Maytag HJ640POVET, HJ640POVET2, HJ640NOVET2, HJ650NOVET, HJ650POVET User Manual

...
Page 1
1VLYIAG
POWER VENT
GAS WATER HEATER
USER'SGUIDE
For Your Safety
AN ODORANTISADDEDTOTHEGASUSEDBYTHISWATERHEATER Model Numbers
HJ640NOVET
lowed exactly, a fire or explosion may result, causing property HJ640NOVET2
damage, personalinjury or death. HJ640POVET2
HJ650NOVET
-WHAT TO DOIFYOU SMELLGAS HJ650POVET2
HJ675NRVETZ
Do not try to light any appliance. HJ675PRVETZ
Do not touch any electrical switch; do not use any phone in
your building.
° Immediately call your gas supplier from a neighbor's phone.
Followthe gassupplier'sinstructions.
if you cannot reachyour gassupplier,callthe fire department.
-Installation and servicemustbe performedby a qualified installer, FORPOTABLEWATER serviceagency or the gas supplier. HEATING ONLY
•,WARNING NOT SUITABLE FOR
Improper installation, adjustment, alteration, service or mainte- SPACE HEATING nance can cause DEATH, SERIOUSBODILYINJURY,OR PROPERTY
DAMAGE. Refer to this manual for assistanceor consultthe local gas utility for further information. NOT FOR USE IN
MANUFACTURED
AWARNING other (MOBILE) HOMES
Flammable vapors may be drawn by air currents from areas of the structure to this appliance.
Caution:
_,WARNING Read and Follow All
READ THE GENERAL SAFETY SECTION BEGINNING ON INSIDE Safety Rules and
COVER AND THEN THIS ENTIRE MANUAL BEFOREINSTALLING Operating Instructions
OR OPERATNG THIS WATER HEATER. Before First Use of
Save this Manual for Future Reference. This Product.
Page 2
Safety Instructions
A, WARNING A, WARNING
Improper installation, adjustment, alteration, service At the time of manufacture this water heater was pro-
or maintenance can cause DEATH, SERIOUS BODILY vided with a combination temperature-pressures relief INJURY, OR PROPERTYDAMAGE. Refer to this manu- valve certified by a nationally recognized testing labo-
al for assistance consult your local gas utility or call ratory that maintains periodic inspection of production Maytag Customer Service at 1-800-788-8899 for an of listed equipment or materiels, as meeting the
authorized servicer for further information, requirements for Relief Valves and Automatic Gas
Shutoff Devices for Hot Water Supply Systems, and the latest edition of ANSI Z21.22 and the code requiR_-
ments of ASME. If replaced, the valve must meet the
AWARNING requirements of local codes,but not lessthan a combi-
WATER HEATERS EQUIPPED FOR ONE TYPE GAS nation temperature and pressure relief valve certified ONLY: This water heater is equipped for one type as meeting the requirements for Relief Valves and
gas only. Check the model rating plate near the gas Automatic Gas Shutoff Devices for Hot Water Supply control valve for the correct gas. DO NOT USE THIS Systems, ANSI Z21.22 by a nationally _cognized test-
WATER HEATER WITH ANY GAS OTHER THAN THE ing laboratory that maintains periodic inspection of ONE SHOWN ON THE MODEL RATING PLATE.Failure production of listod equipment or materials.
to use the correct gas can cause problems which can The valve must be marked with a maximum set pres- result in DEATH, SERIOUS BODILY INJURY, OR PROP- sure not to exceed the marked hydrostatic working
ERTY DAMAGE. If you have any questions or doubts pressure of the water heater (150 Ibs./sq. in.) and a
consult your gas supplier or local utility, discharge capacity not less than the water heater
input rate as shown on the model rating plate. (Electric heaters - watts divided by 1000 x 3415 equal
BTU/Hr. rate.)
AWARNING Your local jurisdictional authority, while mandating the
INSTALLATIONS IN AREAS WHERE FLAMMABLE LIQ- use of a temperature-pressure relief valve complying UIDS (VAPORS)ARE LIKELYTO BEPRESENTOR STOREDI with ANSI Z21.22 and ASME, may require a valve model
(GARAGES, STORAGE, AND UTILITY AREAS, ETC)- different from the one furnished with the water heater. Flammable liquids (suchas gasoline, solvents, propane Compliance with such local requirements must be sat-
(LP) or butane, etc.), all of which emit flammable isfiedby the installer or end user of the water heater vapors, may be improperly/stored or used in such _ with a locally prescribed temperature-pressure relief
areas. The gas water heater .c_nitoror main burner can valve installed in the designated opening in the water ignite such vapors. The resulting flashback and fire can heater in placeof the factory furnished valve.
cause death or serioushums to anyone n the area, as For safe operation of the water heater, the relief valve I
must not be removed from it's designated opening or
well asproperty damage. If installation in such areas is your only option, then I plugged, r I I
the !nstallation must be accomplished in a way that The temperature-p essure relief va ve must be the ignitor and main burner flame are elevatedfrom I installed directly into the fitting of the water heater
the floor at least 18 inches.While this may reduce the designated for the relief valve. Position the valve
chances of flammable vapors from a floor spill being downward and provide tubing so that any discharge ignited, gasoline and other flammable substances will exit only within 6 inchesabove, or at any distance
should never be stored or used in the same room or below the structural floor. Becertain that no contact is area containing a gas water heater or other open made with any live electrical part. The discharge open-
flame or spark producing appliance, ing must not be blocked or reduced in size under any
NOTE: Flammable vapors may be drawn by air currents circumstances. Excessivelength, over 30 feet, or use of from other areas of the structure to the appliance, more than four elbows can cause restriction and
reduce the discharge capacity of the valve. No valve or other obstruction isto be placed between
I the relief valve and the tank. Do not connect tubing
&WARNING
di_-tly to discharge drain unlessa 6" air gap is provid-
|If this water heater will be used in beauty shops, ed. To prevent bodily injury, hazard to life, or property |barber shops, cleaning establishments, or self-ser- damage, the relief valve must be allowed to discharge /vice laundries with dry cleaning equipment, it is water in quantities should circumstances demand. If
imperative that the water heater or water heaters the discharge pipe is not connected to a drain or other be installed so that combustion and ventilation air suitab e means, the water flow may cause property
be taken from outside these areas. Refer to the damage.
"Locating The New Water Heater" section of this _TheDischarge Pipe:
manual and also the latest edition of the National Must notbe smaller in size than the outlet pipe size Fuel Gas Code, ANSI Z223.1, also referred to as NFPA of the valve, or have any reducing couplings or
54 for specifics provided concerning air required, other restrictions.
Must not be plugged or blocked.
Must be of material listed for hot water distribution.
j Must be installed so as to allow complete drainage
&WARNING
I
of both the temperature-pressure relief valve, and
A fire can start if combustible materials such as the discharge pipe. clothing, cleaning materials, or flammable liquids Must terminate at an adequate drain.
are placed against or next to the water heater. ° Must not have any valve between the relief valve
and tank.
2
Page 3
Safety Instructions
AWARNING I AWARNING
A gas water heater cannot operate properly without |This water heater must not be installed directly on
the correct amount of air for combustion. Do not |carpeting. Carpeting must be protected by a metal install Jn a confined area such a closet, unless you |or wood panel beneath the appliance extending
provide air as shown in the "Locating The New |beyond the full width and depth of the appliance by Water Heater _ section. Never obstruct the flow of |at least 3 inches (76.2mm) in any direction, or if the ventilation air. If you have any doubts or questions |appliance is installed in an alcove or closet, the
at all, call your gas company. Failure to provide the |entire floor must be covered by the panel. Failure to proper amount of combustion air can result in a fire /heed this warning may result in a fire hazard.
or explosion and can cause DEATH, SERIOUS BODILY INJURY,OR PROPERTYDAMAGE,
AWARNING
The power vent water heater requires its own (sepa-
rate)venting system. It cannot be connected to an
AWARNING exist ng vent pipe or chimney. It must be term nated
HOTTER WATER CAN SCALD: Water heaters are to the outdoors. Failure to properly install the vent- intended to produce hot water. Water heated to a ing system can result in asphyxiation, a fire or explo-
temperature which will satisfy clothes washing, dish Ision and can cause DEATH, SERIOUS BODILY INJURY, washing, and other sanitizing needs can sca|d and OR PROPERTY DAMAGE.
permanently injure you upon contact. Some people are more likely to be permanently injured by hot water than others, These indude the elderly, children, the infirm, or physically/mentally handicapped. If I _,WARNING
anyone using hot water in your home fits into one of I these groups or if the_ is a local code or state law _ _No vent damper installation is compatible with this
power ventedwater heater design. No vent damper,
requiring a certain temperature water at the hot I whether it is operated thermally or otherwise is to water tap, then you must take special precautions. In [ be installed on this power vented water heater. AI-
addition to using the lowest possible temperature I teration of any part of the factory-furnished vent as- setting that satisfies your hot water needs, a means sembly could result in improper operation due to re-
such as a mixing valve, should be used at the hot striction of flue gases, spillage of flue gases and may water taps used by these people or at the water 'cause carbon monoxide poisoning.
heater. Mixing valves are available at plumbing sup- ply or hardware stores. Follow manufacturers instruc-
tions for installation of the valves. Before changing
the factory setting on the thermostat, read the AWARNING
'_Temperature Regulation" section in this manual.
The appliance and its individual shutoff valve must
be disconnected from the gas supply piping system during any pressure testing of the gas system at
test pressures in excess of ½ pound per square inch
A WARNING (3.5kPa).
Soot build-up indicates a problem that requires cor- The appliance must be isolated from the gas sup- rection before further use. Turn "OFF" gas to water ply piping system by closing its individual manual
heater and leave _OFF" until repairs are made, shutoff valve during any pressure testing of the
gas supply piping system at test pressures equal or
because failure to correct the cause of the sooting lessthan pound per square nch (3.5kPa).
can result in a fire or explosion causing DEATH, SERI- OUS BODILYINJURY,OR PROPERTYDAMAGE,
AWARNING
l AWARNING Chemical vapor corrosion of the flue and vent sys-
tem may occur if air for combustion contains certain
BEFORE LIGHTING [PROPANE (L.P,) GAS WATER chemical vapors. Spray can propellants, cleaning sol- HEATERS]: Propane (L.P.) gas is heavier than air. vents, refrigerator and air conditioner refrigerants, Should there be a leak in the system, the gas will set- swimming pool chemicals, calcium and sodium chlo- tie near the ground. Basements, crawl spaces, skirted ride, waxes, bleach, and process chemicals are typi-
areas under manufactured (mobile) homes (even cal compounds which are potentially corrosive. when ventilated), closets and areas below ground
Ilevel will serve as pockets for the accumulation of
this gas. Before attempting to operate the water
heater or turning on a nearby electrical light switch, be absolutely sure there is no accumulatedgas in the
_,WARNING 1
Obstructed or deteriorated vent systems may pre- sent a serious health risk or asphyxiation.
area. Search for odor of gas by sniffing at ground
level in the vicinity of the appliance. If odor isdetect- ed, follow steps indicated at "For Your Safety" on the
cover page ofth s manua then eave the prem ses.
3 Safety Instructions continued on page 4.
Page 4
Safety Instructions
AWARNING _,WARNING
Minimum clearances between the water heater and Vent termination must not be within 4 feet of any
combustible and noncombustible construction are 0" items such as gas meters, gas valves or other gas reg- at the sides and rear, 5 inches from front of jacket to u at n_l equ pment.
closet door, and 0" from the vent pipe. Clearance from the top of the jacket is 14" (12" on some models).
Provide 24 inches front clearance for servicing and adequate clearance between the jacket top and ceil- ACAUTION
ing tor servicing the flue area. Refer to the label on WATER HEATERS EVENTUALLY LEAK: Installation of
the water heater adjacent to the gas control valve for the water heater must be accomplished in such a all clearances, manner that if the tank or any connections should
leak, the flow of water will not cause damage to the structure. For this reason, it is not advisable to
install the water heater in at attic or upper floor.
AWARNING When such locations cannot be avoided, a suitable
Flood damage to a water heater may not be readily drain pan should be installed under the water visible or immediately detectible. However, over a heater. Drain pans are available at your local hard- period of time a flooded water heater will create ware store, Such a drain pan must be not greater dangerous conditions which can cause DEATH, SERI- than 1½ inches deep, have a minimum length and OUS BODILY INJURY, OR PROPERTY DAMAGE. width of at least 2 inches greater than the water
Contact the Maytag dealer from whom the appli- heater dimensions and must be piped to an ade- ance was purchased or call Maytag Customer Service quate drain. The pan must not restrict combustion
at 1-800-788-8899 for an authorized servicer to air flow. Under no circumstances is the manufactur- replace a flooded water heater. Do not attempt to er to be held liable for any water damage in con-
repair the unit! It must be replaced! nection with this water heater.
AWARNING
HYDROGEN GAS: Hydrogen gas can be produced in a hot water system that has not been used for a long period of time (generally two weeks or more).
Hydrogen gas is extremely flammable and explosive. To prevent the possibility of injury under these con-
ditions, we recommend the hot water faucet be opened for several minutes at the kitchen sink
before any electrical appliances which are connected to the hot water system are used (such as a dish-
washer or washing machine). If hydrogen gas is pre- sent, there will probably be an unusual sound simi-
lar to air escaping through the pipe as the hot water faucet isopened. There must be no smoking or open flame near the faucet at the time it is open.
_,WARNING
INSULATING JACKETS: When installing an external water heater insulation jacket on a gas water heater:
DO NOT cover the temperature-pressure relief valve.
DO NOT put insulation over any part of the top of the gas water heater.
DO NOT put insulation over the gas control valve or
gas control valve/burner cover, or any accessareas to the burner.
DO NOT let insulation around the gas water heater
to get within 8 inches of the floor (air must get to the burner).
DO NOT cover or remove operating instructions,
and safety related warning labels and materials affixed to the water heater.
Failure to heed this will result in the possibility of a
fire or explosion.
