one in place.
5. Screw the handle and cap assembly back into the drain
DISCHARGEPIPE valve and retighten using a wrench. DO NOT OVER
TIGHTEN.
Failure to install and maintain a new properly listed tempera-
6. Follow instructions in the "Filling The Water Heater"
ture-pressure relief valve will release the manufacturer from section. any claim which might result from excessive temperature or 7. Check for leaks.
pressure. 8. Follow the lighting instructions in the "Instructions for
Operation" section to restart the water heater.
If the temperature-pressure relief valve on the appliance weeps or discharges periodically, this HANDLEAND
CAPASSEMBLY
may be due to thermal expansion. Your water heater may have a check valve installed in the _ _-WASHER
water line or a water meter with a check valve. Call Maytag Customer Service at 1-800-788-8899 for an
authorized servicer for further information. Do not plug the temperature-pressure relief valve. _f
Housekeeping
AWARNING
When checking the temperature-pressure relief Vacuum around base of water heater for dust, dirt, and lint on
valve operation, make sure that (1) no one is in a regular basis. front of or around the outlet of the temperature- Combustible materials such as clothing, cleaning materials, or
pressure relief valve discharge line, and (2)that the water manually discharged will not cause any flammable liquids, etc. must not be placed against or adjacent property damage because the water may be to the water heater.
extremely hot. To insure sufficient ventilation and combustion air supply, If after manually operating the valve, it fails to proper clearances from the water heater must be maintained
completely reset and continues to release water, immediately close the cold water inlet to the water at all times.
heater, follow the draining instructions, and replace the temperature-pressure relief valve with
a new one. Service
Before calling for repair service, read the Start Up Conditions and Operational Conditions found in the Troubleshooting
Guide of this manual. If a condition persists or you are uncertain about the opera-
tion of the water beater, let a qualified person check it out.
Call Maytag Customer Service at 1-800-788-8899 for an
authorized servicer.
24
Page 25
Troubleshooting
Start Up Conditions
CONDENSATION THERMAL EXPANSION
Whenever the water heater is filled with cold water, a certain Water supply systems may, because of high line pressure, fre- amount of condensation will form while the burner is on. A quent cut-offs, the effects of water hammer and others, have water heater may appear to be leaking when in Fact the water installed devices such as pressure reducing valves, check is condensation. This usually happens when: valves, back flow preventers, etc. to control these types of
problems. When these devices are not equipped with an inter-
" When a new water heater is filled with cold water for nal by-pass, and no other measures are taken, the devices
the first time. cause the water system to be closed. As water is heated, it
When gas burns and water vapor is produced in water expands (thermal expansion) and closed systems do not allow
heaters, particularly high efficiency models where flue for the expansion of heated water. temperatures are lower. The water within the water heater tank expands as it is heated
When you use large amounts of hot water in a short and increases the pressure of the water system. If the relieving
time and the refill water is very cold. point of the water heater's temperature-pressure relief valve is
reached, the valve wiI1 relieve the excess pressure. The tem-
Moisture from the products of combustion condense on the perature-pressure relief valve is not intended for the con-
cooler tank surfaces and form drops of water which may fall stant relief of thermal expansion. This is an unacceptable
onto the burner or other hot surfaces to produce a "sizzling" or condition and must be corrected.
"frying" noise. It is recommended that any devices installed which cotdd create
Excessive condensation can cause pilot outage due to water a closed system have a by-pass and/or the system have an
running down the flue tube onto the main burner and putting expansion tank to refieve the pressure built by thermal expan- out the pilot, sion in the water system. Expansion tanks are available for
ordering through Maytag Customer Service (1-800-788-8899). Because of the suddenness and amount of water, condensation Contact the local plumbing inspector, water supplier, and/or water may be diagnosed as a "tank leak". After the water in the call Maytag Customer Service at 1-800-788-8899 for an tank warms up (about 1-2 hours), the condition should disap- authorized servicer for assistance in controlling these situations.
pear.
Do not assume the water heater is leaking until there has been enough time for the water in the tank to warm up. STRANGE SOUNDS
An undersized water heater will cause more condensation. Possible noises due to expansion and contraction of some The water heater must be sized properly to meet the family's metal parts during periods of heat-up and cool-down do not
demands for hot water including dishwashers, washing represent harmful or dangerous conditions. machines and shower heads.
