Maxwell MXW 1500 A, MXW 1500 P, MXW 2000 A, MXW 2000 P, MXW 2500 A Instruction Manual

...
INSTRUCTION MANUAL
Air Curtains MAXWELL
Attention, Danger, Safety Advice!
Danger from electric current of high voltage!
Injuries risk!
Danger! Do not step underneath: Heavy load.
Important Information!
AIRDOM05131-R10(18/06/14)
INSTALLATION DIAGRAM – (WITHOUT REGULATION)
INSTALLATION DIAGRAM – (WITH REGULATION)
MAX. Maximum recommended height, MIN Minimum recommended distance (*) Standard units. Under request this distance can be reduced to 1cm when connections are placed inside and water pipes lateral.
Minimum recommended distance between the inlet grille and any obstacle is of 225mm.
Power Supply
To connect the power supply there is a black connection box in each fan of the air curtain (on the back). Connection should be done directly in any black connection box at the ends of the air curtain.
For an ambient air or water heated air curtain, just connect the single phase 230Vx1. In case of an air curtain with electrical heating we will also connect the three phase 400Vx3 of the electrical
element. Optionally under request the current of the electric battery can be three phases 230Vx3 or single phase 230Vx1 depending on model (special wiring diagram will be enclosed).
PCBoard and control (Optional in case the air curtain has regulation incorporated)
To connect the controller there is a PCBoard (printed circuit) located outside the air curtain (on the back). There is no need to open the unit to connect it. Use the telephone cable of 10 meters (RJ45 connectors) supplied with the equipment. The communication between the connector plate and the controller is digital through low-voltage.
Installation work, connection, disconnection, electrical wiring, mechanical maintenance and service must be done by qualified persons observing these instructions and in accordance with all applicable norms and standards. If the unit is operated with additional controller, please consider its specific instructions.
There is no need to open the service door to connect the air curtain. All connections (power supply, control, water pipes when existing) and fixations are external. They are placed on top or lateral of the units. See how to open service door at repairs section.
For safety, the air curtains never have to be stopped by disconnecting from the main supply, always through the controller and wait for 10 minutes at least to disconnect the main supply. In case we do not follow these instructions, the internal parts of the air curtain can be damaged.
Optionally, there are available different accessories and controllers, to meet every customer’s needs (week timer, thermostats, door contacts, anti-freezing sensor, supports, valves, etc…).
Fixing
Units are provided with several external suspension points, depending on the weight and length (see exact situation of the points at the air curtains characteristics page).
Generally air curtains work horizontally but also can be installed vertically using feet (accessories section). The anchor should be managed according to the weights of each unit shown on the technical data page. The
installation can be made through threaded rods, tensors or other supports. See available supports in the accessories section.
Water coils
Water heated air curtains have a PCBoard with an output of 230Vx1 to install an electro valve (open/close water entrance) or any other device. This output can also be used for other low amperage electric device (air curtain option with regulation incorporated)
It is recommended:
Close the warm water circulation (by closing the electro valve) to avoid motor overheating while the unit is OFF. The electro valve is optional.
Install 2 shut-off water valves (supply and return) in order to dismantle the equipment easily.
Install a bleeding point at the highest part of the heating water circuit.
The ambient temperature should be always over +4ºC, otherwise it will be necessary to provide an anti-frost protection device.
Water coils have a draining point placed at the end part of the intake manifold.
TRANSPORT AND STORAGE
Attention! Heavy load. Do not step under hanging load during the transport or assembly.
Store in a dry place and weather protected in its original packaging. In case the packing is open, cover the air curtain to protect it from dust. Do not step or put heavy load over the package to avoid damages to the material. Store temperatures are between -20ºC and +40ºC.
When carrying material, make sure it is not damaged by the forklift (fork penetration in the packaging). Please see the packaging instructions.
L A MXW 1500 1500 734 MXW 2000 2000 984 MXW 2500 2500 1234
Dimensions
30
615
660
361
150
222
6 x M8
1616
60
L
AA
7560
50
79,5
Model Airow
Water
heating capacity 80/60ºC
Water drop
pressure
80/60ºC
Water
connections
80/60ºC
Water
heating capacity 60/40ºC
Water
drop
pressure
60/40ºC
Water
connections
60/40ºC
Fans
power
230V-50Hz
Fans current
230V-50Hz
Noise level (5 m)
Weight
m3/h kW Pa kW Pa kW A dB(A) kg
MXW 1500 A 8000 - - - - - - 0,68 2,96 59 79 MXW 1500 P 7000 40,85 14.770 2x1¼” 32,82 15.440 2x1¼” 0,68 2,96 59 95
MXW 2000 A 12000 - - - - - - 1,02 4,44 61 103 MXW 2000 P 10500 60,66 14.260 2x1¼” 47,87 14.690 2x1¼” 1,02 4,44 61 126
MXW 2500 A 16000 - - - - - - 1,36 5,92 62 126 MXW 2500 P 14000 78,53 14.690 2x1¼” 63,58 17,950 2x1¼” 1,36 5,92 62 158
MAXWELL | Air Curtains For Industrial Doors
• High performance heavy duty industrial air curtains for vertical and horizontal ins­tallations, available in 1.5, 2.0 and 2.5 meters length. Easy dockable modules to reach large dimensions.
• Self-supporting galvanized steel plate housing, powder-coated in white RAL 9016
as standard.Other colors are available on customer request.
• High efciency and low noise axial fans driven with external rotor motor, single
phase 230V/50Hz. Optionally three phase 400V/50Hz
• Ambient models “A”, without heating and warm water heated models “P” up to
120ºC.
• Double outlet with Coanda effect to achieve larger and efcient air jet. Adjustable pitch angle outlet vanes, airfoil shaped.
• Different control options, from simple on/off to full automatic: 2/5 ventilation speed, manual or automatic functioning, remote control, with telephone cable and fast connectors (Plug and Play), interface to connect to BMS, etc...
Characteristics
Specications
Electrical heated models available on customer request. Let us know your needs