![](/html/93/9312/931288df1acfd98602f348786ae591aad6bda17d36e0a3bb082f9936863b5099/bg1.png)
Room Air Conditioners for Double-Hung Windows & Thru the wall installation
Acondicionadores de aire ambientales para ventanas de guillotina y empotrados en la pared
Climatiseurs - Installaton dans un mur ou une fen_tre a guillotine
For Future Reference !i I
Write down the model and serial numbers I
The model and serial numbers can be found on the i
side of the cabinet near the control panel. Use
these numbers in any correspondence or service
calls concerning your air conditioner.
/
Para referencia futura
Escriba los numeros del modelo y de la serie
Puede encontrar los n(imeros de modelo y de serie en el
costado de la rejilla del frente decorativo cerca del panel de
control. Use estos nQmeros en cualquier correspondencia o
Ilamada de servicio con relaci6n a su acondicionador de aire.
Pour r_f_rence ult_rieure
Inscrivez les numeros de modele et de serie
Les num6ros de module et de s6rie se trouvent sur le c6t6 de la
grille ddcorative avant, pros du panneau de commande. Utilisez
ces numdros Iors de toute correspondance ou appel au service
apr_s-vente ayant trait _ votre climatiseur.
Model No., Modelo No., N° de modele
Serial No., Numero de serie, N° de serie
Date of Purchase, Fecha de la compra, Date d'achat
For additional questions please call:
1-866-MAYTAG- 1
or e-maih
customerservice@maytagair, com
Keep these instructions for future reference
![](/html/93/9312/931288df1acfd98602f348786ae591aad6bda17d36e0a3bb082f9936863b5099/bg2.png)
Important Safety Instructions°°°°°°°°°°°°°°°°°°°°°°°°
RECOMMENDEDCIRCUIT
WIRESIZES
(As installed per building code) :
PROTECTORSIZE WIREGAUGE
15 AMP #14 MINIMUM
20 AMP #12 MINIMUM
30 AMP #10 MINIMUM
©©
125V 250V
15A 20A
©©
250V 250V
15A 30A
Electrical Shock Hazard
A
• Plug unit only into grounded electrical outlet.
• Do not use an extension cord or plug adapter with this unit.
• Do not operate unit with decorative front or filter removed.
• Failure to follow these precautions could result in electrical shock, fire or
personal injury.
• If the air conditioner has a serial plate rating of 115 volts and greater than 7.5
amps it must have its own fuse or circuit breaker, and no other device or unit
should be operated on that fuse or circuit breaker. If the air conditioner has a
serial plate rating of 230 volts it must have its own fuse or circuit breaker, and
no other device or unit should be operated on that fuse or circuit breaker.
• We recommend that a qualified electrician install unit in accordance with the
National Electrical Code and local codes and ordinances.
• Do not operate this air conditioner without proper time delay circuit
protection. Refer to serial plate for proper power supply requirements.
• Use copper conductors of correct wire gauge and protector size only.
• Do not alter cord or plug end. Do not remove warning label on cord.
Important Grounding Requirements
Three- )rong grounding plug.
Do not a ter pug enc.
@Grounded three-prong wall receptacle
Single outlet grounding wall receptacle
• Air conditioner has a three-prong grounding plug on the power supply cord,
which must be plugged into a properly grounded three-prong wall receptacle
for your protection against possible shock hazard. For models up to and
including 7.5 amperes use a grounding type wall receptacle to match the
cord plug.
• For models above 7.5 amperes use a single outlet grounding type wall
receptacle to match the cord plug.
A
Additional Safety Precautions
• Do not cut, alter or remove any of the expanded polystyrene (white foam)
inside this air conditioner.
• Do not store or use gasoline or other flammable vapors and liquids in the
vicinity of this or any other appliance. The fumes can create a fire hazard or
explosion.
• Do not introduce objects in the air discharge area. This could cause
permanent damage to your unit.
• Do not pour liquids on the air conditioner as this could cause a
malfunction. Use a damp cloth for cleaning your unit.
• Avoid using strong solvents to clean the air conditioner.
• Clean the air conditioner filter every two weeks to avoid overheating caused
by air obstruction. Do not operate without filter.
• Do not obstruct the air intake area of your air conditioner, as this could
cause overheating, thus activating the units security switch and shutting off
the unit
• Do not block air circulation to outside louvers of cabinet.
• Do not block air flow inside with blinds, curtains, or furniture, or outside
with shrubs, enclosures, or other buildings.