Condensation causes sizzling and popping with the burner Excessive condensation may be noticed during the winter and area during heating and cooling periods and should be consid-
early spring months when incoming water temperatures are at ered normal. See "Condensation" section. their lowest.
Good venting is essential for a gas fired water heater to oper- ate properly as well as to carry away products of combustion
and water vapor.
SMOKE/ODOR
It is not uncommon to experience a small amount of smoke and odor during the initial start-up. This is due to burning off ofoil from metal parts, and will disappear in a short while.
25
Page 26
Troubleshooting (cont'd)
Operational Conditions
SMELLY WATER HIGH TEMPERATURE SHUT OFFSYSTEM
In each glasslined water heater there is installed at least one This water heater is equipped with an automatic gas shut off anode rod (see parts section) for corrosion protection of the system. The high temperature shut offls built into the gas
tank. Certain water conditions will cause a reaction between control valve. This system shuts off the gas supply to the this rod and the water. The most common complaint associat- water heater burners when high water temperatures are pres-
ed with the anode rod is one of a "rotten egg smell". This odor ent. It is non-resettable. If the high temperature shut off actl- is derived from hydrogen sulfide gas dissolved in the water, rates, the gas control valve must be replaced. If this were to The smell is the result of four factors which must all be pres- occur, turn "OFF" the entire gas supply to the water heater. ent for the odor to develop: Call Maytag Customer Service at 1-800-788-8899 for an
authorized servicer.
a. a concentration of sulfate in the supply water. b. little or no dissolved oxygen in the water. =tWARNING i
c. a sulfate reducing bacteria within the water heater. Should overheating occur or the gas supply fail to ]
(This harmless bacteria is non-toxic to humans.) shut off, turn "OFF" the manual gas control valve to !
d. an excess of active hydrogen in the tank.This is caused the app ante.
by the corrosion protective action of the anode.
NOT ENOUGH OR NO HOT WATER
Smelly water may be eliminated or reduced in some water heater models by replacing the anode(s) with one of less active
1. Check the manual gas shut offvalve to be sure it is open.
material, and then chlorinating the water heater tank and all hot water lines. Call Maytag Customer Service at 1-800-788- 2. Check the pilot flame. It may have gone out. All models
8899 for an authorized servicer for further information con- have an opening behind the outer door for viewing the pilot. cerning an Anode Replacement Kit #66001068 and this
Chlorination Treatment. 3. If the pilot is not lit, foUowthe "Lighting" instructions in this
manual or located above the gas control valve on the water If the smelly water persists after the anode replacement and heater to relight the pilot. If the water was extremely hot and chlorination treatment, we can only suggest that continuous is now cold, the high limit safety temperature shut offmay chlorination and filtering conditioning equipment be consid- have put out the burner and pilot. If the high temperature
ered to eliminate the water problem, shut offactivates, the gas control valve must be replaced. Call
Maytag Customer Service at 1-800-788-8899 for an attthor- Do not remove the anode leaving the tank unprotected. By ized servicer.
doing so, all warranty on the water heater tank is voided.
4. The gas control knob must be turned to the "ON" position.
"AIR" IN HOT WATER FAUCETS 5. The temperature adjustment dial may be set too low. See the
"Temperature Regulation" section.
AWARNING 6. The gas company can check the gas input to see ifit is correct.
HYDROGEN GAS: Hydrogen gas can be produced in An underfired water heater will not heat water asquickly. a hot water system that has not been used for a
long period of time (generally two weeks or more). 7. Look for leaking or open hot water faucets. Make sure all are Hydrogen gas is extremely flammable and explo- closed.
sive. To prevent the possibility of injury under these conditions, we recommend the hot water faucet be
opened for several minutes at the kitchen sink 8. The cold water inlet temperature may be colder during the before any electrical appliances which are connect- winter months. It will take longer to heat the water and seem
ed to the hot water system are used (such as a dish- like less hot water. washer or washing machine). If hydrogen gas is
present, there will probably be an unusual sound similar to air escaping through the pipe as the hot 9. If you cannot find what is wrong, callMaytag Customer water faucet is opened. There must be no smoking Service (1-800-788-8899 for an authorized servicer.
or open flame near the faucet at the time it isopen. j
26
Page 27
Troubleshooting (cont'd)
Operational Conditions (cont'd)
WATER IS TOO HOT
1. The temperature adjustment dial may be set too high. See the
"Temperature Adjustment" section. NOTE: A period of time is necessary after an adjustment
has been made for the water temperature to reach the new temperature setting.
