SFT24FXA
Revision 9/02
Reprint 9/02
PW UPS Line Fail Low Batt UPS Alarm/OK Bypass
PW 5125 X X
PW 9120 X X X X
PW 9125 X X
PW 9170+ X X X X
PW 9330 X X X
PW 9340 X X X X
UPS to supported contacts matrix
Description of relay interface card pins and relay information
K1: AC Line AC line OK 1-2 NC
K2: Battery AC line failure 1-3 NO
Battery normal 4-5 NC
K3: UPS Alarm Battery low 4-6 NO
UPS alarm 7-8 NC
UPS ON/OK 7-9 NO
K4: Bypass UPS on bypass 10-12 NC
UPS normal/on inverter 10-11 NO
UPS shutdown** 13-15
Note: UPS alarm/OK and bypass relay information are not available for PW 5125 and PW 9125 UPSs.
Relay interface card contact information
The relay contacts must not be galvanically connected to any mains-connected circuits. Do not use +12VDC
(Pin13) of the relay interface card for any power supply purposes for external devices. Reinforced insulation
to the mains is required for equipment and cables attached to these connections. Relay contacts are rated
for maximum 1A/30VAC or 200mA/60VDC. All relay outputs are galvanically isolated from the other circuits
of the UPS.
BestDock Relay Interface Card shutdown function
Normally-closed (NC)/-open (NO) connection state when the relay interface card is not powered. **The shutdown pin (15) needs minimum of 5 seconds high level signal (connection to +12VDC) to perform the UPS shutdown. Shutdown function is not available for 9125, 9330, and 9340.
Relay # on board System State DB-15 pin# NC/N0
*
JP1 (factory default) JP2 JP3
PW 9120 UPS normal Immediate output off, Immediate output off
--- online when shutdown
pins are opened
On battery Shutdown as in RS-232 Immediate output off, Immediate output off
port; Output off after online when shutdown
120 sec., back online pins are opened
when power returns
PW 9170+ UPS normal --- --- Immediate output off
On battery --- Immediate output off Immediate output off