4
Page 5
Table of Contents
,In tucton........................................................................................................................................................................................................................................................................... -o,ontents
Customer Information .....................................................................................................................6
Accessories ............................................................................................................................................................................ 8
Basic Tools ..................................................................................................................................................................... .8
Instructions for Installation .....................................................................................................9-29
Removing the Old Water Heater ...................................................................................................................................... 9
Typical Installation ............................................................................................................................................................ 10
Locating the New Water Heater ................................................................................................................................... .11,12
Combustion Air and Ventilation ..................................................................................................................................... 12
Venting Clearances ....................................................................................................................................................... 12,13
Combustion Air and Ventilation for Appliances in Unconfined Spaces ............................................................................ 13
Combustion Air and Ventilation for Appliances in Confined Spaces ............................................................................... 14
Water Piping .................................................................................................................................................................... 15
Temperature-Pressure Relief Valve ............................................................................................................................... ..16
Filling the Water Heater ................................................................................................................................................. 17
Wiring. ......................................................................................................................................................................... 17,18
Venting ...................................................................................................................................................................... 19-27
Gas Piping ................................................................................................................................................................. 27,28
Installation Checklist ...................................................................................................................................................... 29
Instructions for Operation ..................................................................................................30-33
Operating ...................................................................................................................................................................... 30-32
Temperature Regulation .................................................................................................................................................. .33
Service and Maintenance ....................................................................................................... 34-36
Venting System Inspection ................................................................................................................................................ .34
Oiling Instructions ....................................................................................................................................................... B4
Burner Inspection ........................................................................................................................................................ .34
Burner Cleaning. .............................................................................................................................................................. 34
L.E Gas Control Valve and Burner Assembly Replacement Information .......................................................................... 35
Draining. ..................................................................................................................................................................... .35
Temperature-Pressure Relief Valve Operation ................................................................................................................. 36
Drain ValveWasher Replacement ................................................................................................................................ 36
Housekeeping ............................................................................................................................................................ 36
Service ................................................................................................................................................................................ .36
:=====================::::::::::::::::::::::::.....:::::::::::::::::::::::::::::::::::
Condensation ......................................................................................................................................................... .37
Smoke/Odor .............................................................................................................................................................. 37
Thermal Expansion ................................................................................................................................................... ..37
Strange Sounds ....................................................................................................................................................... .37
Operational Conditions .............................................................................................................................................. 38,39
Smelly Water ................................................................................................................................................................ 38
"Air" in Hot Water Faucets ......................................................................................................................................... .38
High Temperature Shut Off System ....................................................................................................................... .38
Venting Manual Reset Switch ..................................................................................................................................... 38
Not Enough Hot Water ................................................................................................................................................. 39
Water is too Hot ......................................................................................................................................................... 39
Leakage Checkpoints .............................................................................................................................................. .40
Thermostat and Gas Supply Check .............................................................................................................................. 41
Electrical System Check .......................................................................................................................................... 42-44
Repair Parts List .............................................................................................................................. 46-50
Warranty ................................................................................................................................................................52
5
Page 6
Customer Information
Thank You for purchasing a Maytag water heater. The installation must conform with the instructions in this
Properly installed and maintained, it should give youyears of manual; gas company rules; and Local Codes, or in the trouble free service. It is strongly suggested that this new water absence of LocaI Codes, with the latest edition of the
heater he professionally iastaIted, contact Mayt_g Customer National Fuel Gas code, ANSI Z223.1, also referred to as Service (1-800-788-8899) for recommended installers. NFPA 54. This pubfication is available from your local
Abbreviations Found In This Instruction Manual government or public library or gas company or by writing
CSA - Canadian Standards Association NFPA, Batterymarch Park, Quincy, MA 02269.
NFPA - National Fire Protection Association After reading this manual you have any questions or do not ANSI - American National Standards Institute understand any portion of the instructions, call Maytag
Customer Service at 1-800-788-8899 for an authorized
AWARNING servicer.
This gas-fired water heater is design certified by Carefidly plan the place where you are going to put the CSA INTERNATIONAL under American National water heater. Correct combustion, vent action, and vent
Standard/CSA Standard for Gas Water Heaters ANS pipe installation are very important in preventing death Z21.10.1 * CSA 4.1 (latest edition). The installation from possible carbon monoxide poisoning and fires.
must conform with this manual, Local Codes and with the latest edition of the National Fuel Gas Examine the location to ensure the water heater complies
Code, ANSI Z223.1. with the "Locating the New Water Heater" section in this This publication is available from your local govern- manual.
ment or public library, gas company, or by writing NFPA, Batterymarch Park, Quincy, MA 02269. For California installation this water heater must be braced,
anchored, or strapped to avoid falling or moving during an
Read the "Safety Instructions" section, pages 2, 3 and 4 of earthquake. See instructions for correct instalIation proce- this manual first and then the entire manual carefit!ly. If dures. Instructions may be obtained from your local dealer,
you don't follow the safety rules, the water heater _ not wholesaler, pubfic utilities or California Office of the State
operate properly. It could cause DEATH, SERIOUS Architect, 400 P Street, Sacramento, CA 95814. BODILY INJURY AND/OR PROPERTY DAMAGE. Massachusetts Code requires this water heater to be
This manual contains instructions for the installation, installed in accordance with Massachusetts 248-CMR 2.00:
operation, and maintenance of the gas-fired water heater. State Plumbing Code and 248-CMR 5.00.
It also contains warnings through out the manual that you Compiles with SCAQ.MD rule #1121 and districts having
must read and be aware All warnings and all instruc- equivalent NOx requirements.
tions are essential to the proper operation of the water heater and your safety. Since we cannot put everything on
the first few pages, READ THE ENTIRE MANUAL BEFORE ATTEMPTING TO INSTALL OR OPER-
ATE THE WATER HEATER.
Page 7
Product Specifications
*Model HJ640NOVET HJ640POVET HJ640NOVET2 HJ640POVET2 HJ650NOVET
Tank Capacity
In Gallons 40 40 40 40 50
Type of Gas Natural Propane Natural Propane Natural
B.T.U. rate 40,000 40,000 40,000 40,000 40,000
Recovery Rate
In Gals Per Hr.
@_°F Rise 41 41 41 4I 41 Vent Pipe 3"** 3" ** 3" ** 3" ** 3" **
Diameter 18" 18° 20" 20" 20"
Height To
Top of Blower 68V:' 68%" 68_A" 68V: 67V:'
Model HJ650POVET HJ650NOVET2 HJ650POVET2 HJ675NRVETZ HJ675PRVETZ
Tank Capacity
In Gallons 50 50 50 75 75
Type of Gas Propane Natural Propane Natural Propane
B.T.U. rate 40,000 40,000 40,000 75,000 70,000
Recovery Rate
In Gals Per Hr.
@90°FRise 41 41 41 77 72 Vent Pipe 3" ** 3" ** 3" ** 3"*** 3" ***
Diameter 20" 22" 22" 26%" 26%"
Height To
Top of Blower 67%" 673/4" 67%" 711/2" 711/:
*Adding suffix "D" denotes high altitude (Example HJ640NOVETD). High altitude models have a
B.T.U./Recovery Rate 10% less than shown.
**Limited usage of 2" vent pipe - see pages 19 through 27.
***Limited usage of 4" vent pipe - see pages 19 through 27.
Page 8
Accessoriesand ToolsNeeded
Accessories
To simplify the installation Maytag has available the installa- tion parts shown below. You may or may not need all o£these
accessories depending on your type ofinstaTlation. CalI Maytag Customer Service at 1-800-788-8899 for an autho-
rized installer.
DRAIN PANS AVAILABLE IN 22" DIAMETER
(PART NUMBER 66001011) FOR WATER
HEATERS HAVING A DIAMETER 20" OR LESS, 24" DIAMETER (PART NUMBER 66001105) FOR
EXPANSION TANKS FOR THERMAL EXPANSION WATER HEATERS HAVING A DIAMETER 22"
CONDITIONS AVAILABLE IN Z GALLON (PART OR LESSAND AVAILABLE IN 28" DIAMETER
NUMBER 66001013) AND S GALLON (PART (PART NUMBER 66001012) FOR WATER NUMBER 66001014) CAPACITY HEATERS HAVING A DIAMETER 26" OR LESS
Tools
You may or may not need all of these tools, depending on your ADDITIONAL TOOLS NEEDED
type ofinstaUation. These tools can be purchased at your local WHEN SWEAT SOLDERING hardware store.
i Tubing Cutters or Hacksaw Pipe Wrenches (2) 14" Propane Torch
So fat Solder
Screwdriver Solder Flux
Tin Snips _ _ _ o'WireBrushes
6 Foot Tape of Folding Rule Emery Cloth
Garden Hose _ "_ _
Drill
Pipe dope or Teflon Tape GARDEN HOSE
HACKSAW
P,PE
6,00TTAPEWRENCH0_4..
ROLLOFTEFLONTAPE /4 W,BEBROSH
(USE ONLY ON WATER CONNECTIONS)
1/2" WIRE BRUSH
"_ _ PROPANE TORCH
SLOT-HEAD SCREWDRIVER
TIN SNIPS _;_
PHIU.IPS SCREWDRIVER ROLL OF LEAD FREE
SOFT SOLDER
PIPE DOPE (SQUEEZE TUBE) (USE FOR WATER AND ROLL OF EMERY GAS CONNECTIONS) _ CLOTH SOLDER FLUX TUBING CU'I-rER
8
Page 9
Instructions for Installation
Removing the Old Water Heater
Turn "OFF" the gas supply to the water heater. (_ Disconnect the vent pipe from the draft hood where they
"_" connect to the water heater. In most installations the vent
AWARNING pipe can be lifted off after any screw or other attached
devices are removed. Dispose of the draft hood. The new
If the main9_aslineshutoffservingall gasappliancesisused,
Ialso shut "oii" the gas at each appliance. Leave all gas appli- water heater has the draft hood which must be used for
[ ancesshut"off" unti/thewaterheaterinstallationiscomplete, proper operation.
Q a. If you have copper piping to the water
heater, the two copper water pipes can
cutw--appoximtl
four inches away from where they con-
nect to the water heater. This will
avoid cutting offthe pipes too short.
i::=l_l___ _'_ _ ____ Additional cuts can be made later if
necessary. Disconnect the temperature- pressure reliefvalve drain line. When
the water heater is drained, disconnect
Turn "OFF" the water to the water
the hose from the drain valve. Close
heater. Some installations
require
that
f£ (_ the drain valve. The water heater is
the water be turned offto the entire
r now completely disconnected and
house.
(_ ready to be removed.
Check again sure gas sup-
to make the
ply is "OFF" to the water heater. Then I _ _ Q b. If you have galvanized pipe to the water
disconnect the gas supply connection _._) heater, loosen the two galvanized pipes
from the gas control valve, with a pipe wrench at the union in each
line. Also disconnect the piping
I remaining to the water heater. These
Q Attach a hose to the water heater drain pieces should be saved since they may
valve and
put the other end in a floor _ _ be needed when reconnecting the new
drain or outdoors. Open the water _'-'---_--'_ water beater. Disconnect the tempera- heater drain valve. Open a nearby hot ture-pressure relief valve drain fine.
water faucet which will refieve pressure When the water heater is drained, dis- in the water heater and speed draining, connect the hose from the drain valve.
Close the drain valve. The water heater
ready to be removed.
1 [ .c o..oN
Thewaterpassingout_ maybeextremelyhot.I I Mineralbuildupor sed_accumulated in theold Toavoidbeingscalded,makesureallconnectionsare tight andI |water heater.Thiscausesthewater heaterto bemuchheavier
thatthe waterflow isdirectedawayfromanyperson. ] [thannormalandthisresidue,ifspilledout,couldcausestaining.
9
Page 10
Instructions for Installation (cont'd)
Typical Installation
Vacuum Relief required by some codes
VENTTO (refer to local codes)
OUTDOORS
J COLDWATERINLET
TEMPERATURE-
PRESSURE
RELIEFVALVE
/
DISCHARGEPIPE
(Do not capor plug)
PROVIDEA 6" AIR GAP
BETWEENTHEEND OF
THEDISCHARGEPIPE
WATEROUTLET AND DRAIN
7' power cord (Factorysupplied)
This appliance has beendesign certified as complying with American National Standard/CSA Standard forwater heaters and is consideredsuitable for:
Water(Potable)Heating: All models are%onsideredsuitableforwater (potable)heating."
AWARNING AWARNING [
When the system requires water at temperatures Thiswater heater shallnot be connectedto any heat-
ing systemsor component(s)previouslyusedwith a I
higherthan requiredfor other uses,the hotwater sys- non-potablewater heating appliance. I
tern may requirea meanssuchasa mixingvalve tobe installedto temper the water at certainpointsof use. Some people are more likely to be permanently
injured by hot water than others; these includethe AWARNING
elderly,children,the infirm,or the physically/mentally Toxicchemicalssuchasusedfor treatment of boilersorI
handicapped. Before immersing yourself or anyone non-potable water heating appliancesshall never be
ture.elseinWARNING:hOtwater,HOTTERbesureWATERt°checkiNcREASEsthewater THEtempera'RISKintroducedintoa potablewaterspaceheatingsystem. OF SCALDINJURY.(Alsosee"TemperatureRegulation" NOTE: Toprotectagainstuntimelycorrosionof hot and
section)Mixing valvesare availableat plumbingsup- coldwaterfittings,iris stronglyrecommendedthatdi-elec-
plyor hardwarestores.Followmanufacturersinstruc- tric unionsor couplingsbe installedon thiswater heater
tionsfor installationof thesevalves, whenconnectedto copperpipe.
10
Page 11
Instructions for Installation (cont'd)
Locating the New Water Heater
Youshould carefitlly choose an indoor location for the new water
A
heater, because the placement is a very important consideration
WARNING
I
for the safety of the occupants in the building and for the most DO not use an extension cord. If there is not a suit-I economical use of the appliance. Thiswaterheaterisnotforuse able receptacle and/or local codes prohibit use of a ] in manufactured(mobile)homesoroutdoorinstallation, power cord, f eld wit ng must be prey ded. ]
Whether replacing an old water heater or putting the water heater in a new location, the following critical points must be observed. A CAUTIO N
The location selected should be indoors as close as practical to WATER HEATERS EVENTUALLY LEAK: Installation of theventtermination point, and ascentralizedwith thewater the water heater must be accomplished in such a
manner that if the tank or any connections should
piping system aspossible. The water heater, as all water leak, the flow of water will not cause damage to heaters, willeventually leak. Do not install without adequate the structure. For this reason, it is not advisable to
drainage provisions where water flowwill cause damage, install the water heater in an attic or upper floor.
When such locations cannot be avoided, a suitable
40,000 BTU/HR INPUT MODELS - If vented through an drain pan should be installed under the water outside wall or through the roof, the 3" vent piping cannot heater. Drain pans are available at your local hard-
exceed a total of 115 feet (50 feet if optional 2" vent piping is ware store. Such a drain pan must be not greater used), including vertical and horizontal runs with one 90° than 1½ inches deep, have a minimum length and
elbow. If more elbows are required, the venting distance must width of at least 2 inches greater than the water be reduced 5 feet for every90°elbow. See page 22 for vent heater dimensions and must be piped to an ade-
chart, quate drain. The pan must not restrict combustion
air flow. Under no circumstances is the manufactur-
70,000 AND 75,000 BTU/HR INPUT MODELS- If vent- er to be held liable for any water damage in con- edthrough an outside wall or through the root the 3" vent nection with this water heater.
piping cannot exceed a total of V0feet (110 feet if optional 4" vent piping is used), including vertical and horizontal runs The location selection must provide adequate clearances
with one 90°elbow. If more elbows are required, the venting for servicing and proper operation of the water heater. distance must be reduced 5 feet for every 90°elbow. See page
22 for vent chart. Vent piping cannot slope downward and horizontal runs A WARNING
require _/f'per five foot rise. All horizontal runs require ade- INSTALLATIONS IN AREAS WHERE FLAMMABLE LIQ- quate support at 3 V2foot intervals andvertical runs supported UIDS (VAPORS) ARE LIKELY TO BE PRESENT OR
at 5 foot intervals. STORED (GARAGES, STORAGE, AND UTILITY AREAS,
ETC): Flammable liquids (such as gasoline, solvents,
The water heaterrequires its own (separate)venting system, propane (LP) or butane, etc.), all of which emit It cannot be connected to an existing vent pipe or chimney. It flammable vapors, may be improperly stored or
must terminate to the outdoors. Whenever possible terminate used in such areas. The gas water heater ignitor or [ the vent on the leeward side of the building if vented through main burner can ignite such vapors. The resulting [
an outside wall. NOTE: Condensation maybe created, at flashback and fire can cause death or serious burns I
times, asthecombustiongasesexit thevent capand discol- to anyone in the area, as well as property damage.