2. If lower temperature settings will not lower the water temper-
ature, call Maytag Customer Service (1-800-788-8899) for an authorized servicer.
AWARNING
Due to the nature of the typical gas water heater, the water temperature in certain situations may be hotter than the thermostat setting.
Short, frequent draws of hot water - especially with very cold incoming water - can shock the thermo-
stat into brief operation resulting in hotter and hot-
ter layers of water closer to the top of the tank.
Changes in hot water usage patterns or raisinq the
temperature differential between the cut-on of the thermostat and the cold water temperature will
usually eliminate the problem.
27
Page 28
Troubleshooting (cont'd)
Leakage Checkpoints
Use this guide to check a "Leaking" water heater. Many sus- _i CAUTION ]
pected"Leakers" arenot leaking tanks. Often the sourceof the Read this manual first. Then before checkingthe water canbe found and corrected, water heater make sure the gas supply hasbeen ]
turned HOFF", and never turn the gas HOW' before
If you are not thoroughly familiar with your local gas codes the tank s completely full of water. your water heater, and safety practices, contact your local gas
utifity or call Maytag Customer Service at 1-800-788-8899 _kCAUTION
for an authorized servicer to check the water heater. Never use this water heater unless it is completely [
filled with water. Toprevent damage to the tank, I
the tank must be filledwith water. Water must flow from the hot water faucet before turning "ON" gas
to the water heater. I
_ Water at the draft hood is water vapor which has con-
densed out of the combustion products. This is caused by
a problem in the vent. Call Maytag Customer Service at 1-800-788-8899 for an authorized servicer.
O *Condensation be on pipes in humid weather
may
seen
or pipe connections may be leaking.
O'The primary anode rod fitting may be leaking.
O Smafi amounts of water from relief
temperature-pressure
valve may be due to thermal expansion or high water
pressure in your area.
O* The temperature-pressure relief valve may be leaking at
the tank fitting.
O Water from a drain valve be due to the valve opened
may
slightly.
O'The drain valve may be leaking at the tank fitting.
Combustion products contain water which can
vapor
condense on the cooler surfaces of the tank. Droplets form and drip into the fire or run on the floor. This is
common at the time ofstartup after installation and when incoming water is cold.
O Water in the heater bottom the floor be
water or on
may
from condensation, loose connections, orthe relief valve. DO NOT replace the water heater until a full inspection
of all possible water sources is made and necessary cor-
rective steps taken. Leakage from other appliances, water lines, or ground seepage should also be checked.
O *NOTE:To check where threaded portion enters tank,
insert cotton swab between jacket opening and fitting. If cotton is wet, follow "Draining" instructions in the
"Service and Maintenance" section and then remove fit- ring. Put pipe dope or teflon tape on the threads and
replace. Then follow "Filling the Water Heater" instruc- tions in the "Instructions for Installation" section.
28
Page 29
Repair Parts List
MAYTAG GAS WATER HEATERS
MAYTAG / STATE MAYTAG / STATE
PARTNUMBER CONVERSION KEY PART NUMBER CONVERSION KEY
MAYTAG STATE MAYTAG STATE
66001003 9002400 66001040 0230223 66001004 9002123 66001041 0230224 66001010 9002403 66001042 9002414
66001011 9001609 66001043 9001206 66001012 9001608 66001044 9002415
66001013 ETC2X 66001045 9001207 66001014 ETC5× 66001046 0230124 66001015 9002401 66001047 0230123
66001017 9002321 66001048 0230256 66001020 9000734 66001049 9002417
66001021 9001584 66001050 9002418 66001022 9002419 66001051 9000274
66001023 9000284 66001068 9001453
66001024 9002001 66001079 9000071 66001025 0230120 66001100 0002916490-2
66001026 9002412 66001104 9002970 66001027 9002411 66001105 9002769
66001028 9002410 66001140 9002155 66001029 9000281 66001141 9002156
66001030 9002444 66001142 9002326 66001031 9000944 66001143 9002968
66001032 9000273 66001144 9002969 66001033 9002420 66001145 9000289
66001034 9002445 66001146 9000369 66001035 0230141 66001147 9002971
66001036 9002421 66001148 9002565
!