• Do not run the air conditioner with an outside protective cover in place.
This could result in mechanical damage within the air conditioner.
2
![](/html/93/9312/931288df1acfd98602f348786ae591aad6bda17d36e0a3bb082f9936863b5099/bg3.png)
Installation°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°
Window Requirements:
This air conditioner is factory prepared for installation in standard
double-hung windows with actual opening width of 26 7/8" to 41
5/8" and clear, vertical opening of 15 5/8" minimum from bottom
of sash to sill. Unit can be installed in 23 7/8" wide window, if
cabinet side seals are removed.
Tools Needed
Screwdrivers Ratchet or Driver with 1/4" socket
Carpenter's Level Tape Measure
Window Installation
Decorative Front Removal
1. Remove the 3/8" phillips screws on either side of the cabinet
2. Gently pull forward while grasping both sides of the decorative front.
_ ake sure unit is unplugged before removing the
decorative front.
Removing the Chassis
I, Remove the two (2) shipping screws from the rear bottom side of the
cabinet. These shipping screws may be discarded.
Fastener Identification
Installation Parts Kit contents:
Item Description
O 1" wood screw
_!_ 5/8" wood screw
O
4
Actual size
(_Cabinet (_ 3/8" phillips screw
C) Decorative Front
2, Remove the two (2) antitheft screws from the bottom front sides of
the cabinet. RETAIN THESE SCREWS, they will be replaced later ill
the installation.
3, Slide the chassis out of the cabinet by grasping the base pall handle
and pulling forward while bracing the top bar.
_ ake sure unit is unplugged before removing chassis
from cabinet.
Filler Panel Frame Installation
I, Slide the filler panel frame onto the air conditioner cabinet using the
tracks on the top bar and bottom bar of the unit. Slide the frame as close
to the air conditioner as possible so that the curtain locks into place.
2, Gently pull the frame out until it is the correct length for
your application.
Use caution when working around exposed sharp edges
of the cabinet and sharp coils to avoid injury or torn
clothing.
3
1_ Shipping Screws (_Chassis
C)Cabinet i_Base pan handle
(_ Anti-theft screws
(_Top Bar (_Bottom Bar
(_ Filler Panel Frame (_Cabinet
1_ Filler Panel Locking Edge
![](/html/93/9312/931288df1acfd98602f348786ae591aad6bda17d36e0a3bb082f9936863b5099/bg4.png)
Installation°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°
Window Installation (co.t.)
1 •
Open window, by raising lower window sash, and mark
the center of window sill. Carefully place cabinet in
window and align center hole on the bottom bar with the
center mark on the window sill.
2•
Close lower window sash until it touches behind the top
bar. (Do not release your grip on the cabinet until the
lower window sash is ill its final position).
C) Window sill (_) 1" Wood Screw
(_) Bottom Bar
Side View
3•
Attach the cabinet to the window sill by driving one 1" long
wood screw through the bottom bar into the window sill.
Be sure cabinet maintains an downward pitch. Air
conditioner should slant slightly downward on the
outside as shown by 1/2 a bubble off on a carpenter's
level. This outward pitch prevents water from entering the
room.
Securing the Filler Panels
4. Slide filler panels outward until they touch window sash
tracks.
5•
Secure top of filler panels by driving a 5/8" wood screw
through each top mounting hole into window sash.
C) Carpenter's Level
C) Window sash
(_ Filler Panel
.....0
0 5/8" wood screw
C) Window sill
®
6•
Secure bottom of filler panels by driving a 5/8" wood
screw into window sill through each filler panel tab.
7. Install chassis into cabinet.
_ Do not obstruct the air intake area of your air
conditioner, as this could cause overheating, thus
activating the units security switch and shutting off
the unit. Do not block aiflow inside with blinds,
curtains, or furniture. Do not block airflow outside
with shrubs, enclosures, or other buildings.
Installing the Chassis into the Cabinet
_1. Slide the chassis into the cabinet.
2 • Replace the two antitheft screws at the bottom front sides
of cabinet.
3•
To replace the decorative front, line up the top tabs and
and sides, and gently press into position. Reattach the
screws on both sides of the decorative front. Make sure
the power cord aligns with the power cord slot on the
bottom of the decorative front. Make sure the decorative
front is secure before reconnecting the plug and operating
the unit.