If installation in such areas is your only option,]
orationofsurfaceslnproximitytotheventcapmayoccur, then the installation must be accomplished in a]
way that the ignitor and main burner flame are ele- I
vated from the floor at least 18 inches. While this
AWARNING may reduce the chances of flammable vapors from
The power vent water heater requires its own (sepa- a floor spill being ignited, gasoline and other
rate) venting system. It cannot be connected to an ex- flammable substances should never be stored or isting vent pipe or chimney. It must he terminated to used in the same room or area containing agas
the outdoors. Failure to properly install the venting sys-[ water heater or other open flame or spark produc- tern can result in asphyxiation, a fire or explosion and ing appliance.
cancause DEATH,SERIOUSBODILYINJURY,ORPROPER- i NOTE: Flammable vapors may be drawn by air currents TY DAMAGE. Ifrom other areas of the structure to the appliance.
AWARNING
The water heater comes equipped with a 7 foot power Propellants of aerosol sprays and volatile com- cord which can be used to connect to a 110/120 volt pounds, (cleaners, chlorine based chemicals, refrig-
power source if(l) local codes allow, and (2) there is a erants, etc.) in addition to being highly flammable
in many cases, will also change to corrosive
three prong receptacle available. This unit must have a hydrochloric acid when exposed to the combustion grounded outlettooperate, products of the water heater. The results can be
hazardous, and also cause product failure.
11
Page 12
Instructions for Installation (cont'd)
Locating the New Water Heater (cont'd)
_kWARNING Combustion Air and Ventilation
This water heater must not be installed directly on
carpeting. Carpeting must be protected by a metal When determining the installation location for a power vent or wood panel beneath the appliance extending water heater, snow accumulation and drifting should be con-
beyond the full width and depth of the appliance sidered in areaswhere applicable. by at least 3 inches (76.2mm) in any direction, or if
the appliance is installed in an alcove or closet, the VENTINGCLEARANCES entire floor must be covered by the panel. Failure to heed this warning may result in a fire hazard. 0" clearance for 3" (and optional 2" and 4") PVC, ABS or
CPVC Schedule 40 vent piping from combustible surfaces.
12" minimum from the ground, 9" ceiling overhangs.
•,WARNING Figure 2.
Minimum clearances between the water heater and combustible and noncombustible construction are 0" . The Power Vent outlet terminal shall terminate at least 36"
at the sides and rear, 5 inches from front of jacket to above any forced air inlet into the building located within 10 closet door, and 0" from the vent pipe. Clearance from feet. Figure 3a. the top of the jacket is 14" (12" on some models). Provide 24 inches front clearance for servicing and The Power Vent outlet terminal shall terminate at least 4 feet
adequate clearance between the jacket top and ceil- below, 4 feet horizontally from or 1 foot aboveany door,window ing for servicing the flue area. Refer to the label on or gravity air inlet into the building. Figure 3a.
the water heater adjacent to the gas control valve for all clearances. (see Figure 1). = 18" minimum from other natural draft (gravity) direct vent,
power vent or power direct vent appliance inlet and/or outlet
0" vent(s) when directly above or 135 ° to either side of ceuter
/VENTILATIONI H _ E1 ml _ ¢_-- 24" minimum from any appfiance inlet and/or outlet vents
AIR i i S_ MIN.
/ OPEN'NGsOI 0"HIN. _......_ 5" when direcdy below or 45°to either side of center line. Figure
I { I TOPVIEW I ' 3b.
_ orCtC_ET roPw_vo"_N.
WITHOU T DOOR OF CLOSET
'HAX, WITHDOOR 18" minimum in all directions from any obstruction that may
FRONTVIE_N _IN
OFDOOR interfere. Figure 3c.
I Figure 1 I A,R DUCT The location selection must provide clearances for servicing
and proper operation of the water heater. Figure 4.
_, WARNING Vent termination must not be within 4 feet of any items such
A gas water heater cannot operate properly with- as gas meters, gasvalves or other gas regulating equipment. out the correct amount of air for combustion. Do The venting system must be installed in a manner which
not install in a confined area such a closet, unless allows inspection of the installation of the venting pipes and
you provide air as shown in the "Facts to Consider joints as well asperiodic inspection after installation as
About the Location" section. Never obstruct the flow of ventilation air. If you have any doubts or required by ANSI Standards.
questions at all, call your gas company. Failure to provide the proper amount of combustion air can
result in a fire or explosion and can cause DEATH, AWARNING any
SERIOUS BODILY INJURY, OR PROPERTY Vent termination must not be within 4 feet of
DAMAGE. items such as gas meters, gas valves or other gas
u ating equ pment, reg"
AWARNING
If this water heater will be used in beauty shops, AWARNING Ibarber shops, cleaning establishments, or self-ser-
vice laundries with dry cleaning equipment, it is Failure to have required clearances between water imperative that the water heater or water heaters heater and combustible material will result in a fire
be installed so that combustion and ventilation air hazard.
be taken from outside these areas. Refer to the
"Facts to Consider About the Location" section of this manual and also the latest edition of the
National Fuel Gas Code, ANSI Z223.1, also referred to as NFPA 54 for specifics provided concerning air
required.
12
Page 13
Instructions for Installation (cont'd)
Must maintain
adequate service -_- ........ --
and maintenance /" ""
9" rain. from accessibility. "",, any overhang
- q.of Flue
[ Figure 4 ] //"_'Range of degrees
.. ./" available for vent
................ pipe installation.
Venting Through Roof- Clearances
I Figure 2 I 0" clearance for 3" (or optional 2" and 4") PVC, ABS, or
CPVC Schedule 40 piping from combustible surfaces.
The Power Vent outlet terminal shall terminate at least 18 inches above the roof surface. Figure 5.
_ ,_ The location selection must provide clearances for servic-
ing and proper operation of the water heater. Figure 4.
The venting system must be installed in a manner which
_. _48__ _ _i2, anows inspection of the installation of the venting pipes and
LESSTHAN joints aswell as periodic inspection after installation as
._" required by ANSI Stand_ds.
V_ £_ _in. 45° VENT CA_[i/90° STREETELLW/SCREEN
POWER VENT TERMINAL /f-_-.,
-- : "_ _ '_, [ Figure5 ]
2, CombustionAir andVentilation
_ for AppliancesLocatedin
RAFT (GRAVITY)
' _--_RTUc_AvLEDT, POWERVENT, Unconfined Spaces
_7 OR POWER DIRECT VENT
___. APPLIANCEINLETAND/OR Unconfined Space is aspace whose volume is not Jess than
Figure 3b I OUTLETVENT(S). 50 cubic feet per 1,000 Btu per hour of the aggregate inputJ
rating of all appliances installed in that space. Rooms com-
municating directly with the space in which the appliances are
installed, through openings not furnished with doors, are
_ vent terminal 18" to wail or other considered a part of the unconfined space
obstructionsthat may
interferewithventing. In unconfined spaces in buildings, infdtration may be ade-
-_._18" min. quate to provide air for combustion, ventilation and dilution
of flue gases. However, in buildings of tight construction (for
ventterminal example, weather stripping, heavily insulated, caulked, vapor
rn}in, barrier, etc.), additional air may need to be provided using the18"
methods described in Combustion Air and Ventilation for
Figure I cornerofbuilding Appliances Located in Confined Spaces, b.
3c
I
13
Page 14
Instructions for Installation (cont'd)
CombustionAir andVentilation 1.Whendirectlycommunicatingwiththeoutdoors,each
opening shall have a minimum free area of 1 square inch
for
AppliancesLocatedin per 4,000 BTU per hour oftotalinput rating of all equip-
ConfinedSpaces ment in the enclosure. (See Figure 7.)
Confined Space is a space whose volume is less than 50 cubic 2. When communicating with the outdoors through vertical
feet per 1,000 Btu per hour of the aggregate input rating of all ducts, each opening shall have a minimum free area of 1
appliances installed in that space, square inch per 4,000 BTU per hour of total input rating of
a. ALLAIR FROM INSIDE BUILDINGS: all equipment in the enclosure. (See Figure 8.)
(See Page 12 Figure 1, and Figure 6 below) (each er=dofattic) The confined space shall be provided with two permanent openings communicating directly with an additional
room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space.
The total input of all gas utilization equipment installed in the combined space shall be considered in making this r _ (ends _"abovefloor)
determination. Each opening shall have a minimum free [ Figure 8 J
area of one square inch per 1,000 BTU per hour of the total input rating of all gas utilization equipment in the 3. When communicating with the outdoors through horizon- confined space, but not less than 100 square inches. One tal ducts, each opening shall have a minimum free area of 1 opening shall commence within 12 inches of the top and square inch per 2,000 BTU per hour of total input rating one commencing within 12 inches of the bottom of the of all equipment in the enclosure. (See Figure 9.)
enclosure,
VENT THROUGH _ ROOF
ROOF
: i VENTTO
,[I
, I OOTOOORSI 1
OPENINGS WATER Figure 9
I _ HEATER
[ Figure6 ] >A
4. When ducts are used, they shall be of the same cross-sec- tional area as the free area of the openings to which they
connect. The minimum short side dimension of rectangular
b. ALL AIR FROM OUTDOORS: (see Figures 7-9) air ducts shall not be less than 3 inches. (See Figure 9.)
The confined space shall be provided with two permanent 5. Louvers and Grilles: In calculating free area, consideration openings, one commencing within 12 inches of the top shall be given to the blocking effect of louvers, grilles or
and one commencing within 12 inches from the bottom of screens protecting openings. Screens used shall not be the enclosure. The openings shall communicate directly, or smaller than 1/4inch mesh. If the free area through a design by ducts, with the outdoors or spaces (crawl or attic) that of Iouver or grille is known, it should be used in calculating freely communicate with the outdoors, the size opening required to provide the free area specified.
VENTILATION If the design and free area is not known, it may be assumed
(eachendofattic) VENTTHROUGH that wood louvers will be 20-25 percent free area and metal
ROOF
louvers and grilles _11 have 60-75 percent free area. Louvers and grilles shall be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation.
6. Special Conditions Created by Mechanical Exhausting or Fireplaces: Operation of exhaust fans, ventilation systems,
Figure 7 ] clothes dryers orfireplaces may create conditions requiring
special attention to avoid unsatisfactory operation of
VENTILATIONLOUVERS installed gas utilization equipment.
14
Page 15
Instructions for Installation (cont'd)
Water Piping
AWARNING 2. Look at the top cover of the water heater. The cold water
HOTTER WATER CAN SCALD: Water heaters are inlet is marked cold. Connect the cold water pipe to the
intended to produce hot water. Water heated to a coldwaterinletof the waterheater.
temperature which will satisfyclotheswashing,
dish washing, and other sanitizing needs can scald NOTE: This water heater is super insulated to minimize
and permanently injure you upon contact. Some
people are more likely to be permanently injured by heat loss from the tank. Further reduction in heat loss
hot water than others. These include the elderly, canbeaccompllshedbyinsulatingthehotwaterlines children, the infirm, or physically/mentally handi- _om thewaterheater.
capped. If anyone using hot water in your home fits into one of these groups or if there is a local code or state law requiring a certain temperature water at
the hot water tap, then you must take special pre-
cautions. In addition to using the lowest possible
temperature settingthat satisfies your hot water
needs, a means such as a mixing valve, should be used at the hot water taps used by these people or VENTTO
at the water heater. Mixing valves are available at OUTDOORS _alumbing supply or hardware stores. Follow manu-
cturers instructions for installation of the valves. COLDINLET
Before changing the factory setting on the thermo- WATERLINE
stat, read the "Temperature Regulation" section in this manual. SHUTOFF J
This water heater shall not be connected to any heating sys- tems or component(s) used with a non-potable water heating
appliance.
If a water heater is installed in a closed water supply system; __
TEMPERATURE-
such as one having a back-flow preventer, check valve, water PRESSURERELIEF meter with a check valve, etc.., in the cold water supply; VALVE
I
means shall be provided to control thermal expansion. J Contact the local utility or call Maytag Customer Service HOTOUTLET Center at 1-800-788-8899 for an authorized installer on how TOHOUSE
to control this situation.
NOTE: To protect against untimely corrosion of hot and cold water fittings, it is strongly recommended that di-elec- tric unions or couplings be installed on this water heater
when connected to copper pipe. DISCHARGEPIPE
(Donot capor plug)
The illustration shows the attachment of the water piping to PROVIDEA6" AIR
GAPBETWEENTHE
the water heater. The water heater is equipped with 3/4inch ENDOFTHE
DISCHARGEPiPE
water connections for 40,000 and Btuh models and 1 inch ANDDRAIN water connections for 70,000 and 75,000 Btuh models.
NOTE: If using coppertubing, solder tubing to an adapter
before attaching the adaptor to the cold water inlet connection. Do not solder the cold water supply line directly to the cold
water inlet. It will harm the dip tube and damage the tank.
1. Look at the top cover of the water heater. The water outlet
is marked hot. Connect the hot water pipe to the hot
water outlet on the water heater.
15
Page 16
Instructions for Installation (cont'd)
Temperature-Pressure Relief Valve
_WARNING AWARNING
At the time of manufacturethis water heater was provid- The temperature-pressure relief valve must be manu- ed with a combination temperature-pressuresrelief valve all)' operated at least once a year. Caution should be
certified by a nationally recognizedtesting laboratory that taken to ensure that (1) no one is in front of or
maintains periodic inspection of production of listed around the outlet of the temperature-pressure relief
equipment or materials, as meeting the requirements for valve discharge line, and (2) the water manually dis-
ReliefValvesand Automatic GasShutoff Devicesfor Hot
charged will not cause any bodily injury or property
Water Supply Systems, and the latest edition of ANSI damage becausethe water may be extremely hot. Z21.22 and the code requirements of ASME. If replaced, If after manually operating the valve, it fails to com- the valve mustmeet the requirementsof localcodes,but pletely reset and continues to release water, immedi-
not lessthan a combination temperature and pressure ately close the cold water inlet to the water heater, relief valve certified as meeting the requirements for follow the draining instructions, and replace the
ReliefValvesand Automatic Gas Shutoff Devicesfor Hot temperature-pressure relief valve with a new one. Water Supply Systems,ANSIZ21.22 by a nationally recog- nized testing laboratory that maintainsperiodicinspection
of productionof listed equipment or materials. The valve must be marked with a maximum set pressure
not to exceed the marked hydrostaticworking pressureof the water heater (150 Ibs./sq.in.) and a dischargecapacity
not lessthan the water heater input rate asshown on the model rating plate. (Electric heaters - watts divided by
1000x 3415 equal BTU/Hr.rate.) COLD Your localjurisdictional authority, while mandating the useof atemperature-pressurerelief valve complyingwith ANSIZ21.22 and ASME,may require a valve modeldiffer-
ent from the onefurnishedwith the water heater.
TEMPERATURE-PRES-
Compliancewith suchlocalrequirementsmustbesatisfied
/
SUREREUEFVALVE
by the installer or end user of the water heater with a /f Iocallyprescribed temperature-pressure relief valve installedin the designatedopening in the water heater in placeof the factoryfurnishedvalve. HOT For safe operation of the water heater, the relief valve must not be removed from it's designated opening or -- DISCHARGEPIPE
lugged. (Donotcaporplug)
_perature-pressure relief valve must be installed PROVIDEA6" AIR
into the fitting of the water heater designatedfor GAPBETWEENTHE
'alve. Positionthe valve downward and provide ENDOFTHEDISCHARGEPIPE
tubing so that any dischargewill exit only within 6 inches ANDDRAIN above, or at any distance below the structural floor. Be
certain that no contact is made with any live electrical part. The discharge opening must not be blocked or reducedin size under any circumstances.Excessivelength,
over 30 feet, or use of more than four elbows can cause restrictionand reducethe dischargecapacityof the valve.
