Maxlogic ML-121X Maintenance Manual

COMMISSIONING, OPERATING AND MAINTENANCE MANUAL
MODEL: MAXLOGIC SERIES
SUB MODEL: INTELLIGENT ANALOGUE ADDRESSABLE
FIRE ALARM CONTROL PANEL
ML-121X
CONTENTS
1- INTRODUCTION .................................................................................................................................... 3
2- WARNINGS ........................................................................................................................................... 4
3- MOUNTING........................................................................................................................................... 4
4- PANEL INPUTS....................................................................................................................................... 5
4.1 Mains power supply ........................................................................................................................ 5
4.2 Batteries ......................................................................................................................................... 5
4.3 Detection Devices Inputs (Loop Lines) ............................................................................................. 5
4.4 Panel PC Connection ....................................................................................................................... 6
5- PANEL OUTPUTS ................................................................................................................................... 6
5.1 Sounder Outputs (4 Units) ............................................................................................................... 6
5.2 Auxiliary Power Supply Output (24 V DC) ......................................................................................... 7
5.3 Relay Outputs (3 Units) .................................................................................................................... 7
6- PANEL BUTTONS AND INDICATORS ....................................................................................................... 8
6.1 Control Buttons ............................................................................................................................... 8
6.2 Front Panel Indicators ................................................................................................................... 10
6.3 Internal Indicators ......................................................................................................................... 11
7- PANEL FUSES ...................................................................................................................................... 11
8- POWERING THE PANEL ....................................................................................................................... 12
8.1. First Boot of Panel ........................................................................................................................ 12
8.2. Booting Previously Configured Panel ............................................................................................. 16
9- FIRE EVENT MESSAGE FORMAT on PANEL LCD SCREEN ....................................................................... 17
10- FAULT EVENT MESSAGE FORMAT ON LCD SCREEN ............................................................................ 18
11- PANEL MENU .................................................................................................................................... 18
12- NETWORKING PRINCIPLES................................................................................................................. 23
13- TECHNICAL SPECIFICATIONS.............................................................................................................. 26
14- PANEL MODELS ................................................................................................................................. 27
ANNEX-A PANEL DIMENSIONS AND MOUNTING HOLES .......................................................................... 28
ANNEX-B CONNECTION SCHEME ............................................................................................................. 29
ANNEX-C PANEL SPARE PARTS ................................................................................................................ 30
ANNEX-D SERIAL COMMUNICATION CABLE ............................................................................................. 31
ANNEX-E SCHEME OF MENU FUNCTIONS ................................................................................................ 32
ANNEX-F NETWORK CONNECTION SCHEME ............................................................................................ 36
Maxlogic ML-121X Series
Intelligent Analogue Addressable Fire Alarm Control Panels
1- INTRODUCTION
Maxlogic ML-121X series intelligent analogue addressable fire alarm control panels are provided with 0, 1, 2 loop options and 1000 user-defined zone capacity. Up to 127 analogue addressable devices per loop are allowed to be connected.
Devices operating with VIP protocol such as Photo-Electric Smoke Detectors, Heat Detectors, Multi-Sensor Detectors, Switch Monitor Modules, Relay Controller Modules, Sounder Controller Modules, Loop-powered Addressable Sounders and Zone Monitor Modules are compatible with ML-121X series control panels.
The project planning must be made carefully, in order not to have any difficulties when commissioning the system. Zone location text (up to 40 characters including blank spaces) for each device should be predetermined. Then, the devices should be categorized in zones depending on the physical specifications of the building. After these steps, the panel can be configured via the software program called ‘Loop Manager.
The panel is equipped with 4 programmable and fault monitored 24 V DC 500mA sounder outputs. Panel also contains 3 volt-free 30 V DC 1A relay outputs (fire relay, alarm relay, fault relay) and a 24V DC 500mA auxiliary power supply output. Furthermore, 4 remote control inputs (alarm, silence/sound alarm, reset and fault) exist in the panel.
ML-121X series fire alarm control panels have the optional functions described in TS EN 54-2 standards;
Sounder outputs
ML-121X series fire alarm control panels have also the supporting functions described in TS EN 54-2 standards;
Network: The supporting function used to communicate in network.
NOTE: This user manual is valid for the panel models indicated in 14
th
section.
