MaxPower Corp G8000 User Manual

G8000 Series
ß Output Power Factor 1.0
ß Input Power Factor >0.98
ß Internal Isolation Transformer
ß Input Current THD <5%
ß True On-Line Double Conversion UPS
ß Wide Input Voltage Window
ß IGBT DC Converter / Inverter Design
ß Power Factor Correction for 100% Generator Compatibility
ß Complete Front Access for Installation, Operation and Service
ß External Battery Options for Customized Battery Back-up Time
ß XT Series is for Extreme Applications (Harsh Environments)
See reverse for details
100/150/225/300 kVA UPS
NEW
Higher Output
Power Factor!
ß 100% Unbalanced Load Capability
ß SNMP/ Web-based Monitoring
Model Number T80S3K10KK6XSNH T80S3K15KK6XSNH T80S3K22KK6XSNH T80S3K30KK6XSNH
Capacity kVA / kW 100 / 100 150 / 150 225 / 225 300 / 300
Topology True on-line, double conversion, IGBT PWM, with input power factor correction and unity power factor on output
Input Voltage AC Input 480 V 3 Phase, 3 wire + Gnd / Bypass Input 480 V 3 Phase, 4 wire + Gnd
Voltage Range 408 - 528 V (without utilizing battery)
Power Factor Greater than 0.98
Current THD 5% Max
Frequency 60 Hz 5%)
Current Limit 125% Max
Output Voltage / THD 480 V, 3 Phase, 4 wire + Gnd / 1% THD Typ
Frequency 60 Hz ± 0.01%
Voltage Regulation ± 0.5%
Power Factor 1.0 Unity (20% more power)
Overload (Inverter) 125% for 10 min, 150% for 60 sec
Overload (Bypass) 1000% for 1 cycle, 125% continuous
Battery DC Link 360 V DC
Ripple voltage ± 0.5%
Environ- ment
Temperature Range 0 - 30°C Unity PF (Operating) 0 - 40°C .8 PF (Operating) / -20 - 50°C (Storage)
Relative Humidity 30-95% Non-Condensing
Heat Rejection 23,720 BTUs / Hr. 32,670 BTUs / Hr. 49,000 BTUs / Hr. 65,335 BTUs / Hr.
Efficiency 93.5% 94% 94% 94%
Dimensions Dimensions (L x W x H) 36.8”L x 31.5”W x 78.7”H 55.1”L x 31.5”W x 78.7”H 76.8”L x 35.4”W x 78.7”H
Weight (lbs.) 1680 lbs 2756 lbs 3307 lbs 4400 lbs
Altitude 6,600 ft (2000 m) (Max w/o derating)
Audible Noise < 65 dBA @ 1 m < 68 dBA @ 1 m 70 dBA @ 1 m
Features
Output Unity Power Factor, Dual Input Feed, Output Isolation Transformer, RS232 and Dry Contact Interface
Standards UL 1778, cUL, NEC, ISO9001, ISO14001, ANSI C62.41 (IEEE 587)
Warranty Three Years on Electronics (UPS) when PMs are purchased / Two years full on Battery (See Toshiba warranty policy for full details.)
Service 7x24 Technical Support 1-877-867-8773 (1-UPS-TOS-UPS3)
G8000 Series 100/150/225/300 kVA UPS
UPS ADJUSTABLE SPEED DRIVES MOTORS CONTROLS INSTRUMENTATION PLC
INDUSTRIAL DIVISION
13131 West Little York Road, Houston, Texas 77041 Tel 713/466-0277 Fax 713/466-8773 US 800/231-1412 Canada 800/872-2192 Mexico 001/800/527-1204 www.toshiba.com/ind Copyright 3/2006
Available Through:
*UPSg8000XT060307*