66001037 9002413 66001168 0230209 66001038 9002443 66001169 0230212
66001039 9000945 66001177 0230260
66001180 0230456
29
Page 30
Repair Parts List (cont'd)
MAYTAG GAS WATER HEATERS MODEL NUMBERS:
HN41240X 40 Gallon Natural Gas HN51240X 40 Gallon Natural Gas
HP41240X 40 Gallon Propane (L.R) Gas HP51240X 40 Gallon Propane (L.R) Gas
HN41250X 50 Gallon Natural Gas HN51250X S0 Gallon Natural Gas
18
d 5 1
%
- _
13 4_ 3 ql O
15
12
11
log
3O
Page 31
Repair Parts List (cont'd)
MAYTAG GAS WATER HEATERS MODEL NUMBERS:
HN41240X 40 Gallon Natural Gas
HN51240X 40 Gallon Natural Gas HP41240X 40 Gallon Propane (L.R) Gas
HP51240X 40 Gallon Propane (L.R) Gas HN41250X 50 Gallon Natural Gas
HN51250X 50 Gallon Natural Gas
MODEL NUMBERS
KEY HN41240X HN51240X HP41240X HP51240X HN41250X HN51250X
NO. PART DESCRIPTION PART NUMBERS
1 Temperature-Pressure Relief Valve 66001010 66001010 66001010 66001010 66001010 66001010
2 Primary Anode Rod 66001020 66001020 66001020 66001020 66001020 66001020 3 Drain Valve 66001015 66001015 66001015 66001015 66001015 66001015
4 Drain Valve Washer
(_½2"xW_"x¼"thick)* 66001021 66001021 66001021 66001021 66001021 66001021
5 SecondaryAnode Rod 66001022 66001022 66001022 66001022 66001022 66001022 6 Pilot (Natural) 66001023 66001023 -- -- 66001023 66001023
7 Pilot/Tubing & Thermocouple
Assembly (Propane [LR]) -- -- 66001036 66001036 -- --
8 Thermocouple 66001017 66001017 66001017 66001017 66001017 66001017
9 Pilot Tubing w/Fittings (Natural) 66001024 66001024 -- -- 66001024 66001024
10 Burner Orifice 66001025 66001035 66001040 66001041 66001025 66001035
Drill Size (#33) (#36) (#49) (#51) (#33) (#36)
11 Manifold 66001026 66001026 66001042 66001042 66001037 66001037
12 Burner 66001027 66001027 66001027 66001027 66001027 66001027 13 Outer Door 66001028 66001028 66001028 66001028 66001028 66001028
14 Inner Door 66001029 66001029 66001029 66001029 66001029 66001029
15 Gas Control Valve (Natural) 66001003 66001003 -- -- 66001003 66001003
15 Gas Control Valve (Propane [L.P.]) -- -- 66001004 66001004 -- -- 16 Dip Tube 66001030 66001030 66001030 66001030 66001038 66001038
17 Flue Baffle 66001031 66001031 66001043 66001043 66001039 66001039 18 Draft Hood 66001032 66001032 66001032 66001032 66001032 66001032
19 Cold Water Inlet Heat Trap 66001033 66001033 66001033 66001033 66001033 66001033
20 Pipe Insulation (2ea.) 66001034 66001034 66001034 66001034 66001034 66001034
# Manual 66001100
Also available at most hardware stores.
Now that you have purchased this Gas Water Heater, should a The model number of this Gas Water Heater will be found need ever exist for repair parts or service, simply call Maytag on the model rating plate located near the gas control valve.