Producer-manufacturer or importer firms’ title, address, and telephone number Manufacturer Firm:
MAVILI ELEKTRONIK TICARET VE SANAYI A.S. SERIFALI MAHALLESI, KUTUP SOKAK NO: 27/1-2-4 UMRANIYE / ISTANBUL / TURKEY TEL: +90 216 466 45 05 - +90 216 466 45 10
Service stations’ communication information that related spare parts have been
provided Authorized Services:
MAVILI ELEKTRONIK TICARET VE SANAYI A.S. SERIFALI MAHALLESI, KUTUP SOKAK NO: 27/1-2-4 UMRANIYE / ISTANBUL / TURKEY TEL: +90 216 466 45 05 - +90 216 466 45 10 TEKSIS TEKNIK ELEKTRONIK SIS.TIC. VE SAN. LTD. STI. SERIFALI MAHALLESI, KUTUP SOKAK NO: 27/3 UMRANIYE / ISTANBUL / TURKEY TEL: +90 216 313 60 60 - +90 216 313 47 49
Expected operation life which has been determined and announced by related ministry
This device’s expected operation life is 7 years.
2- WARNINGS
The panel contains static-sensitive high quality electronic control equipment. Do not use the panel before reading this manual.
In case of any fault, only the technicians of the manufacturer or technicians authorized by the manufacturer should repair or maintain the panel.
The person who will operate the system should be well trained on powering and operating the system.
Two years of warranty is valid from the production date as long as the system is used with regard of obeying the rules, instructions and recommendations provided by the manufacturer.
Use the recommended cable types defined in this manual for cabling of panel power supply, sounder power supply and detector line. Do not remove any connections and do not make any connections while mains power supply is connected. Panel’s earth connection must be made definitely.
Do NEVER apply 230V AC 50Hz mains power into the detectors and manual call points input terminals, sounder line outputs and battery connection inputs.
This panel has been designed to operate on 230 V AC 50 Hz power supply. The protective earth connection must be made definitely and the mains power supply must be presented through the device via a fuse assigned only to this device. If the earth connection is not made appropriately, all the conductive parts in the device may result in electrical leakage and this may create hazard.
‘Automatic Learning causes erasing of existing configuration data at the panel. Therefore, it is recommended to download the configuration data to PC, before ‘Automatic Learning.
3- MOUNTING
The chosen mounting site of the panel must be clean, dry, not subject to shock or vibration and easily accessible. The temperature must be in between the temperature range of
-5C° and +50C°. The relative humidity must not be m ore than 95%. The panel should be mounted on a flat surface in such a way that, the indicators should be at
the eye-level and must not be mounted near the sources of excessive heat or cold and inside of any cabinet.
Uncover the panel via the allen key provided with the panel. Panel cable entries from back and top of the panel are available for easy mounting. Mark the
position of the fixing holes according to the respective Annex-A, Figure-2; ensuring that the wall is flat at the chosen location.
Screws or bolts of a minimum of 4mm diameter must be used to mount the cabinet in all four mounting positions. Drill and plug the wall then fix the cabinet using all fixing points.
4- PANEL INPUTS
4.1 Mains power supply
The system is designed to operate with 230V AC 50Hz. Earth connections must be made to earth terminal and earth resistor must be less than 10. The mains supply of the panel must be via an independent self-resetting fuse rated 230V AC 6A. This fuse must be separate from the other fuses and a caution note should be written such as ATTENTION! FIRE ALARM CONTROL PANELS FUSE. DO NOT REMOVE to ensure safe operation of the panel. Recommended cable types are 3x2,5 NYM or 3x2,5 NYA. Connections must be done according to Annex- B, Figure-1.
Do not connect or disconnect loops, mains supply input and PCB connections while the panel is energized, to avoid an electric shock.
4.2 Batteries
Batteries provide continuity of operation during a failure of the mains power supply. The panel uses 2 units of 12 V DC 7Ah dry type batteries. Battery connection scheme can be seen from Annex-B, Figure-14.
4.3 Detection Devices Inputs (Loop Lines)
ML-121X series panels are produced with 0, 1, 2 loop models. Panels with 0 loops (no-loop) are used as repeater panels. Each loop is capable of hosting up to 127 addressable devices. Connection of loop line to the control panel must be as like in Annex-B,
Figure-7. A 0resistor must be connected to the unused loops. Each device in the loop must be addressed via MG-8200 Address Programmer depending on the architectural project of the site.