No valve or other obstruction is to be placedbetween the reliefvalve and the tank. Donot connecttubing directlyto RELIEF VALVE OPENING
dischargedrain unlessa 6" air gap isprovided. To prevent bodilyinjury,hazard to life, or property damage,the relief "THISWATERHEATERISAPPROVEDWITHACOMBINATIONTEMPERATURE-
PRESSURERELIEFVALVE.FORSAFEOPERATIONOFTHEWATERHEATER, valve must be allowed to dischargewater in quantities THERELIEFVALVE(S)MUSTNOTBEREMOVEDFROMITSDESIGNATED shouldcircumstancesdemand. If the dischargepipe isnot POINTOFiNSTALLATiONORPLUGGED."
connected to a drain or other suitable means,the water YOURLOCALJURISDICTIONALAUTHORITy,WHILEMANDATINGTHEUSE flow may causeproperty damage. OFA TEMPERATURE-PRESSURERELIEFVALVECOMPLYINGWITHANSi The DischargePipe: z21.22ANDASME,MAYREQUIREAVALVEMODELDIFFERENTFROMTHE
Must notbe smaller in sizethan the outlet pipe size of ONEFURNISHEDWITHTHEWATERHEATER.
the valve, or have any reducing couplings or other COMPLIANCEWITHSUCHLOCALREQUIREMENTSMUSTBESATISFIEDBY restrictions. THEINSTALLERORENDUSEROFTHEWATERHEATERWITHALOCALLY
PRESCRIBEDTEMPERATURE-PRESSURERELIEFVALVEINSTALLEDINTHE
MUStnot beplugged or blocked. DESIGNATEDOPENINGINTHEWATERHEATER.
Must be of material listedfor hot water distribution.
SEEMANUALHEADING- "TEMPERATURE-PRESSURERELIEFVAWES"FOR
Must be installed so as to allow complete drainage of INSTALLATIONANDMAINTENANCEOFRELIEFVALVE,DISCHARGELINE
both the temperature-pressurerelief valve, and the dis- ANDOTHERSAFETYPRECAUTIONS. chargepipe.
Must terminate at an adequatedrain.
Must not have any valve between the relief valve and tank.
16
Page 17
Instructions for Installation (cont'd)
Filling the Water Heater
I If you are not familiar with electric codes and practices, or if
&CAUTION
Never use this water heater unless it is completely Ii you have any doubt in your ability to connect the wiring to
filled with water. Toprevent damage to the tank, I this water heater, obtain the service of a competent electrician the tank must be filledwith water. Water must flow or contact your local electric utility.
from the hot water faucet before turning "ON" gas I to the water heater. I
_,WARNING
To fill the water heaterwith water: WATER HEATERS EQUIPPED FOR ONE TYPE VOLT-
Close the water heater drain valve by turning the handle to AG g ONLY: This water heater is equipped for the right (clockwise). The drain valve is on the lower front 1101120 volts only. DO NOT USE THIS WATER
HEATER WITH ANY VOLTAGE OTHER THAN THE
of the water heater. ONE SHOWN ABOVE. Failure to use the correct volt-
- Open the cold water supply valve to the water heater, age can cause problems which can result in DEATH,
NOTE: The cold water supply valve must be left open SERIOUS BODILY INJURY OR PROPERTY DAMAG E. If
you have nay questions or doubts consult your
when the water heater is in use. electric company.
To insure complete filling of the tank, allow air to exit by
opening the nearest hot water faucet. Allow water to run
until a constant flow is obtained. This will let air out of the _k CAUTION water heater and the piping. If wiring from the fuse box or circuit breaker box was
aluminum for the old water heater, replace it with
Check all new water piping for leaks. Repair as needed, copper wire. If you wish to reuse the existing alu-
minum wire, have the connection at the water heater
Wiring made by a competent electrician. Contact a local elec-
trical contractor and/or the local electric utility.
USE WITH POWER CORD
The water heater comes equipped with a 7 foot power cord USE WITHOUT POWER CORD which can be used to connect to a 110/120 volt power source if,
(1) local codes allow, and (2) there is a three prong grounded If power cord cannot be used, then follow these wiring receptacle available. This unit must have a grounded outlet to instructions. operate.
7' MAXIMUM 1. Provide a way to easily shut off the electric power when
CORDLENGTH I II working on the water heater. This could be with circuit
(F a
breaker or fuse block in the entrance box or a separate dis-
_ connect switch.
2. Install and connect a circuit directly from the main fitse or circuit breaker box. This circuit must be the right size and
have its own fuse or circuit breaker.
/WIRE NUTS
water heater and junction box when the power cord is not used.
&WARNING
Do not use an extension cord. If there is not a suit- I
able receptac!e and/or local codes prohibit use of a co power cord, field wiring must be provided.
You must provide all wiring of the proper size outside of the GROUNDSCREW _"_1[/ /11 I1l[ S water heater. You must obey local codes and electric company
requirements when you install this wiring.
17
Page 18
Instructions for Installation (cont'd)
Wiring (cont'd)
USE WITHOUT POWER CORD (cont'd)
3. A standard 1/2"conduit opening has been made in the grounded, A green ground screw has been provided on the
water heater junction box for the conduit connection, water heater's junction box. Connect ground wire to this
location. For complete grounding details and all allowable
4. Use wire nuts and connect the power supply wiring to the exceptions, refer to the latest edition of the National wires inside the water heater's junction box. Electrical Code.
5. The water heater must be electrically "grounded" by the 6. Replace the wiring junction cover using the screw installer. The unit will not operate unless it is properly provided.
ACAUTION
Label all wires prior to disconnection when servic-
ing controls. Wiring errors can cause improper and dan_lerous operation, Verify proper operation after serv cing. J
18
Page 19
Instructions for Installation (cont'd)
Venting
_,WARNING _,WARNING
To insure proper venting of this gas-fired water Chemical vapor corrosion of the flue and vent sys-
heater, the correct vent pipe diameter must be uti- tem may occur if air for combustion contains certain lized. Any additions of other gas appliances on chemical vapors. Spray can propellants, cleaning sol-
vent with this water heater will adversely affect vents, refrigerator and air conditioner refrigerants,
the operation of the water heater, swimming pool chemicals, calcium and sodium chlo-
ride, waxes, bleach, and process chemicals are typi-
cal compounds which are potentially corrosive.
The combustion and ventilation air flow must not be obstructed
The power vent water heater requires its own (sepa- 3½" _.
rate) venting system. It cannot be connected to an
existing vent pipe or chimney. It must be terminated to the outdoors. Failure to properly install the vent-
ing system can result in asphyxiation, a fire or explo- sion and can cause DEATH, SERIOUS BODILY INJUR_ OR PROPERTY DAMAGE.
I I
At,WARNING ]
Obstructed or deteriorated vent systems may pre- Horizontal runs must be securelysupportedat foot inter- sent a serious health risk or asphyxiation, vals and vertical runs supported at 5 foot intervals
VENTING THROUGH AN OUTSIDE WALL
AWARNING
The vent pipe fro_heater must slope upward '/8inch per five linear feet. 75 GALLON 70,000 AND 75,000 BTU/HR, MODELS
ONLY (See rating plate for BTU/HR rating)
All vent gases must be completely vented to the outdoors of the 3" PVC, ABS or CPVC Schedule 40 vent piping:
structure (dwelling).
A 3" PVC Schedule 40-45 ° vent cap with wire screen is supplied with the water heater.
_ _ [_ Aa"PVC, ABSorCPVCScheduleeO90°streeteU;used
MIN RISE_" to connect the vent pipe to the water heater when the vent
PERFIVEFEET pipe is to be turned horizontally directly offthe blower (sup-
plied locally).
3" PVC, ABS or CPVC Schedule 40 pipe (must be sup-
plied locally).
A,WARNING 3" PVC, ABS OR CPVC
Failure to have required clearances between water SCHEDULE40- 90*
heater and combustible material will result in a fire STREETELBOW _ [ I
hazard. _- 3" PVC, ABS OR CPVC
SCHEDULE 40 PIPE VENT CAP
WITH SCREEN
AWARNING I
Be sure vent pipe is properly connected to prevent I escape of dangerous flue gases which could cause
deadly asphyxiation. [ ]
19
Page 20
Instructions for Installation (cont'd)
Venting (cont'd)
VENTING THROUGH AN OUTSIDE WALL (cont'd) * The water heater requires its own (separate) venting system.
75 GALLON 70,000 AND 75,000 BTU/HR MODELS ONLY * 4" and Y' PVC, ABS or CPVC Schedule 40 piping and fit-
tings are acceptable materials for the vent system on all 75
The water heater requires its own (separate) venting system, gallon 70,000 and 75,000 BTU/HR models.
3" PVC, ABS or CPVC Schedule 40 piping and fittings are ° It cannot be connected to existing vent piping or chimney. acceptable materials for the vent system on all 75 gallon
70,000 and 75,000 BTU/HR models. It must terminate horizontally to the outdoors.
It cannot be connected to existing vent piping or chimney.
ALL 40 AND 50 GALLON 40,000 BTU/HR MODELS
It must terminate horizontally to the outdoors. ONLY
3" PVC, ABS or CPVC Schedule 40 vent piping:
75 GALLON 70,000 AND 75,000 BTU/HR MODELS
ONLY -- OPTIONAL 4" VENT PIPING A 3" PVC Schedule 40-45 ° vent cap with wire screen is
4" PVC, ABS or CPVC Schedule 40 vent piping: supplied with the water heater.
A 3" PVC, ABS or CPVC Schedule 40-90 ° street ell; used
A wire screen to fit a 4" PVC, ABS or CPVC Schedule 40- to connect the vent pipe to the water heater when the vent
45* vent cap is supplied with the water heater, pipe is to be turned horizontally directly offthe blower (sup-
A 4" PVC, ABS or CPVC Schedule 40-45 °vent cap plied locally). (must be supplied locally). 3" PVC, ABS or CPVC Schedule 40 pipe (must be sup-
* A 3" PVC, ABS or CPVC Schedule 40 pipe, minimum plied locally).
length of 3" (must be supplied locally), to make vent con-
nection at the blower outlet.
3"PVC,ABSORCPVC
SCHEDULE L-_
A 4" to 3" PVC, ABS or CPVC Schedule 40 reducer (must 4090°EL,OWr J I I I
be supplied locally). 3" PVC,ABSORCPVC
SCHEDULE40 PIPE VENTCAP
A 4" PVC, ABS or CPVC Schedule 40-90 °street ell; used _ WITHSCREEN
to connect the vent pipe to the reducer when the vent pipe is to be turned horizontally offthe blower (supplied locally). _ I
4" PVC, ABS or CPVC Schedule 40 pipe (must be sup-
plied locally). The water heater requires its own (separate) venting
system.
4"PVC,ABSORCPVC
4"PVC,ABSORCPVC SCHEDULE40 PiPE 3" PVC, ABS or CPVC Schedule 40 piping and fittings SCHEDULE4090°/_-_
t ,, [ ] _ are acceptable materials for the vent system on all 40 and
STREETELBOW
50 gallon 40,000 BTU/HR models.
4"VENTCAP
[_4" TO3" PVC,ABSOR
CPVCREDUCER WITHSCREEN It cannot be connected to existing vent piping or
_] 3"PVC,ABSORCPVCSCHEDULE40 chimney.
PIPE(MINIMUMLENGTH3")
It must terminate horizontally to the outdoors.
t i
20
Page 21
Instructions for Installation (cont'd)
ALL 40 AND 50 GALLON 40,000 BTU/HR MODELS -- VENTING SYSTEM EXAMPLE INSTALLATIONS FOR ALL OPTIONAL 2" VENT PIPING MODELS
2" PVC, ABS or CPVC Schedule 40 vent piping: The vent piping cannot under any circumstances be run
downhill.
A wire screen to fit a 2" PVC, ABS or CPVC Schedule 40-
45° vent cap is supplied with the water heater.
A 2"PVC,ABSorCPVCSchedule40-45°ventcap
(elbow) (must be supplied locally).
A 3" PVC, ABS or CPVC Schedule 40 pipe, minimum
length of 3" (must be supplied locally), to make vent con-
nection at the blower outlet.
A 3" to 2" PVC, ABS or CPVC Schedule 40 reducer (must
be supplied locally). (_
A 2" PVC, ABS or CPVC Schedule 40-90 ° street ell; used
to connect the vent pipe to the reducer when the vent pipe is The vent piping maybe installed as follows: to be turned horizontally offthe blower (supplied locally).
Horizontal runs require aminimum 1 ,, -/s rise per five feet.
2" PVC, ABS or CPVC Schedule 40 pipe (must be sup-
plied locally). 3
ELBOW
2"PVC,ABSORCPVC EXAMPLE [_, __--'_/_1--I |[-I_
2"PVC,ABSORCPVC SCHEDULE40PIPE
SCHEDULE4_ [_
90°ELBOW I I
VENTCAP
3"TO2" PVC,ABSOR WITHSCREEN
CPVCREDUCER
_ 3"PVC,ABSORCPVC I
SCHEDULE40PIPE
(MINIMUMLENGTH3")
I I ELBOW
EXAMPLE
MIN.RISE%"
The water heater requires its own (separate) venting PERFIVEFEET
system.
2" and 3" PVC, ABS or CPVC Schedule 40 piping and fit- "-I tings are acceptable materials for the vent system on all 40 and 50 gallon 40,000 BTU/HR models. .V
It cannot be connected to existing vent piping or MIN.RISE1/,, chimney. PERFIVEFEET
It must terminate horizontally to the outdoors.
NOTE: See pages 25 to 27 for vertical venting through aroof.
21
Page 22
Instructions for Installation (cont'd)
Venting (cont'd)
VENTING THROUGH AN OUTSIDE WALL (cont'd) * Tbe totalvcrticalandhox_zout_vent mn c=mnotexceedthe
maximum length with the number of 90*elbows asspecified
/ _l_ _L_ in the tables below.If more elbows arerequired, the venting
EL3OW distance must be reduced 5 feet forevery 90*elbow:
EXAMPLEI_- _ T
/ _ MIN.RISE¼"
/ _ PERFIVEFEET 75 GALLON 70,000 AND 75,000 BTU/HR
MODELS ONLY
3" DIA.VENT NUMBER OF 90° DEG.
-- MAX. LENGTH (FT.) ELBOWS*
70 1
J 6s 2
60 3
'/_" 55 4
50 5
_,_ PERFIVEFEET
I 45 6
75 GALLON 70,000 AND 75,000 BTU/HR
75 GALLON 70,000 AND 75,000 BTU/HR MODELS MODELS ONLY--OPTIONAL 4" VENT PIPING (3" VENT) 4" DIA.VENT NUMBER OF 90° DEG.
MAX. LENGTH (FT.) ELBOWS*
Seechartin am columnformax.length. 110 1
105 2
100 3
95 4 90 5
13Y2"MII_ _ 12,,'_all_ MII_RISEVs" 85 6
_ _ _i "_ PERFIVEFEET ALL 40 AND 50 GALLON 40,000 BTU/HR
MODELS ONLY.
3" DIA.VENT NUMBER OF 90° DEG.
MAX. LENGTH (FT.) ELBOWS*
115 1
40 and 50 GALLON 40,000 BTU/HR MODELS (3" VENT) 110 2
105 3 100 4
Seechartinnextcolumnformax.length. 95 5
90 6
ALL 40 AND 50 GALLON 40,000 BTU/HR MODELS --
OPTIONAL 2" VENT PIPING
7
PERFOOT 2" DIA.VENT NUMBER OF 90° DEG,
MAX. LENGTH (FT.) ELBOWS*
50 1
I I 45 2
40 3
35 4 30 5
25 6
NOTE: Two 45*elbows are equivalent to one 90°elbow.
One 90°elbow equals 5 feet of equivalent vent length.