®
(_ Foam Seal
(_ Lower sash
(_ Filler panel
(_ Molding C)Chassis
® Window Sill (_) Dec front
(_ Anti-Theft screw
4. Cut plastic foam seal to width of window and install
between upper and lower window sash.
5. Use latex or silicone sealant (not supplied) to fill any
minor openings.
_ Do not drill a hole in the bottom pan. Unit is
designed to operate with approximately 1/2"
of water in bottom pan.
4
![](/html/93/9312/931288df1acfd98602f348786ae591aad6bda17d36e0a3bb082f9936863b5099/bg5.png)
®@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@
Installing Cabinet in
Minimum Width Window
"1, Remove filler panels on air conditioner cabinet.
2. Refer to steps 1 through 3 of Window Installation instructions.
3. Close window until it touches behind air conditioner top bar.
4. Fasten top bar to window frame using 5/8" washer head screw.
5. If filler is required on sides of air conditioner, cut plastic foam seal
to size and fill both sides.
6. Use silicone or latex sealant (not supplied to fill any minor openings.
7. Install chassis into cabinet.
Consult your authorized dealer or importer for alternative
installation instructions.
Through-the-wall Installation
This air conditioner is designed as a slide-out type chassis, making it
possible to install it through-the-wall in both existing and new
construction. We recommend that this type of installation be performed
with professional assistance.
• IMPORTANT: This appliance must be installed according to all
applicable electrical and building codes and ordinances.
• It is recommended that you have help to install your unit and that you
use proper lifting technique to avoid personal injury.
• It is important that you inspect the condition of the wall where the air
conditioner will be installed.
• Be sure the wall can support the weight of the unit.
• All cabinet louvers MUST BE on the outdoor side of the wall. DO NOT
BLOCK SIDE LOUVERS.
• The cabinet must be installed level from side-to-side and with a
downward tilt from inside to outside.
@
C) Top Bar C) Attach top bar here
Fig. 1
Fig. 2
"1, First remove the Decorative front panel and chassis from the cabinet,
then remove top bar from the cabinet.
2=
Determine the size of the opening for a wood frame by adding 1/8"
to the width and height of the cabinet. Measure height from top of
cabinet to bottom of bar. Add this measurement to the thickness of
wood used to build the frame. This will determine the size of wall
opening needed. Minimum 1" thick lumber is recommended when
building the frame. When determining finish frame thickness, be sure
not to cover side louvers on the cabinet.
:3. Install the finished frame in the wall opening square and level, nail
or screw it securely to the wall and place the cabinet into the framed
wall opening.
4, Make sure cabinet projects into the roomside of the wall 1 1/4" at
the top and 1 1/2" at the bottom to ensure proper tilt and access to
the anti-theft screw, then fasten cabinet to the frame by drilling
twelve (12) 1" wood screws (not supplied) through the cabinet and
into the frame. (Fig. 1 &2)
If installation is made in a building with brick veneer construction, a
steel angle lintel must be used to support the bricks above the
cabinet.(Fig.3)
5=
Install a 3/4" X 1 1/2" wood filler strip between the bottom bar and
the interior, caulk both top and bottom of this strip. After cabinet is
installed caulk all openings, inside and outside between finish frame
and cabinet to prevent moisture from getting to the interior of the
wall. Use of flashing (driprail) will further prevent water from
dripping inside the wall.
6. Install chassis into cabinet.
5
Fig. 3
C) Wood frame
C) 1" wood screws
C) Cabinet
Q Bottom Bar
C) Interior wall
(_ Decorative Front
(_ Minimum lx6 wood
support (nailed or
screwed to wood
frame)
i:
(_2" Wood frame
C)1 1/2" space
C)1 1/4" space
C)Brick veneer
C)Lintel angle
(_Caulking
(_)Flashing (drip rail)
C)Side louvers
(_Wood filler strip
![](/html/93/9312/931288df1acfd98602f348786ae591aad6bda17d36e0a3bb082f9936863b5099/bg6.png)
Operation°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°
Electronic Control Panel
Power Control
The Power Control turns the unit on and
off.
Set Temperature/Timer
Display
Shows the set temperature when the unit
is in operation and hours when the timer
is being set. THE TEMPERATURE
DISPLAY ONLY SHOWS THE SET
TEMPERATURE, NOT THE ACTUAL
ROOM TEMPERATURE.