The semi-duplex two-wire digital serial synchronous communication between the devices connected to the loop and the fire alarm control panel is established by the VIP communication protocol.
Short circuit isolators must be placed in such a way that more than 20 detectors and/or manual call points shall not be out of service in case of any short circuit occurrence in the loop.
The devices should be connected to a one-pair cable to create a loop and should turn back to the panel from the last device.
The loop is energized from the out terminal of the panel and the turn back point toward the panel is the ‘in’ terminal. In case of rupture or short circuit, the loop is energized from both the ‘in’ terminal and the out terminal. Thanks to this functionality; it is provided that the devices, except from the detectors / buttons which are in failure, go on functioning properly while the part in failure is isolated.
It should be used the short circuit isolator for each ‘in’ and out terminals. Thus, if any problem occurs in between the part from any of the ‘in’ or out terminals to the first short circuit isolator location, this part is isolated and the rest of the loop can go on functioning properly.
1x2x1,5+0,8J-Y(st)Y, 1x2x0,8+0,8J-Y(st)Y or 1x2x1,5+0,8J-H(st)H, 1x2x0,8+0,8J-H(st)H coded cables should be used. While cabling (starting from Loop + terminal), cables earth line must be connected to appropriate earth terminal in the control panel (See Annex-B, Figure-2). This earth line should be installed throughout all detectors and call points. Earthing cables should be wired after placing detectors and/or call points and line should be ended. When a return is performed to (Loop -), earthing line should be done as it is shown in Annex-B, Figure-2 and line is ended.
4.4 Panel PC Connection
4.4.1 PC Port Cable connection between panel and PC for data communication is plugged into the PC
Socket which found on front panel of (See Annex-B, Figure-11). The communication cable shown in Annex-D must be used for communication with computer.
4.4.2 Write Enable Switch Write enable switch has two positions as ON” and OFF. (Annex-B, Figure-8) When the
panel is energized while the switch is OFF, the panel runs previously saved data. When the panel is energized while the switch is ON, panel operation modes appears on the screen. More details are provided in Section-8.
4.5 Remote Control Inputs There are remote control inputs on the panel which are likely to control the panel remotely by
the help of any remote button. One terminal of the button is connected to the desired input and other one is connected to GND. (See Annex-B, Figure-6). It should be used the cable with this code; 2x1,5 N2XH or 2x1,5 NYY for remote control input line.
AL : Reactivates alarm condition, sounders and relays which was silenced and positioned by Silence Alarm.
FLT : Activates fault condition. RS : Resets the panel. SIL : Silences sounders and returns the relays to their initial position.
5- PANEL OUTPUTS
5.1 Sounder Outputs (4 Units)
The panel has 4 sounder outputs rated 24 V DC 500mA. In order to monitor the line against to open or short circuit conditions, normally 16 V DC reverse voltage is seen from the sounder outputs. During fire alarm outputs are driven by 24 V DC (Annex-B, Figure-4). Current driven more than 0.5A leads the panel into the fault condition.
2x1,5 N2XH or 2x1,5 NYY cable should be used for the sounder line. 10KOhm resistor, located on sounder outputs from factory default is used as end-of-line resistor and must be connected to the end of the sounder line. Otherwise, open circuit fault is monitored on the sounder line of panel. In case of any open circuit or short circuit faults occurred, it can be displayed on the screen of panel with the line number.
5.2 Auxiliary Power Supply Output (24 V DC)
The panel is equipped with an auxiliary 0.5А 24 V DC power supply output. Exceeding this level causes fault condition. It can be used for supplying power to peripheral devices. 2x1,5 N2XH or 2x1,5 NYY cables should be used for external power supply line. In case of mains power supply failure, the batteries provide power supply to the output (24 V DC). (Annex-B, Figure-3).
5.3 Relay Outputs (3 Units)
The panel has 3 units of relay outputs with volt free changeover contacts rated 1A 30 V DC. These volt-free outputs; fire relay (normally non-energized), alarm relay (normally non­energized) and fault (normally energized). (Annex-B, Figure-5). 2x1,5 N2XH or 2x1,5 NYY cable should be used for relay output line.
5.3.1 Fire Relay : The output is activated on any fire event and it can be used to trigger any other system. The output is returned to its initial position only by pressing ‘Reset button on panel.