22
Page 23
Instructions for Installation (cont'd)
_95" MAX. _-_ 75 GALLON 70,000 AND 75,000 BTU/HR
i _J_l_ MODELS ONLY
MIN.RISEYs" 3" DIA.VENT NUMBER OF 900 DEG.
PERFIVEFEET
2o' t I ONEELBOW MAX. LENGTH (FT.) ELBOWS*(inside bldg.)
EXAMPLE
(EXAMPLE) 60 1
__=__ 55 2
5O 3
3"VENTPIPE 45 4
4O 5
40GALLON 35 6
40,000BTU/HR
I [ MODELEXAMPLE
75 GALLON 70,000 AND 75,000 BTU/HR
Minimum vent length for _ 40,000 Bl_LJ/HR input rood- MODELS ONLY--OPTIONAL 4" VENT PIPING els is 4 feet and 16 inches for all other models. 4" DIA.VENT NUMBER OF 90° DEG.
MAX. LENGTH (FT.) ELBOWS*
100 1
VENTING THROUGH AN OUTSIDE WALL WITH LOW 95 2 GROUND CLEARANCE 90 3
When the vent piping cannot pass through an outside wall 85 4
at a height greater than or equal to 12" above the ground 80 5
(or above snow accumulation level), then the installation 75 6
can be modified as shown below.
_._ ALL 40 AND 50 GALLON 40,000 BTU/HR MODELS
3" DIA.VENT NUMBER OF 90° DEG.
_/, MAX. LENGTH (FT.) ELBOWS*(inside bid9) ""_ 105 1
,oo
95 3 9O 4
t Bs 5
_MULATION LEVEL ALL 40 AND 50 GALLON 40,000 BTU/HR MODELS --
OPTIONAL 2" VENT PIPING
2" DIA.VENT NUMBER OF 90° DEG.
MAX. LENGTH (FT.) ELBOWS*(inside bldg)
40 1 35 2 30 3
Refer to the tables in the next column for maximum vent 25 4
lengths for low ground clearance installations. All installa- 20 5 fions assume the use of two additional 90°elbows and the 15 6
standard 45°vent cap with screen outside of the exterior wall.
NOTE: Two 45°elbows are equivalent to one 90°elbow. One 90°elbow equals 5 feet of equivalent vent length.
23
Page 24
Instructions for Installation (cont'd)
Venting (cont'd)
CEMENTING PVC, ABS OR CPVC PIPEAND FI'I-rlNGS CUTTING OPENING THROUGH AN OUTSIDE WALL
AND COLLAR INSTALLATION
Read and observe all safety information printed on primer,
cleaner, and cement containers. After reading the manual and you have determined the loca-
tion of the opening in the wall, (using the drawing below), cut
_i DANGER j a 21/2"hole for 2" vent piping, 31/{' hole for 3"vent piping or
Primer, cleaner, and c_xtremely flammable. [ a 4'/2" hole for 4" vent piping through an exterior wall.
They are harmful or fatal if swallowed. The vapors are]
harmful. They may irritate eyes and skin andcan be / NOTE: When determining location of the opening in the absorbed through the skin. [ outside wall allow for the l/s" rise per five feet that has taken
] place in the horizontal run.
A PRECAUTIONS
J
Always store prim_ments in cool, dry,/
well ventilated places. Do not store them near heat,| _. OFFLUE............. _ _"__:_l_._
sparks, or flames. Keep containers closed. Use them in [ well ventilated areas. Wear impervious clothing while I 13½_MIN.40&50GAL72_MIN'7SGAL' _-_ PERMN.FIvERISEVs'FEET
handling. Do not smoke, eat, or drink while handling.I
Wash thoroughly after handling and before eating. Wear eye protection when handling. If swallowed, drink water, do not induce vomiting, and call a physician or poison
control cen_erimmediately. If inhaled, c_etfresh air and seek medical attention if il/feelings persist.In caseof eye
and skin contact,immediately flushwith plenty of water for 15 minutes and seek medical attention itirritation
persists.KEEPOUT OR REACHOFCHILDREN. 4oGAL.-60"
50GAL.-59½"
75 GAL- 63½"
All primers, cleaners, and cements must meet all local codes l]
and applicable standards of the American Society For Testing [-_ Materials Standards.
Before using primers, cleaners, and cements, stir or shake, making sure contents are liquid. Do not use if found to be lumpy or jel2*/-like.
1. Cut pipe ends squarely removing all burrs and dirt.
2. Dry fit pipe and fittings to be connected for proper fit. The 3" (or optional 2" or 4") PVC, ABS, or CPVC Schedule
3. Clean pipe and fitting with a primer/cleaner. 40 vent pipe can be run from the water heater through the 4, Apply a thin coat of cement to fitting, avoiding puddling wall or from the wall to the water heater, whichever is most
inside, convenient. The vent pipe must extend a minimum of 11/2"
through the exterior wall. Extending the vent cap as far as
5, Apply a liberal coat of cement to pipe leaving no voids.
possible from the surface of the exterior wall will help mini-
6, QUICKLY assemble parts while cement is fluid! If you mize discoloration of the wall in this area which may be
wait too long, re-coat pipes, caused by the flue gases. Note that the inside collar must be
7. Push pipe completely into socket of fitting, turning as it slipped over the vent piping before locating the pipe through
goes until it bottoms, the wall. Before securing the inside and outside collars to the
8. Hold pipe and fitting together for 30 seconds. Then care- wall, use a silicone sealer between pipe and opening to insure fully clean off excess with a cloth, Allow connections a suf- a water and air tight seal.
ficient time to cure before disturbing.
9. Remember that vent pipes must be adequately and securely supported.
APPROXIMATE SETFING TIME FOR 2½" TO 4" PIPE JOINTS
MOVEMENT COMPLETE
OF JOINT SET
90°F to 150°F ¾ hr. 8 hrs.
50°F to 90°F 1 hr. 15 hrs.
0°F to 50°F 1½ hr. 18 hrs.
24
Page 25
Instructions for Installation (cont'd)
INSTALLATIONSHOWING USEOF PVC,ABSORCPVCPIPE If the optional 4" vent piping is to be used (70,000 BTU/I-Ir.
and higher models only), the 4" street elbow, 4" to 3"reducer and 3" (minimum) section of 3" PVC, ABS or CPVC pipe
EXTERIOR
SJUCO.E_ / _ WAU. must be suppfied locally. The 3" (minimum) section of 3"
sra_t__ / PVC, ABS or CPVC pipe must be attached to the blower
,,x, using 3 sheet metal screws.
_ MIIq.u_'I'_ISIOIq
, THROUGH
EXTIERIO RWALL
se=_v SCREW VENTING THROUGH A ROOF
' ALL.OOELS
3" PVC, ABSor CPVC Schedule 40 vent piping:
j/ A 3" PVC Schedule 40-45* vent cap with wire screen is
SCR_--
COLLAR supplied with the water heater.
$1U¢
S_LE_ / BEDOWNWARDPoSmONEO 3" PVC, ABS, or CPVC Schedule 40 piping'" and fittings
are acceptable materials for the vent system on all models
CONNECTINGPVC, ABS OR CPVCPIPEVENT TO BLOWER and must be supplied locally.
If making an immediate horizontal run of vent offthe blow- 75 GALLON 70,000 AND 75,000 BTU/HR -- oPTIONAL
er, a 3"PVC, ABS orCPVC Schedule 40 (supplied locally) 4" VENT PIPING elbow is required. Place the elbow in the required direction
on the blower and using 3 sheet metal screws, attach the 4" PVC, ABS or CPVC Schedule 40 vent piping:
elbow.
A wire screen to fit a 4" PVC, ABS or CPVC Schedule 40-
_-/_. . 45°vent cap is supplied with the water heater.
SEALWITH [ ]] ] / * A 3"PVC, ABS or CPVC Schedule 40 pipe, minimum
RTVSEALANT _ I _ _'_ length of 3" (must be supplied locally), to make vent con-
nection at the blower outlet.
_"/ _ _ "__ -. A 4"to 3" PVC, ABS or CPVC Schedule 40 reducer (must
/
_" ] ]_(_1 ] _ be supplied locally).
[ 4" and 3" PVC, ABS, or CPVC Schedule 40 piping and
I
fittings are acceptable materials for the vent system on all
If there is to be a vertical run of vent from the blower, the 3" 75 gallon 70,000 and 75,000 BTU/HR models and must be PVC, ABS or CPVC pipe must be attached to the blower supplied locally.
using 3 sheet metal screws.
4"PVC,ABSORCPVC
SCHEDULE40 PIPE
SEALWITH / _ 4"CPvcTOREDUCER3"PVC,ABSOR
RTVSEALANT / "_
(MINIMUMLENGTH3")
If the optional 2"vent piping is to used (40,000 BTU/HR. models only), the 2" street elbow, 3" to 2" reducer and 3"
(minimum) section of 3" PVC, ABS or CPVC pipe must be supplied locally.The 3" (minimum) section of 3" PVC, ABS or CPVC pipe must be attached to the blower using 3 sheet
metal screws.
25
Page 26
Instructions for Installation (cont'd)
Venting (cont'd)
ALL 40 AND 50 GALLON 40,000 BTU/HR MODELS -- SO'STREETELL '_
II
OPTIONAL 2" VENT PIPING 4s'VENTCAp. SEALAROUND i'
FLASHING s
2" PVC, ABS or CPVC Schedule 40 vent piping:
A wire screen to fit a 2" PVC, ABS or CPVC Schedule 40- VEtoCAPMUST
BE POSITIONED
45° vent cap is supplied with the water heater. DOWmVA_Dlr MIN. MAINTAINUSTED
___ /; Sf I',
A 3" PVC, ABS or CPVC Schedule 40 pipe, minimum II
length of 3" (must be supplied locally), to make vent con- ,'_'_"_ 45"ELBOW necfion at the blower outlet.
A 3" to 2" PVC, ABS or CPVC Schedule 40 reducer (must _;_'/
be supplied locally).
SUPPORT LATERALS
I 2" and 3" PVC, ABS, or CPVC Schedule 40 piping and ,/ MIN,EVERY3'h"
fittings areacceptable materials for the vent system on all POSITIONFIRESTOP 40 and 50 gallon 40,000 BTU/HR models and must be
supplied locally.
MAINTAIN USTED
2" PVC, ABS OR CPVC CLEARANCE
EXHAUST VERTICAL
U SCHEDULE 40 PIPE VENT
3" TO 2" PVC, ABS OR CERTIFIED TOTALVERTICAL
CPVC REDUCER w, TER HEATER AND HORIZONTAL RUNS
__ - LOW,
-'-'1 3" PVC, ABS OR CPVC
SCHEDULE 40 PIPE (MINIMUM LENGTH 3")
I I
The water heater requires its own (separate) venting system. The total vertical and horizontalvent runs cannot exceed the
m_odmumlength with the number of 90* elbows as specified
It cannot be connected to existing vent piping or chimney, in the tables below andon page 27. If more elbows are required, the venting distance mustbe reduced 5feet for
It must terminate vertically to the outdoors every 90°elbow:
Typical installation(s) shown in next column.
75 GALLON 70,000 AND 75°000 BTU/HR
Refer to "Cementing PVC, ABS or CPVC Pipe and MODELS ONLY
Fittings" on page 24 and "Connecting Vent to Blower" on
page25. 3" DIA.VENT NUMBER OF 90° DEG.
MAX. LENGTH {FT.) ELBOWS*
70 1 65 2 6O 3 55 4
50 5 45 6
26
Page 27
Instructions for Installation (cont'd)
Gas Piping
VENTING THROUGH A ROOF (cont'd) AWARNING
Make sure the gas supplied is the same type listed
75 GALLON 70,000 AND 75,000 BTU/HR on the model rating plate. The inlet gas pressure
MODELS ONLY--OPTIONAL 4" VENT PIPING must not exceed 10.5 in. water column (2.6 kPa) for
natural gas or 13 in. water column (3.2 kPa) for
4" DIA.VENT NUMBER OF 90° DEG. Propane (L.R) gas. The minimum inlet gas pressure
MAX. LENGTH (FT.) ELBOWS* listed on the model rating plate is for the purpose
110 1 of input adjustment. 105 2
100 3
9s 4 f WARN,NG 1
90 5 IIf thegas control_cted to pressures I
85 6 lexceeding 1/2pound per square inch (3.5kPa), the I
Idamage to the gas control valve could result in a l
Ifire or explosion from leakin 9 gas. I
ALL 40 AND 50 GALLON 40,000 BTU/HR MODELS ONLY
3" DIA.VENT NUMBER OF 90° DEG. [ AWARNING
MAX. LENGTH (FT.) ELBOWS* _lf the maingas line shutoff serving all gas appli-
115 1 lances is used, also turn "off" the gas at each appli-
110 2 lance. Leave all gas appliances shut off until the
105 3 [water heater installation is complete. 100 4
95 5
90 6 A gas fine of sufficient size must be run to the water heater.
Consult the latest edition of National Fuel Gas Code ANSI
ALL40 AND 50 GALLON 40,000 BTU/HR MODELS -- Z223.1, also referred to as NFPA 54 and the gas company
OPTIONAL 2" VENT PIPING concerning pipe size.
2" DIA.VENT NUMBER OF 90° DEG. There must be:
MAX. LENGTH (FT.) ELBOWS* A readily accessible manual shut offvalve in the gas supply
50 1 line serving the water heater, and
45 2 A drip leg (sediment trap) ahead of the gas control valve to 40 3 heIp prevent dirt and foreign materials from entering the
35 4 gas control valve.
30 5 A flexible gas connector or a ground joint union between the 25 6 shutoffvalve and control valve to permit servicing of the unit.
NOTE: Two 45* elbows are equivalent to one 90*elbow. Be sure to check all the gas piping for leaks before lighting the
One 90*elbow equals 5 feet of equivalent vent length, water heater. Use a soapy water solution, not a match or open
flame. Rinse off soapy solution and wipe dry.
Standard Models are for installation up to 3,300 feet above sea level.
High Altitude Models are for installation from 3,300 to 5,500 feet above sea level.
Ifa standard model is installed above 3,300 feet or a high alti- tude model is installed above 5,500 feet, the input rating must
be reduced at the rate of 4 percent for each 1,000 feet above sea level. Contact your local gas utility for further information.
27
Page 28
Instructions for Installation (cont'd)
Gas Piping (cont'd)
AWARNING ] Connecting the gas piping to the gas control valve of'the
The appliance and_ction must be leak 11 water heater can be accomplished by either of the two meth- tested before placing the appliance in operation. ] odsshown.
AWARNING GAS PIPING WITH
FLEXIBLE CONNECTOR
The appliance and its individual shutoff valve
must be disconnected from the gas supply piping ["]GAS SUPPLY PIPING system during any pressure testing of the gas sys-
tem at test pressures in excess of 1/2 pound per
square inch (3.SkPa). MANUALSHUTOFF
The appliance must be isolated from the gas sup- VALVE
ply piping system by closing its individual manual
shutoff valve during any pressure testing of the _'_ FLEXIBLEGASCONNECTOR
gas supply piping system at test pressures equal or less than 1/2 pound per square inch (3.SkPa). LABELEDwITHANsIASsTANDARDsCOMPLYING
GROUNDJOINT LOOP
AWARNING ] UNION (OPTIONAL)
Use pipe joint common tape marked as [
| being resistant to the action of petroleum [Propane[
[(LP')]gases" [ DR,P LEG coGNATRSO1
(SEDIMENT VALVE
3"MIN. TRAP)
SEDIMENT TRAP _ ICAP
A sediment trap shall be installed as close to the inlet of the water heater as practical at the time of water heater installa-
tion. The sediment trap shall be either a tee fitting with a capped nipple in the bottom outlet or other device recognized GAS PIPING WITH ALL BLACK IRON PIPE TO
as an effective sediment trap. Ifa tee fitting is used, it shall be GAS CONTROL
installed in conformance with one of the methods ofinstalla- GASSUPPLYPIPING tion shown.