Temperature/Timer Hour
Controls
These buttons are used to raise or lower
the set temperature in increments of 1 °
from 66°F to 88°F. By depressing both
buttons at once, the display will toggle
between Celsius and Fahrenheit. When
the timer is being set, these buttons are
used to change the hour setting in
increments of 1 from 00 to 24.
Mode Control
A green light will indicate which mode is
currently being utilized.
Cool Mode-
The unit will circulate and cool the air.
Heal; Mode (Heat Models Only) -
The unit will circulate and heat the air.
Heater Safety Feature- When heater is
powered off, low fan will automatically stay
on and run for 60 seconds to ensure the
removal of residual heat, meanwhile, the
Low Fan LED blinks until the low fan stops.
Fan Mode-
The unit will only circulate the air.
Energy Saver Mode -
(The energy saver mode is designed to
operate with Cool mode only). The fan
will switch from the set fan speed to Low
whenever the compressor turns off in
response to the thermostat. When the
compressor cycles back on, the unit will
return to the original fan setting. Speeds
will change automatically as the
temperature in the room changes.
Fan Speed Control - High, Medium, Low and Auto
The settings are adjusted with the Fan Speed Control, each time the button is
depressed it changes the setting. A green light will indicate which setting is currently
being used.
When the Auto feature is selected while the air conditioner is in the Cool or Heat
mode, the fan speeds will change automatically as the temperature in the room
changes. In Cool Mode when the room reaches 7° or more above the set temperature
High Fan will be used, 4 ° or less above the set temperature will use Low fan. In Heat
Mode when the room reaches 7 ° or more below the set temperature High fan will be
used, 4 ° or less below the set temperature will use Low fan. At all other times the fan
will use Medium fan.
Timer Control (The timer can be set to either turn the unit on or off.)
To automatically START the unit using
the Timer mode:
1. Push the timer button while the
power is OFF. The display will read 00.
Adjust the display to show the desired
number of hours before START-UP using
the Temperature/Timer adjustment
arrows.
2. The display will show the amount of
time, in hours, remaining until START-UP.
3. To exit Timer mode, push the Timer
button.
4. A green light next to the Timer
button indicates that the timer is set.
To automatically SHUT-DOWN the unit
using the Timer mode:
1. Push the timer button while the
power is ON. The display will read 00.
Adjust the display to show the desired
number of hours before SHUT-DOWN
using the Temperature/Timer adjustment
arrows. (The display will automatically
return to the set temperature after 10
seconds.)
2. To display the amount of time left
until SHUT-DOWN, push the Timer
button once.
3. To exit Timer mode, push the Timer
button twice.
4. A green light next to the Timer
button indicates that the timer is set.
Electronic Control (Cooling Only)
• Cool
• Energy Save
• Fan
Built in 7hroe Minute Cooling Delay
Electronic Control (Heat/Cool)
Built in Three Minute Cooling Delay
Temperature/Timer Display
Temperature/Timer Adjustment
Timer On/Off
Fan Speed Control
Mode Control
Power Control
_ he heat from this unit is designed
only as a supplemental heat
source in addition to
regular heating systems.
6
![](/html/93/9312/931288df1acfd98602f348786ae591aad6bda17d36e0a3bb082f9936863b5099/bg7.png)
®@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@
Air Conditioner Remote Control
The functions work the same as your air conditioner's touch controls.
Batteries: Remove the cover on the back of the remote controller and insert the batteries with the
(+) and (-) poles pointing in the proper direction.
0
0
CAUTION
• Use onlyAAA or IEC R03 1.5V batteries.
• Remove the batteries ff the remote controller is not used for
a month or longer.
• Do not attempt to recharge the supplied batteries
• Aft batteries should be replaced at the same time.
• Do not dispose of the batteries in a fire as they may
explode.
AAA ......! i
• Do not mix old and new batteries.
• Do not mix alkaline, standard (carbon- zinc), or rechargeable
(nickle-cadmium) batteries.
• Keep batteries and other objects that could be swallowed
away from young children.
Contact a doctor immediately ff an object is swallowed.
Q Filter @ Louvers Q Vent door
Directing Airflow
Unit is engineered with adjustable louvers to direct discharge airflow. Louvers are
manually adjusted by moving levers ill direction of desired airflow.
Cleaning the Air Filter Clean the filter every two weeks
1. Turn Master Control to OFF.
2. Remove the air filter by opening the air intake panel on the decorative front and
pull it out of the unit.