5.3.2 Alarm Relay : The output is activated on any fire event and it can be used to activate any other system. The output is returned to its initial position only by pressing ‘Alarm Silence’ button on panel. If a new alarm occurs, Alarm relay reactivates.
5.3.3 Fault Relay : The output is activated on any fault event, changes its contact in case of mains failure. The output returns to its initial position, if fault condition is removed and the ‘Reset button on the panel is pressed.
Important notice : Fire alarm panel relays operate as signal-based relays. If these relays will activate any other devices as like control relays, then a contactor should be used between the relay and device. In case of high current driven applications, the relay outputs can get damage if there is no contactor. This situation is not subjected to the warranty condition.
6- PANEL BUTTONS AND INDICATORS
6.1 Control Buttons
While control panel is in normal operating condition, it is in ‘Access Level 1. In Access Level 1, the buttons; Silence Buzzer, Lamp Test, More Fires, More Events can be used.
The Silence Buzzer, Lamp Test, More Fires, More Events Buttons can be used in Access Level 1.
Passing ‘Access Level 2’ enables to use other buttons. In order to pass ‘Access Level 2’ button control key is brought to enable position. To prevent unauthorized access, button control key must always be kept as disable position while panel operating in normal condition.
Evacuate : Used for the purpose of evacuation. It requires to be programmed by the Loop Manager Program.
Pressing this button:
- Buzzer sounds.
- Sounders ring.
- Alarm and fire relays get activated.
- Fire LEDs and Evacuation LEDs illuminate.
Alarm : Pressing Alarm button reactivates the sounders and relay outputs which were silenced before.
Silence Alarm : This button is used to silence an alarm and bring relay outputs to their old positions.
Silence Buzzer : This button is used to silence the internal buzzer which rings during fire alarm or any fault condition occur in the system.
Lamp Test : It is used to check all the LEDs and LCD screen of the panel whether they are operate normally or not.
Reset : Resets all existing fire and fault events in the system. Fire and Fault relays are brought to normal position (if fire and fault condition is not proceeding).
More Fires : Among existing events, if there are more than one fire event, this button is used to see fire events in the system.
The latest fire event remains at the bottom of the LCD screen. Pressing More Fire’ button shows all the fire events at the upper part of the LCD screen.
Z o n e s I n A l a r m : 1 A l a r m : 2 F a u l t : 1
* F I R E : M G 6 2 0 8 8 - W a y S w . M o n . Z o n e : 1 *
P : 0 L : 1 A : 2 8 M L - 1 2 X X R e - i n i t i a t e d
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
* F I R E : M G 6 2 0 8 8 - W a y S w . M o n . Z o n e : 1 *
P : 0 L : 1 A : 2 8 M L - 1 2 X X R e - i n i t i a t e d
More Events : If more than one event occurs, it is possible to see all other events by pressing this button. Pressing this button categorizes the events. It is possible to check other events by pressing 1(UP), 3(DOWN) buttons. To see the desired event category, press the button with number 2 (RIGHT). To get back to the main category press ‘EXIT button.
Event categories as below ;
Fires
Tech. Alarms
Announce Event
Informations
Evacuates
Tech. Faults
FF Tel. Event
Disablements
Faults
Alerts
Analog Event
Test
Pre-Alarms
Securities
Internal Events
Direction buttons: Button number 1 : It is used to go upward in the panel’s main menu screen and in the
More Events’ menu.
Button number 2 : It is used to select the desired feature in panel’s main menu and desired category in More Events’ screen and go to right direction.
Button number 3 : It is used to go downward in the panel’s main menu screen and More Events menu.
Button number 4 : It is used to go back to previous menu and go to left direction. Enter : Enter Button is used to see the menu screen and select the desired
feature inside the menu. Exit : It is used to go back to previous menu when LCD screen shows main
panel menu or go back to categories menu from the selected category.
Note: Menu features are described in detail in the 11
th
section of Panel menu. To see the
transitions among menu features please check ANNEX-E Scheme of Menu Functions.
W/Dog Reset : Used for elimination error in case of ‘System Fault LED illuminates. However, if the LED illuminates because of any fault in the central microprocessor preventing the program to run; the button will be useless for this situation (ANNEX-B, Figure-9).
Microprocessor Reset: Microprocessor can be reset by pressing the Microprocessor Reset button. (ANNEX-B, Figure-13)
LCD Lighting : Used to adjust the LCD display contrast with the aid of trimpot (ANNEX-B, Figure-10).