MANUAL
SHUTOFF
&WARNING VALVE
Contaminant's in the gas lines may cause improper operation of the gas control valve that may result
in fire or explosion. Before attaching the gas line I
Ibe sure that all 9as pipe is clean on the inside. To I [I
GROUNDJOINT
trap any dirt or torelgn material in the gas supply
UNION
line, a drip leg (sometimes called a sediment trap) must be incorporated in the piping. The orip leg
must be readily accessible. Install in accordance BLACKPIPE__,, I=lJ GAS
l(_ :-_li_ CONTROL
with the "Gas Piping" section. Refer to the latest _ VALVE
edition of the National Fuel Gas Code, ANSI Z223.1,
_J_ DRIPLEG
also referred to as NFPA 54. EDIMENT
3" MIN. i TRAP)
cAP
28
Page 29
Instructions for Installation (cont'd)
Installation Checklist CHECK FOR LEAKS
BEFOREOPERATING:
Be sure to check all your gas pipes for leaks before operating
Check the gas lines for leaks, your water heater. Use a soapywater solution, not a match or
a. Use a soapy water solution. DO NOT test for gas leaks open flame. Check the factory gas fittings after the main burner
using a match or open flame, is turned "ON". Use a soapy water solution for this, too.
b. Brush the soapywater solution on all gas pipes, joints
and fittings.
c. Check for bubbling soap. This means you have a leak.
Turn "OFF" gas and make the necessary repairs. VENTPIPE
OUTDOORS _
d. Recheck for leaks.
e. Rinse off soapy solution and wipe dry.
Is the new temperature-pressure relief valve properly "_ SHUTOFF
_ _ - VAI_VI_"_VALVE COlD
installed and piped to an adequate drain? See £_..k ..,_,,_- _.u "Temperature-Pressure Relief Valve" section.
Are the cold and hot water lines connected to the water o_
C TEMPERATURE-
heater correctly? See "Water Piping" instructions in the f _:_, 0_ PRESSURERELIEF"Instructions for Installation" section. VALVE
HOT
I-_-DISCHARG E PIPE
Is the water heater completely filled with water? See (Donotcapor "Filling" instructions in the "Instructions for Installation" plug)
section.
GAS SUPPLY
Will a water leak damage anything? See the "Locating the //1 New Water Heater" section.
Is there proper clearance between the water heater and SHUTOFFVALVE anything that might catch fire? See the "Locating the New
water Heater" section.
TEE
Do you have adequate ventilation so that the water heater DRIPLEG
(Sediment trap)
will operate properly? See "Combustion Air and Ventilation" PIPECAP in the "Instructions for Installation" section.
Is the draft hood vent piping properly secured? See "Venting" instructions in the "Instructions for Installation"
section.
Is there proper clearance between the vent pipe and any- thing that might catch on fire? See "Venting" instructions _ _,
in the "Instructions for Installation" section. _'_°
lam/r _oo_ SE_ m_l_R
Is the vent pipe properly sloped and does the vent termi- "_"°_,_",,'2_TJ_ _ _ _,_,_-_ _,_-_0
. _. , 150 wx; _ wc
hate outdoors? See Ventmg mstructmns in the ....
"Instructions for Installation" section,
AUTOMATICSTORAGEWATERHEATER
ELECTRICALRATING:VOLTS115/HZ60/AMPS2
Do you need to call your gas company to check the gas
pipe and its hookup? _._...................
iso_edunder _en_ toS%_tendU*dt_ Inc
MODEL RATING PLATE
29
Page 30
Instructions for Operation
This water heater is equipped with an electrically operated
venting system and electronic control. For the burner to come BLOWERMOTOR _ ---_ VENTINGMANUAL
on, the water heater thermostat must call for heat. Then the N,_w" _ _ _,f RESETSWITCH system will begin sequencing, each section proving itself
before gas is allowed to flow to the burner.
_ DRAFTHOOD
BEFORE THE WATER HEATER WILL OPERATE:
L,
1. The control system must be connected to a grounded
ON/OFF_WITr'H.--..-.. _,,,,-,-AIRPRESSURE
110/120 volt power supply. The control system has an _ _t_...___,_ 'cH overall rating of 2 amps. The water heater must be secure-
ly and adequately grounded in accordance with local codes
and with the latest edition of the National Electrical Code U.__I
ANSI/NFPA 70.
2. The ON/OFF toggle switch, located on the control box OR
above the thermostat must be in the "ON" position for the BLOWERMOTOR electrical control system to operate allowing the gas pot- _ J
tion to operate (ignite burner). VENTINGMANUAL
RESETSWITCH
3. The gas control knob located on the thermostat must be turned to the "ON" position for the gas to be able to flow. DRAFTHOOD
4. The venting manual reset switch must be in the closed //f/ position. See "Venting Manual Reset Switch" in the
"Troubleshooting" section.
5. There is a non-reset-table hi-limit switch in the thermo- ON/OFFSWITCH AIRPRESSURE
stat, which must be good (closed) for the thermostat to be XkN_ i_.._ ,_,,_.c,.,,-,-,-u
operated. See "High Temperature Shut Off System" in the "Troubleshooting" section.
OPERATION
/ GASCONTROL
When the thermostat calls for heat, gas is allowed to flow to /_"-)_:d_'<-_ KNOB
a (N/O) pressure switch dosing it. An electrical circuit is then made to the blower, turning it on. When the blower has achieved sufficient venting, the air pressure switch will close. A 120 volt circuit will be completed through the venting
DIAGNOSTICF _ _ _ 12BYGASVALVE
manual reset switch and on to the 120 volt gas valve. The 120 INDICATOR
volt gas valve will open allowing gas to flow to the burner. /_ /BURNER
The hot surface ignitor will establish a main burner flame. _ /
GASTHERMOSTAT
IGNITOR
3O
Page 31
Instructions for Operation (cont'd)
Operating
_,WARNING
BEFORE OPERATING [PROPANE (L.P.) GAS WATER HEATERS]: Propane (L.P.) gas is heavier than air.
Should there be a leak in the system, the gas will I
settle near the ground. Basements, crawl spaces, skirted areas under manufactured (mobile) homes
(even when ventilated), closets and areas below
ground level will serve as pockets for the accumula- tion of this gas. Before attempting to operate the water heater or turning on a nearby electrical light
switch, be absolutely sure there is no accumulated _ gas in the area. Search for odor of gas by sniffing at I Figure 10 I
ground level in the vicinity of the appliance. If odor is detected, follow steps indicatedat "For Your Safety" on the cover page of this manual then leave the premises.
Operating instructions are located on front of the water heater, above or to one side of the gas control valve.
_WARNING
AN ODORANT ISADDED TO THE GAS USED
BYTHIS WATER HEATER.
FOR YOUR SAFETY IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use any IFigure 111
phone in your building,
L J
Immediately call your gas supplier from a neigh- bor's phone, Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire
department.
AWARNING
DO NOT force the gas control knob. Never use a
tool such as a lever, wrench or pliers. Do not hit or damage the knob. A damaged knob may result in
an explosion and serious injury. If you have prob- INNERDOOR
lem turning the knob, call the gas supplier imme-
diately.
7D5OgARLLON DOgTJRR
31
Page 32
Instructions for Operation (cont'd)
Operating label on the water heater as it appears above the thermostat
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING I
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A.Thisappliancedoesnothavea pilot.Itisequippedwith If you cannotreachyourgas supplier,callthe fire
an ignitiondevicewhichautomaticallylightsthe bum- depertmenL er.Do not try to lightthe burner by hand. C. Useonlyyourhandto pushin orturnthegascontrol
B. BEFOREOPERATINGsmellall aroundthe appliance knob.Neverusetools.If the knobwillnot pushinor
areaforgas.Besuretosmellnexttothe floorbecause turn by hand,don'ttryto repairit,calls qualifiedear- somegasisheavierthanairandwillsettleonthefloor, vicetechnician.Forceor attemptedrepairmayresult WHATTODOIF YOUSMELLGAS ina fireorexplosion.
Donottry to lightanyappliance. D. Do not usethis applianceif any parthas beenunder
Do not touchany electric switch; do not use any water.Immediatelycall a qualifiedservicetechnician phoneinyourbuilding, to inspecttheapplianceandto replaceanypartofthe
Immediatelycallyourgassupplierfroma neighbor's controlsystemand any gascontrolwhich hasbeen phone.Followthegassupplier'sinstructions, underwater.
OPERATING INSTRUCTIONSl
1. STOP! Read the safety information above on this 5. At armslengthaway,turngas controlknobcounter- label, clockwisetothe full "ON" position.(Figure11, page
2. SetON/OFFswitchlever on controlboxto "OFF". 31)
3. Set the thermostat to lowest setting by turning - " .....
therwater temperature dial counter-clockwise,
TOP VIEW OF
( _ _,) to its lowesttemperaturesetting.DO NOT GASCONTROL _._._J/
FORCE. Turngas control knobclockwise to "OFF" position.(Figure10, page31)
4. Wait five (5) minutes to clear out any gas. If you WARNING Do not use gas control knob to regu-
then smell gas, STOP! Follow "B" in the safety late gas flow.
informationabove on this label. If you don't smell 6. At arms lengthaway, set the thermostatto desired
gas, goto thenext step. setting.The mark(A) HOTindicativeof approximate
12g°Fis_aferred startingpoint.Somelocal lawsmay require a lower starting point. If hotter water is
desired,seeinstructionmanualand"warning"below.
7. SetON/OFFswitchleveroncontrol boxto "ON".
WARNING
Hotterwater increasesthe risk ofscaldinjury.Beforechangingtemperaturesettingsee instructionmanual.
TO TURN OFF GAS TO APPLIANCE
1. Set ONOFF switch leveron controlbox to "OFF". 3.Turn gascontrolknob clockwise(_ ) to "OFF"
2. Set the thermostat to lowest setting by turning position.(Figure10,page31). the watertemperaturedialcounter-clockwiea( ,c "-_) to itslowesttemperaturesetting.DO NOT FORCE,
WARNING
This waterheater isequippedfor one type gasonly.Checkthe rating plate nearthe gascontrol valve for the correct gas. Do not usethis water heater with any gas other than the one listed onthe reting plate. Failure to usethe correctgas can cause problemswhich can resultin death, seriousbodilyiniurvor prooertvdam-
age. If you have anyquestionsor doubtsconsultyour gassupplier or gas utility.
Insulationblanketor other insulationwrapping, applied externalto the jacket, may result in unsafeopera-
tion ofthe waterheater.For additional informabon,sea instruction manual.
32
Page 33
Instructions for Operation (cont'd)
Temperature Regulation
Due to the nature of the typical gas water heater, the water tem- Turn the water temperature dial clockwise ( _ ) to perature in certain situations may vary up to 30°F higher or increase the temperature, or counterclockwise ( _ ) to lower at the point of use such as, bathtubs, showers, sink, etc. decrease the temperature.
This means that when the temperature adjustment dial is set at the mark approximating 120°F, the actual water tempera-
ture at any hot water tap could be as high as 150*F or aslow
as90T
Any water heater's intended purpose is to heat water. Hot water is needed for cleaning, (bodies, dishes, clothing). Hot VERYHOT
water will present a scald hazard. Depending on the time ele-
ment, and the people involved (normal adults, children, tod- dlers, elderly, infirm, etc.) scalding may occur at different uu
temperatures. HOT- Is a thermostat setting of approximate 120OF
which will supply hot water at the most
_,WARNING economical temperatures. The temperature
adjustment knob can be turned lower than
HOTTER WATER CAN SCALD: Water heaters are "HOT"ifdesired. intended to produce hot water. Water heated to a
temperature which will satisfy clothes washing, dish washing, and other sanitizing needs can scald and A- Is a thermostat setting of approximately 130°F.
permanently injure you upon contact. Some people are more likely to be permanently injured by hot
water than others. These include the elderly, children, B- Is a thermostat setting of approximately 140°F.
the infirm, or physically/mentally handicapped. If anyone using hot water in your home fits into one of C- Is a thermostat setting of approximately 150°E
these _roups or if there is a local code or state law
requiring a certain temperature water at the hot water tap, then you must take special precautions. In VERYHOT-Is a thermostat setting of approximately 160°E addition to using the lowest possible temperature It is recommended that the dial be set lower
setting that satisfies your hot water needs, a means such as a mixing valve, should be used at the hot whenever possible. water taps used by these people or at the water
heater. Mixing valves are available at plumbing sup- NOTE: Water temperature range of 1200-140°F recom- ply or hardware stores. Follow manufacturers instruc- mendedby mostdishwashermanufacturers.
tions for installation of the valves. Before changing the factory setting on the thermostat, read the "Temperature Regulation" section in this manual.
AWARNING
Never allow small children to us'_ea hot water tap, AWARNING or to draw their own bath water. Never leave a Should overheating occur or the gas supply fail to
child or handicapped person unattended in a bath- shut off, turn "OFF" the manual gas control valve to tub or shower, the appliance.
The thermostat of this water heater has been factory set at its lowest position, to reduce the risk of scald injur_. It isadjustable
and must be reset to the desired temperature setting. The mark ( ) HOT indicative of approximately 120°F is preferred start-
ing point. Some states have a requirement for a lower setting. If you need hotter water, follow directions for temperature adjust- ment, but beware of the warnings in this section.
33
Page 34
Serviceand Maintenance
Venting System Inspection Burner Inspection
At least once a year a visual inspection should be made of the venting system. You should look for: A,WARNING
Obstructionswhich could causeimproper venting. The Flood damage to a water heater may not be readily
visible or immediately detectible. However, over a
combustion and ventilation air flow must not be obstructed, period of time a flooded water heater will create
Damage or deterioration which could causeimproper dangerous conditions which can cause DEATH, SERI- venting orleakageofcombustionproducts. OUS BODILY INJURY, OR PROPERTY DAMAGE.
Contact the Maytag dealer from whom the appli-
Rusted flakes around top of water heater, ance was purchased or call Maytag Customer Service
at 1-800-788-8899 for an authorized servicer to replace a flooded water heater. Do not attempt to
AWARNING repair the unit! It must be replaced!
Chemical vapor corrosion of the flue and vent sys-
tem may occur if air for combustion contains certain At least once a year a visual inspection should be made of
chemical vapors. Spray can propellants, cleaning sol- the main burner and pilot burner. The drawing is for your vents, refrigerator and air conditioner refrigerants,
swimming pool chemicals, calcium and sodium chlo- reference. ride, waxes, bleach, and process chemicals are typi-
cal compounds which are potentially corrosive. You should check for sooting which is not normal and will
impair proper combustion.
_WARNING pre-
Obstructed or deteriorated vent systems may sent a serious health risk or asphyxiation.
AWARNING connected toBe sure the vent piping is properly AWARNING
prevent escape of dangerous flue gasses wh ch Sootbuild-up indicatesa problem that requirescorrection
could cause deadly asphyxiation, beforefurther use.Turn"OFF" gasto waterheater and leave
"OFF" until repairs are made,becausefailure to correct the causeof the sootingcanresultinafire.
