Model Number UPS0600ITSIT UPS1000ITSIT UPS1500ITSIT UPS2000ITSIT
Power Rating
Output Capacity
600VA / 360W 1000VA / 600W 1500VA / 900W 2000VA / 1200W
Power Factor
Output Power Factor
0.6 pf
Input
Voltage
120V +/- 10% at line input, single phase
Frequency
50 or 60 Hz +/- 5Hz auto-sensing
Input Power Connection
Detachable 5-15P Detachable 5-15P Hardwired 5-15P Hardwired 5-20P
Output
Voltage
(on Battery)
Pure sine wave at +/- 5% of nominal, -10% of nominal after low battery warning
Voltage
(on Mains)
120V, -12%/+10%
Voltage
THD
< 5% @ 100% resistive load with 80% battery capacity
Frequency
(on Battery)
50 or 60 Hz +/- 5% auto-sensing
Voltage Regulation (
AVR)
AVR automatically increases (boost) output voltage 17% above input voltage if -9% to -25% of nominal.
AVR decreases (buck) output voltage 14% below input voltage if +9% to +25% of nominal.
Output Receptacles -
Power Distribution
(4) 5-15R (4) 5-15R (6) 5-15R (6) 5-15R
Protection &
Filtering
Spike Protection
780 Joules/6500A
EMI/RF Filter
10dB @ 0.15MHz, 50 dB @ 30 MHz
Overload Protection
UPS automatic shutdown if overload exceeds 110% of nominal @ 20 seconds and 125% @ 5 seconds
Transfer Time
4/6 milliseconds (typical), including detection time
Short Circuit
Active protection with automatic shutdown
Battery
System Type
Hot swappable, sealed Valve Regulated Lead Acid (
VRLA)
Battery
12V / 9.0 AH
Typical Recharge Time
4 hours
(to 90% of full capacity)
Protection
Automatic self-test and discharge protection, Replace battery indicator
Battery Quantity
2 pcs 2 pcs 3 pcs 4 pcs
Net Weight
(lbs)
30.4 lbs 33.0 lbs 55.0 lbs 66.0 lbs
Dimensions
W x D x H (Inches)
5.5" x 17.2" x 8.3" 5.5" x 17.2" x 8.3" 6.7" x 17.7" x 8.9" 6.7" x 17.7" x 8.9"
Communi-
cations
RS-
232
Standard (Detect battery low, schedule UPS on/off, AC Input/Output power status display)
USB
Standard
SNMP
Optional
Operating System
Windows NT, Windows 2000/ME, Windows XP, Linux
Environment
Ambient operation
3,500 meters max. elevation, 0-95% RH non-condensing, 0-40°C
Audible noise @ 1 meter
< 40 dBA < 45 dBA
Storage condition
15,000 meters max. elevation, 0-95% RH non-condensing, 0-40
°
C
Certifications
UL, cUL, FCC Class A
Battery Runtimes (minutes) ***
VA
Standard Internal Battery System
@ 25% Load @ 50% Load @ 75% Load @ 100% Load
600
84 35 20 14
1000
42 17 10 6
1500
42 17 10 6
2000
42 17 10 6
*** Runtimes are estimated
Options
>
SNMP communication cards are available
and sold separately
>
For replacement batteries, please contact
the
UPS Parts Department: 800 637 1738
* See UPS Limited Warranty Rider, Publication No. GETCPQ-UPS
** Contact a factory representative: 800 637 1738
>
Extended Limited Product Warranties Available **
•1 Year
•3 Year
•5 Year
Represented by:
GE Energy – Digital Energy
830 W 40th Street
Chicago, IL 60609
USA
800 637 1738
www.gepowerquality.com
Information subject to change
without notice. Please verify
all details with
GE.
© 2010 General Electric Company
All Rights Reserved