KK-641.002 Rev.No:1 01.08.12 ML-121X User Manual Page | 10
6.2 Front Panel Indicators
FIRE : Fire LEDs illuminate in two conditions; if there is a fire situation in the system or in case of pressing Evacuate button. Each one of these conditions makes the LEDs illuminate in ‘Red’ colour.
Power On : Panel is energized and operates normally. It illuminates as Green’ continuously.
General Fault : If any fault occurs during operation. It illuminates with the specified respective faults such as power fault. It illuminates as ‘Yellow.
Power Fault : It indicates that there is a mains power failure or a problem of battery. It illuminates as yellow’ and related fault condition can be viewed on the LCD screen.
System Fault : Main microprocessor fault. It Illuminates as Yellow. Sounder Disabled : It shows that the sounder outputs on the panel has been disabled and
illuminates as yellow. Disablement : If any device or line disabled in the system this LED illuminates as
‘Yellow’. More Fires : It indicates the presence of more than one fire in the existing event list
of the system. It illuminates as ‘Yellow’. Evacuate : It indicates that the Evacuate button is pressed. The Evacuate button
must be programmed by Loop Manager Software Program. It illuminates as ‘Red.
Alarm : It indicates that the alarm button is pressed, it illuminates as ‘Yellow’. Alarm Silenced : This led shows that incoming alarms are silenced by pressing ‘Alarm
Silenced’ button. It illuminates as ‘Yellow’. Buzzer Silenced : It indicates that the Buzzer Silenced button is pressed and it
illuminates as ‘Yellow’. Zone Disablement : It indicates that one or more zones are disabled from the panel menu.
It illuminates as ‘Yellow. More Events : If there is more than one event in the system this LED illuminates as
‘Yellow’.
KK-641.002 Rev.No:1 01.08.12 ML-121X User Manual Page | 11
6.3 Internal Indicators
Internal Indicators on SLCU (Single Loop Card Unit) (Annex-B, Figure-16); SEND LED: While sending communication signal to the devices in the loop, it blinks as RED. RECEIVE LED: While receiving responses from the devices in the loop, it blinks as
GREEN.
7- PANEL FUSES
Fuses on the panel; SLCU Fuse (FS1) is a self-resetting fuse and becomes active on 0.5А current overload at the
loop output line. The General fault LED illuminates and on LCD screen Loop open or Short circuit’ comment is seen. Panel’s loop output becomes unusable. In each single loop card this fuse is present.
Sounder 1 Self-resetting fuse (FSO3) Self-resetting and becomes active on 0.5А current overload. Sounder fault Led illuminates, and on LCD screen Sounder 1 open circuit’ message is seen. Panel’s sounder-1 output becomes unusable.
Sounder 2 Self-resetting fuse (FSO4) Self-resetting and becomes active on 0.5А current overload. Sounder fault Led illuminates, and on LCD screen Sounder 2 open circuit’ message is seen. Panel’s sounder-2 output becomes unusable.
Sounder 3 Self-resetting fuse (FSO5) Self-resetting and become active on 0.5А current overload. Sounder fault Led illuminates, and on LCD screen Sounder 3 open circuit’ message is seen. Panel’s sounder-3 output becomes unusable.
Sounder 4 Self-resetting fuse (FSO1) Self-resetting and becomes active on 0.5А current overload. Sounder fault Led illuminates, and on LCD screen Sounder 4 open circuit’ message is seen. Panel’s sounder-4 output becomes unusable.
24 V DC Self-resetting Fuse (FSO2) Self-resetting and becomes active on 0.5А current overload or wrong connection into the output. The General fault LED illuminates and 24 V Fault’ comment is seen on LCD screen. 24 V DC output becomes unusable.
Internal Indicators on MLY-0502 Power Supply; 28 V input fuse (F1)
3 A self-resetting fuse becomes active in case the power supply becomes faulty. Battery fuse (F2)
1.1 A self-resetting fuse becomes active upon any fault or short circuit at battery inputs. 28 V output fuse (F3)
3A self-resetting fuse becomes active upon short circuit in 28 V output of power supply. In this case, the outputs of power supply become de-energized.
Note: the placement of the fuses is shown in Annex-B.
Loading...
+ 25 hidden pages