_WARNING
If after inspection of the vent system you found Burner Cleaning
sooting or deterioration, something is wrong. Call
the local gas utility or Maytag Customer Service at NOTE: Burner assembly must be handled carefully to
1-800-788-8899 for an authorized servicer to correct avoid damaging the hot surface ignitor. the problem and clean or replace the flue and vent-
in_ before resuming operation of the water heater. In the event your burner needs cleaning, use the following Fadure to make corrections can result in a fire, or instructions: explosion causing DEATH, SERIOUS BODILY INJUR_
OR PROPERTYDAMAGE.
If inspection of the burner shows that cleaning is required, turn the gas control knob clockwise ( f'_ ) to the "OFF"
Oiling Instructions posi on.
Oil motor every 12 months with 6 drops of SAE 20 motor oil Loose deposits on or around the burner can be removed by
(Fasco motor only), carefially using the hose of a vacuum cleaner inserted through
the access door of the water heater. If the burner needs to be removed for additional cleaning, call the local gas utility or
qualified service agent to remove and clean the burner and cor- rect the problem that required the burner to be cleaned.
34
Page 35
Serviceand Maintenance(cont'd)
L.RGas Control Valve & Burner Draining
Assembly Replacement
Information Re water heater should hedrained if being shut down duting
freezing temperatures. Also periodic draining and cleaning of sediment from the tank may be necessary.
_WARNING
PROPANE(L.R) GAS CONTROL VALVE AND BURNER Turn the gascontrol knob tothe "OFF" position.
ASSEMBLYREPLACEMENTINFORMATION. CLOSE the cold water inlet valve to the water heater.
For Propane (L.P.)Gas Models Only: OPEN a nearby hot water faucet and leave open to allow
Your water heater is equipped with a Propane (L.R) for draining. gas control valve and a main burner assembly with
left hand threads for the following fittings and their Connect a hoseto the drain valveand terminate to an ade- connections, quate drain.
OPEN the water heater drain valve to allow for tank
The connection between the manifold and the
gas control valve (A to B) are left hand threads, draining.
NOTE: If the water heater is going to be shut down and
The connection between the main burner orifice and the manifold (C to D) are left hand threads, drained for an extended period, the drain valve should be
left open with hose connected allowing water to terminate
For ordering these replacementparts, please refer to to an adequate drain.
the "Repair Parts List" section of this manual. Close the drain valve.
Follow instructions in the "Filling The Water Heater" section.
Follow the operating instructions in the "Operation" section to restart the water heater.
_'q_"-'- c
35
Page 36
Serviceand Maintenance (cont'd)
Temperature-Pressure Relief Drain Valve Washer Valve Operation Replacement
The temperature-pressure relief valve must be manually oper- NOTE: For replacement, use a 1%f,x ly,, x Vf' thick washer
ated at least once a year. available at your nearest hardware store. For ordering
replacement washers, refe_ to the "Repair Parts List" section.
1. Turn "OFF" gas supply to water heater.
2. Follow "Draining" instructions.
3. Turning counter clockwise, remove the hex cap below the screw handle.
4. Remove the washer and put the new one in place.
5. Screw the handle and cap assembly back into the drain
DISCHARGEPIPE Valve and retighten using a wrench. DO NOT OVER
TIGHTEN.
Failure to install and maintain a new properly listed tempera-
6. Follow instructions in the "Filling The Water Heater"
ture-pressure refiefvalve will release the manufacturer from
section.
any claim which might result from excessive temperature or 7. Check for leaks. pressure. 8. Follow the fighting instructions in the "Instructions for
Operation" section to restart the water heater.
AWARNING
If the temperature-pressure relief valve on the _
appliance weeps or discharges periodically, this
may be due to thermal expansion. Your water HANDLEAND
CAPASSEMBLY
heater may have a check valve installed in the
water line or a water meter with a check valve. Call _" WASHER
Mayta_ Customer Service at 1-800-788-8899 for an
authorized servicer for further information. Do not
plug the temperature-pressure relief valve.
Housekeeping
AWARNING
When checking the temperature-pressure relief Vacuum around base of water heater for dust, dirt, and lint on
valve operation, make sure that (1) no one is in a regular basls. front of or around the outlet of the temperature- Combustible materials such as clothing, cleaning materials, or
pressure relief valve discharge line, and (2)that the water manually discharged will not cause any flammable liquids, etc. must not be placed against or adjacent property damage because the water may be to the water heater.
extremely hot. To insure sufficient ventilation and combustion air supply, If after manually operating the valve, it fails to proper clearances from the water heater must be maintained
completely reset and continues to release water, immediately close the cold water inlet to the water at all times. heater, follow the draining instructions, and replace the temperature-pressure relief valve with
a new one. Service
Before calling for repair service, read the Start Up Conditions and Operational Conditions found in the Troubleshooting
Guide of this manual.
If a condition persists or you are uncertain about the opera-
tion of the water heater, let a qualified person check it out.
Call Maytag Customer Service at 1-800-788-8899 for an authorized servicer.
36
Page 37
Troubleshooting
Start Up Conditions
CONDENSATION THERMAL EXPANSION
Whenever the water heater is filled with cold water, a certain Water supply systems may, because of high line pressure, fre-
amount of condensatlon will form while the burner is on. A quent cut-offs, the effects of water hammer and others, have
water heater may appear to be leaking when in fact the water installed devices such as pressure reducing valves, check is condensation. This usually happens when: valves, back flow preventers, etc. to control these types of
problems. When these devices are not equipped with an inter-
- When a new water heater is filled with cold water for nal by-pass, and no other measures are taken, the devices the first time. cause the water system to be closed. As water is heated, it
When gas burns and water vapor is produced in water expands (thermal expansion) and closed systems do not allow heaters, particularly high efficiency models where flue for the expansion of heated water.
temperatures are lower. The water within the water heater tank expands as it is heated
When you use large amounts of hot water in a short and increases the pressure of the water system. If the relievlng time and the refill water is very cold. point of the water heater's temperature-pressure relief valve is
reached, the valve will relieve the excess pressure. The tern-
Moisture from the products of combustion condense on the peratm'e-pressure relief valve is not intended for the con- cooler tank surfaces and form drops of water which may fall stant relief of thermal expansion. This is an unacceptable
onto the burner or other hot surfaces to produce a "sizzling" or condition and must be corrected. "frying" noise.
It is recommended that any devices installed which could create
Because of the suddenness and amount of water, condensation a closed system have a by-pass and/or the system have an
water may be diagnosed as a "tank leak". After the water in expansion tank to relieve the pressure built by thermal expan-
the tank warms up (about 1-2 hours), the condition should sion in the water system. Expansion tanks are available for disappear, ordering through Maytag Customer Service (1-800-788-8899).
Contact the local plumbing inspector, water supplier, and/or
Do not assume the water heater is leaking until there has been call Maytag Customer Service at 1-800-788-8899 for an
enough time for the water in the tank to warm up. authorized servicer for assistance in controlling these situations. An undersized water heater will cause more condensation. The water heater must be sized properly to meet the family's
demands for hot water including dishwashers, washing STRANGESOUNDS
machines and shower heads.
Possible noises due to expansion and contraction of some
Excessive condensation may be noticed during the winter and metal parts during periods of heat-up and cool-down do not early spring months when incoming water temperatures are at represent harmfifl or dangerous conditions.
their lowest.
Condensation causes sizzling and popping with the burner
Good venting is essential for a gas fired water heater to oper- area during heating and cooling periods and should be consid- ate properly aswell as to carry away products of combustion ered normal. See "Condensation" section. and water vapor.
SMOKE/ODOR
It is not uncommon to experience a small amount of smoke and odor during the initial start-up. This is due to burning off
of oil from metal parts, and will disappear in a short while.
37
Page 38
Troubleshooting(cont'd)
Operational Conditions
SMELLY WATER HIGH TEMPERATURE SHUT OFF SYSTEM
In each glassllned water heater there is installed at least one This water heater is equipped with an automatic gas shut off
anode rod (see parts section) for corrosion protection of the system. The high temperature shut offis built into the gas
tank. Certain water conditions will cause a reaction between control valve. This system shuts offthe gas supply to the this rod and the water. The most common complaint associat- water heater burners when high water temperatures are pre-
ed with the anode rod is one of a "rotten egg smell". This sent. It is non-resettable. If the high temperature shut off odor is derived from hydrogen sulfide gas dissolved in the activates, the gas control valve must be replaced. If this were
water. The smeU is the result of four factors which must all be to occur, turn "OFF" the entire gas supply to the water heater.
present for the odor to develop: Call Maytag Customer Service at 1-800-788-8899 for an
authorized servicer.
a. a concentration of sulfate in the supply water. b. tittle or no dissolved oxygen in the water.
_,WARNING
I
c. a sulfate reducing bacteria within the water heater. [
(This harmless bacteria is non-toxic to humans.) Should overheating occur or the gas supply fail to I
shut off, turn "OFF n the manual gas control valve to
d. an excess of active hydrogen in the tank. This is caused the appliance. ]
by the corrosion protective action of the anode.
Smelly water may be eliminated or reduced in some water
heater models by replacing the anode(s) with one of less active VENTING MANUAL RESET SWITCH material, and then chlorinatlng the water heater tank and all
hot water lines. Call Maytag Customer Service at 1-800-788- There is a venting manual reset switch located on the draft
8899 for an authorized servicer for further information con- hood. If the venting manual reset switch is activated, it will
cerning an Anode Replacement Kit #66001068 and this not reset itself. Before resetting this venting manual reset
Chlorination Treatment. switch, check for flue blockage and propriety of the venting
system. To reset the venting manual reset switch, press the red
If the smelly water persists after the anode replacement and reset button. chlorination treatment, we can only suggest that continuous chlorination and faltering conditioning equipment be consid- ered to eliminate the water problem. VENTINGMANUAL
VENTINGMANUAL RESETSWITCH
RESETSWITCH BLOWE|
Do not remove the anode leaving the tank unprotected. By _ /MOTOI doing so, all warranty on the water heater tankis voided. {_"--'_ .)_ /f-"_ f
"AIR" IN HOT WATER FAUCETS
_,WARNING __k-_ oRI
HYDROGEN GAS: Hydrogen gas can be produced in I
a hot water system that has not been used for a I
long period of time (generally two weeks or more). Hydrogen gas is extremely flammable and explo-I
sive. To prevent the possibility of injury under these I conditions, we recommend the hot water faucet be
opened for several minutes at the kitchen sink
before any electrical appliances which are connect- DRAFTHOOD
ed to the hot water system are used (such as a dish- washer or washing machine). If hydrogen gas is pre-
sent, there will probably be an unusual sound simi-
lar to air escaping through the pipe as the hot
water faucet is opened. There must be no smoking
or open flame near the faucet at the time it isopen.
38
Page 39
Troubleshooting (cont'd)
Operational Conditions (cont'd)
NOT ENOUGH OR NO HOT WATER WATER IS TOO HOT
1. Check the manual gas shut offvalve to be sure it is open. 1. The temperature adjustment dial may be set too high. See the
"Temperature Adjustment" section.
2. If the diagnostic indicator on the front of the thermostat is NOTE: A period of tlme is necessary after an adjustment blinking, the control must be manually reset by cycling the has been made for the water temperature to reach the new
control system. To do this, turn the electrical power supply temperature setting. offend then on.
2. If lower temperature settings will not lower the water temper-
3. The gas control knob must be tamed to the "ON" position.
ature, call Maytag Customer Service (1-800-788-8899) for an authorized servicer.
4. The ON/OFF switch on the control box must be "ON'.
5. The temperature adjustment dial may be set too low. See the "Temperature Regnlafion" section. _kWARNING
Due to the nature of the typical gas water heater,
6. The gascompanycancheckthegasinput to seeif it iscorrect, the water temperature in certain situations may be
hotter than the thermostat setting.
An underfired water heater will not heat water as quickly. Short, frequent draws of hot water - especially with
very cold incoming water - can shock the thermo-
7. Look for leakingoropen hot water faucets.Make sureall are stat into brief operation resulting in hotter and hot-
closed, ter layers of water closer to the top of the tank.
Changes in hot water usage patterns or raisinc_the
8. The cold water inlet temperature may be colder during the temperature differential between the cut-on ot the
thermostat and the cold water temperature will
winter months. It will take longer to heat the water and usually eliminate the problem.
seem flEe less hot water.
9. If you cannot find what iswrong, call Maytag Customer
Service (1-800-788-8899 for an authorized servicer.
39
Page 40
Troubleshooting (cont'd)
Leakage Checkpoints
Use this guide to check a "Leaking" water heater. Many sus- [ _ CAUTION ] pected "Leakers" are not leaking tanks. Often the source of _|Read this manual first. Then before checking the 11
the water can be found and corrected. /water heater make sure the gas supply has been I
[turned "OFF", and never turn the gas uON" before I
If you arenot thoroughly familiar with your localgascodes [ the tank is completely full of water, j
your water heater, and safety practices, contact your local gas
utility or call Maytag Customer Service at 1-800-788-8899 [ A CAUTION '] for an authorized servicer to check the water heater. /Never use this water heater unless it is completely I
/filled with water. Toprevent damage to the tank, I |the tank must be filledwith water. Water must flow I
/from the hot water faucet before turning "ON" gas] [ to the water heater. ]
O Water the draft hood is water which has con-
at
vapor
densed out of the combustion products. This is caused by a problem in the vent. Call Maytag Customer Service
at 1-800-788-8899 for an authorized servicer.
O *Condensation be seen on pipes in humid weather
may
or pipe connections may be leaking.
O'The primary anode rod fitting may be leaking.
O Small amounts of water from relief
temperature-pressure valve may be due to thermal expansion or high water pressure in your area.
O* The relief Valve be at
leaking
temperature-pressure
may
the tank fitting.
_ Water from a drain valve may be due to the valve opened
slightly.
O'The drain valve be the tank
leakingmay
at
fitting.
Combustion products contain water vapor which can condense on the cooler surfaces of the tank. Droplets
form and drip into the fire or run on the floor. This is common at the time of startup after installation and when incoming water is cold.
Water in the heater bottom the floor be
water or on
may
from condensation, loose connections, or the relief valve. DO NOT replace the water heater until a flail inspection
of all possible water sources is made and necessary cor- rective steps taken. Leakage from other appliances, water lines, or ground seepage should also be checked.
*NOTE: To check where threaded portion enters tank, insert cotton swab between jacket opening and fitting. If cotton is wet, follow "Draining" instructions in the
"Service and Maintenance" section and then remove fit-
ring. Put pipe dope or teflon tape on the threads and replace. Then follow "Filling the Water Heater" instruc-
u
tions in the Instructions for Installation section.
4O
Page 41
Troubleshooting (cont'd)
A, WARNING I AWARNING
This troubleshooting guide has been supplied J /Label all wiring before disconnecting any wiring;
for use by qualified service personnel who have I |to ensure correct reconnection. Failure to follow
a complete understanding of both electricity /this instruction could cause improper and possible and gas. |dangerous operation, resulting in DEATH, SERIOUS
|BODILY INJURY, OR PROPERTYDAMAGE.
THERMOSTAT AND GAS SUPPLY CHECK
No ................ Is gas being supplied to the Yes
thermostat?
l
I I
[Turn "ON" gas supply. J {Is gas cock knob turned "ON"? {
I I
' Yes
{ {
[T_ogascock_ohto_ON,_.....No.....
T
Is thermostat calling for heat? Run (hot) water from heater and turn I
ad)ustment knob higher. Check usmg a manometer at thermostat
pressure tap.
Yes
1
Is there a minimum gas pressure 4" W.C. for naturalgas or 10"
W.C. for propane (L.P.) gas?
[ - I
Call gas company to increase ................ No ............. ;
gas pressure. Yes
GO TO ELECTRICAL SYS- ,_
TEM CHECK SECTION
41
Page 42
Troubleshooting (cont'd)
Diagram for "Electrical System Check" on pages 43 and 44.