3. Wash in hot soapy water, rinse and shake dry.
4. Replace the filter, with the front of the filter toward you.
5. To dry the filter thoroughly, run your unit for a few minutes. Remember, only a
clean filter works properly and delivers top efficiency at every setting.
_ ote: Failure to keep air filter clean will result in poor air circulation.
DO NOT operate without filter. This can render the unit inoperative.
Proper use and care of your air conditioner will help ensure longer life of the
unit. It is recommended to annually inspect and clean the coils and condensate
water passages. Expense of annual inspection is the consumer's responsibility.
7
![](/html/93/9312/931288df1acfd98602f348786ae591aad6bda17d36e0a3bb082f9936863b5099/bg8.png)
Maintenance°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°
Service To save tinqe and expense, check the following before calling an authorized service station.
Insufficient Cooling
• Turn Master Control to OFF.
• Shut all windows and doors in room.
• Remove any obstructions from inside and outside louvers.
• Close Vent Door (available on some models).
• Inspect filter and clean if dirty.
• Turn Thermostat and Master Controls to coolest settings.
Under certain conditions the cooling coils directly behind the
filter, may ice up and block the airflow. This is a common
occurrence in air conditioners caused when the outside
temperature drops below 70°F (21°C) while the humidity
remains high. If this happens, simply turn the unit off and allow
the ice to melt, then resume normal operation.
Insufficient Heating- Heating Models Only
• Turn Master Control to OFF.
• Shut all windows and doors in room.
• Remove any obstructions from inside and outside louvers.
• Close Vent.
• Turn Thermostat to Warmer and Master Control to HI HEAT.
Unit Fails to Start
• Turn Master Control to OFF.
• Replug line cord plug into outlet to be sure electrical contact
is being made. (If firm contact is not being made, outlet may
have to be replaced).
• Turn Master Control to HI FAN. If air circulating fan does not
operate, check house circuit breaker (or fuses).
For Models Installed in North America - If Service or Parts are Required First, make the recommended checks. If it appears that
service or parts are still required, see your room air conditioner warranty "How to Obtain Warranty Service or Parts".
For Models Installed Outside North America For room air conditioners purchased for use outside North America, the
manufacturer does not extend any warranty either expressed or implied. Consult your local dealer for any warranty terms
extended by the importer in your country.
Visit www.fedders.com for obtaining serviceable parts beyond your warranty period.
Troubleshooting Guide
Occurrence
Air conditioner will not operate
Air from unit does not
feel cold enough
Air conditioner cooling,
but room is too warm --
ice forming on cooling coil
behind decorative front
Air conditioner cooling, • Dirty air filter air restricted.
but room too warm --
NO ice forming on cooling coil • Thermostat set too warm.
behind decorative front • Fan selector set on LOW
Noise when unit is cooling • Air movement sound.
Water dripping inside • Improper installation.
when unit is cooling
Water dripping outside • Unit removing large quantity of moisture V"
when unit is cooling from humid room.
Possible Cause
• Wall plug disconnected,
• House fuse blown or circuit breaker tripped.
• Power switch in OFF position.
• Unit accidentally turned off by moving the
thermostat to a higher temperature and then
immediately turned back to a colder position.
• Unit turned off and then on too quickly.
• Thermostat set too low for cooling.
• Selector in FAN position.
• Thermostat set too warm.
• Room temperature below 70°F.
• Outdoor temperature below 70°F.
• Dirty air filter air restricted.
• Thermostat set too cold for nighttime cooling.
• Sound of fan hitting water-moisture
removal system.
• Window vibration poor installation.
Solutions
V" Push plug firmly into wall outlet.
Replace fuse with time delay type
or reset circuit breaker.
Turn power switch to ON position.
Wait approximately 3 minutes.
Listen for the compressor to start.
V" If air conditioner is turned off,
wait 3 minutes before restarting.
V" Adjust thermostat to higher setting for cooling.
V" Set selector to COOL position.
V" Set thermostat to colder temperature.
V" Cooling may not occur until room
temperature rises above 70°F.
V" To defrost the coil, set selector to FAN position.
Then, set thermostat to warmer position.
V" Clean filter. See "Cleaning the Air Filter" section.
To defrost, set selector to FAN.
V" To defrost the coil, set selector to FAN position.
Then, set thermostat to a normal position.
V" Clean air filter.
Refer to "Cleaning Air Filter" section.
V" Set thermostat to colder setting.
_ Set fan speed selector to HIGH
for maximum coolin R.
V" The sound of rushing air is normal. If too loud,
turn selector to lower fan setting.