Customer Service at 1-800-788-8899 for an authorized servicer. Be sure to provide pertinent facts when you call. When ordering repair parts, always give the following infor-
mation:
THIS IS A REPAIR PARTS LIST, NOT A PACKING Model Number
Serial Number
LIST. Part Description
Part Number
31
Page 32
Repair Parts List(cont'd)
MAYTAG GAS WATER HEATERS MODEL NUMBERS:
HP41250X 50 Gallon Propane (L.R) Gas HP51250X 50 Gallon Propane (L.P.) Gas
HN41250Q 50 Gallon Natural Gas HN51250Q 50 Gallon Natural Gas
HP41250Q 50 Gallon Propane (L.R) Gas HP51250Q 50 Gallon Propane (L.R) Gas
18 i_ 119
.L II ,' l /
5 _., 16
t_
13 4_3 O
12
11
log
32
Page 33
Repair Parts List (cont'd)
MAYTAG GAS WATER HEATERS MODEL NUMBERS:
HP41250X 50 Gallon Propane (L.P.)Gas HP51250X 50 Gallon Propane (L.R) Gas
HN41250Q 50 Gallon Natural Gas HN51250Q 50 Gallon Natural Gas
HP41250Q 50 Gallon Propane (L.R) Gas HP51250Q 50 Gallon Propane (L.P.)Gas
MODEL NUMBERS
KEY HP41250X HPS1250X HN41250Q HN51250Q HP41250q HP51250q
NO. PART DESCRIPTION PARTNUMBERS
1 Temperature-Pressure Relief Valve 66001010 66001010 66001010 66001010 66001010 66001010
2 Primary Anode Rod 66001020 66001020 66001020 66001020 _ 66001020 66001020 3 Drain Valve 66001015 66001015 66001015 66001015 66001015 66001015
4 Drain Valve Washer
('½f'x'Y."x'/f'thick) 66001021 66001021 66001021 66001021 66001021 66001021
5 Secondary Anode Rod 66001022 66001022 66001022 66001022 66001022 66001022 6 Pilot (Natural) -- -- 66001023 66001023 -- --
7 Pilot/Tubing & Thermocouple
Assembly (Propane [L.P.]) 66001036 66001036 -- -- 66001036 66001036
8 Thermocouple 66001017 66001017 66001017 66001017 66001017 66001017 9 Pilot Tubin 9 w/Fittings 66001024 66001024 66001024 66001024 66001024 66001024
10 Burner Orifice 66001040 66001041 66001046 66001047 66001048 66001040
Drill Size (#49) (#51) (#30) (#32) (#47) (#49)
11 Manifold 66001044 66001044 66001037 66001037 66001044 66001044
12 Burner 66001027 66001027 66001027 66001027 66001027 66001027 13 Outer Door 66001028 66001028 66001028 66001028 66001028 66001028
14 Inner Door 66001029 66001029 66001029 66001029 66001029 66001029
15 Gas Control Valve (Natural) -- -- 66001003 66001003 -- --
15 Gas Control Valve (Propane [L.P.]) 66001004 66001004 -- -- 66001004 66001004
16 Dip Tube 66001038 66001038 66001038 66001038 66001038 66001038
17 Flue Baffle 66001045 66001045 66001049 66001049 66001050 66001050
18 Draft Hood 66001032 66001032 66001051 66001051 66001051 66001051
19 Cold Water Inlet Heat Trap 66001033 66001033 66001033 66001033 66001033 66001033
20 Pipe Insulation (2ea.) 66001034 66001034 66001034 66001034 66001034 66001034
# Manual 66001100
Also available at most hardware stores.
Now that you have purchased this Gas Water Heater, should a The model number of this Gas Water Heater will be found need ever exist for repair parts or service, simply call Maytag on the model rating plate located near the gas control valve.
Customer Service at 1-800-788-8899 for an authorized servicer. Be sure to provide pertinent facts when you call. When ordering repair parts, always give the following infor-
mation:
THIS IS A REPAIR PARTS LIST, NOT A PACKING Model Number
Serial Number
LIST. Part Description
Part Number
33
Page 34
Repair Parts List (cont'd)
MAYTAG GAS WATER HEATERS MODEL NUMBERS:
HN41275Q 75 Gallon Natural Gas HN51275Q 75 Gallon Natural Gas
HP41275Q 75 Gallon Propane (LP.) Gas HP51275Q 75 Gallon Propane (L.R) Gas
16 _//i 17
I I.--......