NATURAL GAS 4_ W.C. MIN.
PROPANE (LP) GAS 10_ W.C. MIN.
MANIFOLD
42
Page 43
Troubleshooting (cont'd)
ELECTRICAL SYSTEM CHECK AWARNING
(Use diagram on page 42) Label all wiring before disconnecting any wiring;
to ensure correct reconnection. Failure to follow this instruction could cause improper and possible
dangerous operation, resulting in DEATH, SERIOUS
BODILY INJURY, OR PROPERTY DAMAGE.
Visually check that all compo-
No ................. nents are wired correctly accord- Yes
; ing to wiring diagram on unit.
I I I
Correct by wiring according to Thermostat is calling for heat.
diagram. " .................. (run cold water)
J
Yes
Go to "Thermostat and Gas _,_.....
Supply Check" section. No .........
Does power cord or power
wiring have 110/120 volts avail-
[ ................... able (receptacle and/or junction
l box) with grounded connector?
r i
fSupplyl10,120volts.t_.....No........:
k i
Yes
[Turn"ON". _'_ ................. No .............. q Is on/off switch "ON"?
I
Yes
"ON"?Isdiagnostic indicator light .q_................. No ................ blinking?ISdiagnostic indicator light
n
I
No
i -- Yes Yes
[ Replace control. I
Turn power "OFF" and back "ON".
I
Doesthehotsurfacet Istherea"SVt
ignitor glow after power - No -_'_ voltage between - No "- I control. is turned"ON"? I1 andI2?
I
Check flame sensor. I_ [ i Yes YesDoes burner light - I _ I
IMake sure it is placed in _'-/ then go out? f"*"_
flame,
I
{ , , [ Replace hot surface ignitor assembly. [
Yes No
Replace hot surface igmtor assembly. ,_--- [ Is blower running? Yes
No
i
continued on nextpage continued on nextpage
43
Page 44
Troubleshooting (cont'd)
continuedj%m previous page
I
Yes
ground. No - ground. - No '-'_ Replace control.
I i
Yes Yes
] Check at #2 for l15V to
_ No ....... ]ground.
Replace blower. Replace/correct wiring.
Yes
Replace Hi-fimit switch.
| Check at #8 for l15V to
No, ""l ground.
Replaceair _-- Check 1/4"WC pres- _ Remove venting I [pressure switch. If OK sure at line to air -,_- If OK "| system restrictions. Yes
pressure switch.
,r........ No ........ Is burner "ON"?
,,
', I
'_ Yes
Replace thermostat.
All systems operational.
44
Page 45
Notes
45
Page 46
Repair Parts List
2__3 _PVC ABS or CPVC Items for all_J other models supplied locally
_Or _40 and 50 Gallon models
, 28 __@
27
10 1112_1
2s_lk
24"Q_
20
23 29
21 17
22 30
16
r
46
Page 47
Repair Parts List (cont'd)
MAYTAG GAS WATER HEATERS MODEL NUMBERS:
HJ640NOVET 40 Gallon Natural Gas HJ640POVET2 40 Gallon Propane (L.R) Gas
HJ640POVET 40 Gallon Propane (L.R) Gas HJ650NOVET 50 Gallon Natural Gas HJ640NOVET2 40 Gallon Natural Gas
MODEL NUMBERS
KEY HJ640NOVET HJ640POVET HJ640NOVET2 HJ64OPOVET2 HJ650NOVET NO. PART DESCRIPTION PART NUMBERS
1 Vent Cap w/Screen (PVC) 66001255 66001255 66001255 66001255 66001255
2 Wall Collar 66001262 66001262 66001262 66001262 66001262
3 Schedule 40 Vent Pipe .....
4 Schedule 40 90° Elbow .....
5 Vent-Blower Adapter (75Gal.) .....
6 Blower (75Gal,) .....
7 Blower Gasket (75 Gal.) .....
8 Ventinq Manual Reset Switch 66001367 66001367 66001367 66001367 66001367
9 Draft Hood Assembly (75 Gal.) .....
9 Blower/Draft Hood Ass'y(40 & 50 Gal.) 66001366 66001366 66001366 66001366 66001366
10 Dip Tube 66001307 66001307 66001307 66001307 66001306 11 Anode Rod 66001189 66001189 66001189 66001189 66001189 12 Temperature-Pressure Relief Valve 66001079 66001079 66001216 66001216 66001079
13 Drain Valve 66001016 66001016 66001181 66001181 66001016
14 Drain Valve Washer
(_½2"x 'Y_" x VB"thick) * 66001021 66001021 66001021 66001021 66001021
15 Inner Door 66001029 66001029 66001029 66001029 66001029
16 Hot Surface Iqnition Assembly 66001299 66001299 66001299 66001299 66001299 17 Burner Assembly (Nat.) 66001027 -- 66001027 -- 66001027
17 Burner Assembly (L.P.) -- 66001027 -- 66001027 -- 18 Orifice (Natural) Standard 66001025 -- 66001025 -- 66001025
Drill Size #_3 #_ #_1
18 Orifice (Natural) High Altitude 66001035 -- 66001035 -- 66001035
Drill Size #36 #36 #36
18 Orifice (Propane-L.P.) Standard -- 66001172 -- 66001172 --
Drill Size #50 #50
18 Orifice (Propane-L.P.) High Altitude -- 66001041 -- 66001041 --
Drill Size #51 #51
19 Manifold (Nat.) 66001386 -- 66001319 -- 66001319 19 Manifold (L.R) -- 66001387 -- 66001318 --
20 Gas Control Valve (Nat.) 66001345 -- 66001081 -- 66001345 20 Gas Control Valve (L.P.) -- 66001346 -- 66001296 -- 21 Thermostat Cover 66001302 66001302 66001302 66001302 66001302
22 Manifold Cover 66001190 66001190 66001190 66001190 66001190 23 Air Pressure Switch Cover 66001258 66001258 66001258 66001258 66001258 24 On/Off Switch 66001247 66001247 66001247 66001247 66001247 25 Air Pressure Switch 66001369 66001369 66001369 66001369 66001368 26 Power Cord 66001372 66001372 66001372 66001372 66001372 27 Flue Baffle 66001370 66001370 66001370 66001370 66001371
28 Baffle Adapter Collar 66001187 66001187 66001187 66001187 66001187 29 Drain Pan See Page 8
30 Water Heater Stand 66001243 I 66001243 I 66001243 I 66001243 I 66001243
# Manual 66001156
*Also available at most hardware stores. The model number of this Gas Water Heater will be found
on the model rating plate located near the gas control valve.
Now that you have purchased this Gas Water Heater, should a need ever exist for repairparrs or service, simply call Maytag When ordering repair parts, always give the foUowing
Customer Service at 1-800-788-8899 for an authorized servicer, information: Be sure to provide pertinent facts when yon call. Model Number
Serial Number
THIS IS A REPAIR PARTS LIST, NOT A PACKING Part Number LIST. Part Description
47
Page 48
Repair Parts List
2__ _PVC, ABS OR CPVC Items for all
_J other models supplied locally
_r_
o 40 and 50 Gallon models
27
11
1 10
2s_
24'_
"--d--
23 29
21 17
22 30
16
or
48
Page 49
Repair Parts List (cont'd)
MAYTAG GAS WATER HEATERS MODEL NUMBERS:
HJ650POVET S0 Gallon Propane (L.R) Gas HJ675NRVETZ 75 Gallon Natural Gas
HJ650NOVET2 50 Gallon Natural Gas HJ675PRVETZ 75 Gallon Propane (L.P.) Gas
HJ650POVET2 50 GallonPropane (L.R) Gas
MODEL NUMBERS
KEY HJ650POVET HJ650NOVET2 HJ650POVET2 HJ675NRVETZ HJ675PRVETZ
NO. PARTDESCRIPTION PARTNUMBERS
1 Vent Cap w/Screen (PVC) 66001255 66001255 66001255 66001255 66001255
2 Wall Collar 66001262 66001262 66001262 66001262 66001262
3 Schedule 40 Vent Pipe .....
4 Schedule 40 90° Elbow .....
5 Vent-Blower Adapter (75Gal.) -- -- -- 66001403 66001403
6 Blower (75Gal.) -- -- -- 66001402 66001402 7 Blower Gasket (75 Gal.) -- -- -- 66001291 66001291
8 Ventinq Manual Reset Switch 66001367 66001367 66001367 66001342 66001342 9 Draft Hood Assembly (75 Gal.) -- -- -- 66001401 66001401 9 Blower/Draft Hood Ass'y(40 & 50Gal. 66001366 66001366 66001366 -- --
10 Dip Tube 66001306 66001306 66001306 66001306** 66001306** 11 Anode Rod 66001189 66001189 66001189 66001189 66001189
12 Temperature-Pressure Relief Valve 66001079 66001216 66001216 66001216 66001216 13 Drain Valve 66001016 66001181 66001181 66001181 66001181
14 Drain Valve Washer
('A2" x Wd' x _" thick)* 66001021 66001021 66001021 66001021 66001021
15 Inner Door 66001029 66001029 66001029 66001146 66001146 16 Hot Surface Ignition Assembly 66001299 66001299 66001299 66001299 66001299
17 Burner Assembly (Nat.) -- 66001027 -- 66001185 -- 17 Burner Assembly (L.P.) 66001027 -- 66001027 -- 66001185
18 Orifice (Natural) Standard -- 66001025 -- 66001169 --
Drill Size #33 #23
18 Orifice (Natural) High Altitude -- 66001035 -- 66001168 --
Drill Size #36 #27
18 Orifice (Propane-L.P.) Standard 66001172 -- 66001172 -- 66001174
Drill Size #50 #50 #42
18 Orifice (Propane-L.P.) High Altitude 66001041 -- 66001041 -- 66001177
Drill Size #51 #51 #43
19 Manifold (Nat.) -- 66001297 -- 66001283 --
19 Manifold (LP.) 66001318 -- 66001298 -- 66001349 20 Gas Control Valve (Nat.) -- 66001081 -- 66001081 --
20 Gas Control Valve (L.P.) 66001346 -- 66001296 -- 66001296
21 Thermostat Cover 66001302 66001302 66001302 66001302 66001302 22 Manifold Cover 66001190 66001190 66001190 66001200 66001200 23 Air Pressure Switch Cover 66001258 66001258 66001258 66001258 66001258 24 On/Off Switch 66001247 66001247 66001247 66001247 66001247 25 Air Pressure Switch 66001368 66001368 66001368 66001294 66001294 26 Power Cord 66001372 66001372 66001372 66001372 66001372 27 Flue Baffle 66001371 66001371 66001371 66001404 66001404
28 Baffle Adapter Collar 66001187 66001187 66001187 66001195 66001195 29 Drain Pan See Paqe 8
30 Water Heater Stand 66001243 t 66001243 I 66001243 I -- I --
# Manual 66001156
*Also available at most hardware stores. **Requires adaptor 66001271 The model number of this Gas Water Heater will be found
on the model rating plate located near the gas control valve.
Now that you have purchased this Gas Water Heater, should a need ever exist for repair parts or service, simply call Maytag When ordering repair parts, always give the following
Customer Service at 1-800-788-8899 for an authorized servicer, information: Be sure to provide pertinent factswhen you call. Model Number
Serial Number
THIS 1S A REPAIR PARTS LIST, NOT A PACKING Part Nmnber LIST. Part Description
49
Page 50
Repair Parts List (cont'd)
MAYTAG GAS WATER HEATERS
MAYTAG/STATE MAYTAG/STATE
PART NUMBER CONVERSION KEY PARTNUMBER CONVERSION KEY
MAYTAG STATE MAYTAG STATE
66001011 9001609 66001262 9001993 66001012 9001608 66001271 9002284 66001013 ETC2X 66001283 9002461 66001014 ETC5X 66001291 9002508 66001016 9002402 66001294 9002511
66001021 9001584 66001296 9002515 66001025 0230120 66001297 9002516 66001027 9002411 66001298 9002517 66001029 9000281 66001299 9002518 66001035 0230141 66001302 9002524
66001041 0230224 66001306 9002546 66001068 9001453 66001307 9002547
66001079 9000071 66001318 9002598 66001105 9002769 66001319 9002599 66001146 9000369 66001342 9002678 66001156 0002919050-0 66001345 9002751 66001168 0230209 66001346 9002752 66001169 0230212 66001349 9002979 66001172 0230225 66001366 9003081 66001174 0230247 66001367 9003082
66001177 0230260 66001368 9003089 66001181 9000058 66001369 9003090
66001185 9000349 66001370 9003093 66001187 9000275 66001371 9003094 66001189 9000279 66001372 9003095 66001190 9000358 66001386 9003137 66001200 9000454 66001387 9003138 66001216 9000728 66001401 9003153 66001243 9001422 66001402 9003152 66001247 9001773 66001403 9003154
66001255 9001957 66001404 9003157 66001258 9001971
50
Page 51
Notes
51
Page 52
Warranty
FULL ONE YEAR WARRANTY
For One Year from the date of Original Retail Purchase, any part which fails in normal home use will be repaired or replaced free of charge.
If a leak occurs in the Tank, a new water heater of the closest capacity and quality then available, will be replaced free of charge.
The warranty of the replacement is the balance of the original water heater's Warranty.
LIMITED PARTS WARRANTY
After the First year and through the Sixth Year from the date of Original Retail Purchase, any Parts which fail due to a defect in materials or workmanship, will be replaced or repaired free of charge for the part itself, with the owner
paying all other costs, including labor, mileage and transportation. If the water heater is subjected to commercial, institutional, industrial or non-resldential use, the above warranty cov-
erage for parts that are proved to be defective in material or workmanship is effective for one year from the date of the Original Retail Purchase.
The warranty of the replacement is the balance of the original water heater's Warranty, or twelve months from the date of the part(s) purchase, whichever comes first.
Blower fan and assembly are warrantied for five years. The warranty is limited to the original owner of the water heater.
LIMITED TANK WARRANTY AGAINST LEAKS
After the First Year and through the Sixth Year from the date of Original Retail Purchase, if a leak occurs in the Tank, a new water heater of the closest capacity and quality then available, will be replaced free of charge for the
water heater, with the owner paying all other costs, including labor, mileage and transportation. If the water heater is subjected to commercial, institutional, industrial or non-residential use, the above warranty cov-
erage for tanks that are proved to be defective in material or workmanship is effective for two years from the date of the Original Retail Purchase.
The warranty of the replacement is the balance of the original water heater's Warranty. Please note: The Full and Limited Warranty applies only while this water heater is used in the United States of Ametica.
The warranty is limited to the original owner of the water heater.
TO RECEIVE WARRANTY SERVICE
To locate an authorized service company in your area contact the Maytag dealer from whom your appliance was pur- chased; or call Maytag Customer Service at the number listed below. Should you not receive satisfactory warranty
service, please call or write:
Maytag Customer Service
P.O. Box 2370 Cleveland, TN 37320-2370
U.S.A. 1-800-788-8899
When contacting Maytag Customer Service be sureto provide the Model and Serial Number of your appliance, The Name and Address of the Dealer from whom you purchased the appliance and the Date of Purchase.
MAYTAG WATER HEATERS ARE MANUFACTURED AND THIS WARRANTY PROVIDED BY
STATE INDUSTRIES, INC., ASHLAND CITY, TN. MAYTAG IS A TRADEMARK OF MAYTAG COR- PORATION AND IS USED UNDER LICENSE TO STATE INDUSTRIES, INC.
11-01 66001156
0002919050-0
Loading...