V" This is normal when humidity is high.
Close doors, windows and registers.
V" Refer to installation instructions
check with installer.
V" Tilt air conditioner slightly to the outside to
allow water drainage. Refer to installation
instructions check with installer.
This is normal during excessively humid clays.
8
![](/html/93/9312/931288df1acfd98602f348786ae591aad6bda17d36e0a3bb082f9936863b5099/bg9.png)
Warrantyooooooooooooooooooooooooooooooooooooooooooooooooooo
For Models Installed
in North America - If Service
or Parts are Required
First, make the recommended checks. If it appears that service or
parts are still required, see your room air conditioner warranty
"How to Obtain Warranty Service or Parts".
For Models Installed
Outside North America
For room air conditioners purchased for use outside North
America, the manufacturer does not extend any warranty either
expressed or implied. Consult your local dealer for any
warranty terms extended by the importer in your country.
Room Air Conditioner Warranty
(Within the 48 contiguous United States, state of Hawaii,
the District of Columbia, Puerto Rico and Canada)
Full (FiveYear) Parts and Labor Warranty
During the five years after the date of original purchase,
Fedders North America will, through its authorized servicers
and free of charge to the owner or any subsequent user, repair
or replace any parts which are defective in material or
workmanship due to normal use. Ready access to the air
conditioner is the responsibility of the owner.
Note: In the event of any required parts replacement
within the period of this warranty, Fedders North America
replacement parts shall be used and will be warranted
only for the period remaining on the original warranty.
Exceptions
The above warranty does not cover failure to function caused
by damage to the unit while in your possession (other than
damage caused by defect or malfunction), or by its improper
installation, or by unreasonable use of the unit, including
without limitation, failure to provide reasonable and necessary
maintenance or to follow the written Installation and Operating
Instructions. If the unit is put to commercial, business, rental, or
other use or application other than for consumer use, we make
no warranties, express or implied, including but not limited to,
any implied warranty of merchantability or fitness for particular
use or purpose.
THE REMEDIES PROVIDED FOR IN T_tE ABOVE EXPRESS
WARRANTY ARE THE SOLE AND EXCLUSIVE REMEDIES
T_tEREFOR, NO OTHER EXPRESS WARRANTIES ARE MADE.
ALL IMPLIED WARRANTIES, INCLUDING BUT NOT LIMITED
TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR
FITNESS FOR A PARTICULAR USE OR PURPOSE, ARE
LIMITED IN DURATION TO FIVE YEARS FROM T_tE DATE OF
ORIGINAL PURC_tASE. IN NO EVENT SHALL FEDDERS
NORT_t AMERICA BE LIABLE FOR INDIRECT, INCIDENTAL,
OR CONSEQUENTIAL DAMAGES, EVEN IF ADVISED IN
ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES. NO
WARRANTIES, EXPRESS OR IMPLIED, ARE MADE TO ANY
BUYER UPON RESALE.
Some states do not allow limitations on how long an implied
warranty lasts or do not allow the exclusion or limitation of
incidental or consequential damages, so the above limitations
or exclusions may not apply to you. This warranty gives you
specific legal rights, and you may also have other rights which
may vary from state to state.
No warranties are made for units sold outside of the above
stated areas. Your distributor or final seller may provide a
warranty on units sold outside of these areas.
How to Obtain
Warranty Service or Parts
Service for your room air conditioner will be provided by
CareCo, a division of the manufacturer with authorized
independent CareCo servicers nationwide.
Note: Before calling for service, carefully read the
Installation and Operating Instructions booklet. Then ff
you need service:
1. Call a CareCo authorized servicer and advise them of model
number, serial number, date of purchase and nature of
complaint. Service will be provided during normal working
hours. Contact your dealer for the name of an authorized
servicer if unknown to you.
2. If your dealer is unable to give you the name of a servicer or
if you need other assistance, call the following toll-free
number for the name of an authorized servicer or authorized
parts distributor:
1-866-MAYTAG 1
or you may write:
CareCo, Service Department
415 W. Wabash Ave., P.O.Box 200
Effingham, IL 62401
Proof of Purchase Date
It is the responsibility of the consumer to establish the original
purchase date for warranty purposes. We recommend that a bill
of sale, cancelled check, or some other appropriate payment
record be kept for that purpose.
Maytagis atrademarkof theMaytagCorporationandis usedunderlicensebyFeddersNorthAmerica,Inc.
9