..........."h il
I I i I
T ! II
I I I ii
2
17 _i 14
t_
4_3 O o
11
'T 2
34
Page 35
Repair Parts List (cont'd)
MAYTAG GAS WATER HEATERS
MODEL NUMBERS: HN41275Q 75 Gallon Natural Gas
HN51275Q 75 Gallon Natural Gas
HP41275Q 75 Gallon Propane (L.R) Gas
HP51275Q 75 Gallon Propane (L.R) Gas
MODEL NUMBERS
KEY HN41275Q HN51275qlHP41275Q HP51275Q
NO. PARTDESCRIPTION PART NUMBERS
1 Temperature-Pressure Relief Valve 66001079 66001079 66001079 66001079 2 Primary Anode Rod 66001020 66001020 66001020 66001020
3 Drain Valve 66001015 66001015 66001015 66001015
4 Drain Valve Washer
(_½2"x _3/,, x ½" thick) 66001021 66001021 66001021 66001021
5 I Pilot (Natural) 66001140 66001140 -- -- 5 Pilot (Propane [L.P.]) -- -- 66001141 66001141
6 Thermocouple 66001017 66001017 66001017 66001017
7 Pilot Tubing w/Fittings 66001142 66001142 66001142 66001142 8 Burner Orifice 66001169 66001168 66001180 66001177
Drill Size (#23) (#27) (#41) (#43)
0 Manifold 66001143 66001143 66001144 66001144Burner 66001145 66001145 66001145 66001145 11 Outer Door 66001028 66001028 66001028 66001028 12 InnerDoor 66001146 66001146 66001146 66001146
13 Gas Control Valve (Natural) 66001104 66001104 -- -- 13 Gas Control Valve (Propane [L.P.]) -- -- 66001004 66001004 14 Dip Tube 66001030 66001030 66001030 66001030
15 FlueBaffle 66001147 66001147 66001147 66001147 16 Draft Hood 66001051 66001051 66001051 66001051 17 Cold and Hot Water Nipples 66001148 66001148 66001148 66001148
# Manual 66001100
*Also available at most hardware stores.
Now that you have purchased this Gas Water Heater, should a The model number this Gas Water Heater will be found need ever exist for repair parts or service, simply call Maytag on the model rating plate located near the gas control valve.
Customer Service at 1-800-788-8899 for an authorized servicer. Be sure to provide pertinent facts when you call. When ordering repair parts, always give the following infor-
mation:
Model Number
THIS IS A REPAIR PARTS LIST, NOT A PACKING Serial Number
LIST. Part Description
Part Number
35
Page 36
Warranty
FULL ONE YEAR WARRANTY
For One Year from the date of Original Retail Purchase, any part which fails in normal home use will be repaired or replaced free of charge.
If a leak occurs in the Tank, a new water heater of the closest capacity and quality then available, will be replaced free of charge.
The warranty of the replacement is the balance of the original water heater's Warranty.
LIMITED PARTS WARRANTY
After the First year and through the Twelfth Year from the date of Original Retail Purchase, any Parts which fail due to a defect in materials or workmanship, will be replaced or repaired free of charge for the part itself, with the owner paying all other costs, including labor, mileage and transportation.
If the water heater is subjected to commercial, institutional, industrial or non-residential use, the above warranty cov- erage for parts that are proved to be defective in material or workmanship is effective for one year from the date of
the Original Retail Purchase. The warranty of the replacement is the balance of the original water heater's Warranty, or twelve months from the
date of the part(s) purchase, whichever comes first. The warranty is limited to the original owner of the water heater.
LIMITED TANK WARRANTY AGAINST LEAKS
After the First Year and through the Twelfth Year from the date of Original Retail Purchase, if a leak occurs in the Tank, a new water heater of the closest capacity and quality then available, will be replaced free of charge for the
water heater, with the owner paying all other costs, including labor, mileage and transportation.
If the water heater is subjected to commercial, institutional, industrial or non-residential use, the above warranty cov- erage for tanks that are proved to be defective in material or workmanship is effective for two years from the date of
the Original Retail Purchase. The warranty of the replacement is the balance of the original water heater's Warranty.
Please note: The Full and Limited Warranty applies only while this water heater is used in the United States of America.
The warranty is limited to the original owner of the water heater.
TO RECEIVE WARRANTY SERVICE
To locate an authorized service company in your area contact the Maytag dealer from whom your appfiance was pur-
chased; or call Maytag Customer Service at the number listed below. Should you not receive satisfactory warranty
service, please call or write:
Maytag Customer Service P.O. Box 2370
Cleveland, TN 37320-2370
U.S.A. 1-800-788-8899
When contacting Maytag Customer Service be sure to provide the Model and Serial Number of your appliance, The
Name and Address of the Dealer from whom you purchased the appliance and the Date of Purchase.
MAY;FAG WATER HEATERS ARE MANUFACTURED AND THIS WARRANTY PROVIDED BY
STATE INDUSTRIES, INC., ASHLAND CITY, TN. MAYTAG IS A TRADEMARK OF MAYTAG COR- PORATION AND IS USED UNDER LICENSE TO STATE INDUSTRIES, INC.
09-01 66001100
0002916490-2
Loading...