ONLINE EMERGENCY LIGHTING INVERTER
Keep the lights “ON” when you need them the most.
Three Phase 3 KW - 125 KW
Made In The USA
Defends your environment against unwanted
power outage and electrical disturbances by providing:
DSPM Watchdog software always on guard.
•
Display monitor keeps you in control 24/7.
Dependable DSP/PWM technology for unsurpassed reliability.
Economical for the lowest overall cost for your
light safety, with an Energy Star Rating.
Temperature compensating technology that
controls batteries for the longest battery life.
Sealed maintenance free batteries.
Full light output for entire 90 minutes.
Self-diagnostics for a safe and secure lighted environment.
Pure sine wave output for all types of lamps.
ECM module is a patented technology used by DSPM.
Backup solutions for multiple applications such as:
indoor and outdoor emergency lighting, exits,
cash registers, computers, strategic electronics and more!
10 Year pro-rated battery warranty.
5 Year power train warranty.
Meets federal, state and local codes:
UL924, NFPA 101, NFPA 70, NEC and OSHA.
Cities of Chicago and New York Approved.
Complies with the Buy American Act.
Input
Operation:
082-0020-01 Rev. E
Normal
Standby
Maintenance
AC to DC
Converter
Maintenance
Bypass Switch
Battery
DC to AC
Inverter
Static
Bypass
Switch
Output
System
Control Alarm
and Display
Email: info@DSPManufacturing.com
1921 S. Quaker Ridge Place
Ontario, CA 91761
Ph: 1.877.DSPM POWER
1.877.377.6769
Fax: 909.930.3335

*Standard Power Levels..........**3.0, 4.5, 6.0, 8.0, 10.0, 12.0, 16.0, 20.0,
24.0, 30.0, 40.0, 60.0, 80.0, 100.0 and 125.0 KW
*Input Voltage ..........................208Y/120, 480Y/277, 208 or 480VAC
*Input Voltage Range...............+10%. -15%
*Output Voltage........................208Y/120 or 480Y/277 VAC
*Output Voltage Regulation......±3% for all loads and battery discharge mode
*Output Frequency Range........60 Hz, ±1%
Output Wave Form...................Sine-wave <5% @ 100% linear load
Crest Factor..............................2.5:1 typical
Input Protection........................Input Main Circuit Breaker
Output Protection.....................Output Main Circuit Breaker
Surge Protection......................The unit will protect itself and the load
against surges as defined in
ANSI/EEE C62.45 category A and B
Battery......................................Sealed maintenance-free (AGM) lead calcium
Recharge Current.....................Conforms to UL924 standards
External Battery........................Provision for hardware connection of
external battery cabinets or DC source
Efficiency..................................≥92% at 100% linear load
Audible Noise...........................<45dB measured on Response Curve “A”
Safety Agencies.......................Listed to UL standard 924
Operating Temperature............0º to 40ºC (32º to 104ºF)
Storage Temperature...............-20º to 60ºC (-4º to 140ºF)
Humidity...................................5 - 95%, Non-condensing
*Consult factory for others.
**No line to line loads for 3.0 - 6.0 kw units.
Specifications subject to change without notice.
Eternalight
3
Series
Power
Rating
KVA/KW W H D WNo. H D
OE3
(Consult
factory
for others)
Represented by:
UPS Battery Weight
Cabinet
Dimensions
3 42” 71” 22.5” not required
4.5 42” 71” 22.5” not required
6 42” 71” 22.5” not required
8 42” 71” 22.5” 42”1 71” 22.5”
10 42” 71” 22.5” 42”1 71” 22.5”
12 42” 71” 22.5” 42”1 71” 22.5”
16 42” 71” 22.5” 42”1 71” 22.5”
20 42” 71” 22.5” 42”2 71” 22.5”
24 42” 71” 22.5” 42”2 71” 22.5”
30 42” 71” 22.5” 42”2 71” 22.5”
40 42” 71” 22.5” 42”3 71” 22.5”
60 50” 71” 32”
80 50” 71” 32”
100 50” 71” 32”
125 50” 71” 32”
Cabinet
Dimensions
Consult Factory
Consult Factory
Consult Factory
Consult Factory
(combined)
(lbs)
980
1100
1350
1700
2250
2700
2950
3800
4350
5150
6790
Options:
ECM - Environmental Control Module
NOF120 - Normally OFF Circuit 120VAC
NOF227 - Normally OFF Circuit 277VAC
NOH120 - Normally OFF “Hold On” 120VAC
NOH227 - Normally OFF “Hold On” 277VAC
OCB - Output Circuit Breaker(s)
EPO- Emergency Power Off
RSSP - Remote Indicator Panel
EIR - Ethernet Interface with RS232
FAX - Fax Modem
FC - Form C Contacts
SRB - Seismic-Rated Bracket
STU3 - Onsite Startup
IDB - Internal Dimmer Bypass
EMB - External Maintenance Bypass
EW - Extended Warranty
Email: info@DSPManufacturing.com
1921 S. Quaker Ridge Place
Ontario, CA 91761
Ph: 1.877.DSPM POWER
1.877.377.6769
Fax: (909)930-3335